ord-d-als27l-c009.pdf
PDF 447 KB Posted
- Solicitation number
- 697DCK-20-R-00436
About this file
This solicitation is for construction services for the establishment of NAVAIDS facilities serving extended Runway 9R-27L at O'Hare International Airport in Chicago, Illinois. The contractor shall provide all labor, supervision, materials, and equipment to perform the project in accordance with contract clauses, drawings, and specifications, with a performance time of 605 calendar days and an anticipated start date of November 15, 2020. The estimated price range for this procurement is between $5,000,000 to $10,000,000. Interested firms must demonstrate successful completion of similar projects both in dollar amount and scope of work at operational airports. Offers must be submitted by October 7, 2020 and include documentation of past experience, ability to meet the specified construction schedule and insurance requirements, bonding capability, and a small business subcontracting plan. Technical questions must be submitted in writing by the proposal deadline.
View the file
Other files
Show 40 more
Latest 50 of 158 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
o rd -d -a ls l-c .d g n
/2
/2
:3
:1
P
M G re g o ry C
T R S p e n c e r
A
B
C
D
E
F
G
H
8 7 6 5 4 3 2 1
H
G
F
E
D
C
12345678
REVDRAWING NO
DATE JCN
APPROVED BY
ISSUED BY
CHECKED
DRAWN
DESIGNED
SUBMITTED BY
REVIEWED BY
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV
DATE
APPROVED
DESCRIPTION JCN
DATE
REDLINE
APVD
A
SCALE: 1/2" = 1’-0"
SOUTH WALL OF REGULATOR ROOM
ELEVATION
GROUNDING PLATE
TO MULTI-POINT
2" CONDUIT
C-17
HVAC-2
SCALE: 1/2" = 1’-0"
NORTH WALL OF REGULATOR ROOM
ELEVATION
8" SQ. DUCT FOR CTRL AND GROUNDING CABLES ONLY, 12’-0" LONG
A-23R
C-10
C-1
C-5
T-2
2’-6"8’-4 7/8" 2’-7" 3’-7" 3’-7" 3’-0" 2’-9" 3’-0" 3’-6" 2’-9" 2’-0"
1’-0"
9" 8" 1’-0" 9"2’-1" 9" 2’-3" 1’-8" 6" 2’-1" 9" 2’-8" 1’-0" 1’-9" 2’-0" 1’-0" 9" 9" 9" 9" 1’-2" 10" 6"6"6"
2" CONDUIT TO
CCR NO. 1 THRU CCR NO. 5
FLASHERS
TO
TO A-23E
2" CONDUITCCR NO. 1 THRU CCR NO. 5
2" CONDUIT TO
(5" SP.)
4" CONDUIT
MC-1
2" CONDUIT
TO DIST. PANEL, D-20
C-8
C-8A
C-12 C-2
C-6
C-7
POWER CABLES, 5’-0" LONG
8" SQUARE DUCT FOR
4"x4"
NOTE 2
SEE
HVAC-1
B-5
STATION, C-14
FLASHER TEST
FE
EXIT
B-5
"7
MAIN GROUNDING PLATE
ELECTRONIC
CAUTION
CAUTION
DANGER
C-9
C-11
EXIT
FE
C-18
IN THIS SQUARE DUCT
SHALL BE INSTALLED
GROUNDING CONDUCTORS
ONLY POWER AND
ON REAR WALL
SQUARE DUCT
2" CONDUIT TO
2-2" CONDUIT WITH FLASHER CONTROL CABLE
CABLE JUNCTION BOX, A-23E
2" CONDUIT TO CONTROL
CABLE JUNCTION BOX, E-11
2" CONDUIT TO CONTROL
CONDUCTOR. SEE NOTE 1.
PERIMETER GROUNDING
1" CONDUIT TO
TO COUNTERPOISE
2" CONDUIT
DUCT
6" SQUARE
UNISRUT (TYP)
P1000 GALVANIZED
BY CONTRACTOR)
INSTALLED
(PROVIDED AND
SHUT-OFF SWITCH
E/G EMERGENCY
REMOTE
IN 1" CONDUIT
GROUNDING CONDUCTOR
2/0 AWG THWN GREEN
PANEL
CONTROL
TO E/G
TYPICAL)
(SEE NOTE 10,
3" CONDUIT
MAINTENANCE CONCRETE PADS (TYP)
(TYP)
2" EMT
NOTE 1
SEE
C-13, 1" SCH80 PVC
OUTPUT CABINET, C-4
CABLES TO HIGH VOLTAGE
2" CONDUIT WITH CONTROL
(TYPICAL)
CABLE J-BOX
CONTROL
4" X 4" X 2"
WALL (TYPICAL)
THE EXTERIOR
UNIT C-18 ON
THRU WALL TO
1" GRS NIPPLE
CABLES
CONTROL
CONDUIT FOR
3/4" EMT
CIRCUIT IN PANEL C-6
WIRE TO HVAC-1 AND HVAC-2
2 #6 AND 1 #6 INSULATED GREEN
NOTE
SEE
POWER
FOR
CABLES
CONDUIT
3/4" EMT
NEMA 1 J-BOX (TYPICAL)
6" X 6" X 4"
HVAC UNITS
TYPICAL AT
UNIT C-18, NEMA 3R,
DISCONNECT SWITCH,
CABLES
CONTROL
CONDUIT FOR
3/4" EMT
UPS
FED FROM
(TYP. OF 2)
20A REC.
EM LT
EM LT
CONDUIT (SPARE WITH PULL CORD)
OUTPUT CABINET, C-4 1-2"
CABLES FROM HIGH VOLTAGE
8 5KV LOOP POWER #2-1/C
6-2" CONDUIT-EACH WITH
SEE NOTE 10
DISTRIBUTION PANEL, C-6,
2" CONDUIT FROM POWER
DUCT
6" SQUARE
(TYPICAL)
RECEPTACLE
120V
E D
M
IS
S
U E
D F
O R
NAVAIDS
IL
10/31/2019 1898272
ORD-D-ALS27L-C009
C O
N S
T R
U C
T
IO
N
ENGINEERING SERVICES
ALS
CHICAGO O’HARE INTERNATIONAL AIRPORTCHICAGO
PROJECT ENGINEER MGR: ENGINEERING
o rd -d -a ls l-c .d g n
THIS DRAWING PRODUCED ON THE AGL REGION MICROSTATION SYSTEM
ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA
1.
2.
NEMA 1 ENCLOSURE.
INSTALL POWER SURGE ARRESTER, RV-1 (GFM) FOR DISTRIBUTION PANEL, C-6 IN 15" X 12" X 4", 3.
FOR CONNECTION (BY FAA INSTALLATION REPRESENTATIVES)
AND 12 AWG GROUND IN CONDUITS. LEAVE 3’ COIL OF EACH CONDUCTOR IN JUNCTION BOX
INSTALL JUNCTION BOXES AT LOCATIONS SHOWN AND INSTALL 2-1/C 12 AWG THWN POWER
4.
EXPANSION ANCHORS.
SECURE FLOOR-MOUNTED EQUIPMENT TO CONCRETE FLOOR USING 3/8" X 5" STEEL
5.
TERMINATED BY FAA INSTALLATION PERSONNEL
INSIDE BUILDING. CONDUIT WILL BE CUT TO REQUIRED LENGTH AND CONDUCTOR WILL BE
GROUNDING CONDUCTOR USING EXOTHERMIC WELD AND LEAVE 2’ OF CONDUCTOR COILED
TRACER HIGH ENERGY GROUNDING CONDUCTOR. BOND END OF CONDUCTOR TO PERIMETER
INSTALL 1" SCHEDULE 80 PVC CONDUIT THRU FLOOR WITH 4 AWG THWN GREEN W/RED
6.
LEAVE 3’ COIL OF WIRE IN BOX C-10 FOR CONNECTION BY FAA INSTALLATION PERSONNEL.
TRACER HIGH ENERGY GROUNDING CONDUCTOR FOR TRANSIENT SUPPRESSION BOX, C-10.
INSTALL 1" SCHEDULE 80 PVC CONDUIT THRU FLOOR WITH 4 AWG THWN GREEN W/RED
9.
10.
11.
12.
13.
DRAWING ORD-D-ALS27C-E010 AND E011. 2 SHEETS MAY BE REQUIRED.
LOCATION OF CONTRACTOR PROVIDED 11"X17" ONE LINE DIAGRAM AS REQUIRED PER
7.
NOTES:
LEGEND:
DISCONNECT SWITCH FOR HVAC UNITS (TYPICAL OF 3)
STORAGE CABINET
WORK BENCH
FLASHER TEST STATION
GROUNDING PLATE
KOHLER E/G MONITORING UNIT
UNINTERRUPTABLE POWER SUPPLY
CONTROL CABLE TRANSIENT SUPPRESSION BOX
CODEX MODEM WITH SHELF
INPUT SURGE ASSEMBLY, UNIT 15A
SAFETY DISCONNECT SWITCH, UNIT 15
50 KVA TRANSFORMER, UNIT 14
DISTRIBUTION PANEL, UNIT 13
REMOTE MONITORING SUBSYSTEM, UNIT 12
HIGH VOLTAGE OUTPUT CABINET, UNIT 6
CONSTANT CURRENT REGULATOR, UNIT 5
480 VAC INPUT CABINET, UNIT 4
SUBSTATION CONTROL & MONITOR ASSEMBLY, UNIT 3
HVAC UNIT MASTER CONTROLLER
INSIDE TEMPERATURE SENSOR (2 REQUIRED)
REGULATOR ROOM CONTROL CABLE JUNCTION BOX
E/G CONTROL CABLE JUNCTION BOX
A-23R A-23E
C-18 C-17 C-16 C-14 C-13 C-12 C-11 C-10 C-9 C-8A C-8 C-7 C-6 C-5 C-4 C-3 C-2 C-1
MC-1
T-2
INSTALLED BY FAA INSTALLATION PERSONNEL
THIS ITEM WILL BE FURNISHED BY GOVERNMENT AND *
PROPER INSTALLATION.
BY OTHERS. COORDINATE TO ENSURE
CLOUDED ITEMS TO BE INSTALLED
GRAPHIC SCALE:
SCALE: 1/2" = 1’-0"
5’1’ 2’01’
D-23 D-20
D-19 D-18 D-17 D-16 D-15 D-14 D-13 D-12 D-11 D-10 D-9 D-8 D-7 D-6 D-5 D-4 D-3 D-2
D-1
RUNWAY 27L ALSF-2 / 9R LOCALIZER
EQUIPMENT ROOM INTERIOR ELEVATIONS
KE
RC
14.
15.
16.
17.PENETRATE FLOOR SLAB.
MAINTAIN A MINIMUM OF 2" SEPARATION BETWEEN ADJACENT CONDUITS AS THEY
FOR PROPER ENTRY TO ELECTRICAL EQUIPMENT AS SHOWN AND APPROVED BY THE FAA.
THE CONTRACTOR IS RESPONSIBLE FOR LOCATING CONDUIT PENETRATIONS OF CONCRETE SLAB 8.
DISCONNECT SWITCH FOR D-16
NAVAIDS DISTRIBUTION PANEL BOARD
SWITCH
LOCALIZER ROOM DISTRIBUTION PANEL DISCONECT
EYE WASH STATION
FUEL TANK MONITOR CONTROL PANEL
POWER DISTRIBUTION PANELBOARD
STORAGE CABINET (ROLLERS)
CURRENT TRANSFORMER CABINET
SERVICE ENTRANCE DISCONNECT SWITCH
METER ENCLOSURE
E/G REMOTE CONTROL & MONITOR BOX
TRANSIENT SURGE SUPPRESSORS
DAY TANK
LOAD BANK CONTROL PANEL
AUTOMATIC LOAD BANK
BATTERY CHARGER
VENTILATION POWER AND CONTROL BOX
LOAD BANK DISCONNECT SWITCH
37.5 KVA TRANSFORMER
TRANSFER AND BYPASS SWITCH
DIESEL ENGINE GENERATOR FRAME AUTOMATIC
TEMPORARY POWER C-6 (OR ITS SUBSTITUTE) CONNECTION TO RG FROM PANEL D-20.
PLATES WITH #2 GREEN WITH ORANGE TRACER ROUTED IN 1" SCH80 PVC.
INSTALL 2" SCH80 PVC CONDUIT CONTAINING 1-500 MCM OR 2-4/0 GREEN. CONNECT BOTH
OUTLET TO BE INSTALLED TO NOT INTERFERE WITH CABINETS, WORKBENCHES, EQPT E.T.C.
THIS APPIES TO ALL WIREWAYS AT ALL FACILITIES.
MINIMUM 6 AWG INSULATED GREEN COPPER CONDUCTOR PER FAA-STD-019F, PARAGRAPH 4.2.6.4.2.
ALL INDIIVIDUAL SECTIONS OF ALL METALLIC WIREWAYS SHALL BE BONDED TOGETHER WITH A
PROVIDED SHALL BE SUITABLE FOR ELECTRICAL FIRES.
CONTRACTOR TO FURNISH AND MOUNT FIRE EXTINGUISHERS AS SHOWN. ALL FIRE EXTINGUISHERS
CONNECTING CONDUITS SHALL BE SEALED WITH DUCT SEAL AS REQUIRED BY FAA-STD-019F.
ALL FACILITIES).
PVC TO RIGID CONDUIT ADAPTERS MUST NOT BE ENCASED IN CONCRETE. (TYPICAL FOR
CARRYING ONLY GROUND WIRE SHALL BE SCHEDULE 80 PVC.
WALLS OF THE BUILDING MUST BE PVC COATED GRS CONDUIT OF THE SIZE INDICATED. CONDUITS
ALL CONDUITS THAT COME IN CONTACT WITH THE EARTH AND EXTENDING 10’ BEYOND THE OUTSIDE
TO THEIR ALSF EQUIPMENT.
COORDINATE WITH THE CITY’S CONTRACTOR ON THE LOCATION AND PROPER CONDUIT CONNECTIONS
E-17 E-16 E-15 E-14 E-12 E-10 E-9 E-8 E-7 E-6 E-5 E-4 E-3 E-2 E-1
DME EQUIPMENT RACK
STORAGE CABINET
WORK BENCH
SURGE PROTECTION UNIT FOR PANEL E-3
LOCALIZER POWER PULLBOX
MULTI-POINT GROUNDING PLATE
CONTROL CABLE JUNCTION BOX
RF JUNCTION BOX
FLOOR-MOUNTED BATTERY BOX
INNER MARKER CABINET
FAR FIELD MONITOR CABINET
FIBER OPTICS EQUIPMENT RACK
LOCALIZER ROOM DISTRIBUTION PANEL
LOCALIZER JUNCTION BOX
LOCALIZER EQUIPMENT RACK
| 2020-07-02T13:53:03-0500 | |
| RAFAEL CRAME |
| 2020-07-09T15:09:43-0500 | |
| LUIS N DOMINGUEZ |