This is a technical specification document for concrete reinforcing work prepared by Herbert, Rowland & Grubic, Inc. for West Manchester Township in Pennsylvania under Project No. 7297.0444. The specification establishes requirements for reinforcing bars, welded wire fabric, and reinforcement accessories to be incorporated into cast-in-place concrete structural elements. The work scope includes supply and installation of deformed reinforcing steel bars complying with ASTM A615 specifications with 60 ksi yield strength, deformed bar mats per ASTM A184, welded steel wire fabric per ASTM A185, and associated accessory materials including tie wire and bar supports. Installation requirements mandate proper spacing, support, and positioning of reinforcement in accordance with ACI 318 standards, with specific depth tolerances of plus or minus 3/8 inch for reinforcement depths greater than 8 inches and plus or minus 1/2 inch for depths of 8 inches or less. Shop drawings must indicate bar sizes, spacings, locations, splice locations, bending and cutting schedules, and quantities prior to fabrication. The related contract opportunity indicates bids are due by 10:00 AM local time on Wednesday, May 20, 2026, with no pre-bid conference scheduled.

The specification requires manufacturers to provide certification that all products supplied comply with the Pennsylvania Steel Products Procurement Act and meet or exceed specified requirements. Materials must be delivered in manufacturer's original packaging and stored in clean, dry locations remote from construction operations. Reinforcement fabrication must follow CRSI 10-MSP standards and ACI 318 guidelines for bend diameters and splice locations. Special chairs, bolsters, and spacers adjacent to weather-exposed concrete surfaces must be plastic-coated steel to prevent corrosion. Tie wire must be minimum 16 gauge annealed type, and bar supports must include load-bearing pads to prevent damage to vapor retarders. The specification does not indicate specific quantities, pricing, or funding amounts, as this document serves as the technical standard for the excavation and maintenance contract work orders that will be issued by West Manchester Township on an as-needed basis.

View the file

Other files

File Type Posted
32 92 19 - Seeding.pdf PDF
31 05 16 - Aggregates For Earthwork.pdf PDF
00 45 36 EEO Certificate.pdf PDF
01 22 00 - Unit Prices.pdf PDF
33 05 05.31 - Hydrostatic Testing.pdf PDF
00 01 01 - YO Cover.pdf PDF
01 26 13 - Requests for Interpretation.pdf PDF
01 40 00 - Quality Requirements.pdf PDF
31 23 16 - Excavation.pdf PDF
01 74 19 - Construction Waste Management and Disposal.pdf PDF
00 73 53 - Anti-Pollution Measures.pdf PDF
01 41 26 - Permit Requirements.pdf PDF
32 12 16 - Asphalt Paving.pdf PDF
31 23 19 - Dewatering.pdf PDF
01 61 00 - Product Requirements.pdf PDF
00 43 13 - Bid Bond PENAL SUM Form.pdf PDF
01 31 19 - Project Meetings.pdf PDF
00 01 10 - Table of Contents.pdf PDF
01 42 00 - References.pdf PDF
31 23 16.13 - Trenching.pdf PDF
00 45 19 Non Collusion Affidavit.pdf PDF
Sanitary and Storm Sewer Maintenance & Emergency Construction Details.pdf PDF
33 42 00 - Stormwater Conveyance.pdf PDF
31 10 00 - Site Clearing.pdf PDF
02 57 00 - Sinkhole Remediation.pdf PDF
33 31 11 - Public Sanitary Sewerage Gravity Piping.pdf PDF
33 05 05.43 - Mandrel Testing.pdf PDF
01 50 00 - Temporary Facilities and Controls.pdf PDF
00 11 13 - Advertisement for Bids.pdf PDF
00 63 13 - RFI Form.pdf PDF
01 73 00 - Execution Requirements.pdf PDF
00 52 00 - Agmnt btw Own and Cntr for Const Con Stip Price.pdf PDF
31 23 23 - Fill.pdf PDF
33 05 61 - Concrete Manholes and Inlets.pdf PDF
32 13 13 - Concrete Paving.pdf PDF
03 30 00 - Cast-in-Place Concrete.pdf PDF
31 25 00 - Erosion And Sedimentation Controls.pdf PDF
32 17 23 - Pavement Markings.pdf PDF
01 57 28 - Temporary Flow Control.pdf PDF
31 05 13 - Soils For Earthwork.pdf PDF
33 05 05.36 - Vacuum Testing.pdf PDF
02 41 13.23 - Utility Line Removal.pdf PDF
33 05 05.41 - Air Testing.pdf PDF
33 31 23 - Sanitary Sewerage Force Main Piping.pdf PDF
31 23 16.26 - Rock Removal.pdf PDF
00 31 43 - Permit Applications.pdf PDF
00 73 73 - Statutory Requirements.pdf PDF
00 61 13.13 - Performance Bond.pdf PDF
32 11 23 - Aggregate Base Courses.pdf PDF
00 63 36 - Work Order Form.pdf PDF
Show 40 more

Latest 50 of 69 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

03 20 00 - CONCRETE REINFORCING

Herbert, Rowland & Grubic, Inc. 03 20 00 - 1 007297.0444

SECTION 03 20 00 - CONCRETE REINFORCING

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Reinforcing bars.

2. Welded wire fabric.

3. Reinforcement accessories.

B. Related Requirements:

1. Section 03 10 00 - Concrete Forming and Accessories: Form materials, waterstops, and accessories required to form cast-in-place concrete.

2. Section 03 30 00 - Cast-in-Place Concrete: Cast-in-place or in-situ concrete for structural building frame, slabs on grade, and other concrete components associated with building.

1.2 REFERENCE STANDARDS

A. American Concrete Institute:

1. ACI 301 - Specifications for Structural Concrete.

2. ACI 318 - Building Code Requirements for Structural Concrete.

3. ACI 530/530.1 - Building Code Requirements and Specification for Masonry

Structures.

4. ACI SP-66 - ACI Detailing Manual.

B. American Welding Society:

1. AWS D1.4 - Structural Welding Code - Reinforcing Steel.

C. ASTM International:

1. ASTM A184 - Standard Specification for Welded Deformed Steel Bar Mats for

Concrete Reinforcement.

2. ASTM A615 - Standard Specification for Deformed and Plain Carbon-Steel Bars for

Concrete Reinforcement.

3. ASTM A704 - Standard Specification for Welded Steel Plain Bar or Rod Mats for

Concrete Reinforcement.

4. ASTM A706 - Standard Specification for Deformed and Plain Low-Alloy Steel Bars for Concrete Reinforcement.

5. ASTM A767 - Standard Specification for Zinc-Coated (Galvanized) Steel Bars for

Concrete Reinforcement.

6. ASTM A775 - Standard Specification for Epoxy-Coated Steel Reinforcing Bars.

7. ASTM A884 - Standard Specification for Epoxy-Coated Steel Wire and Welded

Wire Reinforcement.

8. ASTM A934 - Standard Specification for Epoxy-Coated Prefabricated Steel

Reinforcing Bars.

9. ASTM A996 - Standard Specification for Rail-Steel and Axle-Steel Deformed Bars for Concrete Reinforcement.

Herbert, Rowland & Grubic, Inc. 03 20 00 - 2 007297.0444

10. ASTM A1064 - Standard Specification for Carbon-Steel Wire and Welded Wire Reinforcement, Plain and Deformed, for Concrete.

D. Concrete Reinforcing Steel Institute:

1. CRSI 10-MSP - Manual of Standard Practice.

2. CRSI 10PLACE - Placing Reinforcing Bars.

1.3 COORDINATION

A. Coordinate Work of this Section with placement of formwork, formed openings, and other Work.

1.4 SUBMITTALS

A. Section 01 33 00 - Submittal Procedures: Requirements for submittals.

B. Shop Drawings:

1. Indicate bar sizes, spacings, locations, splice locations, and quantities of reinforcing steel and welded wire fabric.

2. Indicate bending and cutting schedules.

3. Indicate supporting and spacing devices.

C. Manufacturer's Certificate:

1. Certify that products meet or exceed specified requirements.

2. Submit certification that all products supplied under this Section comply with the

Pennsylvania Steel Products Procurement Act.

1.5 QUALITY ASSURANCE

A. Perform Work according to ACI 318.

B. Prepare Shop Drawings according to ACI SP-66.

1.6 DELIVERY, STORAGE, AND HANDLING

A. Section 01 61 00 - Product Requirements: Requirements for transporting, handling, storing, and protecting products.

B. Requirements for transporting, handling, storing, and protecting products shall be completed per manufacturer’s recommendation.

C. Inspection: Accept materials on Site in manufacturer's original packaging and inspect for damage.

D. Store materials according to manufacturer instructions.

E. Protection:

1. Protect materials from moisture by storing in clean, dry location remote from construction operations areas.

2. Provide additional protection according to manufacturer instructions.

Herbert, Rowland & Grubic, Inc. 03 20 00 - 3 007297.0444

1.7 EXISTING CONDITIONS

A. Field Measurements:

1. Verify field measurements prior to fabrication.

2. Indicate field measurements on Shop Drawings.

PART 2 - PRODUCTS

2.1 REINFORCEMENT

A. Reinforcing Steel:

1. Comply with ASTM A615.

2. Yield Strength: 60 ksi.

3. Billet Bars: Deformed.

4. Finish: Uncoated.

B. Deformed Bar Mats:

1. Material: Steel bars.

2. Comply with ASTM A184.

3. Fabrication: ASTM A615.

4. Yield Strength: 60 ksi.

5. Finish: Uncoated.

C. Stirrup Steel:

1. Comply with ANSI/ASTM A82.

2. Finish: Uncoated.

D. Welded Steel Wire Fabric:

1. Comply with ASTM A185.

2. Plain Type, in coiled rolls.

3. Finish: Uncoated.

2.2 FABRICATION

A. Fabricate concrete reinforcement according to CRSI 10-MSP.

B. Form reinforcement bends with minimum diameters according to ACI 318.

C. Form ties and stirrups from following:

1. Bars No. 10 and Smaller: No. 3 deformed bars.

2. Bars No. 11 and Larger: No. 4 deformed bars.

D. Splicing:

1. If not indicated on Drawings or Shop Drawings, locate reinforcement splices at point of minimum stress.

2. Obtain approval of splice locations from Engineer.

2.3 ACCESSORY MATERIALS

A. Tie Wire:

Herbert, Rowland & Grubic, Inc. 03 20 00 - 4 007297.0444

1. Minimum 16 gage, annealed type.

B. Chairs, Bolsters, Bar Supports, and Spacers:

1. Size and Shape: To strengthen and support reinforcement during concrete placement conditions.

2. Furnish load-bearing pad on bottom to prevent vapor retarder puncture.

C. Special Chairs, Bolsters, Bar Supports, and Spacers Adjacent to Weather-Exposed Concrete Surfaces:

1. Material: Plastic-coated steel.

2. Size and Shape: To meet Project conditions.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Place, support, and secure reinforcement against displacement.

B. Do not deviate from required position beyond specified tolerance.

C. Do not weld crossing reinforcement bars for assembly except as permitted by Engineer.

D. Do not displace or damage vapor retarder.

E. Accommodate placement of formed openings.

F. Spacing:

1. Space reinforcement bars with minimum clear spacing according to ACI 318.

2. If bars are indicated in multiple layers, place upper bars directly above lower bars.

G. Conform to applicable code for concrete cover over reinforcement.

3.2 TOLERANCES

A. Section 01 40 00 - Quality Requirements: Requirements for tolerances.

B. Install reinforcement within following tolerances for flexural members, walls, and compression members:

1. Reinforcement Depth Greater Than 8 Inches:

a. Depth Tolerance: Plus or Minus 3/8 inch.

b. Tolerance on minimum concrete cover: Minus 3/8 inch.

2. Reinforcement Depth Less Than or Equal to 8 Inches:

a. Depth Tolerance: Plus or Minus 1/2 inch.

b. Tolerance on minimum concrete cover: Minus 1/2 inch.

C. Foundation Walls: Install reinforcement within tolerances according to ACI 530/530.1.

END OF SECTION