This federal solicitation requests offers for construction services to establish NAVAIDS facilities serving extended Runway 9R-27L at O'Hare International Airport in Chicago, Illinois. The contractor shall provide all labor, supervision, materials, and equipment to perform the project in accordance with drawings, specifications and a 605 calendar day performance period starting November 15, 2020. The estimated price range for this procurement is between $5 million and $10 million. Offerors must have experience on similar aviation projects and adhere to the specified construction schedule. Submissions are due October 7, 2020 and shall include past performance questionnaires, insurance documentation, bonding verification, and a small business subcontracting plan. The soliciting agency is the Department of Transportation Federal Aviation Administration Southwestern Region.

View the file

Other files

File Type Posted
697DCK-20-R-00436 - Amendment 0001.pdf PDF
ord-d-als09r-e009.pdf PDF
ord-d-gs09r-c004.pdf PDF
ord-d-als09r-m001.pdf PDF
ord-d-gs27l-c006.pdf PDF
ord-d-ald09r-g024.pdf PDF
ord-d-ald09r-g015.pdf PDF
ord-d-gs27l-a001.pdf PDF
ord-d-ald09r-g008.pdf PDF
ord-d-gs27l-c003.pdf PDF
ord-d-als09r-e006.pdf PDF
ord-d-loc27l-c007.pdf PDF
ord-d-ald09r-g017.pdf PDF
ord-d-als27l-c006.pdf PDF
ord-d-als09r-c006.pdf PDF
ord-d-als27l-e006.pdf PDF
Attachment No. 12 - Required Checklist for Underground Storage Tank Installation.pdf PDF
ord-d-gs27l-e001.pdf PDF
ord-d-loc27l-c003.pdf PDF
ord-d-als09r-e005.pdf PDF
Attachment No. 20 - Past Performance Questionnaire.doc DOC document
ord-d-gs09r-a001.pdf PDF
ord-d-im09r-c001.pdf PDF
ord-d-als27l-e005.pdf PDF
ord-d-als27l-m002.pdf PDF
ord-d-als09r-e012.pdf PDF
ord-d-ald09r-g031.pdf PDF
ord-d-als09r-e008.pdf PDF
ord-d-gs27l-c004.pdf PDF
ord-d-ald09r-g004.pdf PDF
ord-d-gs09r-c005.pdf PDF
ord-d-als27l-m003.pdf PDF
ord-d-als09r-c011.pdf PDF
ord-d-als09r-m004.pdf PDF
ord-d-loc09r-c003.pdf PDF
ord-d-ald09r-g022.pdf PDF
ord-d-gs27l-c005.pdf PDF
Attachment No. 18 - Contract Insurance Requirements - Chicago Department of Aviation.pdf PDF
ord-d-als27l-c012.pdf PDF
Attachment No. 02 - Special Specifications.pdf PDF
ord-d-ald09r-g014.pdf PDF
Attachment No. 14 - Ground Resistance Testing Form.xlsx XLSX spreadsheet
ord-d-ald09r-g002.pdf PDF
ord-d-als27l-c014.pdf PDF
Attachment No. 19 - Small Business Subcontracting Plan - 697DCK-20-R-00436.pdf PDF
697DCK-20-R-00436.pdf PDF
ord-d-loc27l-c004.pdf PDF
ord-d-loc09r-c002.pdf PDF
ord-d-als09r-e013-1.pdf PDF
Attachment No. 04 - Section L-110 - Installation of Airport Underground Electrical Duct.pdf PDF
Show 40 more

Latest 50 of 158 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

o rd -d -a ls l-c .d g n

/2

/2

:2

:0

P

M G re g o ry C

T R S p e n c e r

A

B

C

D

E

F

G

H

8 7 6 5 4 3 2 1

H

G

F

E

D

C

12345678

REVDRAWING NO

DATE JCN

APPROVED BY

ISSUED BY

CHECKED

DRAWN

DESIGNED

SUBMITTED BY

REVIEWED BY

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV

DATE

APPROVED

DESCRIPTION JCN

DATE

REDLINE

APVD

A

TYP

TYP

TYP

TYP

7 TYP

6 TYP

TYP

DOWNSPOUT

TYP

3 2

9 9 8

3 12

TYP

HVAC-2 HVAC-1 TYP

TYP

19 19 19 19 19

CONTINUOUS RIDGE VENT

CONTINUOUS RIDGE VENT

H V

A C

H V

A C

H V

A C

C-18C-18

TYP.

ASTRAGAL (TYP.)

2’-6"13’-0"13’-0"13’-0"13’-0"13’-0"2’-6"

2’-0" MIN. (TYP)

SCALE: 1/4" = 1’-0"

SOUTH ELEVATION

SCALE: 1/4" = 1’-0"

SCALE: 1/4" = 1’-0"

EAST ELEVATION

WEST ELEVATION

SEE NOTE 12

04’ 4’ 8’

SCALE: 1/4" = 1’-0"

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

NOTES:

NUMBERED LEGEND:

15.

16.

DOOR. THE STAMP OR LABEL SHALL NOT BE PAINTED OVER.

INDICATED BY A STAMP OR METAL LABEL VISIBLE WHEN OPENING THE

DOORS AND DOOR FRAMES SHALL BE FIRE RATED. FIRE RATING SHALL BE

AS WELL AS AN EXTERIOR DOOR SWEEP WITH TRIM.

A TOE KICK SHALL BE PROVIDED ON THE INTERIOR SIDE OF THE DOOR,

INTERIOR AND EXTERIOR DOORS TO E/G ROOM ALONG WITH AN NFPA PLACARD.

CONTRACTOR SHALL PROVIDE A "HEARING PROTECTION REQUIRED" SIGN ON

DOWNSPOUTS SHALL BE BONDED TO THE LIGHTNING PROTECTION SYSTEM.

AND EXACT LOCATION WITH THE FAA R.E. (TYP 2 PLACES).

DENOTING THE FIRE DEPARTMENT BUILDING NUMBER. COORDINATE BUILDING NUMBER

CONTRACTOR SHALL PROVIDE AND INSTALL A SIGN ON THE BUILDING FACING ROAD APPROACH

COORDINATE SIGN SIZE, COLORING AND ROOM DESIGNATIONS WITH FAA RESIDENT ENGINEER.

ROOM. THE SIGN SHALL INCLUDE A COLOR REPRESENTATION OF THE FAA LOGO.

DESIGNATES THE ROOM’S USE, I.E., GENERATOR ROOM, LOCALIZER ROOM, EQUIPMENT

CONTRACTOR SHALL PROVIDE AND INSTALL A SIGN ON EACH EXTERIOR DOOR THAT

PROVIDED AT THE EXIT POINT OF THE DOWNSPOUT. SHALL NOT DRAIN ACROSS SIDEWALK.

CONTRACTOR SHALL INSTALL A MIDDLE GUTTER DOWNSPOUT. PROPER DRAINAGE SHALL BE

ON BOTH DOORS TO EG ROOM AND ON WALL NEAR TANK.

STORAGE TANK. COORDINATE EXACT LOCATION WITH FAA RESIDENT INSPECTOR.

CONTRACTOR TO FURNISH AND INSTALL 12"x12" NFPA PLACARD FOR UNDERGROUND

ALL EXTERIOR LIGHTS MUST BE LED TYPE WITH PHOTO CONTROL ONLY.

APPLY ANTI-SEIZE COMPOUND TO ALL THREADED EXTERIOR CONNECTIONS.

PROTECTION SYSTEM.

GUTTERS SHALL BE CONTINUOUS AND SEAMLESS AND MUST BE BONDED TO THE LIGHTNING

PROVIDE SNOW GUARDS ABOVE ALL EXTERIOR DOORS.

PROVIDE PIPE WITH EYEBOLT AND HASP FOR ALL EXTERIOR SERVICE DOORS.

6 BARE BONDED TO DOWN-CONDUCTORS.#VIA

BOND ALL EXTERIOR METALLIC ITEMS TO THE LIGHTNING PROTECTION SYSTEM

SEALER, EXTERIOR GRADE.

CONTRACTOR SHALL SEAL ALL PENETRATIONS THROUGH BUILDING WALLS WITH SILICONE

BOOK. SUBMIT SUBSTITUTIONS PER SPECIFICATIONS.

MANUFACTURER WITH A DETAILED LIST OF MATERIAL AND AN INSTALLATION INSTRUCTION

WARRANTY, PER SPECIAL SPECIFICATIONS. MATERIAL SHALL BE PROVIDED BY THE

TRIM SYSTEM SHALL BE FABRICATED BY ONE MANUFACTURER AS A COMPLETE SYSTEM, WITH

STANDING SEAM METAL ROOFING PANELS, SIDING PANELS, AND SOFFIT, FASCIA, AND

BLOCK (TYPICAL)

CONCRETE SPLASH

DOWNSPOUT WITH

FLIGHT CHECK ANTENNA

1 1/4" GRS MAST FOR

FURNISH AND INSTALL

PERSONNEL)

BY FAA INSTALLATION

(FURNISHED AND INSTALLED

FLIGHT INSPECTION ANTENNA

W/DAMPER, CD-2

INTAKE HOOD

60"W X 48"H

CD-1

W/DAMPER,

INTAKE HOOD

28"W X 4"H

FUEL TANK VENTS

DAY TANK AND U/G

RAIN CAP

E/G EXHAUST PIPE

STAINLESS STEEL

VENTILATION FAN, EF-1

SEE NOTE 9

NFPA PLACARD

BEYOND

HVAC-3

TO AVOID CONFLICTS (TYPICAL)

C-18 WITH INTERIOR EQUIPMENT

COORDINATE LOCATIONS OF UNIT

SEE NOTE 8

LIGHT, B-4 (TYPICAL)

EXTERIOR FLOOD

W/DAMPER, CD-1

INTAKE HOOD

28"W X 24"H

W/DAMPER, CD-2

INTAKE HOOD

60"W X 48"H

JUNCTION BOX

CONTROL WIRING

NEMA 3R

4" X 4" X 4"

CONDUIT. SEE NOTE 15

GROUND IN 3/4" LIQUID-TIGHT FLEXIBLE

6 INSULATED GREEN #6 AWG AND 1 #2

(STAINLESS STEEL)

HOOD W/DAMPER, BD-1

64"W X 52"H EXHAUST

GFI RECEPTACLE IN WATERPOOF HOUSING AND IN-USE COVER

DOOR SIGN, SEE NOTE 11

DISCONNECT SWITCH (UNIT C-18)

5" CONCRETE SPLASH BLOCK AND ROOF GUTTERING DOWNSPOUT

DOOR HOLDER STOP

DOOR HOLDERS WITH HOOK LATCH

SNOW GUARD ABOVE ALL EXTERIOR DOORS. (3 ROWS PER SMACA STANDARDS)

WHITE. PROVIDE SHOP DRAWINGS FOR SUBSTITUTION. SEE NOTE 1.

FASCIA SYSTEM FROM FABRAL MEETS SPECIFICATIONS. COLOR SHALL BE

20 YEAR WARRANTY ON FACTORY FINISH. DECOR-FLUSH METAL SOFFIT AND

PAINTED ALUMINIUM WITH HIDDEN FASTENERS, CONTINUOUSLY VENTED AND

YEAR WARRANTY ON FACTORY FINISH. SOFFIT SHALL BE HEAVY GAUGE

FASCIA MATERIAL SHALL BE 24 GA. STEEL WITH HIDDEN FASTENERS AND 20

SHOP DRAWINGS FOR SUBSTITUTION. COLOR SHALL BE WHITE. SEE NOTE 1.

STEEL AND NEOPRENE WASHER WITH COLOR TO MATCH PANEL. PROVIDE

SHEATHING USING STAINLESS STEEL SCREWS WITH A NO. 14 X 1" COMBINATION

FROM FABRAL MEETS SPECIFICATIONS. PANELS SHALL BE FASTENED TO

FADE AND CHALK WARRANTY. MIGHTI-RIB PBR METAL SIDING SYSTEM

10-YEAR WARRANTY AGAINST EDGE RUST AND ACID RAIN, AND 30-YEAR

STEEL, EXPOSED FASTENERS, LIFETIME FILM INTEGRITY WARRANTY.

STRUCTURAL EXPOSED FASTENER WALL SYSTEM, 26 GA., GRADE 80 KSI

INSTALLED OVER 3/4" SHEATHING.

SPECIFICATIONS. COLOR SHALL BE WHITE. PANELS SHALL BE

FROM FABRAL METAL WALL AND ROOFING SYSTEMS MEETS

ROOFING MATERIAL. SLIM SEAM METAL ROOFING (16" COVERAGE)

20 YEAR WARRANTY ON FACTORY FINISH, LIFETIME WARRANTY ON

STANDING SEAM METAL ROOFING SYSTEM, 24 GA., GRADE 40 STEEL,

BONDING STRAP, THOMPSON CAT. NO. 588, FROM DOOR FRAME TO DOOR.

4/0 AWG BARE COPPER PERIMETER GROUNDING CONDUCTOR, 30" BELOW GRADE.

FINISHED GRADE (MINIMUM).

3/4"X 10’ STAINLESS STEEL GROUNDING ELECTRODE, 12" BELOW

MIN 6’-0" ABOVE GRADE, CARRYING ROOF AND DOWN CONDUCTOR.

1" SCHEDULE 80 PVC CONDUIT FROM 12" BELOW GRADE TO

BONDED TO ROOF AND DOWN CONDUCTOR.

509X, CONNECTING PARALLEL CLAMP TO BONDING PLATE AT ITEMS TO BE

BONDING CONDUCTOR, 6 AWG BARE COPPER OR THOMPSON CAT. NO. 14X OR

TO ROOF AND DOWN CONDUCTOR.

PARALLEL CLAMP, THOMPSON CAT. NO. 565, CONNECTING BONDING CONDUCTOR

SHOWN. ITEMS NOT SHOWN BONDED DO NOT REQUIRE BONDING.

DOWN CONDUCTOR TO WALL-MOUNTED EQUIPMENT AND DOOR FRAME AS

TINNED BRONZE BONDING PLATE, THOMPSON CAT. NO. 702, BONDING ROOF AND

BASES TO ROOF WITH ROOF ADHESIVE THOMPSON CAT. NO. 731.

CAT. NO. 730 SPACED 30" O.C. MAXIMUM ON ROOF. FASTEN ADHESIVE POINT

STAMPED ADHESIVE CABLE HOLDER WITH BREAK-AWAY TABS, THOMPSON

ENCASED IN 1" DIA. SCHEDULE 80 PVC @ 12" BELOW GRADE, 8" MIN SWEEP RAD.

DIAGONALLY OPPOSITE BUILDING CORNERS. CONDUCTOR MUST BE

WELD BOTH ENDS OF THIS CONDUCTOR TO GROUNDING ELECTRODES AT

ROOF AND DOWN CONDUCTOR, THOMPSON CAT. NO. 32. EXOTHERMICALLY

ADHESIVE, M1 BY CHEMLINK.

THOMPSON CAT. NO. 71A. FASTEN ADHESIVE SADDLE TO ROOF WITH

AND ADAPTER THOMPSON CAT. NO. 665 AND ADJUSTABLE RIDGE SADDLE

LONG COPPER AIR TERMINAL WITH NICKEL-PLATED ROUNDED BLUNT TIP

AIR TERMINAL ASSEMBLY (5 REQUIRED) CONSISTING OF A 5/8" DIA X 12"

E D

M

IS

S

U E

D F

O R

NAVAIDS

IL

10/31/2019 1898272

ORD-D-ALS27L-C007

C O

N S

T R

U C

T

IO

N

ENGINEERING SERVICES

ALS

CHICAGO O’HARE INTERNATIONAL AIRPORTCHICAGO

PROJECT ENGINEER MGR: ENGINEERING

o rd -d -a ls l-c .d g n

THIS DRAWING PRODUCED ON THE AGL REGION MICROSTATION SYSTEM

ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA

RUNWAY 27L ALSF-2/9R LOCALIZER

EXTERIOR ELEVATIONS

2020-07-02T13:52:02-0500
RAFAEL CRAME
2020-07-09T14:58:52-0500
LUIS N DOMINGUEZ

File details come from the government source that posted it. Updated .