This document provides details for a federal solicitation seeking construction services for the establishment of NAVAIDS facilities at O'Hare International Airport in Chicago, Illinois. The contractor shall furnish all labor, materials, equipment, and supervision to complete the project in accordance with contract drawings and specifications for an estimated price range of $5 million to $10 million. The performance period is 605 calendar days with an anticipated start date of November 15, 2020. Offerors must demonstrate successful past performance on similar airport projects both in dollar value and scope of work. Submissions are due by October 7, 2020 and must include a performance schedule, liability insurance documentation, bonding verification, and a small business subcontracting plan utilizing the provided form.
View the file
Other files
Show 40 more
Latest 50 of 158 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
o rd -d -a ld r-g .d g n
/2
/2
:3
:2
A
M G re g o ry C
T R S p e n c e r
A
B
C
D
E
F
G
H
8 7 6 5 4 3 2 1
H
G
F
E
D
C
12345678
REVDRAWING NO
DATE JCN
APPROVED BY
ISSUED BY
CHECKED
DRAWN
DESIGNED
SUBMITTED BY
REVIEWED BY
FEDERAL AVIATION ADMINISTRATION
DEPARTMENT OF TRANSPORTATION
REV
DATE
APPROVED
DESCRIPTION JCN
DATE
REDLINE
APVD
A
BONDING STRAP DOOR-
TO-FRAME THOMPSON
A/C
ANTENNA MAST
24" MAX
ALONG ROOF EDGE, 36" OC MAX
FAN
JB
S N
SEE NOTE 3
FLIGHT CHECK
CONDUIT TO EQUIPMENT
CABLES CONTINUE IN
TO ADJACENT TOWER (IF APPLICABLE, SEE NOTE 5)
(BOND GUARD WIRE TO SHELTER PERIMETER GROUND)
DIRECT-EARTH BURIED CABLES CONTINUE
EXOTHERMIC WELD (TYPICAL)
CAT. NO. 240X. SEE NOTE 3.
PIPE BONDING CLAMP, THOMPSON
4/0 AWG BARE (TYPICAL)
DOWN CONDUCTOR TO
EXOTHERMICALLY WELD
SERVICE ENTRANCE SWITCH
SEE NOTE 3.
36" OC MAX ON SIDING.
CAT. NO. A702 (TYPICAL).
BONDING PLATE, THOMPSON
CAT. NO. A532 (TYP OF 2)
SADDLE BASE, THOMPSON
ALONG RIDGE, 36" OC MAX
THOMPSON CAT. NO. A533
RIDGE CABLE SUPPORT,
CABLE HOLDER, THOMPSON CAT. NO. A166XX
CAT. NO. A141 (TYPICAL)
PARALLEL CLAMP, THOMPSON
CAT. NO. A588
GROUNDING CONDUCTOR
2 AWG BARE COPPER
NO. A28. SEE NOTE 1.
CONDUCTOR, THOMPSON CAT.
ALUMINUM ROOF AND DOWN
THOMPSON CAT. NO. 667BT (TYPICAL)
AIR TERMINAL WITH ADAPTER, 5/8" X 36",
GALVANIZED RIGID STEEL CONDUIT
AIR TERMINAL SUPPORT, THOMPSON CAT. NO. 82CA
2’ TO 6’
EXOTHERMIC WELD (TYPICAL)
CONNECTIONS)
GROUNDING ELECTRODE
(TYPICAL FOR ALL
EXOTHERMIC WELD
PVC CONDUIT STUB
GROUND WIRE IN 3/4"
4/0 AWG BARE COPPER
CONDUCTOR
GROUNDING ELECTRODE
SERVICE ENTRANCE
2 AWG THWN
4/0 AWG BARE COPPER, 30" DEEP
PERIMETER GROUNDING CONDUCTOR
DETAIL
NOT TO SCALE
BONDING STRAP
LOAD DISTRIBUTION WASHER
SEE TABLE "A".
1/4" DIAMETER AND GREATER.
REQUIRED FOR BOLTED CONNECTIONS
BELLEVILLE SPRING WASHERS.
BONDING BOLT
METAL ITEM TO BE BONDED
INSULATED CONDUCTORS. SEE NOTE 7.
2" PVC CONDUIT WITH TWO 4/0 AWG
(IF APPLICABLE, SEE NOTE 5)
TO ADJACENT TOWER
BOLTED CONNECTIONS FOR ELECTRICAL BONDING
MINIMUM 8" RADIUS
DOWN CONDUCTOR,
DETAIL
ROOF CONDUCTOR
EQUIVALENT
THOMPSON NO. 141 OR
MECHANICAL CONNECTOR
NOT TO SCALE
DOWN CONDUCTOR CONNECTION
CABLE HOLDER
CABLE HOLDER
DETAIL
ROOF CONDUCTOR
NOT TO SCALE
PER NOTE 7.
MAIN OR SUPPLEMENTAL GROUNDING PLATE
10’ (TYP)
ENCASED PVC CONDUIT
GROUNDING BUSHING OR TRANSITION TO CONCRETE
(TYPICAL).
A MINIMUM OF 12" DEEP
STEEL. TOP SHALL BE
3/4" X 10’ STAINLESS
GROUNDING ELECTRODE,
NOTE 9.
PER ORD-D-ALD09-G021
GROUND ACCESS WELL
E D
M
IS
S
U E
D F
O R
NAVAIDS
IL
07/24/2019 1898272
ORD-D-ALD09R-G026
C O
N S
T R
U C
T
IO
N
ENGINEERING SERVICES
ALD
CHICAGO O’HARE INTERNATIONAL AIRPORTCHICAGO
PROJECT ENGINEER MGR: ENGINEERING
o rd -d -a ld r-g .d g n
THIS DRAWING PRODUCED ON THE AGL REGION MICROSTATION SYSTEM
ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA
BOLT SIZE TORQUE (FT-LBS) NO. OF WASHERS REQ’D
1/4" 10 3
SOLON PART NO.
4-EH-70-301
21 3 5-EH-80-301
3/8" 34 3 6-EH-89-301
55 6
83 2 8-18-125-301
5/8" 3
5/16"
7/16"
9/16"
1/2"
3/4" 3
7/8" 3
3 15-H-187-1771"
7-L-70-301
N/A
10-EH-150-177
12-EH-168-177
14-EH-168-177
N/A
FROM FAA STD-019E, SECTION 4.1.1.2.4.2, TABLE II
TORQUE AND SPRING WASHER REQUIREMENTS FOR BOLTED BONDS
TABLE "A"
NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
EQUIPMENT SHELTER FOR NAVAIDS
DETAILS FOR TYPICAL WOOD-FRAMED
LIGHTNING PROTECTION AND GROUNDING
RC
MINIMUM 2’-0" FROM ANY STRUCTURES.
COORDINATE WITH FAA COTR ON EXACT PLACEMENT OF GROUND ACCESS WELL.
THE SITE SPECIFIC DRAWINGS INCLUDED IN THIS SET.
AS DOOR, AIR HANDLERS, AND JUNCTION BOXES ARE CORRECTLY SHOWN ON
INSTALLATION ON A TYPICAL SHELTER. LOCATIONS OF SHELTER FEATURES SUCH
THIS DRAWING SHOWS THE LIGHTNING PROTECTION SYSTEM WITH RESPECT TO
DETAILS.
SEE DWG E006 FOR GROUNDING PLATE ASSEMBLY, INSTALLATION, AND CONNECTION
TO CONDUIT AND PERIMETER GROUNDING CONDUCTOR WITH EXOTHERMIC WELDS.
PERIMETER GROUNDING WIRE USING 2 AWG BARE COPPER GROUND WIRE CONNECTED
EXOTHERMIC WELD. CONTINUOUS METALLIC CONDUITS SHALL BE BONDED TO
BUSHING AND CONNECTED TO THE PERIMETER GROUNDING CONDUCTOR WITH AN
A 2 AWG BARE COPPER BONDING WIRE SHALL BE CONNECTED TO GROUNDING
GROUNDING BUSHINGS SHALL BE INSTALLED AT ENDS OF METALLIC CONDUITS.
THE ANTENNA TOWER. BOND EXTERIOR METAL OBJECTS AS DESCRIBED ABOVE.
THE LIGHTNING PROTECTION COVERAGE PROVIDED BY THE AIR TERMINAL ON
CONDUCTORS ARE NOT REQUIRED FOR A GLIDE SLOPE SHELTER BECAUSE OF
EITHER SIDE OF THE ASSOCIATED STRUCTURE. AIR TERMINALS AND DOWN
SHALL CONNECT TO TWO ADDITIONAL GROUNDING ELECTRODES PLACED ON
GROUNDING CONDUCTOR SHALL EXTEND AROUND THE ANTENNA TOWER AND
FOR A GLIDE SLOPE FACILITY, THE 4/0 AWG BARE COPPER PERIMETER
SHALL BE BENT TO LESS THAN A 90° ANGLE.
NO CONDUCTOR SHALL BE BENT TO LESS THAN AN 8" RADIUS NOR
DOWN CONDUCTORS WITH 6 AWG BARE MINIMUM.
JUNCTION BOXES, AND ANY MISCELLANEOUS EXTERIOR METAL OBJECTS TO
BOND A/C, VENT FAN, HOOD, FLIGHT CHECK ANTENNA MAST, DOOR FRAME,
SHALL BE ALUMINUM.
ALL CLAMPS, BONDING DEVICES, DOWN CONDUCTORS, AND STRAPS
AND AS NOTED BELOW.
TO COMPLETE THE LIGHTNING PROTECTION SYSTEM SHOWN ON THIS SHEET
CONTRACTOR SHALL FURNISH AND INSTALL LIGHTNING PROTECTION ITEMS
9.
| 2020-07-02T13:28:40-0500 | |
| RAFAEL CRAME |
| 2020-07-09T13:31:36-0500 | |
| LUIS N DOMINGUEZ |