This document provides details for a federal contract solicitation for construction services for the establishment of NAVAIDS facilities serving an extended runway at O'Hare International Airport in Chicago, Illinois. The contractor shall provide all labor, materials, and equipment to perform the project in accordance with contract clauses, drawings, and specifications over a 605 calendar day performance period with an anticipated start date of November 15, 2020. The estimated price range for this procurement is between $5 million and $10 million. Interested firms must demonstrate successful completion of similar projects both in dollar amount and scope of work at an operational airport. Offers are due by October 7, 2020. Offerors must submit documentation including a cover letter, signed solicitation form, past performance references, a construction schedule, financial capability letter, liability insurance certificate, bonding letter, bid bond form, and small business subcontracting plan.

View the file

Other files

File Type Posted
697DCK-20-R-00436 - Amendment 0001.pdf PDF
ord-d-als09r-e009.pdf PDF
ord-d-gs09r-c004.pdf PDF
ord-d-als09r-m001.pdf PDF
ord-d-gs27l-c006.pdf PDF
ord-d-als27l-c007.pdf PDF
ord-d-ald09r-g024.pdf PDF
ord-d-ald09r-g015.pdf PDF
ord-d-gs27l-a001.pdf PDF
ord-d-ald09r-g008.pdf PDF
ord-d-gs27l-c003.pdf PDF
ord-d-als09r-e006.pdf PDF
ord-d-loc27l-c007.pdf PDF
ord-d-als27l-c006.pdf PDF
ord-d-als09r-c006.pdf PDF
ord-d-als27l-e006.pdf PDF
Attachment No. 12 - Required Checklist for Underground Storage Tank Installation.pdf PDF
ord-d-gs27l-e001.pdf PDF
ord-d-loc27l-c003.pdf PDF
ord-d-als09r-e005.pdf PDF
Attachment No. 20 - Past Performance Questionnaire.doc DOC document
ord-d-gs09r-a001.pdf PDF
ord-d-im09r-c001.pdf PDF
ord-d-als27l-e005.pdf PDF
ord-d-als27l-m002.pdf PDF
ord-d-als09r-e012.pdf PDF
ord-d-ald09r-g031.pdf PDF
ord-d-als09r-e008.pdf PDF
ord-d-gs27l-c004.pdf PDF
ord-d-ald09r-g004.pdf PDF
ord-d-gs09r-c005.pdf PDF
ord-d-als27l-m003.pdf PDF
ord-d-als09r-c011.pdf PDF
ord-d-als09r-m004.pdf PDF
ord-d-loc09r-c003.pdf PDF
ord-d-ald09r-g022.pdf PDF
ord-d-gs27l-c005.pdf PDF
Attachment No. 18 - Contract Insurance Requirements - Chicago Department of Aviation.pdf PDF
ord-d-als27l-c012.pdf PDF
Attachment No. 02 - Special Specifications.pdf PDF
ord-d-ald09r-g014.pdf PDF
Attachment No. 14 - Ground Resistance Testing Form.xlsx XLSX spreadsheet
ord-d-ald09r-g002.pdf PDF
ord-d-als27l-c014.pdf PDF
Attachment No. 19 - Small Business Subcontracting Plan - 697DCK-20-R-00436.pdf PDF
697DCK-20-R-00436.pdf PDF
ord-d-loc27l-c004.pdf PDF
ord-d-loc09r-c002.pdf PDF
ord-d-als09r-e013-1.pdf PDF
Attachment No. 04 - Section L-110 - Installation of Airport Underground Electrical Duct.pdf PDF
Show 40 more

Latest 50 of 158 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

o rd -d -a ld r-g .d g n

/2

/2

:0

:5

A

M G re g o ry C

T R S p e n c e r

A

B

C

D

E

F

G

H

8 7 6 5 4 3 2 1

H

G

F

E

D

C

12345678

REVDRAWING NO

DATE JCN

APPROVED BY

ISSUED BY

CHECKED

DRAWN

DESIGNED

SUBMITTED BY

REVIEWED BY

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV

DATE

APPROVED

DESCRIPTION JCN

DATE

REDLINE

APVD

A

1.

2.

(TO BE USED WHERE RELATIVELY LARGE GROUNDING SYSTEMS ARE INSTALLED)

THE RESIDENT ENGINEER.

PART OF THE PERMANENT FACILITIES FILES. THREE COPIES WILL BE PROVIDED TO

TOGETHER WITH THE RESISTANCE MEASUREMENT WORKSHEET (FIG 2) WILL BECOME

TO MONITOR AND/OR VERIFY THE EARTH ELECTRODE RESISTANCE TEST. THIS SKETCH

SIMILAR TO THAT SHOWN IN FIG. 1. AN FAA RESIDENT ENGINEER SHALL BE PRESENT

PREPARE A NEAT SKETCH OF THE FACILITY GROUND SYSTEM OF THE NEW FACILITY

NEW FACILITIES - A QUALIFIED ELECTRICIAN FURNISHED BY THE CONTRACTOR SHALL

3.

A.

THE ELECTRODE UNDER TEST.

CONNECT THE TERMINALS MARKED C1 AND P1 TOGETHER AND CONNECT THEM TO

B.

BE RUN 90 DEGREES TO ALS) KEEP C2 & P2 LEADS SEPARATED AS FAR AS POSSIBLE.

ILLUSTRATED IN FIG. 1 (FOR LONG SYSTEMS SUCH AS ALS. THE C2 PROBE LINE SHOULD

METALS. THEN LOCATE THE PROBE AS FAR AS POSSIBLE FROM THESE MATERIALS AS

SYSTEM FOR THE FACILITY AND DETERMINE THE LOCATION OF ALL SUCH BURIED

FOR PLACEMENT OF THR C2 PROBE, EXAMINE THE CONFIGURATION OF THE ELECTRODE

PIPES, POWER AND SIGNAL CABLES, FUEL TANKS ETC. IN CHOOSING THE DIRECTION

ELECTRODE UNDER TEST AND FROM THE OTHER BURIED METALS SUCH AS UTILITY

POSITION THE C2 PROBE ALONG A LINE WHICH MAXIMIZES THE DISTANCE FROM THE

C.

PLOT ENOUGH POINTS TO ACCURATELY DETERMINE WHERE CURVE LEVELS OFF.

62% OF THE C2 POSITIONS). IT MAY NOT BE NECESSARY TO PLOT THE FULL 500’.

READINGS FOR EACH C2 & P2 PROBE POSITION. (NOTE THAT THE P2 POSITIONS ARE

POSITION THE C2 PROBE AT DISTANCES AS SHOWN IN FIG. 3. RECORD THE METER

D.

CURVE LEVELS OFF. (SEE FIG.3)

CORRESPONDING C2 PROBE POSITIONS AS NECESSARY TO DETERMINE WHERE

NEXT. PLOT ON A GRAPH AS MANY RECORDED RESISTANCE READINGS VERSUS THE

E.

CURVE TO ITS ASYMPTOTIC VALUE.

THE TRUE VALUE OF RESISTANCE CAN BE ESTIMATED BY EXTRAPOLATING THE

C2

PROBE

DISTANCE

50’

100’

150’

200’

250’

300’

350’

400’

450’

500’

P2

PROBE

DISTANCE

(.62 X C2)

31’

62’

318’

279’

248’

217’

185’

154’

124’

93’

METER

READING

W

7.5

5.2

5.9

5.2

4.2’

3.4

3.8

3.4

3.4

3.1

POWER LINE

POTENTIAL

COIL

POTENTIAL

RESISTANCE

CIRCUIT

COIL

CURRENT

CURRENT

REVERSER

POTENTIAL

COMMUTATOR

C2

P2P1

C1

SWITCH

RANGE

DC GENERATOR

BEING TESTED

GROUND CONNECTOR

DEPTH OF REFERENCE RODS

RESISTANCE =

500’ 318’

279’450’

400’ 248’

217’350’

300’ 185’

154’250’

200’ 124’

93’150’

100’ 62’

31’50’

C2

PROBE

DISTANCE

P2

PROBE

DISTANCE

(.62 X C2)

RESISTANCE

METER

READING

W

50’ 100’ 150’ 200’250’300’350’400’450’500’

PROBE C2 LOCATION

R E

S

IS

T A

N C

E

W

PROBE C2 LOCATION

500’450’400’350’300’250’200’150’100’50’

R W

R E

S

IS

T A

N C

E

W

DEPTH OF REFERENCE RODS

RESISTANCE = 2.8 W

NOT TO SCALE

01 1 2

SCALE IN FEET

10.5597

REFERENCE

AUXILIARY OR

AND TURNED OVER TO THE FAA RESIDENT ENGINEER

BACKFILL. THE TEST RESULTS SHALL BE TABULATED

ALL GROUND RODS SHALL BE TESTED PRIOR TO

OR COUNTERPOISE

GROUND ROD FIELD

LINE CABLES

SIGNAL/CONTROL

RESISTANCE TEST ROUTE

C

P O

S

IT

IO

N S

1’

’15

S

IT

IO

N S

UTILITY LINES

ALTERNATE TEST ROUTE

TRUE R W = 2.8 W

LEVELS OFF.

TO ACCURATELY DETERMINE WHERE CURVE

THE FULL 500 FT. PLOT ENOUGH POINTS

IT MAY NOT BE NECESSARY TO PLOT

NOTE:

RESISTANCE

FAA FACILITY

ARRAY, RVR, AND PAPI FACILITY.

PROVIDE ONE COMPLETED SHEET FOR EACH ALSF, GLIDE SLOPE, LOCALIZER ANTENNA

(SUCH AS THE BIDDLE NULL BALANCE EARTH TESTER). PROCEED AS FOLLOWS:

WITH AN INSTRUMENT DESIGNED FOR THE PURPOSE USING THE FALL POTENTIAL METHOD

NEW AND EXISTING FACILITIES - MEASURE THE RESISTANCE OF THE ELECTRODE SYSTEM

NOT TO SCALE

FIG. 1, EARTH RESISTANCE MEASUREMENT AT A TYPICAL FACILITY

FIG. 2, RESISTANCE

MEASUREMENT WORKSHEETS

SCHEMATIC OF CONNECTORS

OF GROUND TESTERS

FIG. 3, SAMPLE OF A COMPLETED

RESISTANCE MEASUREMENT WORKSHEET

METHOD "B"

GRAPHIC SCALE

E D

M

IS

S

U E

D F

O R

NAVAIDS

IL

07/24/2019 1898272

ORD-D-ALD09R-G017

C

N S

T R

U C

T

IO

N

ENGINEERING SERVICES

ALD

CHICAGO O’HARE INTERNATIONAL AIRPORTCHICAGO

PROJECT ENGINEER MGR: ENGINEERING

o rd -d -a ld r-g .d g n

THIS DRAWING PRODUCED ON THE AGL REGION MICROSTATION SYSTEM

ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA

RUNWAY 9R-27L NAVAIDS

EARTH RESISTANCE MEASUREMENT

RC

2020-07-02T13:23:00-0500
RAFAEL CRAME
2020-07-09T12:36:23-0500
LUIS N DOMINGUEZ