This document includes a ground resistance testing form template and details of a federal contract opportunity for construction services. The contract is for establishment of NAVAIDS facilities serving an extended runway at O'Hare International Airport in Chicago, Illinois. The opportunity involves providing all labor, materials, equipment, and construction services to complete the project in accordance with drawings, specifications and contract terms. The performance period is 605 calendar days with an anticipated start of November 15, 2020. The estimated price range for the procurement is between $5 million and $10 million. Offerors must meet minimum experience requirements and submit all required documents by the closing date of October 7, 2020, including past performance references, schedules, financial information, insurance documentation and subcontracting plans. The solicitation is being conducted by the Federal Aviation Administration Southwestern Region.
View the file
Other files
Show 40 more
Latest 50 of 158 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Ground Resistance Test Form
| TECHNICAL REFERENCE | Location (City / State) | Date Prepared | Page No. | |||||||
| DATA RECORD | ||||||||||
| Cost Center Code | Location Ident. | Facility Alpha Code | Facility Ident. Code | S | C | F | T | M |
| Reference Handbook / Directive for: GROUND RESISTANCE TESTING | |||
| FAA-STD-019f Change 1 Lightning and Surge Protection, Grounding, Bonding and Shielding Requirements for Facilities and Electronic Equipment, Ref 4.4.2 | |||
| FAA-HDBK-010 Change 1 Recommended Practices and Procedures for Lightning and Surge Protection, Grounding, Bonding and Shielding Implementation, Ref. 3.9.1 and 4.2.3 | |||
| FAA-HDBK-011 Fundamental Considerations of Lightning and Surge Protection, Grounding, Bondind and Shielding, Ref. 3.4.3 | |||
| Equipment Used: | Type of Test: | Date of Test: | Soil Condition: |
| Humidity: | Temperature: | Dimension of Ground Grid: | "C" Probe Spacing (C1,C2): | 250.0 | |||
| Depth of Probes (C2, P2): | Calculated Ground Resistance: | 3.02 Ohms | Comments: | ||||
| FIELD DATA FOR GROUND RESISTANCE TESTING | |||||||
| Distance from Grid (C1 to P2) Calculated Feet | Resistance (from Meter) Ohms | ||||||
| P21 = 0.1C = | 25 | 0.80 | |||||
| P22 = 0.2C = | 50 | 1.12 | |||||
| P23 = 0.3C = | 75 | 1.60 | |||||
| P24 = 0.4C = | 100 | 2.00 | |||||
| P25 = 0.5C = | 125 | 2.30 | |||||
| P26 = 0.6C = | 150 | 2.70 | |||||
| P27 = 0.7C = | 175 | 4.30 | |||||
| P28 = 0.8C = | 200 | 5.80 | |||||
| P29 = 0.9C = | 225 | 8.40 |
| The theoretical earth resistance is at 62% of the current probe distance. | |
| The 62% distance of this test is: | 155.0 |
Sketch the Ground Grid Plot below and indicate the position and direction of this test.
(Compass Orientation can be rotated as needed.)
Ground Resistance Plot
Measured Resistance 25 50 75 100 125 150 175 200 225 0.8 1.1200000000000001 1.6 2 2.2999999999999998 2.7 4.3 5.8 8.4 62% Resistance Point 155 10 Distance from Ground Grid (Ft)
Resistance (Ohms)
Instructions
| NOTES: | ||
| 1. All areas to be filled in by the user are shaded in a light bluish gray. All other cells are locked and cannot be selected to protect the template. | ||
| 2. Each time you open this template and edit it, it will automatically save as a new, separate document. The template will retain its original condition for future use. | ||
| 3. It is recommended that you input the ground grid area in as a plot: A' x B' first. Then calculate the distance you want to position the current probe, C2. | ||
| To obtain at least 90% accuracy on the ground resistance, the distance you use for the current probe (C2) from the point of connection to the EES [labeled as the "C" Probe Spacing (C1, C2) on the form] is recommended to be either 3 times the longest diagonal in your plot (diagonal = the square root of (A2 + B2), or, if the plot is very large, then one to two times the distance of the longest side of your plot. This is taken from FAA-HDBK-011 Chapter 3.4.3. |
4. Perform the test and record your resistance measurements for each P2 position in the table on the left of the chart. The chart will automatically update and the template will calculate the theoretical earth ground resistance at a P2 position that is 62% from the EES connection for your plot and automatically fill this value in the cell labeled "Calculated Ground Resistence". This is the official results of your test.
5. Finally, you'll notice I already have values on the form. This is so you can see how the chart plots and calculates. Go ahead and punch in some new numbers and distances to test out the form. Use old data that you have to check the form's calculated outputs.
A (ft) B (ft) image1.png