This is a Facility Maintenance Plan (FMP) template spreadsheet for recurring maintenance of fuel systems at Sheppard Air Force Base in Wichita Falls, TX. The document details maintenance requirements for components of the bulk fuel storage facility (#1014), including air vents, ball valves, basket strainers, check valves, filter separators, gauges, motors, pumps, and other fuel system equipment.

The template contains specific maintenance schedules (quarterly, semi-annual, annual) and procedures for each component type, along with manufacturer details, model numbers, sizes, and locations within the facility. Key systems covered include five filter separators, multiple pantograph loading arms, emergency fuel shutoff systems, overfill protection systems, and various pumps and motors. The document serves as a comprehensive maintenance tracking tool, listing inspection requirements, operator requirements, and mission impact considerations for each piece of equipment. The facility operates 24 hours per day at 117 South D Avenue and uses both above-ground and underground storage tanks for fuel storage and distribution.

View the file

Other files

File Type Posted
Sources Sought FUELS - Programmatic Rev1 7 May 25.docx DOCX document
3.4 Appendix B - Attachment 4 - SO Tracker-20210628.xlsx XLSX spreadsheet
6.0 - Appendix E ISR 15-Bulk_Fuel_Facilities FY25.xlsx XLSX spreadsheet
2.0 Appendix A RM_SO Process_20241220_PgM Reviewed Incorporated.docx DOCX document
3.1 Appendix B - Attachment 1 - Three Week Look Ahead_20230420.xlsx XLSX spreadsheet
3.2 Appendix B - Attachment 2 - Monthly Report Format 20240910.docx DOCX document
2.2 Appendix A - Attachment 2 Contractor Travel Expense Report_20240910.xlsx XLSX spreadsheet
9.0 Appendix H - Minor Repairs Incidental to Maintenance Activities POJ 20231009.xlsx XLSX spreadsheet
7.0 CUID - v2.1.pdf PDF
8.0 Appendix G_UFC 3-460-03 Maintenance Table- v4.3.pdf PDF
6.0 Appendix E ISR 14_operational_fuel_facilities FY25.xlsx XLSX spreadsheet
3.0 Appendix B Reporting Requirements_20240910.docx DOCX document
4.0 Appendix C Task Order Specifications_202401216.docx DOCX document
5.0 Appendix D Antiterrorism and OPSEC 20230206.docx DOCX document
PWS LEX FMP Template - v2.2.xlsx XLSX spreadsheet
PWS VNC FMP Template - v2.2.xlsx XLSX spreadsheet
PWS KEQ FMP Template - v2.2.xlsx XLSX spreadsheet
PWS CVZ FMP Template - v2.2.xlsx XLSX spreadsheet
PWS PBA FMP Template - v2.2.xlsx XLSX spreadsheet
PWS GRB FMP Template - v2.2.xlsx XLSX spreadsheet
PWS BRO FMP Template - v2.2.xlsx XLSX spreadsheet
PWS BAR FMP Template - v2.2.xlsx XLSX spreadsheet
PWS EFS FMP Template - v2.2.xlsx XLSX spreadsheet
PWS LAU FMP Template - v2.2.xlsx XLSX spreadsheet
PWS CHF FMP Template - v2.2.xlsx XLSX spreadsheet
PWS BEU FMP Template - v2.2.xlsx XLSX spreadsheet
PWS GDF FMP Template - v2.2.xlsx XLSX spreadsheet
PWS BLI FMP Template - v2.2.xlsx XLSX spreadsheet
PWS TKR FMP Template - v2.2.xlsx XLSX spreadsheet
PWS RBN FMP Template - v2.2.xlsx XLSX spreadsheet
PWS MAA FMP Template - v2.2.xlsx XLSX spreadsheet
PWS FSH FMP Template - v2.2.xlsx XLSX spreadsheet
PWS FSO FMP Template - v2.2.xlsx XLSX spreadsheet
PWS LRG FMP Template - v2.2.xlsx XLSX spreadsheet
PWS RRT FMP Template - v2.2.xlsx XLSX spreadsheet
PWS ALT FMP Template - v2.2.xlsx XLSX spreadsheet
PWS TUL FMP Template - v2.2.xlsx XLSX spreadsheet
PWS BL2 FMP Template - v2.2.xlsx XLSX spreadsheet
PWS ELL FMP Template - v2.2.xlsx XLSX spreadsheet
PWS WRF FMP Template - v2.2.xlsx XLSX spreadsheet
PWS LLD FMP Template - v2.2.xlsx XLSX spreadsheet
PWS DYE FMP Template - v2.2.xlsx XLSX spreadsheet
12.0 PWS Appendix K Real Property Data_20230420.xlsx XLSX spreadsheet
PWS RAN FMP Template - v2.2.xlsx XLSX spreadsheet
PWS FSM FMP Template - v2.2.xlsx XLSX spreadsheet
PWS _Fuels RMMR 20241220.docx DOCX document
Show all 46

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Administrative

LocationSite NameSheppard AFB Site #1
RPSUID3274
DLA Site CodeSHP
Hours of Operation24 Hours of Operation
Address117 South D Avenue, Wichita Falls, TX 76311
ContractContractor
Contract #
Local POCsQAE Name
QAE Phone
QAE Email
Alt QAE Name
Alt QAE Phone
Alt QAE Email
DLA/SCP POCsDLA PM Name
DLA PM Phone
DLA PM Email
SCP PM Name
SCP PM Phone
SCP PM Email
Contractor POCsContractor PM Name
Contractor PM Phone
Contractor PM Email
Contractor QC Name
Contractor QC Phone
Contractor QC Email
Contractor SM Name
Contractor SM Phone
Contractor SM Email
USACE POCsUSACE PM/COR Name
USACE PM/COR Phone
USACE PM/COR Email
USACE PE Name
USACE PE Phone
USACE PE Email
USACE KO Name
USACE KO Phone
USACE KO Email

Facility Maintenance Plan

FMP v2.2 &P of &N

Instructions:

This table shows the minimum information required. Additional details should be included based on site specific requirements. Additional POCs may be required.

General Facility Description Facility Description

Purpose:

This Facility Maintenance Plan provides guidance for Contractor personnel in the operation, inspection, and maintenance of permanently installed fuel facilities operated under the control of the Quality Assurance Evaluators. Federal, state, and local environmental laws and regulations shall be complied with if this plan is in conflict with them.

Scope:

The instructions prescribed by this plan outline general fuels maintenance information associated with fuel storage and dispensing systems and provides the minimum periodic contractor maintenance and inspection criteria requirements for the systems. This plan is to be used in conjunction with other existing directives governing fuel system operations and maintenance requirements. Conotractor will properly maintain and repair federally funded petroleum systems and facilities in order to provide compliance with applicable code, criteria, and federal, state, local and/or host nation regulations.

Fuels Facilities:

Organizational tanks, and associated dispensing equipment are maintained and operated by the owning organization. Fuel system maintenance contractors shall perform all maintenance and associated procurement actions on installed fuel systems.

Each installation under the Southwest Division contract are military land-based facilities who receive, store, distribute, and/or dispense liquid fuels.

Standard fuel system equipment includes:

a) Above Ground Sorage Stanks (AST), Underground Storage Tanks (UST)

b) Filter/separator and other filtration device maintenance access, particularly element removal.

c) Manual valves

d) Meter Registers, and Flow Meters.

e) Control Valves.

f) Pumps

g) Tank Monitoring Equipment and Instruments

h) Alarms

i) Fire Fighting Equipment

Site Specific General Information:

Facility Maintenance Plan

FMP v2.2 &P of &N

Instructions:

Include a general facility overview and description of each fuel system for the sites in accordance with UFC 3-460-01. Examples include: Bulk Storage Facilities, Aircraft Fueling Facilities, Marine and Dispensing Facilities, Ground Products Fueling Facilities, Alternate POL Facilities, and Support Facilities. Also include facility #s, facility names, fuel type, photos, and any other pertinent information.

Include Site Specific Conditions and Restrictions in this tab.

Communication Plan

Facility Maintenance Plan

FMP v2.2 &P of &N

Instructions:

Communication plan shall address in/out briefs, lines of communication, coordination for access, etc.

Safety

Facility Maintenance Plan

FMP v2.2 &P of &N

Instructions:

Site Specific Addendum and Activity Hazard Analysis, which are Attachments to the APP, specific to activities or tasks related to recurring maintenance for this site.

RM Schedule

Facility Maintenance Plan

FMP v2.2 &P of &N

Instructions:

Link RM schedule here

Task Matrix

Applicable Facility AssetsUFC System Level Maintenance FrequencySpecial Considerations
Real Property Unique Identifier
(RPUID)Real Property Facility #Real Property Facility NameOperational AreaComponent TypeBase Asset IDComponent Unique Identifier (CUID)MakeModelCapacity/SizeQSAUFC Section ReferenceAdditional Manufacturer RM RequirementsOperator/ equipment RequirementsSystem availabilityOther ContractComments
1014Bulk StoragePump HouseAutomatic Air VentsAir EliminatorArmstrong11AV0.75 in.00X3-10.2No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
1014Bulk StorageFilter PadAutomatic Air VentsAir EliminatorArmstrong11AV0.75 in.00X3-10.2No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission ImpactF/S 5
1014Bulk StorageFilter PadAutomatic Air VentsAir EliminatorArmstrong11AV0.75 in.00X3-10.2No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission ImpactF/S 4
1014Bulk StorageFilter PadAutomatic Air VentsAir EliminatorArmstrong11AV0.75 in.00X3-10.2No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission ImpactF/S 1
1014Bulk StorageFilter PadAutomatic Air VentsAir EliminatorArmstrong11AV0.75 in.00X3-10.2No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission ImpactF/S 2
1014Bulk StorageFilter PadAutomatic Air VentsAir EliminatorArmstrong11AV0.75 in.00X3-10.2No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission ImpactF/S 3
1014Bulk StoragePump HouseBack-Up Power GeneratorsGeneratorCumminsQSB5-G3N/AXX0Back-Up Power GeneratorsNo Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission ImpactBulk yard emergency power generator
1014Bulk StoragePump HouseBall ValvesSample ValveGammonIllegible0.25 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StoragePump HouseBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StoragePump HouseBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StoragePump HouseBall ValvesBall ValveConbracoApollo1.25 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact1 1/4�
1014Bulk StoragePump HouseBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StoragePump HouseBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StoragePump HouseBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StoragePump HouseBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StoragePump HouseBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StoragePump HouseBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StoragePump HouseBall ValvesBall ValveConbracoApollo1.25 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact1 1/4�
1014Bulk StoragePump HouseBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StoragePump HouseBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StoragePump HouseBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StoragePump HouseBall ValvesBall ValveConbracoApollo1.5 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StorageFilter PadBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S5
1014Bulk StorageFilter PadBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 5
1014Bulk StorageFilter PadBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 4
1014Bulk StorageFilter PadBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 4
1014Bulk StorageFilter PadBall ValvesBall ValveVelanIllegible1.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 1
1014Bulk StorageFilter PadBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 1
1014Bulk StorageFilter PadBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 1
1014Bulk StorageFilter PadBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 2
1014Bulk StorageFilter PadBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 2
1014Bulk StorageFilter PadBall ValvesBall ValveGeneralIllegible6.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 2
1014Bulk StorageFilter PadBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 3
1014Bulk StorageFilter PadBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 3
1014Bulk StorageFilter PadBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 3
1014Bulk StorageFilter PadBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 3
1014Bulk StorageFilter PadBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 3
1014Bulk StorageFilter PadBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 3
1014Bulk StorageFilter PadBall ValvesBall ValveConbracoApollo1.5 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactFilter pad low point
1014Bulk StoragePipelineBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactTK 32 Inlet
1014Bulk StoragePipelineBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactTK 32 inlet
1014Bulk StorageFilter PadBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 1
1014Bulk StorageFilter PadBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 1
1014Bulk StorageFilter PadBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 2
1014Bulk StorageFilter PadBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 2
1014Bulk StorageFilter PadBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 3
1014Bulk StorageFilter PadBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 3
1014Bulk StorageFillstandsBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactFillstand 2
1014Bulk StorageFillstandsBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactFillstand 2
1014Bulk StorageFillstandsBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOff load rack 1
1014Bulk StorageOffload RacksBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOffload 2
1014Bulk StorageOffload RacksBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOffload 2
1014Bulk StorageOffload RacksBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOffload 4
1014Bulk StorageOffload RacksBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOffload 4
1014Bulk StorageOffload RacksBall ValvesBall ValveIllegibleIllegible2.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOffload 5
1014Bulk StorageOffload RacksBall ValvesBall ValveConbracoApollo1.5 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOffload 5
1014Bulk StorageFilter PadBall ValvesBall ValveConbracoApollo1.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 4
1014Bulk StorageFilter PadBall ValvesBall ValveConbracoApollo1.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 1
1014Bulk StorageFilter PadBall ValvesBall ValveConbracoApollo1.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 2
1014Bulk StorageFilter PadBall ValvesBall ValveVelanIllegible0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 2
1014Bulk StorageFilter PadBall ValvesBall ValveVelanIllegible0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 1
1014Bulk StoragePump HouseBall ValvesBall ValveIllegibleIllegible0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StorageFilter PadBall ValvesBall ValveGammonUNK0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 2
1014Bulk StorageFilter PadBall ValvesBall ValveConbracoApollo0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 2
1014Bulk StorageFilter PadBall ValvesBall ValveIllegibleIllegible0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 3
1014Bulk StorageOffload RacksBall ValvesBall ValveConbracoApollo0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOffload 2
1014Bulk StorageOffload RacksBall ValvesBall ValveConbracoApollo0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOffload 4
1014Bulk StorageOffload RacksBall ValvesBall ValveConbracoApollo0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOffload 4
1014Bulk StoragePump HouseBall ValvesBall ValveConbracoApollo4.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StoragePump HouseBall ValvesBall ValveConbracoApollo0.25 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StoragePump HouseBall ValvesBall ValveConbracoApollo0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StoragePump HouseBall ValvesBall ValveFlow-TekTFM-16001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StoragePump HouseBall ValvesBall ValveConbracoApollo0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact1 1/4�
1014Bulk StoragePump HouseBall ValvesBall ValveGammonIllegible0.25 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StoragePump HouseBall ValvesBall ValveGammonIllegible0.25 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StoragePump HouseBall ValvesBall ValveConbracoApollo0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StoragePump HouseBall ValvesBall ValveConbracoApollo0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StoragePump HouseBall ValvesBall ValveConbracoApollo0.25 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StoragePump HouseBall ValvesBall ValveConbracoApollo0.25 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StoragePump HouseBall ValvesBall ValveConbracoApollo0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StoragePump HouseBall ValvesBall ValveConbracoApollo0.25 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StoragePump HouseBall ValvesBall ValveGammonGTP-2305V0.25 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StoragePump HouseBall ValvesBall ValveConbracoApollo0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StorageFilter PadBall ValvesBall ValveConbracoApollo0.25 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StorageFilter PadBall ValvesBall ValveConbracoApollo0.25 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StorageFilter PadBall ValvesBall ValveConbracoApollo0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StorageFilter PadBall ValvesBall ValveConbracoApollo0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 5
1014Bulk StorageFilter PadBall ValvesBall ValveGammonGTP-2305V0.25 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 5
1014Bulk StorageFilter PadBall ValvesBall ValveGammonGTP-2305V0.25 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 4
1014Bulk StorageFilter PadBall ValvesBall ValveConbracoApollo0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 4
1014Bulk StorageFilter PadBall ValvesBall ValveGammonGTP-2305V0.25 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 4
1014Bulk StorageFilter PadBall ValvesBall ValveConbracoApollo0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 1
1014Bulk StorageFilter PadBall ValvesBall ValveGammonGTP-2305V0.25 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 1
1014Bulk StorageFilter PadBall ValvesBall ValveGammonGTP-2305V0.25 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 1
1014Bulk StorageFilter PadBall ValvesBall ValveGammonGTP-2305V0.25 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 2
1014Bulk StorageFilter PadBall ValvesBall ValveConbracoApollo0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 2
1014Bulk StorageFilter PadBall ValvesBall ValveGammonGTP-2305V0.25 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 3
1014Bulk StorageFilter PadBall ValvesBall ValveGammonGTP-2305V0.25 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 3
1014Bulk StorageFilter PadBall ValvesBall ValveConbracoApollo0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 3
1014Bulk StorageFilter PadBall ValvesBall ValveConbracoApollo0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 3
1014Bulk StoragePump HouseBall ValvesBall ValveConbracoApollo0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactPRT
1014Bulk StoragePump HouseBall ValvesBall ValveConbracoApollo0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactPRT
1014Bulk StoragePipelineBall ValvesBall ValveConbracoApollo0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactTK 32 inlet
1014Bulk StoragePipelineBall ValvesBall ValveFlow-TekRPTFE1.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactTK 32 Outlet
1014Bulk StoragePipelineBall ValvesBall ValveFlow-TekRPTFE1.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactTK 32 Outlet
1014Bulk StoragePipelineBall ValvesBall ValveConbracoApollo2.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactTK 32 Outlet
1014Bulk StoragePipelineBall ValvesBall ValveFlow-TekRPTFE1.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactTK 33 Inlet
1014Bulk StoragePipelineBall ValvesBall ValveFlow-TekRPTFE1.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactTK 33 Inlet
1014Bulk StoragePipelineBall ValvesBall ValveConbracoApollo2.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactTK 33 Inlet
1014Bulk StoragePipelineBall ValvesBall ValveFlow-TekRPTFE1.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactTK 33 Outlet
1014Bulk StoragePipelineBall ValvesBall ValveFlow-TekRPTFE1.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactTK 33 Outlet
1014Bulk StoragePipelineBall ValvesBall ValveConbracoApollo2.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactTK 33 Outlet
1014Bulk StoragePipelineBall ValvesBall ValveFlow-TekRPTFE1.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactTK 34 Inlet
1014Bulk StoragePipelineBall ValvesBall ValveFlow-TekRPTFE1.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactTK 34 Inlet
1014Bulk StoragePipelineBall ValvesBall ValveConbracoApollo2.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactTK 34 Inlet
1014Bulk StoragePipelineBall ValvesBall ValveFlow-TekRPTFE1.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactTK 34 Outlet
1014Bulk StoragePipelineBall ValvesBall ValveFlow-TekRPTFE1.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactTK 34 Outlet
1014Bulk StoragePipelineBall ValvesBall ValveConbracoApollo2.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactTK 34 Outlet
1014Bulk StoragePipelineBall ValvesBall ValveConbracoApollo2.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactTK 34 Outlet
1014Bulk StoragePipelineBall ValvesBall ValveConbracoApollo2.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactTK 34 Inlet
1014Bulk StorageFillstandsBall ValvesBall ValveFlow-TekRPTFE1.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactFill stand 1
1014Bulk StorageFillstandsBall ValvesBall ValveFlow-TekRPTFE1.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactFill stand 1
1014Bulk StorageFillstandsBall ValvesBall ValveFlow-TekRPTFE1.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactFill stand 3
1014Bulk StorageFillstandsBall ValvesBall ValveFlow-TekRPTFE1.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactFill stand 3
1014Bulk StorageFillstandsBall ValvesBall ValveConbracoApollo4.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactFill stand 3
1014Bulk StorageFillstandsBall ValvesBall ValveConbracoApollo0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOff load rack 1
1014Bulk StorageFillstandsBall ValvesBall ValveFlow-TekRPTFE1.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOff load rack 1
1014Bulk StorageOffload RacksBall ValvesBall ValveConbracoApollo0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOffload 3
1014Bulk StorageOffload RacksBall ValvesBall ValveFlow-TekRPTFE1.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOffload 3
1014Bulk StorageOffload RacksBall ValvesBall ValveFlow-TekRPTFE1.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOffload 3
1014Bulk StorageOffload RacksBall ValvesBall ValveConbracoApollo0.25 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOffload 4
1014Bulk StorageOffload RacksBall ValvesBall ValveUNKUNK0.25 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOffload 5
1014Bulk StorageOffload RacksBall ValvesBall ValveFlow-TekRPTFE1.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOffload 5
1014Bulk StorageOffload RacksBall ValvesBall ValveConbracoApollo0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOffload 5
1014Bulk StorageOffload RacksBall ValvesBall ValveConbracoApollo0.25 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOffload 5
1014Bulk StorageOffload RacksBall ValvesBall ValveFlow-TekRPTFE4.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOffload 5
1014Bulk StorageOffload RacksBall ValvesBall ValveNibcoIllegible1.5 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOffload 5
1014Bulk StorageOffload RacksBall ValvesBall ValveConbracoApollo0.5 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOffload 5
1014Bulk StorageFilter PadBall ValvesBall ValveFlow-TekIllegible6.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 4
1014Bulk StorageFilter PadBall ValvesBall ValveBrayIllegible6.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 5
1014Bulk StorageFilter PadBall ValvesBall ValveBrayIllegible6.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 4
1014Bulk StorageFillstandsBall ValvesBall ValveIllegibleIllegible4.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactFill stand 1
1014Bulk StorageFillstandsBall ValvesBall ValveIllegibleIllegible4.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactFill stand 3
1014Bulk StorageFillstandsBall ValvesBall ValveIllegibleIllegible4.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactFillstand 2
1014Bulk StorageOffload RacksBall ValvesBall ValveIllegibleIllegible4.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOffload 2
1014Bulk StorageOffload RacksBall ValvesBall ValveIllegibleIllegible4.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOffload 4
1014Bulk StorageOffload RacksBall ValvesBall ValveIllegibleIllegible4.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOffload 5
1014Bulk StorageFilter PadBall ValvesBall ValveFlow-TekCF8M6.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1014Bulk StorageFilter PadBall ValvesBall ValveConbracoApollo8.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactF/S 4/5 bypass line
1014Bulk StorageFillstandsBall ValvesBall ValveConbracoApollo6.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactFillstand 2
1014Bulk StorageFillstandsBall ValvesBall ValveConbracoApollo4.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOff load rack 1
1014Bulk StorageOffload RacksBall ValvesBall ValveConbracoApollo4.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactOffload 3
1014Bulk StoragePump HouseBasket StrainersBasket StrainerKeckleyIllegible6.0 in.XX03-6.4Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyDaily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyNo Mission Impact
1014Bulk StoragePump HouseBasket StrainersBasket StrainerKeckleyIllegible6.0 in.XX03-6.4Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyDaily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyNo Mission Impact
1014Bulk StoragePump HouseBasket StrainersBasket StrainerKeckleyIllegible6.0 in.XX03-6.4Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyDaily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyNo Mission Impact
1014Bulk StoragePump HouseBasket StrainersBasket StrainerKeckleyIllegible6.0 in.XX03-6.4Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyDaily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyNo Mission Impact
1014Bulk StorageFillstandsBasket StrainersBasket StrainerTitanIllegible4.0 in.XX03-6.4Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyDaily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyNo Mission ImpactFill stand 1
1014Bulk StorageFillstandsBasket StrainersBasket StrainerTitanIllegible6.0 in.XX03-6.4Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyDaily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyNo Mission ImpactBetween fill stand 2 and 1
1014Bulk StorageFillstandsBasket StrainersBasket StrainerMulerIllegible4.0 in.XX03-6.4Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyDaily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyNo Mission ImpactOffl load rack 1
1014Bulk StorageOffload RacksBasket StrainersBasket StrainerMuellerIllegible4.0 in.XX03-6.4Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyDaily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyNo Mission ImpactOffload 2
1014Bulk StorageOffload RacksBasket StrainersBasket StrainerUNKIllegible4.0 in.XX03-6.4Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyDaily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyNo Mission ImpactOffload 3
1014Bulk StorageOffload RacksBasket StrainersBasket StrainerMuellerIllegible4.0 in.XX03-6.4Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyDaily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyNo Mission ImpactOffload 4
1014Bulk StorageOffload RacksBasket StrainersBasket StrainerUNKIllegible4.0 in.XX03-6.4Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyDaily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyNo Mission ImpactOffload 5
1014Bulk StorageOffload RacksBasket StrainersBasket StrainerHaywardIllegible2.0 in.XX03-6.4Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyDaily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyNo Mission ImpactOffload 5
1014Bulk StorageFilter PadCanopiesCanopyUnmarkedUnmarkedN/AXX011-2.2No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
1014Bulk StorageOffload RacksCanopiesCanopyUnmarkedUnmarkedN/AXX011-2.2No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission ImpactCanopy 1 at offload racks
1014Bulk StorageOffload RacksCanopiesCanopyUnmarkedUnmarkedN/AXX011-2.2No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission ImpactCanopy 2
1014Bulk StorageOffload RacksCentrifugal PumpsPumpGouldsIllegibleIllegibleXXX3-8.1During routine pump inspections only the easy to monitor factors such as pressure, temperature, vibration etc can be checKed. But during quarterly inspections, shaft alignment and oil levels should also be checked. Change Oil AnnuallyNo Operator RequirementNo Mission ImpactOffload 5
1014Bulk StorageFillstandsCheck ValvesCheck ValveApollo62104010.75 in.XX06-6.2.8Visual for damage, leaks, tightness.No Operator RequirementPartial System OOSOff load rack 1
1014Bulk StorageFillstandsCheck ValvesCheck ValveWheatlyIllegible4.0 in.XX06-6.2.8Visual for damage, leaks, tightness.No Operator RequirementPartial System OOSOff load rack 1
1014Bulk StorageOffload RacksCheck ValvesCheck ValveApollo62104010.75 in.XX06-6.2.8Visual for damage, leaks, tightness.No Operator RequirementPartial System OOSOffload 2
1014Bulk StorageOffload RacksCheck ValvesCheck ValveWheatley910-45027-1214.0 in.XX06-6.2.8Visual for damage, leaks, tightness.No Operator RequirementPartial System OOSOffload 2
1014Bulk StorageOffload RacksCheck ValvesCheck ValveApollo62104010.75 in.XX06-6.2.8Visual for damage, leaks, tightness.No Operator RequirementPartial System OOSOffload 3
1014Bulk StorageOffload RacksCheck ValvesCheck ValveWheatlyIllegible4.0 in.XX06-6.2.8Visual for damage, leaks, tightness.No Operator RequirementPartial System OOSOffload 3
1014Bulk StorageOffload RacksCheck ValvesCheck ValveApollo62104010.75 in.XX06-6.2.8Visual for damage, leaks, tightness.No Operator RequirementPartial System OOSOffload 4
1014Bulk StorageOffload RacksCheck ValvesCheck ValveWheatlyIllegible4.0 in.XX06-6.2.8Visual for damage, leaks, tightness.No Operator RequirementPartial System OOSOffload 4
1014Bulk StorageOffload RacksCheck ValvesCheck ValveApollo62104010.75 in.XX06-6.2.8Visual for damage, leaks, tightness.No Operator RequirementPartial System OOSOffload 5
1014Bulk StorageOffload RacksCheck ValvesCheck ValveIllegibleIllegible4.0 in.XX06-6.2.8Visual for damage, leaks, tightness.No Operator RequirementPartial System OOSOffload 5
1014Bulk StorageOffload RacksCheck ValvesCheck ValveApollo62104011.5 in.XX06-6.2.8Visual for damage, leaks, tightness.No Operator RequirementPartial System OOSOffload 5
1014Bulk StoragePipelineCheck ValvesCheck ValveApollo62104010.75 in.XX06-6.2.8Visual for damage, leaks, tightness.No Operator RequirementPartial System OOSTK 32 inlet
1014Bulk StoragePump HouseCheck ValvesCheck ValveMeritVSC102-120.75 in.XX06-6.2.8Visual for damage, leaks, tightness.No Operator RequirementPartial System OOS
1014Bulk StorageFilter PadDifferential Pressure GaugesDP GaugeGammonGTP-534-300 - 30 PSIXXX6-7.2Periodic calibration of this instrument is unnecessary because the graduated scale is made to match the characteristics (load/deflection curve) of the spring. If the spring loses some of its strength for some reason, the ”free length” must be shortened. Afull length spring will always provide accurate readings. This is a fundamental truth about compression springs. This spring is at its “free full length” when there is zero differential pressure; the top of the piston is then in the “zero” band of the graduated scale.Quarterly - Clean outside of gauge glass.Partial System OOSF/S 5