This is a Facility Maintenance Plan (FMP) template spreadsheet for recurring maintenance of fuel systems at Sheppard Air Force Base in Wichita Falls, TX. The document details maintenance requirements for components of the bulk fuel storage facility (#1014), including air vents, ball valves, basket strainers, check valves, filter separators, gauges, motors, pumps, and other fuel system equipment.
The template contains specific maintenance schedules (quarterly, semi-annual, annual) and procedures for each component type, along with manufacturer details, model numbers, sizes, and locations within the facility. Key systems covered include five filter separators, multiple pantograph loading arms, emergency fuel shutoff systems, overfill protection systems, and various pumps and motors. The document serves as a comprehensive maintenance tracking tool, listing inspection requirements, operator requirements, and mission impact considerations for each piece of equipment. The facility operates 24 hours per day at 117 South D Avenue and uses both above-ground and underground storage tanks for fuel storage and distribution.
View the file
Other files
Show all 46
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Administrative
| Location | Site Name | Sheppard AFB Site #1 |
| RPSUID | 3274 | |
| DLA Site Code | SHP | |
| Hours of Operation | 24 Hours of Operation | |
| Address | 117 South D Avenue, Wichita Falls, TX 76311 | |
| Contract | Contractor | |
| Contract # | ||
| Local POCs | QAE Name | |
| QAE Phone | ||
| QAE Email | ||
| Alt QAE Name | ||
| Alt QAE Phone | ||
| Alt QAE Email | ||
| DLA/SCP POCs | DLA PM Name | |
| DLA PM Phone | ||
| DLA PM Email | ||
| SCP PM Name | ||
| SCP PM Phone | ||
| SCP PM Email | ||
| Contractor POCs | Contractor PM Name | |
| Contractor PM Phone | ||
| Contractor PM Email | ||
| Contractor QC Name | ||
| Contractor QC Phone | ||
| Contractor QC Email | ||
| Contractor SM Name | ||
| Contractor SM Phone | ||
| Contractor SM Email | ||
| USACE POCs | USACE PM/COR Name | |
| USACE PM/COR Phone | ||
| USACE PM/COR Email | ||
| USACE PE Name | ||
| USACE PE Phone | ||
| USACE PE Email | ||
| USACE KO Name | ||
| USACE KO Phone | ||
| USACE KO Email |
Facility Maintenance Plan
FMP v2.2 &P of &N
Instructions:
This table shows the minimum information required. Additional details should be included based on site specific requirements. Additional POCs may be required.
General Facility Description Facility Description
Purpose:
This Facility Maintenance Plan provides guidance for Contractor personnel in the operation, inspection, and maintenance of permanently installed fuel facilities operated under the control of the Quality Assurance Evaluators. Federal, state, and local environmental laws and regulations shall be complied with if this plan is in conflict with them.
Scope:
The instructions prescribed by this plan outline general fuels maintenance information associated with fuel storage and dispensing systems and provides the minimum periodic contractor maintenance and inspection criteria requirements for the systems. This plan is to be used in conjunction with other existing directives governing fuel system operations and maintenance requirements. Conotractor will properly maintain and repair federally funded petroleum systems and facilities in order to provide compliance with applicable code, criteria, and federal, state, local and/or host nation regulations.
Fuels Facilities:
Organizational tanks, and associated dispensing equipment are maintained and operated by the owning organization. Fuel system maintenance contractors shall perform all maintenance and associated procurement actions on installed fuel systems.
Each installation under the Southwest Division contract are military land-based facilities who receive, store, distribute, and/or dispense liquid fuels.
Standard fuel system equipment includes:
a) Above Ground Sorage Stanks (AST), Underground Storage Tanks (UST)
b) Filter/separator and other filtration device maintenance access, particularly element removal.
c) Manual valves
d) Meter Registers, and Flow Meters.
e) Control Valves.
f) Pumps
g) Tank Monitoring Equipment and Instruments
h) Alarms
i) Fire Fighting Equipment
Site Specific General Information:
Facility Maintenance Plan
FMP v2.2 &P of &N
Instructions:
Include a general facility overview and description of each fuel system for the sites in accordance with UFC 3-460-01. Examples include: Bulk Storage Facilities, Aircraft Fueling Facilities, Marine and Dispensing Facilities, Ground Products Fueling Facilities, Alternate POL Facilities, and Support Facilities. Also include facility #s, facility names, fuel type, photos, and any other pertinent information.
Include Site Specific Conditions and Restrictions in this tab.
Communication Plan
Facility Maintenance Plan
FMP v2.2 &P of &N
Instructions:
Communication plan shall address in/out briefs, lines of communication, coordination for access, etc.
Safety
Facility Maintenance Plan
FMP v2.2 &P of &N
Instructions:
Site Specific Addendum and Activity Hazard Analysis, which are Attachments to the APP, specific to activities or tasks related to recurring maintenance for this site.
RM Schedule
Facility Maintenance Plan
FMP v2.2 &P of &N
Instructions:
Link RM schedule here
Task Matrix
| Applicable Facility Assets | UFC System Level Maintenance Frequency | Special Considerations | |||||||||||||||||
| Real Property Unique Identifier | |||||||||||||||||||
| (RPUID) | Real Property Facility # | Real Property Facility Name | Operational Area | Component Type | Base Asset ID | Component Unique Identifier (CUID) | Make | Model | Capacity/Size | Q | S | A | UFC Section Reference | Additional Manufacturer RM Requirements | Operator/ equipment Requirements | System availability | Other Contract | Comments | |
| 1014 | Bulk Storage | Pump House | Automatic Air Vents | Air Eliminator | Armstrong | 11AV | 0.75 in. | 0 | 0 | X | 3-10.2 | No Additional Manufacturer Requirements | No Operator/equipment Requirements | No Mission Impact | |||||
| 1014 | Bulk Storage | Filter Pad | Automatic Air Vents | Air Eliminator | Armstrong | 11AV | 0.75 in. | 0 | 0 | X | 3-10.2 | No Additional Manufacturer Requirements | No Operator/equipment Requirements | No Mission Impact | F/S 5 | ||||
| 1014 | Bulk Storage | Filter Pad | Automatic Air Vents | Air Eliminator | Armstrong | 11AV | 0.75 in. | 0 | 0 | X | 3-10.2 | No Additional Manufacturer Requirements | No Operator/equipment Requirements | No Mission Impact | F/S 4 | ||||
| 1014 | Bulk Storage | Filter Pad | Automatic Air Vents | Air Eliminator | Armstrong | 11AV | 0.75 in. | 0 | 0 | X | 3-10.2 | No Additional Manufacturer Requirements | No Operator/equipment Requirements | No Mission Impact | F/S 1 | ||||
| 1014 | Bulk Storage | Filter Pad | Automatic Air Vents | Air Eliminator | Armstrong | 11AV | 0.75 in. | 0 | 0 | X | 3-10.2 | No Additional Manufacturer Requirements | No Operator/equipment Requirements | No Mission Impact | F/S 2 | ||||
| 1014 | Bulk Storage | Filter Pad | Automatic Air Vents | Air Eliminator | Armstrong | 11AV | 0.75 in. | 0 | 0 | X | 3-10.2 | No Additional Manufacturer Requirements | No Operator/equipment Requirements | No Mission Impact | F/S 3 | ||||
| 1014 | Bulk Storage | Pump House | Back-Up Power Generators | Generator | Cummins | QSB5-G3 | N/A | X | X | 0 | Back-Up Power Generators | No Additional Manufacturer Requirements | No Operator/equipment Requirements | No Mission Impact | Bulk yard emergency power generator | ||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Sample Valve | Gammon | Illegible | 0.25 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Conbraco | Apollo | 1.25 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | 1 1/4� | ||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Conbraco | Apollo | 1.25 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | 1 1/4� | ||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Conbraco | Apollo | 1.5 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S5 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 5 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 4 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 4 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Velan | Illegible | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 1 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 1 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 1 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 2 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 2 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | General | Illegible | 6.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 2 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 3 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 3 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 3 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 3 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 3 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 3 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Conbraco | Apollo | 1.5 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Filter pad low point | ||||
| 1014 | Bulk Storage | Pipeline | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | TK 32 Inlet | ||||
| 1014 | Bulk Storage | Pipeline | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | TK 32 inlet | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 1 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 1 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 2 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 2 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 3 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 3 | ||||
| 1014 | Bulk Storage | Fillstands | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Fillstand 2 | ||||
| 1014 | Bulk Storage | Fillstands | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Fillstand 2 | ||||
| 1014 | Bulk Storage | Fillstands | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Off load rack 1 | ||||
| 1014 | Bulk Storage | Offload Racks | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Offload 2 | ||||
| 1014 | Bulk Storage | Offload Racks | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Offload 2 | ||||
| 1014 | Bulk Storage | Offload Racks | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Offload 4 | ||||
| 1014 | Bulk Storage | Offload Racks | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Offload 4 | ||||
| 1014 | Bulk Storage | Offload Racks | Ball Valves | Ball Valve | Illegible | Illegible | 2.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Offload 5 | ||||
| 1014 | Bulk Storage | Offload Racks | Ball Valves | Ball Valve | Conbraco | Apollo | 1.5 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Offload 5 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Conbraco | Apollo | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 4 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Conbraco | Apollo | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 1 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Conbraco | Apollo | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 2 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Velan | Illegible | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 2 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Velan | Illegible | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 1 | ||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Illegible | Illegible | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Gammon | UNK | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 2 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Conbraco | Apollo | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 2 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Illegible | Illegible | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 3 | ||||
| 1014 | Bulk Storage | Offload Racks | Ball Valves | Ball Valve | Conbraco | Apollo | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Offload 2 | ||||
| 1014 | Bulk Storage | Offload Racks | Ball Valves | Ball Valve | Conbraco | Apollo | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Offload 4 | ||||
| 1014 | Bulk Storage | Offload Racks | Ball Valves | Ball Valve | Conbraco | Apollo | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Offload 4 | ||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Conbraco | Apollo | 4.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Conbraco | Apollo | 0.25 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Conbraco | Apollo | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Flow-Tek | TFM-1600 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Conbraco | Apollo | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | 1 1/4� | ||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Gammon | Illegible | 0.25 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Gammon | Illegible | 0.25 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Conbraco | Apollo | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Conbraco | Apollo | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Conbraco | Apollo | 0.25 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Conbraco | Apollo | 0.25 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Conbraco | Apollo | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Conbraco | Apollo | 0.25 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Gammon | GTP-2305V | 0.25 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Conbraco | Apollo | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Conbraco | Apollo | 0.25 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Conbraco | Apollo | 0.25 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Conbraco | Apollo | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Conbraco | Apollo | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 5 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Gammon | GTP-2305V | 0.25 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 5 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Gammon | GTP-2305V | 0.25 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 4 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Conbraco | Apollo | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 4 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Gammon | GTP-2305V | 0.25 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 4 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Conbraco | Apollo | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 1 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Gammon | GTP-2305V | 0.25 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 1 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Gammon | GTP-2305V | 0.25 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 1 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Gammon | GTP-2305V | 0.25 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 2 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Conbraco | Apollo | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 2 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Gammon | GTP-2305V | 0.25 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 3 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Gammon | GTP-2305V | 0.25 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 3 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Conbraco | Apollo | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 3 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Conbraco | Apollo | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 3 | ||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Conbraco | Apollo | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | PRT | ||||
| 1014 | Bulk Storage | Pump House | Ball Valves | Ball Valve | Conbraco | Apollo | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | PRT | ||||
| 1014 | Bulk Storage | Pipeline | Ball Valves | Ball Valve | Conbraco | Apollo | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | TK 32 inlet | ||||
| 1014 | Bulk Storage | Pipeline | Ball Valves | Ball Valve | Flow-Tek | RPTFE | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | TK 32 Outlet | ||||
| 1014 | Bulk Storage | Pipeline | Ball Valves | Ball Valve | Flow-Tek | RPTFE | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | TK 32 Outlet | ||||
| 1014 | Bulk Storage | Pipeline | Ball Valves | Ball Valve | Conbraco | Apollo | 2.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | TK 32 Outlet | ||||
| 1014 | Bulk Storage | Pipeline | Ball Valves | Ball Valve | Flow-Tek | RPTFE | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | TK 33 Inlet | ||||
| 1014 | Bulk Storage | Pipeline | Ball Valves | Ball Valve | Flow-Tek | RPTFE | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | TK 33 Inlet | ||||
| 1014 | Bulk Storage | Pipeline | Ball Valves | Ball Valve | Conbraco | Apollo | 2.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | TK 33 Inlet | ||||
| 1014 | Bulk Storage | Pipeline | Ball Valves | Ball Valve | Flow-Tek | RPTFE | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | TK 33 Outlet | ||||
| 1014 | Bulk Storage | Pipeline | Ball Valves | Ball Valve | Flow-Tek | RPTFE | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | TK 33 Outlet | ||||
| 1014 | Bulk Storage | Pipeline | Ball Valves | Ball Valve | Conbraco | Apollo | 2.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | TK 33 Outlet | ||||
| 1014 | Bulk Storage | Pipeline | Ball Valves | Ball Valve | Flow-Tek | RPTFE | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | TK 34 Inlet | ||||
| 1014 | Bulk Storage | Pipeline | Ball Valves | Ball Valve | Flow-Tek | RPTFE | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | TK 34 Inlet | ||||
| 1014 | Bulk Storage | Pipeline | Ball Valves | Ball Valve | Conbraco | Apollo | 2.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | TK 34 Inlet | ||||
| 1014 | Bulk Storage | Pipeline | Ball Valves | Ball Valve | Flow-Tek | RPTFE | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | TK 34 Outlet | ||||
| 1014 | Bulk Storage | Pipeline | Ball Valves | Ball Valve | Flow-Tek | RPTFE | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | TK 34 Outlet | ||||
| 1014 | Bulk Storage | Pipeline | Ball Valves | Ball Valve | Conbraco | Apollo | 2.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | TK 34 Outlet | ||||
| 1014 | Bulk Storage | Pipeline | Ball Valves | Ball Valve | Conbraco | Apollo | 2.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | TK 34 Outlet | ||||
| 1014 | Bulk Storage | Pipeline | Ball Valves | Ball Valve | Conbraco | Apollo | 2.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | TK 34 Inlet | ||||
| 1014 | Bulk Storage | Fillstands | Ball Valves | Ball Valve | Flow-Tek | RPTFE | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Fill stand 1 | ||||
| 1014 | Bulk Storage | Fillstands | Ball Valves | Ball Valve | Flow-Tek | RPTFE | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Fill stand 1 | ||||
| 1014 | Bulk Storage | Fillstands | Ball Valves | Ball Valve | Flow-Tek | RPTFE | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Fill stand 3 | ||||
| 1014 | Bulk Storage | Fillstands | Ball Valves | Ball Valve | Flow-Tek | RPTFE | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Fill stand 3 | ||||
| 1014 | Bulk Storage | Fillstands | Ball Valves | Ball Valve | Conbraco | Apollo | 4.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Fill stand 3 | ||||
| 1014 | Bulk Storage | Fillstands | Ball Valves | Ball Valve | Conbraco | Apollo | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Off load rack 1 | ||||
| 1014 | Bulk Storage | Fillstands | Ball Valves | Ball Valve | Flow-Tek | RPTFE | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Off load rack 1 | ||||
| 1014 | Bulk Storage | Offload Racks | Ball Valves | Ball Valve | Conbraco | Apollo | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Offload 3 | ||||
| 1014 | Bulk Storage | Offload Racks | Ball Valves | Ball Valve | Flow-Tek | RPTFE | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Offload 3 | ||||
| 1014 | Bulk Storage | Offload Racks | Ball Valves | Ball Valve | Flow-Tek | RPTFE | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Offload 3 | ||||
| 1014 | Bulk Storage | Offload Racks | Ball Valves | Ball Valve | Conbraco | Apollo | 0.25 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Offload 4 | ||||
| 1014 | Bulk Storage | Offload Racks | Ball Valves | Ball Valve | UNK | UNK | 0.25 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Offload 5 | ||||
| 1014 | Bulk Storage | Offload Racks | Ball Valves | Ball Valve | Flow-Tek | RPTFE | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Offload 5 | ||||
| 1014 | Bulk Storage | Offload Racks | Ball Valves | Ball Valve | Conbraco | Apollo | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Offload 5 | ||||
| 1014 | Bulk Storage | Offload Racks | Ball Valves | Ball Valve | Conbraco | Apollo | 0.25 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Offload 5 | ||||
| 1014 | Bulk Storage | Offload Racks | Ball Valves | Ball Valve | Flow-Tek | RPTFE | 4.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Offload 5 | ||||
| 1014 | Bulk Storage | Offload Racks | Ball Valves | Ball Valve | Nibco | Illegible | 1.5 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Offload 5 | ||||
| 1014 | Bulk Storage | Offload Racks | Ball Valves | Ball Valve | Conbraco | Apollo | 0.5 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Offload 5 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Flow-Tek | Illegible | 6.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 4 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Bray | Illegible | 6.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 5 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Bray | Illegible | 6.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 4 | ||||
| 1014 | Bulk Storage | Fillstands | Ball Valves | Ball Valve | Illegible | Illegible | 4.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Fill stand 1 | ||||
| 1014 | Bulk Storage | Fillstands | Ball Valves | Ball Valve | Illegible | Illegible | 4.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Fill stand 3 | ||||
| 1014 | Bulk Storage | Fillstands | Ball Valves | Ball Valve | Illegible | Illegible | 4.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Fillstand 2 | ||||
| 1014 | Bulk Storage | Offload Racks | Ball Valves | Ball Valve | Illegible | Illegible | 4.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Offload 2 | ||||
| 1014 | Bulk Storage | Offload Racks | Ball Valves | Ball Valve | Illegible | Illegible | 4.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Offload 4 | ||||
| 1014 | Bulk Storage | Offload Racks | Ball Valves | Ball Valve | Illegible | Illegible | 4.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Offload 5 | ||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Flow-Tek | CF8M | 6.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | |||||
| 1014 | Bulk Storage | Filter Pad | Ball Valves | Ball Valve | Conbraco | Apollo | 8.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | F/S 4/5 bypass line | ||||
| 1014 | Bulk Storage | Fillstands | Ball Valves | Ball Valve | Conbraco | Apollo | 6.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Fillstand 2 | ||||
| 1014 | Bulk Storage | Fillstands | Ball Valves | Ball Valve | Conbraco | Apollo | 4.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Off load rack 1 | ||||
| 1014 | Bulk Storage | Offload Racks | Ball Valves | Ball Valve | Conbraco | Apollo | 4.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | Offload 3 | ||||
| 1014 | Bulk Storage | Pump House | Basket Strainers | Basket Strainer | Keckley | Illegible | 6.0 in. | X | X | 0 | 3-6.4 | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | |||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | ||||||||||||||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | No Mission Impact | ||||||||||||||||||
| 1014 | Bulk Storage | Pump House | Basket Strainers | Basket Strainer | Keckley | Illegible | 6.0 in. | X | X | 0 | 3-6.4 | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | |||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | ||||||||||||||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | No Mission Impact | ||||||||||||||||||
| 1014 | Bulk Storage | Pump House | Basket Strainers | Basket Strainer | Keckley | Illegible | 6.0 in. | X | X | 0 | 3-6.4 | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | |||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | ||||||||||||||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | No Mission Impact | ||||||||||||||||||
| 1014 | Bulk Storage | Pump House | Basket Strainers | Basket Strainer | Keckley | Illegible | 6.0 in. | X | X | 0 | 3-6.4 | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | |||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | ||||||||||||||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | No Mission Impact | ||||||||||||||||||
| 1014 | Bulk Storage | Fillstands | Basket Strainers | Basket Strainer | Titan | Illegible | 4.0 in. | X | X | 0 | 3-6.4 | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | |||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | ||||||||||||||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | No Mission Impact | Fill stand 1 | |||||||||||||||||
| 1014 | Bulk Storage | Fillstands | Basket Strainers | Basket Strainer | Titan | Illegible | 6.0 in. | X | X | 0 | 3-6.4 | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | |||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | ||||||||||||||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | No Mission Impact | Between fill stand 2 and 1 | |||||||||||||||||
| 1014 | Bulk Storage | Fillstands | Basket Strainers | Basket Strainer | Muler | Illegible | 4.0 in. | X | X | 0 | 3-6.4 | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | |||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | ||||||||||||||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | No Mission Impact | Offl load rack 1 | |||||||||||||||||
| 1014 | Bulk Storage | Offload Racks | Basket Strainers | Basket Strainer | Mueller | Illegible | 4.0 in. | X | X | 0 | 3-6.4 | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | |||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | ||||||||||||||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | No Mission Impact | Offload 2 | |||||||||||||||||
| 1014 | Bulk Storage | Offload Racks | Basket Strainers | Basket Strainer | UNK | Illegible | 4.0 in. | X | X | 0 | 3-6.4 | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | |||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | ||||||||||||||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | No Mission Impact | Offload 3 | |||||||||||||||||
| 1014 | Bulk Storage | Offload Racks | Basket Strainers | Basket Strainer | Mueller | Illegible | 4.0 in. | X | X | 0 | 3-6.4 | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | |||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | ||||||||||||||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | No Mission Impact | Offload 4 | |||||||||||||||||
| 1014 | Bulk Storage | Offload Racks | Basket Strainers | Basket Strainer | UNK | Illegible | 4.0 in. | X | X | 0 | 3-6.4 | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | |||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | ||||||||||||||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | No Mission Impact | Offload 5 | |||||||||||||||||
| 1014 | Bulk Storage | Offload Racks | Basket Strainers | Basket Strainer | Hayward | Illegible | 2.0 in. | X | X | 0 | 3-6.4 | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | |||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | ||||||||||||||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | No Mission Impact | Offload 5 | |||||||||||||||||
| 1014 | Bulk Storage | Filter Pad | Canopies | Canopy | Unmarked | Unmarked | N/A | X | X | 0 | 11-2.2 | No Additional Manufacturer Requirements | No Operator/equipment Requirements | No Mission Impact | |||||
| 1014 | Bulk Storage | Offload Racks | Canopies | Canopy | Unmarked | Unmarked | N/A | X | X | 0 | 11-2.2 | No Additional Manufacturer Requirements | No Operator/equipment Requirements | No Mission Impact | Canopy 1 at offload racks | ||||
| 1014 | Bulk Storage | Offload Racks | Canopies | Canopy | Unmarked | Unmarked | N/A | X | X | 0 | 11-2.2 | No Additional Manufacturer Requirements | No Operator/equipment Requirements | No Mission Impact | Canopy 2 | ||||
| 1014 | Bulk Storage | Offload Racks | Centrifugal Pumps | Pump | Goulds | Illegible | Illegible | X | X | X | 3-8.1 | During routine pump inspections only the easy to monitor factors such as pressure, temperature, vibration etc can be checKed. But during quarterly inspections, shaft alignment and oil levels should also be checked. Change Oil Annually | No Operator Requirement | No Mission Impact | Offload 5 | ||||
| 1014 | Bulk Storage | Fillstands | Check Valves | Check Valve | Apollo | 6210401 | 0.75 in. | X | X | 0 | 6-6.2.8 | Visual for damage, leaks, tightness. | No Operator Requirement | Partial System OOS | Off load rack 1 | ||||
| 1014 | Bulk Storage | Fillstands | Check Valves | Check Valve | Wheatly | Illegible | 4.0 in. | X | X | 0 | 6-6.2.8 | Visual for damage, leaks, tightness. | No Operator Requirement | Partial System OOS | Off load rack 1 | ||||
| 1014 | Bulk Storage | Offload Racks | Check Valves | Check Valve | Apollo | 6210401 | 0.75 in. | X | X | 0 | 6-6.2.8 | Visual for damage, leaks, tightness. | No Operator Requirement | Partial System OOS | Offload 2 | ||||
| 1014 | Bulk Storage | Offload Racks | Check Valves | Check Valve | Wheatley | 910-45027-121 | 4.0 in. | X | X | 0 | 6-6.2.8 | Visual for damage, leaks, tightness. | No Operator Requirement | Partial System OOS | Offload 2 | ||||
| 1014 | Bulk Storage | Offload Racks | Check Valves | Check Valve | Apollo | 6210401 | 0.75 in. | X | X | 0 | 6-6.2.8 | Visual for damage, leaks, tightness. | No Operator Requirement | Partial System OOS | Offload 3 | ||||
| 1014 | Bulk Storage | Offload Racks | Check Valves | Check Valve | Wheatly | Illegible | 4.0 in. | X | X | 0 | 6-6.2.8 | Visual for damage, leaks, tightness. | No Operator Requirement | Partial System OOS | Offload 3 | ||||
| 1014 | Bulk Storage | Offload Racks | Check Valves | Check Valve | Apollo | 6210401 | 0.75 in. | X | X | 0 | 6-6.2.8 | Visual for damage, leaks, tightness. | No Operator Requirement | Partial System OOS | Offload 4 | ||||
| 1014 | Bulk Storage | Offload Racks | Check Valves | Check Valve | Wheatly | Illegible | 4.0 in. | X | X | 0 | 6-6.2.8 | Visual for damage, leaks, tightness. | No Operator Requirement | Partial System OOS | Offload 4 | ||||
| 1014 | Bulk Storage | Offload Racks | Check Valves | Check Valve | Apollo | 6210401 | 0.75 in. | X | X | 0 | 6-6.2.8 | Visual for damage, leaks, tightness. | No Operator Requirement | Partial System OOS | Offload 5 | ||||
| 1014 | Bulk Storage | Offload Racks | Check Valves | Check Valve | Illegible | Illegible | 4.0 in. | X | X | 0 | 6-6.2.8 | Visual for damage, leaks, tightness. | No Operator Requirement | Partial System OOS | Offload 5 | ||||
| 1014 | Bulk Storage | Offload Racks | Check Valves | Check Valve | Apollo | 6210401 | 1.5 in. | X | X | 0 | 6-6.2.8 | Visual for damage, leaks, tightness. | No Operator Requirement | Partial System OOS | Offload 5 | ||||
| 1014 | Bulk Storage | Pipeline | Check Valves | Check Valve | Apollo | 6210401 | 0.75 in. | X | X | 0 | 6-6.2.8 | Visual for damage, leaks, tightness. | No Operator Requirement | Partial System OOS | TK 32 inlet | ||||
| 1014 | Bulk Storage | Pump House | Check Valves | Check Valve | Merit | VSC102-12 | 0.75 in. | X | X | 0 | 6-6.2.8 | Visual for damage, leaks, tightness. | No Operator Requirement | Partial System OOS | |||||
| 1014 | Bulk Storage | Filter Pad | Differential Pressure Gauges | DP Gauge | Gammon | GTP-534-30 | 0 - 30 PSI | X | X | X | 6-7.2 | Periodic calibration of this instrument is unnecessary because the graduated scale is made to match the characteristics (load/deflection curve) of the spring. If the spring loses some of its strength for some reason, the ”free length” must be shortened. Afull length spring will always provide accurate readings. This is a fundamental truth about compression springs. This spring is at its “free full length” when there is zero differential pressure; the top of the piston is then in the “zero” band of the graduated scale. | Quarterly - Clean outside of gauge glass. | Partial System OOS | F/S 5 |