This solicitation is for construction services for the establishment of NAVAIDS facilities at O'Hare International Airport in Chicago, Illinois. The contractor shall provide all labor, supervision, materials, and equipment to perform the project in accordance with drawings, specifications, and contract clauses. The performance period is 605 calendar days with an anticipated start date of November 15, 2020. The estimated price range for this procurement is between $5,000,000 to $10,000,000. Interested firms must have successfully completed similar projects both in dollar amount and scope of work at an operational airport. Offers are due by October 7, 2020. Offerors must include a cover letter, signed solicitation form, past experience, proposed schedule, financial capability letter, liability insurance certificate, bonding letter, bid bond form, and small business subcontracting plan. At least two customer satisfaction questionnaires are also required. The soliciting agency is the Department of Transportation Federal Aviation Administration Southwestern Region.

View the file

Other files

File Type Posted
697DCK-20-R-00436 - Amendment 0001.pdf PDF
ord-d-als09r-e009.pdf PDF
ord-d-gs09r-c004.pdf PDF
ord-d-als09r-m001.pdf PDF
ord-d-gs27l-c006.pdf PDF
ord-d-als27l-c007.pdf PDF
ord-d-ald09r-g024.pdf PDF
ord-d-ald09r-g015.pdf PDF
ord-d-gs27l-a001.pdf PDF
ord-d-ald09r-g008.pdf PDF
ord-d-gs27l-c003.pdf PDF
ord-d-als09r-e006.pdf PDF
ord-d-loc27l-c007.pdf PDF
ord-d-ald09r-g017.pdf PDF
ord-d-als27l-c006.pdf PDF
ord-d-als09r-c006.pdf PDF
ord-d-als27l-e006.pdf PDF
Attachment No. 12 - Required Checklist for Underground Storage Tank Installation.pdf PDF
ord-d-gs27l-e001.pdf PDF
ord-d-loc27l-c003.pdf PDF
ord-d-als09r-e005.pdf PDF
Attachment No. 20 - Past Performance Questionnaire.doc DOC document
ord-d-gs09r-a001.pdf PDF
ord-d-im09r-c001.pdf PDF
ord-d-als27l-e005.pdf PDF
ord-d-als27l-m002.pdf PDF
ord-d-als09r-e012.pdf PDF
ord-d-ald09r-g031.pdf PDF
ord-d-als09r-e008.pdf PDF
ord-d-gs27l-c004.pdf PDF
ord-d-ald09r-g004.pdf PDF
ord-d-gs09r-c005.pdf PDF
ord-d-als27l-m003.pdf PDF
ord-d-als09r-c011.pdf PDF
ord-d-als09r-m004.pdf PDF
ord-d-loc09r-c003.pdf PDF
ord-d-ald09r-g022.pdf PDF
ord-d-gs27l-c005.pdf PDF
Attachment No. 18 - Contract Insurance Requirements - Chicago Department of Aviation.pdf PDF
ord-d-als27l-c012.pdf PDF
Attachment No. 02 - Special Specifications.pdf PDF
ord-d-ald09r-g014.pdf PDF
Attachment No. 14 - Ground Resistance Testing Form.xlsx XLSX spreadsheet
ord-d-ald09r-g002.pdf PDF
ord-d-als27l-c014.pdf PDF
Attachment No. 19 - Small Business Subcontracting Plan - 697DCK-20-R-00436.pdf PDF
697DCK-20-R-00436.pdf PDF
ord-d-loc27l-c004.pdf PDF
ord-d-loc09r-c002.pdf PDF
ord-d-als09r-e013-1.pdf PDF
Show 40 more

Latest 50 of 158 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

G.S. RACK CNVC OUTLET

OBSTRUCTION LIGHT

FOTS RACK CNVC OUTLET

HVAC UNIT

MAIN

100A

20A

60A

20A

20A

20A

15A

30A

BLDG. LIGHTS

GS EQMT CABINET

TDZ RVR (SIE BOX)

20A

20A

SPARE

20A

20A

20A

5 20A

15A

20A

G

N

EMERGENCY LIGHT

20A

20A

TDZ RVR (OBSTR LIGHT / CONV OUTLET)

N

G

S S

LINE-1

LINE-2

NEUTRAL

LINE-1

LINE-2

NEUTRAL

GROUND

G

20A

NOT TO SCALE

POWER PANEL WIRING DIAGRAM

P-5

TRANSFORMER,

FROM STEP-UP

63 48

L1

L2

N

GND

TVSS

TVSS

#2 AWG

CNVC. OUTLETS

CNVC. OUTLETS

N

FIBER OPTIC RACK ATS

N

L2 L1

G

JUMPER

#2 GROUNDING

CITY RPU

RUNWAY 9R RPU

9R PAPI

FIBER OPTIC RACK UPS

SEE ORD-D-GS09R-C005

FOR CONTINUATION

ANTENNA HEATERS

30A

1I

2I

3I

4I

5I

6I

7I

8I

9I

10I

11I

12I

13I

14I

15I

16I

17I

18I

19I

20I

21I

22I

I

25I

26I

27I

28I

34F

35F

36F

37F

38I

39I

40I

41I

42I

43I

44I

45I

ITEM PREFIXES:

ABBREVIATIONS:

46I

48I

49I

50I

51I

I

I

I

I

I

I

I

I

I

NUMBERED LEGEND:

I

OR BY FAA MAINTENANCE PERSONNEL

F=TO BE INSTALLED OR PLACED BY EITHER THE FAA INSTALLATION CREW,

I =FURNISH AND INSTALL

29I

30I

31I

F

I

F

F

F

I

I

I

I

I

I

I

BARE GND = BARE COPPER GROUNDING CONDUCTOR

GREEN GND = GREEN INSULATED COPPER GROUNDING CONDUCTOR

GRSC = GALVANIZED RIGID STEEL CONDUIT, SCHEDULE 40

I

I

I 75

I 76

I

UNIT WITH TWO 1/C 10 AWG THWN. SEE NOTE 2 E004. SUBMIT FOR GRILLS.

SPECIFICATIONS. PROVIDE SHOP DRAWINGS FOR SUBSTITUTIONS. WIRE THIS

ECONOMIZER VENT FAN. BARD CAT. NO. W12AAAA03EW4XXJ MEETS

HVAC THROUGH-WALL UNIT WITH 11,100 BTU A/C, 3.6-KW HEAT STRIP, AND

COMPLIENT) LITHONIA LIGHTING CAT. NO. LBL4LP840 RFD230716 MEETS SPECIFICATION.

4’ LED WRAPAROUND LIGHT W/ CLASS B DRIVER (TO BE FCC PART 15 CLASS B

ASSEMBLY REQUIRED BY ELECTRICAL CONTRACTOR. SEE NOTE 19 E006.

5000-3-100-72. #WORK BENCH SHALL BE 72" KENDALL HOWARD LAN STATION ITEM

1 AWG U.S.E.#1 1/2" CONDUIT WITH THREE 1/C

4"X4" ELECTRICAL JUNCTION BOX TO EXTERIOR LIGHT FIXTURE ITEM 55.

24619, LCD-8 SNOW SWITCH. MOUNT UNIT ABOVE ROOF.#DEICING CONTROLLER, ETI CAT

WITH HYDRAULICALLY CRIMPED LUGS AT THE GROUND PLATE.

GROUNDING CONDUCTOR 2 . EXOTHERMIC WELD AT PERIMETER GROUND (EES) AND CONNECT

CONDUITS CONNECTING THE GROUND PLATE INSIDE THE SHELTER TO THE PERIMETER

4/0 AWG COPPER, GREEN RHW CABLE IN EACH OF TWO 2" SCHEDULE 80 PVC#ONE 1/C

ELECTRONIC MAIN GROUNDING PLATE PER DRAWING ORD-D-ALS09R-E006.

A-6N6P MEETS SPECIFICATIONS.

6" x 6" x 4" POWER JUNCTION BOX, NEMA 4X, HOFFMAN A6R64HCR WITH PANEL, HOFFMAN

ORD-D-GS09R-COO5. CONNECTION TO JUNCTION BOX SHALL USE MYERS HUB.

WIRES AND GROUNDING WIRE FOR OBSTRUCTION LIGHTS AND ANTENNA HEATERS, PER SHEET

1" PVC FROM POWER JUNCTION BOX 43 TO GLIDE SLOPE ANTENNA TOWER, WITH POWER

SHELTER FASCIA USING 2-HOLE PIPE STRAP. CONDUIT END AT ROOF SHALL BE THREADED.

PENETRATION, AND SHALL EXTEND TO 12" ABOVE ROOF PEAK. SECURE CONDUIT TO

1 1/4" GRSC FOR FLIGHT CHECK ANTENNA. CONDUIT SHALL BEND TWICE TO AVOID ROOF

CABLES IN THIS CONDUIT.

ORD-D-GS09C-C003 THE FAA INSTALLATION CREW WILL INSTALL ANTENNA FEED COAXIAL

2 1/2" PVC CONDUIT FROM BOX 39 TO GLIDE SLOPE ANTENNA TOWER PER SHEET

WITH PANEL CAT. NO. A-36P30. CENTER BOX LEFT TO RIGHT ON OUTSIDE WALL.

RF JUNCTION BOX: 36" X 30" X 12" NEMA 4X ENCLOSURE, HOFFMAN CAT. NO. A-36R3012HCR

NIPPLE SHALL BE CENTERED 6’ FROM LEFT WALL AND 4’-2 3/4" OFF FLOOR.

2 1/2" GRSC NIPPLE THROUGH WALL, WITH INSULATED GROUNDING BUSHINGS.

BATTERY RACK FOR MARK 20A GLIDE SLOPE EQUIPMENT.

MARK 20 GLIDE SLOPE DISTRIBUTION UNIT AND RECOMBINING UNIT CABINET.

2" CONDUIT FROM RACK 34 TO CABINET 36 .

MARK 20 GLIDE SLOPE TRANSMITTER RACK.

WITH DUCT SEAL.

ALL CONDUITS ENTERING THE BUILDING FROM THE EXTERIOR SHALL BE SEALED

DUCT SEAL PER THE NEC.

THE CONNECTING CONDUITS ON JUNCTION BOX 63 SHALL BE SEALED WITH

FROM FLOWING DIRECTLY ONTO THE GLIDE SLOPE ELECTRONIC EQUIPMENT.

INSTALL AIRFLOW DEFLECTOR OVER THE HVAC SUPPLY GRILL TO PREVENT AIR

FOR ELECTRICAL FIRES AS SHOWN.

CONTRACTOR SHALL FURNISH AND MOUNT FIRE EXTINGUISHER SUITABLE

SEALED WITH DUCT SEAL PER FAA-STD-019F.

THE CONNECTING CONDUITS OF THE SURGE PROTECTION DEVICE SHALL BE

FOR ADDITIONAL NOTES, SEE SHEET ORD-D-GS09C-E001.

GENERATOR INLET

EMERGENCY

PORTABLE

A.

B.

C.

D.

E.

F.

33F

F

I 77

BLOCKS FOR TRANSITION OF RVR & PAPI POWER.

12" X 12" X 6" NEMA 1 JB WITH BACK PANEL. PROVIDE TERMINAL

MID-SPAN CONDUIT SUPPORT PER ORD-D-ALD09R-G027.

RVR FUSED DISCONNECT 30A, NEMA 4X.

RVR STEP-UP TRANSFORMER, NEMA 4X, 120/240 VAC, 60Hz, 10KVA

MODEL RAYVOSS 120-2S-M3-3-06-A.

AC SURGE ARRESTER WITH INTEGRAL DISCONNECT AND FUSING, RAYCAP

CONDUIT TO HVAC UNIT FOR THERMOSTAT CABLE.

4" X 4" NEMA 4X JUNCTION BOX WITH 3/4" LIQUID-TIGHT FLEXIBLE

LEAVE TWO CONDUIT EMPTY FOR USE BY FAA.

FOUR 1" EMT CONDUIT BETWEEN PANELBOARD 19 AND SQUARE DUCT 15 .

MK-20 ILS INTRUSION SWITCH

RUNWAY 9R RPU FUSED DISCONNECT SWITCH, 30A, NEMA 4X.

FLIGHT INSPECTION ANTENNA

MK-20 ILS OUTSIDE TEMPERATURE SENSOR

MK-20 ILS SMOKE DETECTOR

FIRE EXTINGUISHER, TYPE A, B, C, 20 LBS, POTTER ROEMER TYPE 3020 MEETS SPECIFICATIONS.

THERMOSTAT, SEE NOTE D.

16"x14"x8" POWER JUNCTION BOX NEMA 1. INSTALL TERMINAL BLOCK FOR PAPI AND/OR RVR HERE

SPARE 2" PVC COATED GRSC TO EDGE OF PLOT (SPARE). CAP END OF CONDUIT.

GROUND ACCESS WELL APPROXIMATE LOCATION PER ORD-D-ALD09R-G021.

OR APPROVED EQUAL.

240/120V, UL LISTED, IN A NEMA 1 ENCLOSURE, ASCO SERIES 7000 CAT. NO. D07NTSA20100F50C

MANUAL TRANSFER SWITCH (MTS), 100A, SINGLE PHASE, 2-POLE WITH SOLID NEUTRAL,

CONDUCTOR FOR CONNECTION TO THE 9R RPU BY OTHERS.

2" PVC COATED GRSC FROM ITEM 69 TO A POINT 10 FEET BEYOND THE PERIMETER GROUNDING

SPECIFICATIONS.

EXIT ILLUMINATED WITH LED LAMPS, EXITRONIX PART NUMBER CSX-2-3-1-3-W-EL2-G2 MEETS

12 W, SEALED BEAM H.I.T. LAMPS, 90-MINUTE RUN TIME WITH 24-HOUR RECHARGE TIME,

EMERGENCY LIGHTING UNIT WITH STEEL HOUSING (CITY OF CHICAGO APPROVED), 6-VOLT,

EYEBOLT.

PIPE SHALL HAVE A LATCHING HOOK, AND DOOR SHALL HAVE A CORRESPONDING

2" SCH 40 GALV. STEEL PIPE DOOR STOP TO 4’ BELOW FINISHED GRADE.

LANDING AND STEPS PER SHEET A001.

PROVIDE WITH TWO LED ENGINES.

FINISH, AS MANUFACTURED BY LITHONIA, PART NUMBER WSR-2-10A700/40K-SR3-120-PE-DDBTXD.

WALL MOUNTED LED EXTERIOR LIGHT FIXTURE WITH PHOTO CELL, STANDARD DARK BRONZE

DUPLEX RECEPTACLE PER NOTE 3. BOTTOM OF RECEPTACLE SHALL BE 36" ABOVE FLOOR.

LIGHT SWITCH PER NOTE 3 E006.

CONTRACTOR. SEE NOTE 19 E006.

36" X 72" X 18" STORAGE CABINET TO BE FURNISHED AND INSTALLED BY THE

E D

M

IS

S

U E

D F

O R

NAVAIDS

189827202/28/2020D

IL

SDK

SDK 12/21/2010 992152

ORD-D-GS09R-E002 D

REH05/23/2019179806210/31/2019C

REH1798062FOL800 RWY 9C-27C BP2 PHASE 109/25/2018B

SK10/29/201299125212/21/2010A

ENGINEERING SERVICES

OMP - ESTABLISH OF NAVAID

GS

CHICAGO O’HARE INTERNATIONAL AIRPORTCHICAGO

PROJECT ENGINEER MGR: ENGINEERING - CHICAGO

AS BUILT-FOL800 RWY 9C-27C BP2 PH1

CONVERT 9R (JAV) GS TO CAPTURE EFFECT

o rd -d -g s r-e .d g n

THIS DRAWING PRODUCED ON THE AGL REGION MICROSTATION SYSTEM

ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA

A S -B

U

IL

T

GLIDE SLOPE - RUNWAY 9R

AND EQUIPMENT SCHEDULE

EQUIPMENT SHELTER WIRING

NOTES:

FIBER OPTIC TELECOMMUNICATION SYSTEM (FOTS) RACK.

WIRE MESH CABLE TRAY FROM BOX 30 TO RACK 33.

SEE NOTES 4 & 5 E006. (FIBER CABLES BY OTHERS).

FOR THE FIBER OPTIC CABLES. THE OTHER 4" CONDUITS WILL BE SPARE.

TRACER WIRES. ONE CONDUIT MUST CONTAIN FOUR 1" YELLOW INNERDUCTS

CARRYING TWO 24-STRAND SINGLEMODE FIBER OPTIC CABLES AND METALLIC

FOUR 4" PVC COATED GRSC FROM BOX 30 TO COMMUNICATION HANDHOLE,

TO BE 6’-0" ABOVE FLOOR. SEE NOTE 13 E006.

HOFFMAN CAT. NO. A-36N308LP WITH BACK PANEL. TOP OF JUNCTION BOX

FIBER OPTIC CABLE JUNCTION BOX: 36" X 36" X 8" NEMA 1 ENCLOSURE,

4"X4" ELECTRICAL JUNCTION BOX FOR HVAC DISCONNECT SWITCH.

SEE NOTES 5 & 12 E006.

WITH MOUNTING TRACK AND END BARRIERS, SQUARE ’D’ 9080 TYPE G, OR EQUAL.

TERMINATE THE CABLE IN BOX 27 ON MOLDED NYLON TERMINAL MINI-BLOCKS,

6 AWG GREEN GND.#19 REA SPEC. PE-89 CONTROL CABLE AND ONE 1/C #ONE 6PR

2" PVC COATED GRSC FROM BOX 27 CONTINUOUS TO TOUCHDOWN RVR, WITH

JUNCTION BOX TO BE 6’-0" ABOVE FLOOR.

HOFFMAN CAT. NO. A-30N308LP WITH INTERNAL PANEL. TOP OF THE

CONTROL CABLE JUNCTION BOX: 30" X 30" X 8" NEMA 1 ENCLOSURE,

6 GREEN GROUND TO PAPI. SEE NOTE 5 E006.#POWER CABLES AND ONE 1/C

AWG USE-2#32" PVC COATED GRSC FROM PANEL BOARD ITEM 19 CONTAINING THREE 1/C

2" PVC COATED GRSC (SPARE TO HANDHOLE). SEE NOTE 5 E006.

4"X4" ELECTRICAL JUNCTION BOX FOR HVAC CONTROL CABLE TO THERMOSTAT.

30A, 2-POLE, NEMA 4X HEAVY DUTY DISCONNECT SWITCH FOR HVAC UNIT 51.

6 INSULATED GREEN TO MID-RVR (TO HANDHOLE).#AND 1/C

ONE 12 PAIR NO. 19 SHIELDED SIGNAL CABLES

2" PVC COATED GRSC WITH CABLES OF 22 (TO HANDHOLE). SEE NOTE 5 E006.

6 AWG GREEN GND. SEE NOTES 4 AND 5 E001.# AWG TYPE USE-2 AND ONE 1/C #41/C

2" PVC COATED GRSC FROM PANELBOARD 19 CONTINUOUS TO TOUCHDOWN RVR, WITH TWO

PROVIDE DOOR-IN-DOOR COVER, SURFACE MOUNTED. FILL ALL SPACES WITH SPARES.

NO. NQ30L1C, IN NEMA 1 ENCLOSURE MIN 20" WIDE. DOOR SWINGS AWAY FROM ENTRANCE.

WITH 100A MAIN BREAKER (KIT REQUIRED), 30-1 POLE SPACES, INTERIOR SQUARE ’D’ CAT.

SHELTER PANELBOARD WITH COPPER CURRENT-CARRYING PARTS, 240VAC, 100A-RATED

IN A 15-DEGREE ANGLE BACK BOX, HUBBELL CAT. NO. BB1002W, WITH CLOSURE CAP.

INLET FOR STANDY ENGINE GENERATOR, HUBBELL CAT. NO. HBL 4100B12W, MOUNTED

6 GREEN CONTINUOUS TO PAPI.#19 CONTROL CABLE AND ONE 1/C #CONTAINING ONE 12 PR

2" PVC COATED GRSC FROM CONTROL CABLE JUNCTION BOX (ITEM 27) (TO HANDHOLE)

PROVIDE 5’ SLACK WITHIN JUNCTION BOX.

4/0 GREEN GROUND WITH RED TRACER. #ONE 1 1/4" SCH. 80 PVC CONTAINING A

6" SQUARE DUCT. TOP OF SQUARE DUCT TO BE 4" BELOW CEILING.

6 AWG INSULATED GREEN GND, THHN/THWN. IN 1 1/2" GRS.#1 AWG + ONE 1/C #THREE 1/C

2 BONDING JUMPER.#BOND THE GEC TO JUNCTION BOX 63 WITH

2 AWG GREEN GND GROUNDING ELECTRODE CONDUCTOR (GEC).#1" SCHEDULE 80 PVC WITH

LIGHT WIRES. LOOP 24" OF EXTRA SLACK WIRE IN LOWER JUNCTION BOX FOR USE BY FAA.

4"X4" DEEP POWER JUNCTION BOXES FOR ANTENNA HEATER CABLES AND OBSTRUCTION

100A FUSES IN NEMA 1 ENCLOSURE, SQUARE ’D’ F SERIES H223N, OR EQUAL. SEE NOTE 3 E006.

SERVICE ENTRANCE RATED FUSIBLE, HEAVY DUTY DISCONNECT SWITCH 100A, 2-POLE CLASS J, 2 1/2" METAL CONDULET FITTINGS.

6 AWG GREEN GND. SEE NOTE 2 E006.#AND ONE 1/C

2 AWG TYPE U.S.E. SERVICE ENTRANCE CABLES #2 1/2" GRSC WITH THREE 1/C

6 INSULATED GREEN GROUND.#2 AWG AND ONE 1/C #1 1/2" CONDUIT WITH THREE 1/C

DISCONNECT SWITCH.

25KVA TRANSFORMER, SINGLE PHASE, 2400V, 120/240V WITH INTERNAL

RAYVOSS 120-2S-N1-3-06-A. SEE NOTE 3 E006.

AC SURGE ARRESTER WITH INTERNAL DISCONNECT AND FUSING, RAYCAP MODEL

TO THE EES PER NOTE 1 E001, AND TO THE GROUNDING CONNECTOR.

GAR-SERIES CONNECTORS MEET SPECIFICATIONS. ATTACH A 2 AWG BARE GND

GROUNDING CONNECTOR ON GRSC, PROPERLY SIZED TO THE CONDUIT. BURNDY

2 BARE. SEE NOTE 5 E006.#TRANSFORMER GROUND ROD W/

ONE 4" CONDUIT WILL BE SPARE WITH PULL CORD. GROUND THE NEUTRAL TO THE

1 AWG U.S.E. FROM TRANSFORMER.#(2)-WAY, 4" PVC COATED GRSC WITH THREE 1/C

3/4" X 10’ STAINLESS STEEL GROUNDING ROD. SEE NOTE 1 E006.

SYSTEM (EES), OR COUNTERPOISE. SEE NOTE 1 E006.

GRADE. THIS CONDUCTOR AND RODS 3 COMPRISE THE EARTH ELECTRODE

4/0 AWG BARE COPPER PERIMETER GROUNDING CONDUCTOR, 24" BELOW FINISHED #

BUILDING CODE AND ENERGY CODES.

SHEET ORD-D-GS09C-A001. THE SHELTER MUST MEET THE CITY OF CHICAGO

REINFORCED CONCRETE FOUNDATION AND WOOD FRAME EQUIPMENT SHELTER PER

o rd -d -g s r-e .d g n

/2

/2

:0

:2

P

M G re g o ry C

T R S p e n c e r

A

B

C

D

E

F

G

H

8 7 6 5 4 3 2 1

H

G

F

E

D

C

12345678

REVDRAWING NO

DATE JCN

APPROVED BY

ISSUED BY

CHECKED

DRAWN

DESIGNED

SUBMITTED BY

REVIEWED BY

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV

DATE

APPROVED

DESCRIPTION JCN

DATE

REDLINE

APVD

A

2020-07-02T14:17:45-0500
RAFAEL CRAME
2020-07-09T16:16:37-0500
LUIS N DOMINGUEZ