This solicitation is for construction services to establish NAVAIDS facilities serving an extended runway at Chicago O'Hare International Airport. The contractor shall provide all labor, supervision, materials, and equipment to perform the project, including installation of sensors, conduits, junction boxes, and other electrical work. The performance period is 605 calendar days, with an anticipated start of November 15, 2020. The estimated price range for this procurement is $5 million to $10 million. Interested firms must demonstrate experience on similar airport projects of comparable size and scope. Offers are due by October 7, 2020 and must include details on past performance, schedule, insurance, bonding, and small business subcontracting plans. The Federal Aviation Administration Southwestern Region is the contracting agency.
View the file
Other files
Show 40 more
Latest 50 of 158 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
o rd -d -a ls l-e .d g n
/2
/2
:5
:1
P
M G re g o ry C
T R S p e n c e r
A
B
C
D
E
F
G
H
8 7 6 5 4 3 2 1
H
G
F
E
D
C
12345678
REVDRAWING NO
DATE JCN
APPROVED BY
ISSUED BY
CHECKED
DRAWN
DESIGNED
SUBMITTED BY
REVIEWED BY
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV
DATE
APPROVED
DESCRIPTION JCN
DATE
REDLINE
APVD
A
T Y
P
DOOR
FITTING
EMT COMPRESSION
3/4" EMT CONDUIT
T Y
P
3/4" EMT CONDUIT
FITTING
EMT COMPRESSION
FITTING
EMT COMPRESSION
4" SQUARE x 2 1/8" DEEP
STANDARD ELECTRICAL BOX
4" SQUARE x 2 1/8" DEEP
STANDARD ELECTRICAL BOX
14 AWG THWN BLACK 14 AWG THWN BLACK
14 AWG THWN RED
+ - 7 8
1" TYP
67854
NOC
1" TYP
NOC
PWR
INTRUSION SWITCH INSTALLATION
FOR SINGLE DOOR
INTRUSION SWITCH INSTALLATION
FOR DOUBLE DOOR (TYPICAL)
ION SMOKE DETECTOR HOOK-UPPHOTO SMOKE DETECTOR HOOK-UP
NOT TO SCALE NOT TO SCALE
NOT TO SCALENOT TO SCALE
AUX AUX
3/4" EMT CONDUIT
INACTIVE DOOR
BOX 4"x4"x2"
OUTLET
STANDARD
14 AWG THWN RED
4"X4"X2"
STANDARD OUTLET BOX
WITH SWITCH
CABLE PROVIDED
FITTING
COMPRESSION
EMT
3/4" EMT CONDUIT
DESCRIPTION
SWITCHING DIODE, DS1,
P/N JAN1N4148-1
POWER SENSOR
NEW BEDFORD PANORAMEX CORP, UPLAND, CA
PART NO U3003618-01
RESISTOR, 499 OHM, 1% TOL 1/4 WATT
P/N RLR07C4990FR, MIL-R-39017/1
12/24 VDC RELAY MODULE, NO A77-716B
SYSTEM SENSOR, DIV. OF PITTWAY
ST CHARLES, IL
NEW BEDFORD PANORAMEX CORP., UPLAND, CA
PART NO U3001121-01
NEW BEDFORD PANORAMEX CORP., UPLAND, CA
PART NO U3003384-01
NEW BEDFORD PANORAMEX CORP., UPLAND, CA
PART NO U3003385-01
NEW BEDFORD PANORAMEX CORP., UPLAND, CA
PART NO U3003386-01
PART NO U3001120-01
NO QTY
NEW BEDFORD PANORAMEX CORP., UPLAND, CA
INTRUSION SWITCH, ASSOCIATED CONDUIT, AND WIRING
SMOKE DETECTOR, ASSOCIATED CONDUIT, AND WIRING
INSTALL OUTSIDE TEMPERATURE SENSOR ASSEMBLY
INSTALL INSIDE TEMPERATURE SENSOR ASSEMBLY
INSTALL ION SMOKE DETECTOR
INSTALL PHOTO SMOKE DETECTOR
INSTALL INTRUSION SWITCH
REMARKS
SEE NOTE 1.
ALSF-2 EQUIPMENT.
FURNISHED WITH
ALSF-2 EQUIPMENT
FURNISHED WITH
ALSF-2 EQUIPMENT
FURNISHED WITH
ALSF-2 EQUIPMENT
FURNISHED WITH
ALSF-2 EQUIPMENT
FURNISHED WITH
INSTALLATION PERSONNEL
INSTALLED BY FAA
FURNISHED AND
INSTALLATION PERSONNEL
INSTALLED BY FAA
FURNISHED AND
INSTALLATION PERSONNEL
INSTALLED BY FAA
FURNISHED AND
INSTALLATION PERSONNEL
INSTALLED BY FAA
FURNISHED AND
INSTALLATION PERSONNEL
INSTALLED BY FAA
FURNISHED AND
INSTALLATION PERSONNEL
INSTALLED BY FAA
FURNISHED AND
ENVIRONMENTAL EQUIPMENT SCHEDULE
11 1
ALSF-2 EQUIPMENT ROOM
ROOM
GENERATOR
ENGINE/
LOCALIZER
EQUIPMENT
ROOM
5’-3"
14’-6 1/4"
3/4" EMT
SEE NOTE 2
3’-0"
EF-1
D-1
E-9
E-10
E-2
E-6
E-4
E-1
E-5
E-8
E-12
T-3
C-13 C-10
A-23R
C-8A
C-8
D-11
D-2
D-8
D-9
D-17
T-1
D-3
C-4
HVAC-1HVAC-2
MC-1
HVAC-3
CD-2
D-4
T-2
A-23E
CD-1
D-7
D-12
D-14
D-10
D-13
E-15
E-16
C-12
C-2
C-7 C-6
C-11
C-9
C-5
T-2
C-1
D-20
D-18
C-14
D-15
FE FE
FE
FE
(C-3)
NO. 1
CCR
(C-3)
NO. 2
CCR
(C-3)
NO. 3
CCR
(C-3)
NO. 4
CCR
(C-3)
NO. 5
CCR
C-18
C-17
C-16
C-18
C-18
E-11
E-7
E-7
E-7
E-7
SCALE: 3/8" = 1’-0"
PLAN
3/4" EMT
SUBSYSTEM, C-5
MONITORING
REMOTE
WITH SENSOR
SWITCH, D-2
E/G TRANSFER
D-23
D-19
D-16
3/4" EMT
E-14
E-3
D-10B
D-10A
OF WIRE WAY
TO TOP
GANG BOX
4" x 4"
3/4" EMT
OF WIREWAY
TIE INTO TOP
E D
M
IS
S
U E
D F
O R
NAVAIDS
IL
10/31/2019 1898272
ORD-D-ALS27L-E005
C O
N S
T R
U C
T
IO
N
ENGINEERING SERVICES
ALS
CHICAGO O’HARE INTERNATIONAL AIRPORTCHICAGO
PROJECT ENGINEER MGR: ENGINEERING
o rd -d -a ls l-e .d g n
THIS DRAWING PRODUCED ON THE AGL REGION MICROSTATION SYSTEM
ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA
NOTES:
1.
2.
3.
REPRESENTATIVES.
AND MONITORING CONDUCTORS WILL BE FURNISHED AND INSTALLED BY FAA INSTALLATION
THROUGH BOX ABOVE PANEL PRIOR TO TERMINATING CONDUCTORS AT BREAKERS. CONTROL
DUCT. CONTRACTOR SHALL LOOP 3/C 10 AWG POWER CABLE FOR OBSTRUCTION LIGHTS
DOOR TO OCTAL JUNCTION BOX AND CONTINUE CONDUIT TO PENETRATION AT TOP OF SQUARE
RACK LOCATION AND SHALL INSTALL A 3/4" EMT CONDUIT FROM JUNCTION BOX ABOVE
CONTRACTOR SHALL INSTALL AN OCTAL JUNCTION BOX ON CEILING ABOVE FUTURE LOCALIZER
FROM POWER PANEL E-3 TO BOX ABOVE PANEL AND CONTINUE CONDUIT TO BOX ABOVE DOOR.
ON WALL ABOVE POWER DISTRIBUTION PANEL E-3 AND SHALL INSTALL 3/4" EMT CONDUIT
WILL INSTALL THIS SWITCH. CONTRACTOR SHALL INSTALL ANOTHER ELECTRICAL JUNCTION BOX
BY THE GOVERNMENT WITH THE LOCALIZER EQUIPMENT. FAA INSTALLATION REPRESENTATIVES
THIS BOX WILL BE USED TO PROVIDE WIRING TO AN INTRUSION SWITCH WHICH IS PROVIDED
CONTRACTOR SHALL INSTALL A 4" X 4" JUNCTION BOX ON WALL ABOVE THE DOUBLE DOOR.
INSTALLATION.
CONTRACTOR SHALL INSTALL THE REQUIRED CONDUIT, GANG BOXES, ETC. FOR THEIR
THE SMOKE DETECTOR AND LOCALIZER EQUIPMENT SHALL BE INSTALLED BY OTHERS. THE
SENSORS WILL BE FURNISHED AND INSTALLED BY FAA INSTALLATION PERSONNEL.
HARDWARE SHALL BE STAINLESS STEEL. CONDUITS SHALL BE FLUSH-MOUNTED. WIRING FOR
SIDE OF BUILDING EXTERIOR AND 8’ ABOVE TOP OF FOUNDATION. ALL EXTERIOR FASTENING
OUTSIDE TEMPERATURE SENSOR WITH COVER SHALL BE INSTALLED ON THE SOUTHEAST
RUNWAY 27L ALSF-2 / 9R LOCALIZER
ENVIRONMENTAL SENSORS INSTALLATION
KE
RC
SCALE: 3/8" = 1’-0"
4’ 6’2’02’
N
| 2020-07-02T14:02:06-0500 | |
| RAFAEL CRAME |
| 2020-07-09T15:41:22-0500 | |
| LUIS N DOMINGUEZ |