PWS LEX FMP Template - v2.2.xlsx

XLSX spreadsheet 81 KB Posted

Attached to
Sources Sought - CEHNC FUELS PROGRAM
Solicitation number
PANHES-25-P-0000-001794
Issued by

About this file

This is a Facility Maintenance Plan (FMP) template spreadsheet for tracking maintenance requirements at the Lexington Army Aviation Support Facility (AASF) No. 1 fuel facility located at 16201 144th St, Lexington, OK. The template contains detailed maintenance scheduling and tracking information for fuel system components including filter separators, pumps, valves, tanks, piping, meters, and other equipment at the bulk fuel storage facility.

The spreadsheet is organized into multiple tabs covering administrative information, general facility description, communication plans, safety requirements, recurring maintenance schedules, and component identifiers. It provides a standardized format for documenting maintenance frequencies, inspection requirements, manufacturer specifications, operator requirements, and system impact considerations for each piece of equipment. Key components tracked include four 20,000 gallon storage tanks, multiple filter separators rated at 600 GPM, centrifugal pumps, ball valves, pressure gauges, fuel loading systems, and associated piping and electrical systems. The template appears to be version 2.2 dated October 31, 2022.

View the file

Other files

File Type Posted
Sources Sought FUELS - Programmatic Rev1 7 May 25.docx DOCX document
3.4 Appendix B - Attachment 4 - SO Tracker-20210628.xlsx XLSX spreadsheet
6.0 - Appendix E ISR 15-Bulk_Fuel_Facilities FY25.xlsx XLSX spreadsheet
2.0 Appendix A RM_SO Process_20241220_PgM Reviewed Incorporated.docx DOCX document
3.1 Appendix B - Attachment 1 - Three Week Look Ahead_20230420.xlsx XLSX spreadsheet
3.2 Appendix B - Attachment 2 - Monthly Report Format 20240910.docx DOCX document
2.2 Appendix A - Attachment 2 Contractor Travel Expense Report_20240910.xlsx XLSX spreadsheet
9.0 Appendix H - Minor Repairs Incidental to Maintenance Activities POJ 20231009.xlsx XLSX spreadsheet
7.0 CUID - v2.1.pdf PDF
8.0 Appendix G_UFC 3-460-03 Maintenance Table- v4.3.pdf PDF
6.0 Appendix E ISR 14_operational_fuel_facilities FY25.xlsx XLSX spreadsheet
3.0 Appendix B Reporting Requirements_20240910.docx DOCX document
4.0 Appendix C Task Order Specifications_202401216.docx DOCX document
5.0 Appendix D Antiterrorism and OPSEC 20230206.docx DOCX document
PWS VNC FMP Template - v2.2.xlsx XLSX spreadsheet
PWS KEQ FMP Template - v2.2.xlsx XLSX spreadsheet
PWS CVZ FMP Template - v2.2.xlsx XLSX spreadsheet
PWS SHP FMP Template - v2.2.xlsx XLSX spreadsheet
PWS PBA FMP Template - v2.2.xlsx XLSX spreadsheet
PWS GRB FMP Template - v2.2.xlsx XLSX spreadsheet
PWS BRO FMP Template - v2.2.xlsx XLSX spreadsheet
PWS BAR FMP Template - v2.2.xlsx XLSX spreadsheet
PWS EFS FMP Template - v2.2.xlsx XLSX spreadsheet
PWS LAU FMP Template - v2.2.xlsx XLSX spreadsheet
PWS CHF FMP Template - v2.2.xlsx XLSX spreadsheet
PWS BEU FMP Template - v2.2.xlsx XLSX spreadsheet
PWS GDF FMP Template - v2.2.xlsx XLSX spreadsheet
PWS BLI FMP Template - v2.2.xlsx XLSX spreadsheet
PWS TKR FMP Template - v2.2.xlsx XLSX spreadsheet
PWS RBN FMP Template - v2.2.xlsx XLSX spreadsheet
PWS MAA FMP Template - v2.2.xlsx XLSX spreadsheet
PWS FSH FMP Template - v2.2.xlsx XLSX spreadsheet
PWS FSO FMP Template - v2.2.xlsx XLSX spreadsheet
PWS LRG FMP Template - v2.2.xlsx XLSX spreadsheet
PWS RRT FMP Template - v2.2.xlsx XLSX spreadsheet
PWS ALT FMP Template - v2.2.xlsx XLSX spreadsheet
PWS TUL FMP Template - v2.2.xlsx XLSX spreadsheet
PWS BL2 FMP Template - v2.2.xlsx XLSX spreadsheet
PWS ELL FMP Template - v2.2.xlsx XLSX spreadsheet
PWS WRF FMP Template - v2.2.xlsx XLSX spreadsheet
PWS LLD FMP Template - v2.2.xlsx XLSX spreadsheet
PWS DYE FMP Template - v2.2.xlsx XLSX spreadsheet
12.0 PWS Appendix K Real Property Data_20230420.xlsx XLSX spreadsheet
PWS RAN FMP Template - v2.2.xlsx XLSX spreadsheet
PWS FSM FMP Template - v2.2.xlsx XLSX spreadsheet
PWS _Fuels RMMR 20241220.docx DOCX document
Show all 46

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Administrative

LocationSite NameLexington AASF No 1
RPSUID5890
DLA Site CodeLEX
Hours of Operation0800-1600
Address16201 144th St, Lexington, OK 73051
ContractContractor
Contract #
Local POCsQAE Name
QAE Phone
QAE Email
Alt QAE Name
Alt QAE Phone
Alt QAE Email
DLA/SCP POCsDLA PM Name
DLA PM Phone
DLA PM Email
SCP PM Name
SCP PM Phone
SCP PM Email
Contractor POCsContractor PM Name
Contractor PM Phone
Contractor PM Email
Contractor QC Name
Contractor QC Phone
Contractor QC Email
Contractor SM Name
Contractor SM Phone
Contractor SM Email
USACE POCsUSACE PM/COR Name
USACE PM/COR Phone
USACE PM/COR Email
USACE PE Name
USACE PE Phone
USACE PE Email
USACE KO Name
USACE KO Phone
USACE KO Email

Facility Maintenance Plan

FMP v2.2 &P of &N

Instructions:

This table shows the minimum information required. Additional details should be included based on site specific requirements. Additional POCs may be required.

General Facility Description Facility Description

Purpose:

This Facility Maintenance Plan provides guidance for Contractor personnel in the operation, inspection, and maintenance of permanently installed fuel facilities operated under the control of the Quality Assurance Evaluators. Federal, state, and local environmental laws and regulations shall be complied with if this plan is in conflict with them.

Scope:

The instructions prescribed by this plan outline general fuels maintenance information associated with fuel storage and dispensing systems and provides the minimum periodic contractor maintenance and inspection criteria requirements for the systems. This plan is to be used in conjunction with other existing directives governing fuel system operations and maintenance requirements. Conotractor will properly maintain and repair federally funded petroleum systems and facilities in order to provide compliance with applicable code, criteria, and federal, state, local and/or host nation regulations.

Fuels Facilities:

Organizational tanks, and associated dispensing equipment are maintained and operated by the owning organization. Fuel system maintenance contractors shall perform all maintenance and associated procurement actions on installed fuel systems.

Each installation under the Southwest Division contract are military land-based facilities who receive, store, distribute, and/or dispense liquid fuels.

Standard fuel system equipment includes:

a) Above Ground Sorage Stanks (AST), Underground Storage Tanks (UST)

b) Filter/separator and other filtration device maintenance access, particularly element removal.

c) Manual valves

d) Meter Registers, and Flow Meters.

e) Control Valves.

f) Pumps

g) Tank Monitoring Equipment and Instruments

h) Alarms

i) Fire Fighting Equipment

Site Specific General Information:

Facility Maintenance Plan

FMP v2.2 &P of &N

Instructions:

Include a general facility overview and description of each fuel system for the sites in accordance with UFC 3-460-01. Examples include: Bulk Storage Facilities, Aircraft Fueling Facilities, Marine and Dispensing Facilities, Ground Products Fueling Facilities, Alternate POL Facilities, and Support Facilities. Also include facility #s, facility names, fuel type, photos, and any other pertinent information.

Include Site Specific Conditions and Restrictions in this tab.

Communication Plan

Facility Maintenance Plan

FMP v2.2 &P of &N

Instructions:

Communication plan shall address in/out briefs, lines of communication, coordination for access, etc.

Safety

Facility Maintenance Plan

FMP v2.2 &P of &N

Instructions:

Site Specific Addendum and Activity Hazard Analysis, which are Attachments to the APP, specific to activities or tasks related to recurring maintenance for this site.

RM Schedule

Facility Maintenance Plan

FMP v2.2 &P of &N

Instructions:

Link RM schedule here

Task Matrix

Applicable Facility AssetsUFC System Level Maintenance FrequencySpecial Considerations
Real Property Unique Identifier
(RPUID)Real Property Facility #Real Property Facility NameOperational AreaComponent TypeBase Asset IDComponent Unique Identifier (CUID)MakeModelCapacity/SizeQSAUFC Section ReferenceAdditional Manufacturer RM RequirementsOperator/ equipment RequirementsSystem availabilityOther ContractComments
40C35FTKOABulk StorageFilter SeparatorsIssue Filter Separator 1VelconHV2838200600 GPMX3-6.2Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. Replace filter cartridges when the acceptable maximum differential pressure is reached, the maximum in-service duration has passed, or the fuel becomes visibly dirty or discolored.Daily - Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges.No Mission Impact
40C35FTKOABulk StorageFilter Seperator Control ValvesFilter Seperator Control ValvesCla ValM119300 psiXX4-4.2.2No Manufacturers Data Available. Adjustment not advised unless formal training is received.No Operator RequirementNo Mission Impact
40C35FTKOABulk StorageRefuel Control ValvesFilter Seperator Control ValvesCla ValM119300 psiX4-3.2.5No Manufacturers Data Available. Adjustment not advised unless formal training is received.No Operator RequirementNo Mission Impact
40C35FTKOABulk StoragePressure Relief ValvesPressure Relief ValvesTaylor82E53515111"X4-3.2.6No Manufacturers Data Available. Adjustment not advised unless formal training is received.No Operator RequirementPartial System OOS
40C35FTKOABulk StoragePressure Relief ValvesPressure Relief ValvesTaylor82E53515111"X4-3.2.6No Manufacturers Data Available. Adjustment not advised unless formal training is received.No Operator RequirementPartial System OOS
40C35FTKOABulk StoragePressure Relief ValvesPressure Relief ValvesTaylor82E53515111"X4-3.2.6No Manufacturers Data Available. Adjustment not advised unless formal training is received.No Operator RequirementPartial System OOS
40C35FTKOABulk StorageDifferential Pressure GaugesDifferential Pressure GaugesGammonGTP-534-30S0-30 psiXX6-7.2Periodic calibration of this instrument is unnecessary because the graduated scale is made to match the characteristics (load/deflection curve) of the spring. If the spring loses some of its strength for some reason, the ”free length” must be shortened. Afull length spring will always provide accurate readings. This is a fundamental truth about compression springs. This spring is at its “free full length” when there is zero differential pressure; the top of the piston is then in the “zero” band of the graduated scale.Quarterly - Clean outside of gauge glass.Partial System OOS
40C35FTKOABulk StorageSight Flow IndicatorsSight Flow IndicatorsVisi-Flow1400 Series1"6-12.3Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.No Mission Impact
40C35FTKOABulk StorageSight Flow IndicatorsSight Flow IndicatorsVisi-Flow1400 Series1"6-12.3Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.No Mission Impact
40C35FTKOABulk StorageSight Flow IndicatorsSight Flow IndicatorsVisi-Flow1400 Series1"6-12.3Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.No Mission Impact
40C35FTKOABulk StorageBall ValveBall ValveValworx5530243"X6-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
40C35FTKOABulk StorageBall ValveBall ValveValworx5530243"X6-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
40C35FTKOABulk StorageBall ValveBall ValveValworx5530243"X6-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
40C35FTKOABulk StorageBall ValveBall ValveValworx5530243"X6-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
40C35FTKOABulk StorageBall ValveBall ValveValworx5530243"X6-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
40C35FTKOABulk StorageBall ValveBall ValveValworx5530243"X6-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
40C35FTKOABulk StorageBall ValveBall ValveValworx5530243"X6-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
40C35FTKOABulk StorageBall ValveBall ValveValworx5530243"X6-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
40C35FTKOABulk StorageLoading Fuel HosesIssue HoseGoodyearAPI 1529 Type C10' X 3"XX3-9.1Aircraft fueling hose shall be inspected before use each day. The hose shall be extended as it normally would be for fueling and checked for evidence of blistering, carcass saturation or separation, cuts, nicks, or abrasions that expose reinforcement material, and for slippage, misalignment, or leaks at couplings.Weekly - Visually inspect hoses for loose covers, cracks, brittle surface coatings, exposed wire braids, exposed reinforcement, flattening, kinks, and bulges or soft spots which might indicate broken or displaced reinforcement.
Monthly - Pressurize hose to normal working pressure. Check flanged and threaded connections for leaks and inspect hose couplers for fluid seepage by pushing at the base of the coupling with your thumbs; a hose softened by fluid seepage must be replaced.Partial System OOS
40C35FTKOABulk StorageStatic Ground SystemGround ReelHannayHGR1003/16" x 100ftXX9-1.6.2Measure the ground resistance with an instrument designed specifically to measure and document earth/ground resistance, soil resistivity, and current flow. Conduct the test by using the fall-of-potential method as described in the Institute of Electronic and Electrical Engineers (IEEE) Standard 81.If fall-of-potential tests cannot be performed, it is acceptable to measure resistance at each accessible ground rod using a clamp-on ground resistance tester. Provide the Engineer with written, certified test results for each testing location.No Operator RequirementNo Mission Impact
40C35FTKOABulk StorageBasket StrainerBasket StrainerTitan1253"3-6.4Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyDaily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyPartial System Impact if Required
40C35FTKOABulk StoragePositive Displacement MeterOffload 1Veeder-Root0788700-06330 - 600 gpmX3-7.1Inspect counter head for unusual noises and smooth operation. Inspect temperature element operation of meters equipped with temperature
compensation featureMonthly - Inspect counter head for unusual noises and smooth operation.Partial System OOS
40C35FTKOABulk StoragePressure and Vacuum Pressure GaugePressure and Vacuum Pressure GaugeAshcroftUnknownminus 30 to 300 psiXXX6-7.1Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use.Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system.Partial System OOS
40C35FTKOABulk StoragePressure and Vacuum Pressure GaugePressure GaugeAshcroftUnknown0 - 100 psiXXX6-7.1Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use.Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system.Partial System OOS
40C35FTKOABulk StoragePressure and Vacuum Pressure GaugePressure GaugeAshcroftUnknown0 - 200 psiXXX6-7.1Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use.Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system.Partial System OOS
40C35FTKOABulk StoragePressure and Vacuum Pressure GaugePressure GaugeAshcroftUnknown0 - 200 psiXXX6-7.1Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use.Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system.Partial System OOS
40C35FTKOABulk StorageCentrifugal PumpsIssue Pump 1Goulds3196300 GPMXX3-8.1During routine pump inspections only the easy to monitor factors such as pressure, temperature, vibration etc can be checKed. But during quarterly inspections, shaft alignment and oil levels should also be checked. Change Oil AnnuallyNo Operator RequirementTemporary System OOS
40C36FTKOABulk StorageElectric MotorIssue Pump 1US ElectricalAB39E3535 RPMsXXX9-1.7(1) Inadequate ventilation or air flow

(2) Unbalanced voltage or an overload

(3) Bearing failure

(4) Insulation failure

(5) Shaft misalignmentNo Operator RequirementTemporary Mission Impact
40C35FTKOABulk StorageMotor ControlsIssue Pump 1UnknownUnknownUnknownXX9-1.4Moving parts should operate easily without excessive friction. Check operation of contactors and relays by hand, feeling for any binding or sticking. Look for loose pins, bolts, or bearings. If the control is dirty, it should be wiped or blown clean.

Contact inspection. Check contacts for pitting and signs of overheating, such as discoloration of metal, charred insulation, or odor. Be sure contact pressure is adequate and the same on all poles; verify with manufacturer's specification. Watch for frayed flexible leads.

Contact resistance testing. On essential controls, perform contact-resistance tests with a low-resistance ohmmeter on a regular basis. Proper contact resistance should be about 50 micro-ohms. Record readings for future comparison. This will indicate trends in the condition of contacts.

Overload relay inspection. Overload relays should receive a thorough inspection and cleaning. You also should check for proper setting.No Operator RequirementTemporary Mission Impact
40C35LE400Bulk StoragePositive Displacement MeterIssue 1Liquid ControlsM-42-245 - 450 gpmX3-7.1Inspect counter head for unusual noises and smooth operation. Inspect temperature element operation of meters equipped with temperature
compensation featureMonthly - Inspect counter head for unusual noises and smooth operation.Partial System OOS
40C35FTKODBulk StorageFilter SeparatorsIssue Filter Separator 2VelconHV2838200600 GPMX3-6.2Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. Replace filter cartridges when the acceptable maximum differential pressure is reached, the maximum in-service duration has passed, or the fuel becomes visibly dirty or discolored.Daily - Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges.No Mission Impact
40C35FTKODBulk StorageFilter Seperator Control ValvesFilter Seperator Control ValvesCla ValM119300 psiXX4-4.2.2No Manufacturers Data Available. Adjustment not advised unless formal training is received.No Operator RequirementNo Mission Impact
40C35FTKODBulk StoragePressure Relief ValvesPressure Relief ValvesTaylor82E53515111"X4-3.2.6No Manufacturers Data Available. Adjustment not advised unless formal training is received.No Operator RequirementPartial System OOS
40C35FTKODBulk StorageDifferential Pressure GaugesDifferential Pressure GaugesGammonGTP-534-30S0-30 psi0.250.056-7.2Periodic calibration of this instrument is unnecessary because the graduated scale is made to match the characteristics (load/deflection curve) of the spring. If the spring loses some of its strength for some reason, the ”free length” must be shortened. Afull length spring will always provide accurate readings. This is a fundamental truth about compression springs. This spring is at its “free full length” when there is zero differential pressure; the top of the piston is then in the “zero” band of the graduated scale.Quarterly - Clean outside of gauge glass.No Mission Impact
40C35FTKODBulk StorageSight Flow IndicatorsSight Flow IndicatorsVisi-Flow1400 Series1"6-12.3Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.No Mission Impact
40C35FTKODBulk StorageSight Flow IndicatorsSight Flow IndicatorsVisi-Flow1400 Series1"6-12.3Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.No Mission Impact
40C35FTKODBulk StorageSight Flow IndicatorsSight Flow IndicatorsVisi-Flow1400 Series1"6-12.3Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.No Mission Impact
40C35FTKODBulk StorageBall ValveBall ValveValworx5530243"X6-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
40C35FTKODBulk StorageBall ValveBall ValveValworx5530243"X6-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
40C35FTKODBulk StorageBall ValveBall ValveValworx5530243"X6-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
40C35FTKODBulk StorageBall ValveBall ValveValworx5530243"X6-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
40C35FTKODBulk StorageBall ValveBall ValveValworx5530243"X6-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
40C35FTKODBulk StorageBall ValveBall ValveValworx5530243"X6-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
40C35FTKODBulk StorageBall ValveBall ValveValworx5530243"X6-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
40C35FTKODBulk StorageBall ValveBall ValveValworx5530243"X6-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
40C35FTKODBulk StorageLoading Fuel HosesIssue HoseGoodyearAPI 1529 Type C10' X 3"XX3-9.1Aircraft fueling hose shall be inspected before use each day. The hose shall be extended as it normally would be for fueling and checked for evidence of blistering, carcass saturation or separation, cuts, nicks, or abrasions that expose reinforcement material, and for slippage, misalignment, or leaks at couplings.Weekly - Visually inspect hoses for loose covers, cracks, brittle surface coatings, exposed wire braids, exposed reinforcement, flattening, kinks, and bulges or soft spots which might indicate broken or displaced reinforcement.
Monthly - Pressurize hose to normal working pressure. Check flanged and threaded connections for leaks and inspect hose couplers for fluid seepage by pushing at the base of the coupling with your thumbs; a hose softened by fluid seepage must be replaced.Partial System OOS
40C35FTKODBulk StorageStatic Ground SystemGround ReelHannayHGR1003/16" x 100ftXX9-1.6.2Measure the ground resistance with an instrument designed specifically to measure and document earth/ground resistance, soil resistivity, and current flow. Conduct the test by using the fall-of-potential method as described in the Institute of Electronic and Electrical Engineers (IEEE) Standard 81.If fall-of-potential tests cannot be performed, it is acceptable to measure resistance at each accessible ground rod using a clamp-on ground resistance tester. Provide the Engineer with written, certified test results for each testing location.No Operator RequirementNo Mission Impact
40C35FTKODBulk StorageBasket StrainerBasket StrainerTitan1253"3-6.4Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyDaily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyPartial System Impact if Required
40C35FTKODBulk StoragePositive Displacement MeterOffload 2Veeder-Root0788700-06330 - 600 gpmX3-7.1Inspect counter head for unusual noises and smooth operation. Inspect temperature element operation of meters equipped with temperature
compensation featureMonthly - Inspect counter head for unusual noises and smooth operation.Partial System OOS
40C35FTKODBulk StoragePressure and Vacuum Pressure GaugePressure and Vacuum Pressure GaugeAshcroftUnknownminus 30 - 300 psiXXX6-7.1Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use.Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system.Partial System OOS
40C35FTKODBulk StoragePressure and Vacuum Pressure GaugePressure GaugeAshcroftUnknown0 to 200 psiXXX6-7.1Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use.Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system.Partial System OOS
40C35FTKODBulk StoragePressure and Vacuum Pressure GaugePressure GaugeAshcroftUnknown0 to 200 psiXXX6-7.1Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use.Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system.Partial System OOS
40C35FTKODBulk StoragePressure and Vacuum Pressure GaugeVacuum GaugeAshcroftUnknownminus 30 - 0 psiXXX6-7.1Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use.Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system.Partial System OOS
40C35FTKODBulk StorageCentrifugal PumpsIssue Pump 2Goulds3196300 GPMXX3-8.1During routine pump inspections only the easy to monitor factors such as pressure, temperature, vibration etc can be checKed. But during quarterly inspections, shaft alignment and oil levels should also be checked. Change Oil AnnuallyNo Operator RequirementTemporary System OOS
40C36FTKODBulk StorageElectric MotorIssue Pump 2US ElectricalAB39E3535 RPMsXXX9-1.7(1) Inadequate ventilation or air flow

(2) Unbalanced voltage or an overload

(3) Bearing failure

(4) Insulation failure

(5) Shaft misalignmentNo Operator RequirementTemporary Mission Impact
40C35FTKOABulk StorageMotor ControlsIssue Pump 2UnknownUnknownUnknownXX9-1.4Moving parts should operate easily without excessive friction. Check operation of contactors and relays by hand, feeling for any binding or sticking. Look for loose pins, bolts, or bearings. If the control is dirty, it should be wiped or blown clean.

Contact inspection. Check contacts for pitting and signs of overheating, such as discoloration of metal, charred insulation, or odor. Be sure contact pressure is adequate and the same on all poles; verify with manufacturer's specification. Watch for frayed flexible leads.

Contact resistance testing. On essential controls, perform contact-resistance tests with a low-resistance ohmmeter on a regular basis. Proper contact resistance should be about 50 micro-ohms. Record readings for future comparison. This will indicate trends in the condition of contacts.

Overload relay inspection. Overload relays should receive a thorough inspection and cleaning. You also should check for proper setting.No Operator RequirementTemporary Mission Impact
40C35LE400Bulk StoragePositive Displacement MeterIssue 2Liquid ControlsM-42-245 - 450 gpmX3-7.1Inspect counter head for unusual noises and smooth operation. Inspect temperature element operation of meters equipped with temperature
compensation featureMonthly - Inspect counter head for unusual noises and smooth operation.Partial System OOS
40C35FTKOMBulk StorageFilter SeparatorsReceipt Filter Separator 1VelconHV2838200600 GPMX3-6.2Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. Replace filter cartridges when the acceptable maximum differential pressure is reached, the maximum in-service duration has passed, or the fuel becomes visibly dirty or discolored.Daily - Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges.No Mission Impact
40C35FTKOMBulk StorageFilter Seperator Control ValvesFilter Seperator Control ValvesCla ValM119300 psiXX4-4.2.2No Manufacturers Data Available. Adjustment not advised unless formal training is received.No Operator RequirementNo Mission Impact
40C35FTKOMBulk StorageBack Pressure Control ValvesBack Pressure Control ValvesCla ValM119300 psiXX4-4.2.6No Manufacturers Data Available. Adjustment not advised unless formal training is received.No Operator RequirementNo Mission Impact
40C35FTKOMBulk StoragePressure Relief ValvesPressure Relief ValvesTaylor82E53515111"X4-3.2.6No Manufacturers Data Available. Adjustment not advised unless formal training is received.No Operator RequirementPartial System OOS
40C35FTKOMBulk StoragePressure Relief ValvesPressure Relief ValvesTaylor82E53515111"X4-3.2.6No Manufacturers Data Available. Adjustment not advised unless formal training is received.No Operator RequirementPartial System OOS
40C35FTKOMBulk StoragePressure Relief ValvesPressure Relief ValvesTaylor82E53515111"X4-3.2.6No Manufacturers Data Available. Adjustment not advised unless formal training is received.No Operator RequirementPartial System OOS
40C35FTKOMBulk StorageDifferential Pressure GaugesDifferential Pressure GaugesGammonGTP-534-30S0-30 psiXX6-7.2Periodic calibration of this instrument is unnecessary because the graduated scale is made to match the characteristics (load/deflection curve) of the spring. If the spring loses some of its strength for some reason, the ”free length” must be shortened. Afull length spring will always provide accurate readings. This is a fundamental truth about compression springs. This spring is at its “free full length” when there is zero differential pressure; the top of the piston is then in the “zero” band of the graduated scale.Quarterly - Clean outside of gauge glass.Partial System OOS
40C35FTKOMBulk StorageSight Flow IndicatorsSight Flow IndicatorsDixonTTMA-Flanged4"6-12.3Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.No Mission Impact
40C35FTKOMBulk StorageSight Flow IndicatorsSight Flow IndicatorsVisi-Flow1400 Series1"6-12.3Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.No Mission Impact
40C35FTKOMBulk StorageSight Flow IndicatorsSight Flow IndicatorsVisi-Flow1400 Series1"6-12.3Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.No Mission Impact
40C35FTKOMBulk StorageSight Flow IndicatorsSight Flow IndicatorsVisi-Flow1400 Series1"6-12.3Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.No Mission Impact
40C35FTKOMBulk StorageOffloading Fuel HosesOffloading hoseHewitt5004" x 10'XX3-9.2Aircraft fueling hose shall be inspected before use each day. The hose shall be extended as it normally would be for fueling and checked for evidence of blistering, carcass saturation or separation, cuts, nicks, or abrasions that expose reinforcement material, and for slippage, misalignment, or leaks at couplings.Weekly - Visually inspect hoses for loose covers, cracks, brittle surface coatings, exposed wire braids, exposed reinforcement, flattening, kinks, and bulges or soft spots which might indicate broken or displaced reinforcement.
Monthly - Pressurize hose to normal working pressure. Check flanged and threaded connections for leaks and inspect hose couplers for fluid seepage by pushing at the base of the coupling with your thumbs; a hose softened by fluid seepage must be replaced.Partial System OOS
40C35FTKOMBulk StorageCentrifugal PumpsReciept Pump 1Goulds3196300 GPMXX3-8.1During routine pump inspections only the easy to monitor factors such as pressure, temperature, vibration etc can be checKed. But during quarterly inspections, shaft alignment and oil levels should also be checked. Change Oil AnnuallyNo Operator RequirementTemporary System OOS
40C36FTKOMBulk StorageElectric MotorReciept Pump 1TECOCAT X03023545 RPMsXXX9-1.7(1) Inadequate ventilation or air flow

(2) Unbalanced voltage or an overload

(3) Bearing failure

(4) Insulation failure

(5) Shaft misalignmentNo Operator RequirementTemporary Mission Impact
40C35FTKOABulk StorageMotor ControlsReciept Pump 1UnknownUnknownUnknownXX9-1.4Moving parts should operate easily without excessive friction. Check operation of contactors and relays by hand, feeling for any binding or sticking. Look for loose pins, bolts, or bearings. If the control is dirty, it should be wiped or blown clean.

Contact inspection. Check contacts for pitting and signs of overheating, such as discoloration of metal, charred insulation, or odor. Be sure contact pressure is adequate and the same on all poles; verify with manufacturer's specification. Watch for frayed flexible leads.

Contact resistance testing. On essential controls, perform contact-resistance tests with a low-resistance ohmmeter on a regular basis. Proper contact resistance should be about 50 micro-ohms. Record readings for future comparison. This will indicate trends in the condition of contacts.

Overload relay inspection. Overload relays should receive a thorough inspection and cleaning. You also should check for proper setting.No Operator RequirementTemporary Mission Impact
40C35FTKOMBulk StorageStatic Ground SystemGround ReelHannayHGR503/16" x 75ftXX9-1.6.2Measure the ground resistance with an instrument designed specifically to measure and document earth/ground resistance, soil resistivity, and current flow. Conduct the test by using the fall-of-potential method as described in the Institute of Electronic and Electrical Engineers (IEEE) Standard 81.If fall-of-potential tests cannot be performed, it is acceptable to measure resistance at each accessible ground rod using a clamp-on ground resistance tester. Provide the Engineer with written, certified test results for each testing location.No Operator RequirementNo Mission Impact
40C35FTKOMBulk StorageBasket StrainerBasket StrainerTitan1253"3-6.4Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyDaily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyPartial System Impact if Required
40C35FTKOMBulk StoragePositive Displacement MeterOffload 3Veeder-Root0788700-06330 - 600 gpmX3-7.1Inspect counter head for unusual noises and smooth operation. Inspect temperature element operation of meters equipped with temperature
compensation featureMonthly - Inspect counter head for unusual noises and smooth operation.Partial System OOS
40C35FTKOMBulk StoragePressure and Vacuum Pressure GaugePressure and Vacuum Pressure GaugeAshcroftUnknownminus 30 - 300 psiXXX6-7.1Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use.Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system.Partial System OOS
40C35FTKOMBulk StoragePressure and Vacuum Pressure GaugePressure GaugeAshcroftUnknown0 to 200 psiXXX6-7.1Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use.Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system.Partial System OOS
40C35FTKOMBulk StoragePressure and Vacuum Pressure GaugePressure GaugeAshcroftUnknown0 to 200 psiXXX6-7.1Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use.Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system.Partial System OOS
40C35FTKOMBulk StoragePressure and Vacuum Pressure GaugeVacuum GaugeAshcroftUnknownminus 30 - 0 psiXXX6-7.1Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use.Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system.Partial System OOS
40C35LE400Bulk StoragePositive Displacement MeterTransfer/Recirculation 1Liquid ControlsM-10-215 - 150 gpmX3-7.1Inspect counter head for unusual noises and smooth operation. Inspect temperature element operation of meters equipped with temperature
compensation featureMonthly - Inspect counter head for unusual noises and smooth operation.Partial System OOS
40C35LE400Bulk StorageFilter SeparatorsReceipt Filter Separator 2VelconHV2838200600 GPMX3-6.2Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. Replace filter cartridges when the acceptable maximum differential pressure is reached, the maximum in-service duration has passed, or the fuel becomes visibly dirty or discolored.Daily - Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges.No Mission Impact
40C35LE400Bulk StorageFilter Seperator Control ValvesFilter Seperator Control ValvesCla ValM119300 psiXX4-4.2.2No Manufacturers Data Available. Adjustment not advised unless formal training is received.No Operator RequirementNo Mission Impact
40C35LE400Bulk StorageBack Pressure Control ValvesBack Pressure Control ValvesCla ValM119300 psiXX4-4.2.6No Manufacturers Data Available. Adjustment not advised unless formal training is received.No Operator RequirementNo Mission Impact
40C35LE400Bulk StoragePressure Relief ValvesPressure Relief ValvesTaylor82E53515111"X4-3.2.6No Manufacturers Data Available. Adjustment not advised unless formal training is received.No Operator RequirementPartial System OOS
40C35LE400Bulk StoragePressure Relief ValvesPressure Relief ValvesTaylor82E53515111"X4-3.2.6No Manufacturers Data Available. Adjustment not advised unless formal training is received.No Operator RequirementPartial System OOS
40C35LE400Bulk StoragePressure Relief ValvesPressure Relief ValvesTaylor82E53515111"X4-3.2.6No Manufacturers Data Available. Adjustment not advised unless formal training is received.No Operator RequirementPartial System OOS
40C35LE400Bulk StorageDifferential Pressure GaugesDifferential Pressure GaugesGammonGTP-534-30S0-30 psiXX6-7.2Periodic calibration of this instrument is unnecessary because the graduated scale is made to match the characteristics (load/deflection curve) of the spring. If the spring loses some of its strength for some reason, the ”free length” must be shortened. Afull length spring will always provide accurate readings. This is a fundamental truth about compression springs. This spring is at its “free full length” when there is zero differential pressure; the top of the piston is then in the “zero” band of the graduated scale.Quarterly - Clean outside of gauge glass.Partial System OOS
40C35LE400Bulk StorageSight Flow IndicatorsSight Flow IndicatorsDixonTTMA-Flanged4"6-12.3Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.No Mission Impact
40C35LE400Bulk StorageSight Flow IndicatorsSight Flow IndicatorsVisi-Flow1400 Series1"6-12.3Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.No Mission Impact
40C35LE400Bulk StorageSight Flow IndicatorsSight Flow IndicatorsVisi-Flow1400 Series1"6-12.3Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.No Mission Impact
40C35LE400Bulk StorageSight Flow IndicatorsSight Flow IndicatorsVisi-Flow1400 Series1"6-12.3Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.No Mission Impact
40C35LE400Bulk StorageOffloading Fuel HosesOffloading hoseHewitt5004" x 10'XX3-9.2Aircraft fueling hose shall be inspected before use each day. The hose shall be extended as it normally would be for fueling and checked for evidence of blistering, carcass saturation or separation, cuts, nicks, or abrasions that expose reinforcement material, and for slippage, misalignment, or leaks at couplings.Weekly - Visually inspect hoses for loose covers, cracks, brittle surface coatings, exposed wire braids, exposed reinforcement, flattening, kinks, and bulges or soft spots which might indicate broken or displaced reinforcement.
Monthly - Pressurize hose to normal working pressure. Check flanged and threaded connections for leaks and inspect hose couplers for fluid seepage by pushing at the base of the coupling with your thumbs; a hose softened by fluid seepage must be replaced.Partial System OOS
40C35LE400Bulk StorageCentrifugal PumpsReciept Pump 2Goulds3196300 GPMXX3-8.1During routine pump inspections only the easy to monitor factors such as pressure, temperature, vibration etc can be checKed. But during quarterly inspections, shaft alignment and oil levels should also be checked. Change Oil AnnuallyNo Operator RequirementTemporary System OOS
40C36LE401Bulk StorageElectric MotorReciept Pump 2Toshiba0302XPEA21B-P3535 RMsXXX9-1.7(1) Inadequate ventilation or air flow

(2) Unbalanced voltage or an overload

(3) Bearing failure

(4) Insulation failure

(5) Shaft misalignmentNo Operator RequirementTemporary Mission Impact
40C35FTKOABulk StorageMotor ControlsReciept Pump 2UnknownUnknownUnknownXX9-1.4Moving parts should operate easily without excessive friction. Check operation of contactors and relays by hand, feeling for any binding or sticking. Look for loose pins, bolts, or bearings. If the control is dirty, it should be wiped or blown clean.

Contact inspection. Check contacts for pitting and signs of overheating, such as discoloration of metal, charred insulation, or odor. Be sure contact pressure is adequate and the same on all poles; verify with manufacturer's specification. Watch for frayed flexible leads.

Contact resistance testing. On essential controls, perform contact-resistance tests with a low-resistance ohmmeter on a regular basis. Proper contact resistance should be about 50 micro-ohms. Record readings for future comparison. This will indicate trends in the condition of contacts.

Overload relay inspection. Overload relays should receive a thorough inspection and cleaning. You also should check for proper setting.No Operator RequirementTemporary Mission Impact
40C35LE400Bulk StorageStatic Ground SystemGround ReelHannayHGR503/16" x 75ftXX9-1.6.2Measure the ground resistance with an instrument designed specifically to measure and document earth/ground resistance, soil resistivity, and current flow. Conduct the test by using the fall-of-potential method as described in the Institute of Electronic and Electrical Engineers (IEEE) Standard 81.If fall-of-potential tests cannot be performed, it is acceptable to measure resistance at each accessible ground rod using a clamp-on ground resistance tester. Provide the Engineer with written, certified test results for each testing location.No Operator RequirementNo Mission Impact
40C35LE400Bulk StorageBasket StrainerBasket StrainerTitan1253"3-6.4Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyDaily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyPartial System Impact if Required
40C35LE400Bulk StoragePositive Displacement MeterOffload 4Veeder-Root0788700-06330 - 600 gpmX3-7.1Inspect counter head for unusual noises and smooth operation. Inspect temperature element operation of meters equipped with temperature
compensation featureMonthly - Inspect counter head for unusual noises and smooth operation.Partial System OOS
40C35LE400Bulk StoragePressure and Vacuum Pressure GaugePressure and Vacuum Pressure GaugeAshcroftUnknownminus 30 - 300 psiXXX6-7.1Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use.Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system.Partial System OOS
40C35LE400Bulk StoragePressure and Vacuum Pressure GaugePressure GaugeAshcroftUnknown0 to 200 psiXXX6-7.1Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use.Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system.Partial System OOS
40C35LE400Bulk StoragePressure and Vacuum Pressure GaugePressure GaugeAshcroftUnknown0 to 200 psiXXX6-7.1Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use.Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system.Partial System OOS
40C35LE400Bulk StoragePressure and Vacuum Pressure GaugeVacuum GaugeAshcroftUnknownminus 30 - 0 psiXXX6-7.1Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use.Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system.Partial System OOS
40C35LE400Bulk StoragePositive Displacement MeterTransfer/Recirculation 2Liquid ControlsM-10-215 - 150 gpmX3-7.1Inspect counter head for unusual noises and smooth operation. Inspect temperature element operation of meters equipped with temperature
compensation featureMonthly - Inspect counter head for unusual noises and smooth operation.Partial System OOS
40C35LE401Bulk StorageAboveground Shop Fabricated TanksTank 1Steel Tank Institute1236320,000 gallonX8-5.1No Manufacturer Requirements AvailableMonthly - Monthly External Inspection (Identified as P in Table 8-2): Visually inspect for exterior signs of corrosion or coating deterioration. Visually inspect weld seams, tank-to-saddle connections, tank supports, tank anchors, foundation and anchor bolts, overfill valves and alarms, normal vents, emergency vents, leak detection probe or water/petroleum accumulation in the interstice on double-walled tanks, leaking valves, fittings, or components, spill containment systems and release prevention barriers. Leaking valves, fittings or components shall be repaired immediately or immediately removed from service and isolated to prevent further discharge. Any irregularities, (e.g., missing valve handles, bolts, nuts, screens) will be assessed for priority and repaired as soon as possible or as required depending on the nature of the defect (See Appendix E for an example of the STI SP001 Standard Monthly Inspection Checklist).
Annually - Annual External Inspection (Identified as P in Table 8-2): A more detailed examination of the tank and appurtenances shall be performed on an annual basis (See Appendix E for an example of the STI SP001 Standard Annual Inspection Checklist).No Mission Impact
40C35LE401Bulk StorageAboveground PipingPipingN/AN/AN/AX6-1.3No Manufacturer Requirements AvailableWeekly - Conduct petroleum fuel piping visual inspection in accordance with Section 6-1.5 Pipeline Visual Inspection.No Mission impact
40C35LE401Bulk StorageEmergency VentsVentMorrison Brothers244OUnknownX8-9.4No Manufacturer Requirements AvailableNo Operator RequirementNo Mission Impact
40C35LE401Bulk StorageFlame ArrestorsVentMorrison Brothers351S & 748AN/AX8-9.5No Manufacturer Requirements AvailableNo Operator RequirementTemporary Mission Impact
40C35LE401Bulk StoragePressure Relief ValvesPressure Relief ValvesTaylor82E53515111"X4-3.2.6No Manufacturers Data Available. Adjustment not advised unless formal training is received.No Operator RequirementPartial System OOS