PWS BLI FMP Template - v2.2.xlsx
XLSX spreadsheet 122 KB Posted
- Attached to
- Sources Sought - CEHNC FUELS PROGRAM
- Solicitation number
- PANHES-25-P-0000-001794
About this file
This is a Facility Maintenance Plan template for fuel system operations at Fort Bliss, specifically for Biggs Airfield and Hot Refuel facilities located at 11023 Railroad Ave, El Paso, TX. The template outlines maintenance requirements for permanently installed fuel facilities operated under Quality Assurance Evaluators, covering inspection and maintenance schedules for equipment including above/underground storage tanks, filter separators, valves, pumps, meters, containment systems, and safety equipment.
The document details specific maintenance tasks and frequencies (daily, weekly, monthly, quarterly, annually) for equipment like Facet filter separators, Veeder Root meters, Baldor and Clyde Union pumps, emergency eyewash stations, and static grounding systems. Key systems covered include two 180,000-gallon aviation fuel tanks (11113 and 11114), multiple filter separators rated at 600 GPM, and various ball/gate valves throughout the facility. The plan emphasizes compliance with federal, state and local environmental regulations while providing guidance for contractor personnel in maintaining fuel storage and dispensing systems. As a template, it contains fields for entering site-specific information like POC details and maintenance schedules.
View the file
Other files
Show all 46
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Administrative
| Location | Site Name | Fort Bliss |
| RPSUID | 4985 | |
| DLA Site Code | BLI | |
| Hours of Operation | 0800-1600 | |
| Address | 11023 Railroad Ave, El Paso, TX 79916 | |
| Contract | Contractor | |
| Contract # | ||
| Local POCs | QAE Name | |
| QAE Phone | ||
| QAE Email | ||
| Alt QAE Name | ||
| Alt QAE Phone | ||
| Alt QAE Email | ||
| DLA/SCP POCs | DLA PM Name | |
| DLA PM Phone | ||
| DLA PM Email | ||
| SCP PM Name | ||
| SCP PM Phone | ||
| SCP PM Email | ||
| Contractor POCs | Contractor PM Name | |
| Contractor PM Phone | ||
| Contractor PM Email | ||
| Contractor QC Name | ||
| Contractor QC Phone | ||
| Contractor QC Email | ||
| Contractor SM Name | ||
| Contractor SM Phone | ||
| Contractor SM Email | ||
| USACE POCs | USACE PM/COR Name | |
| USACE PM/COR Phone | ||
| USACE PM/COR Email | ||
| USACE PE Name | ||
| USACE PE Phone | ||
| USACE PE Email | ||
| USACE KO Name | ||
| USACE KO Phone | ||
| USACE KO Email |
Facility Maintenance Plan
FMP v2.2 &P of &N
Instructions:
This table shows the minimum information required. Additional details should be included based on site specific requirements. Additional POCs may be required.
General Facility Description Facility Description
Purpose:
This Facility Maintenance Plan provides guidance for Contractor personnel in the operation, inspection, and maintenance of permanently installed fuel facilities operated under the control of the Quality Assurance Evaluators. Federal, state, and local environmental laws and regulations shall be complied with if this plan is in conflict with them.
Scope:
The instructions prescribed by this plan outline general fuels maintenance information associated with fuel storage and dispensing systems and provides the minimum periodic contractor maintenance and inspection criteria requirements for the systems. This plan is to be used in conjunction with other existing directives governing fuel system operations and maintenance requirements. Conotractor will properly maintain and repair federally funded petroleum systems and facilities in order to provide compliance with applicable code, criteria, and federal, state, local and/or host nation regulations.
Fuels Facilities:
Organizational tanks, and associated dispensing equipment are maintained and operated by the owning organization. Fuel system maintenance contractors shall perform all maintenance and associated procurement actions on installed fuel systems.
Each installation under the Southwest Division contract are military land-based facilities who receive, store, distribute, and/or dispense liquid fuels.
Standard fuel system equipment includes:
a) Above Ground Sorage Stanks (AST), Underground Storage Tanks (UST)
b) Filter/separator and other filtration device maintenance access, particularly element removal.
c) Manual valves
d) Meter Registers, and Flow Meters.
e) Control Valves.
f) Pumps
g) Tank Monitoring Equipment and Instruments
h) Alarms
i) Fire Fighting Equipment
Site Specific General Information:
Facility Maintenance Plan
FMP v2.2 &P of &N
Instructions:
Include a general facility overview and description of each fuel system for the sites in accordance with UFC 3-460-01. Examples include: Bulk Storage Facilities, Aircraft Fueling Facilities, Marine and Dispensing Facilities, Ground Products Fueling Facilities, Alternate POL Facilities, and Support Facilities. Also include facility #s, facility names, fuel type, photos, and any other pertinent information.
Include Site Specific Conditions and Restrictions in this tab.
Communication Plan
Facility Maintenance Plan
FMP v2.2 &P of &N
Instructions:
Communication plan shall address in/out briefs, lines of communication, coordination for access, etc.
Safety
Facility Maintenance Plan
FMP v2.2 &P of &N
Instructions:
Site Specific Addendum and Activity Hazard Analysis, which are Attachments to the APP, specific to activities or tasks related to recurring maintenance for this site.
RM Schedule
Facility Maintenance Plan
FMP v2.2 &P of &N
Instructions:
Link RM schedule here
Task Matrix
| Applicable Facility Assets | UFC System Level Maintenance Frequency | Special Considerations | ||||||||||||||||
| Real Property Unique Identifier | ||||||||||||||||||
| (RPUID) | Real Property Facility # | Real Property Facility Name | Operational Area | Component Type | Base Asset ID | Component Unique Identifier (CUID) | Make | Model | Capacity/Size | Q | S | A | UFC Section Reference | Additional Manufacturer RM Requirements | Operator/ equipment Requirements | System availability | Other Contract | Comments |
| 48125 | 11111 | Biggs Airfield | Fuel Truck Containment Areas | Fillstand | N/A | N/A | N/A | X | X | 11-1.1 | No Manufacturer Requirements Available | Monthly - Remove debris from around security fence. Inspect fence grounding points. Ensure connections are not loose or damage. | ||||||
| 48125 | 11111 | Biggs Airfield | Remote Spill Containment | N/A | N/A | N/A | X | X | 11-1.2 | No Manufacturer Requirements Available | Annually - Secondary containment systems degrade and will collect debris which can clog drainage inlets or prevent drain valves from sealing properly. Test drain valves for leakage through the valve. | |||||||
| 48125 | 11111 | Biggs Airfield | Remote Spill Containment | N/A | N/A | N/A | X | X | 11-1.2 | No Manufacturer Requirements Available | Annually - Secondary containment systems degrade and will collect debris which can clog drainage inlets or prevent drain valves from sealing properly. Test drain valves for leakage through the valve. | |||||||
| 48125 | 11111 | Biggs Airfield | Remote Spill Containment | N/A | N/A | N/A | X | X | 11-1.2 | No Manufacturer Requirements Available | Annually - Secondary containment systems degrade and will collect debris which can clog drainage inlets or prevent drain valves from sealing properly. Test drain valves for leakage through the valve. | |||||||
| 48125 | 11111 | Biggs Airfield | Remote Spill Containment | N/A | N/A | N/A | X | X | 11-1.2 | No Manufacturer Requirements Available | Annually - Secondary containment systems degrade and will collect debris which can clog drainage inlets or prevent drain valves from sealing properly. Test drain valves for leakage through the valve. | |||||||
| 48125 | 11111 | Biggs Airfield | Canopies | Fillstnd 1 and 2 / Offload | N/A | N/A | N/A | 11-2.2 | No Manufacturer Requirements Available | No Operator Requirement | ||||||||
| 48125 | 11111 | Biggs Airfield | Canopies | Filter House | N/A | N/A | N/A | 11-2.2 | No Manufacturer Requirements Available | No Operator Requirement | ||||||||
| 48125 | 11111 | Biggs Airfield | Canopies | Fillstand #3 and 4 | N/A | N/A | N/A | 11-2.2 | No Manufacturer Requirements Available | No Operator Requirement | ||||||||
| 48125 | 11111 | Biggs Airfield | Emergency Eyewash/Showers | Fixed / Filter House | N/A | N/A | N/A | X | X | X | 11-3 | Weekly - Equipment installed within 10 seconds from the hazard and on the same plane as the hazard Pathway is clear of obstructions Plumbed equipment activated to ensure compliant operation and to clear any sediment Self-contained equipment checked to determine if the flushing fluid needs to be changed or supplemented Equipment free of broken or missing parts Equipment protected against freezing User protected from scalding water | No Operator Requirement | |||||
| 48125 | 11111 | Biggs Airfield | Emergency Eyewash/Showers | Portable / Offload | N/A | N/A | N/A | X | X | X | 11-3 | Weekly - Equipment installed within 10 seconds from the hazard and on the same plane as the hazard Pathway is clear of obstructions Plumbed equipment activated to ensure compliant operation and to clear any sediment Self-contained equipment checked to determine if the flushing fluid needs to be changed or supplemented Equipment free of broken or missing parts Equipment protected against freezing User protected from scalding water | No Operator Requirement | |||||
| 48125 | 11111 | Biggs Airfield | Emergency Eyewash/Showers | Portable / Fillstand #3/4 | N/A | N/A | N/A | X | X | X | 11-3 | Weekly - Equipment installed within 10 seconds from the hazard and on the same plane as the hazard Pathway is clear of obstructions Plumbed equipment activated to ensure compliant operation and to clear any sediment Self-contained equipment checked to determine if the flushing fluid needs to be changed or supplemented Equipment free of broken or missing parts Equipment protected against freezing User protected from scalding water | No Operator Requirement | |||||
| 48125 | 11111 | Biggs Airfield | Oil/Water Seperators | N/A | N/A | N/A | X | X | 11-5 | No Manufacturer Requirements Available | No Operator Requirement | |||||||
| 48125 | 11111 | Biggs Airfield | Signage and Marking | N/A | N/A | N/A | 2-7 | No Manufacturer Requirements Available | Monthly - Check permanent signs and markings for adequacy and readability. Repair or replace deteriorated or illegible signs and markings. | |||||||||
| 48126 | 11111 | Biggs Airfield | Air Eliminator Tanks | Offload | Unk | Unk | Unk | X | 3-10.1 | The most common indication of mechanical air and |
vapor eliminator failure is leakage in and around the cover and valve plate area. Common causes of air eliminator failure are valve plate wear, a broken reed strip, a damaged cover gasket, and a punctured float filled with product.
1. Remove the cover screws from the air eliminator cover with a 1/2 inch wrench or socket, and pull the cover, vent plate and seal ring from the housing.
2. Inspect the raised ridge of the vent port opening in the middle of the valve plate for marring or debris. Inspect the seal ring for damage.
3. Replace the seal ring and/or valve plate. Tighten the
| cover screws to a torque of 17.5 - 20.5 ft-lbs. | No Operator Requirement | |||||||||||
| 48127 | 11111 | Biggs Airfield | Air Eliminator Tanks | Offload | Unk | Unk | Unk | X | 3-10.1 | The most common indication of mechanical air and |
vapor eliminator failure is leakage in and around the cover and valve plate area. Common causes of air eliminator failure are valve plate wear, a broken reed strip, a damaged cover gasket, and a punctured float filled with product.
1. Remove the cover screws from the air eliminator cover with a 1/2 inch wrench or socket, and pull the cover, vent plate and seal ring from the housing.
2. Inspect the raised ridge of the vent port opening in the middle of the valve plate for marring or debris. Inspect the seal ring for damage.
3. Replace the seal ring and/or valve plate. Tighten the
| cover screws to a torque of 17.5 - 20.5 ft-lbs. | No Operator Requirement | ||||||||||||||
| 48125 | 11111 | Biggs Airfield | Automatic Air Vents | Filter House | Unk | Unk | Unk | X | 3-10.2 | Normally the DUOVENT valve does not require maintenance. If maintenance is required, remove the valve; the presence of shut-off valve RIA allows this operation without emptying the system. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Automatic Air Vents | Filter House | Unk | Unk | Unk | X | 3-10.2 | Normally the DUOVENT valve does not require maintenance. If maintenance is required, remove the valve; the presence of shut-off valve RIA allows this operation without emptying the system. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Filter Separators | Issue #1 | Facet | HCS-643-236 | 600 GPM | X | 3-6.2 | Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. Replace filter cartridges when the acceptable maximum differential pressure is reached, the maximum in-service duration has passed, or the fuel becomes visibly dirty or discolored. | Daily - Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. | ||||
| 48125 | 11111 | Biggs Airfield | Filter Separators | Issue #2 | Facet | HCS-643-236 | 600 GPM | X | 3-6.2 | Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. Replace filter cartridges when the acceptable maximum differential pressure is reached, the maximum in-service duration has passed, or the fuel becomes visibly dirty or discolored. | Daily - Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. | ||||
| 48125 | 11111 | Biggs Airfield | Filter Separators | Receipt #1 | Facet | HCS-643-236 | 600 GPM | X | 3-6.2 | Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. Replace filter cartridges when the acceptable maximum differential pressure is reached, the maximum in-service duration has passed, or the fuel becomes visibly dirty or discolored. | Daily - Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. | ||||
| 48125 | 11111 | Biggs Airfield | Filter Separators | Receipt #2 | Facet | HCS-643-236 | 600 GPM | X | 3-6.2 | Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. Replace filter cartridges when the acceptable maximum differential pressure is reached, the maximum in-service duration has passed, or the fuel becomes visibly dirty or discolored. | Daily - Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. | ||||
| 48125 | 11111 | Biggs Airfield | Positive Displacement Meters | Fillstand #1 | Veeder Root | 0788700-063 / 204574795 | 0-600 | X | 3-7.1 | Inspect counter head for unusual noises and smooth operation. Inspect temperature element operation of meters equipped with temperature | |||||
| compensation feature | Monthly - Inspect counter head for unusual noises and smooth operation. | ||||||||||||||
| 48125 | 11111 | Biggs Airfield | Positive Displacement Meters | Fillstand #2 | Veeder Root | 0788700-063 / 204574795 | 0-600 | X | 3-7.1 | Inspect counter head for unusual noises and smooth operation. Inspect temperature element operation of meters equipped with temperature | |||||
| compensation feature | Monthly - Inspect counter head for unusual noises and smooth operation. | ||||||||||||||
| 48125 | 11111 | Biggs Airfield | Positive Displacement Meters | Fillstand #3 | Veeder Root | 0788700-063 / 204574795 | 0-600 | X | 3-7.1 | Inspect counter head for unusual noises and smooth operation. Inspect temperature element operation of meters equipped with temperature | |||||
| compensation feature | Monthly - Inspect counter head for unusual noises and smooth operation. | ||||||||||||||
| 48125 | 11111 | Biggs Airfield | Positive Displacement Meters | Fillstand #4 | Veeder Root | 0788700-063 / 204574795 | 0-600 | X | 3-7.1 | Inspect counter head for unusual noises and smooth operation. Inspect temperature element operation of meters equipped with temperature | |||||
| compensation feature | Monthly - Inspect counter head for unusual noises and smooth operation. | ||||||||||||||
| 48125 | 11111 | Biggs Airfield | Centrifigal Pumps | Tank 11113 PRT | Baldor Reliance | CA421181 | 10 GPM | X | X | 3-8.1 | During routine pump inspections only the easy to monitor factors such as pressure, temperature, vibration etc can be checKed. But during quarterly inspections, shaft alignment and oil levels should also be checked. Change Oil Annually | No Operator Requirement | |||
| 48125 | 11111 | Biggs Airfield | Centrifigal Pumps | Tank 11114 PRT | Baldor Reliance | CA433660 | 10 GPM | X | X | 3-8.1 | During routine pump inspections only the easy to monitor factors such as pressure, temperature, vibration etc can be checKed. But during quarterly inspections, shaft alignment and oil levels should also be checked. Change Oil Annually | No Operator Requirement | |||
| 48125 | 11111 | Biggs Airfield | Centrifigal Pumps | Filter House PRT | Baldor Reliance | CA433693 | 10 GPM | X | X | 3-8.1 | During routine pump inspections only the easy to monitor factors such as pressure, temperature, vibration etc can be checKed. But during quarterly inspections, shaft alignment and oil levels should also be checked. Change Oil Annually | No Operator Requirement | |||
| 48125 | 11111 | Biggs Airfield | Centrifigal Pumps | Issue Pump 1 | Clyde Union | 800002436A | 600 GPM | X | X | 3-8.1 | During routine pump inspections only the easy to monitor factors such as pressure, temperature, vibration etc can be checKed. But during quarterly inspections, shaft alignment and oil levels should also be checked. Change Oil Annually | No Operator Requirement | |||
| 48125 | 11111 | Biggs Airfield | Centrifigal Pumps | Issue Pump 2 | Clyde Union | 800002436A | 600 GPM | X | X | 3-8.1 | During routine pump inspections only the easy to monitor factors such as pressure, temperature, vibration etc can be checKed. But during quarterly inspections, shaft alignment and oil levels should also be checked. Change Oil Annually | No Operator Requirement | |||
| 48125 | 11111 | Biggs Airfield | Centrifigal Pumps | Reciept 1 | Baldor Reliance | CM11005ZA-2 | 600 GPM | X | X | 3-8.1 | During routine pump inspections only the easy to monitor factors such as pressure, temperature, vibration etc can be checKed. But during quarterly inspections, shaft alignment and oil levels should also be checked. Change Oil Annually | No Operator Requirement | |||
| 48125 | 11111 | Biggs Airfield | Centrifigal Pumps | Reciept 2 | Clyde Union | CM11005ZA-2 | 600 GPM | X | X | 3-8.1 | During routine pump inspections only the easy to monitor factors such as pressure, temperature, vibration etc can be checKed. But during quarterly inspections, shaft alignment and oil levels should also be checked. Change Oil Annually | No Operator Requirement | |||
| 48125 | 11111 | Biggs Airfield | Offload Fuel Hoses | Offload 1 | Unk | Unk | 4 Inch | X | X | 3-9.2 | Aircraft fueling hose shall be inspected before use each day. The hose shall be extended as it normally would be for fueling and checked for evidence of blistering, carcass saturation or separation, cuts, nicks, or abrasions that expose reinforcement material, and for slippage, misalignment, or leaks at couplings. | Weekly - Visually inspect hoses for cracks brittle surface coatings, exposed wire braids, exposed reinforcement, flattening, kinks, and bulges or soft spots which might indicate broken or displaced reinforcement. | |||
| 48125 | 11111 | Biggs Airfield | Offload Fuel Hoses | Offload 2 | Unk | Unk | 4 Inch | X | X | 3-9.2 | Aircraft fueling hose shall be inspected before use each day. The hose shall be extended as it normally would be for fueling and checked for evidence of blistering, carcass saturation or separation, cuts, nicks, or abrasions that expose reinforcement material, and for slippage, misalignment, or leaks at couplings. | Weekly - Visually inspect hoses for cracks brittle surface coatings, exposed wire braids, exposed reinforcement, flattening, kinks, and bulges or soft spots which might indicate broken or displaced reinforcement. | |||
| 48125 | 11111 | Biggs Airfield | Filter Seperator Control Valves | Filter House | Unk | Unk | Unk | X | X | 4-4.2.2 | No Manufacturers Data Available. Adjustment not advised unless formal training is received. | No Operator Requirement | |||
| 48125 | 11111 | Biggs Airfield | Filter Seperator Control Valves | Filter House | Unk | Unk | Unk | X | X | 4-4.2.2 | No Manufacturers Data Available. Adjustment not advised unless formal training is received. | No Operator Requirement | |||
| 48125 | 11111 | Biggs Airfield | Filter Seperator Control Valves | Filter House | Unk | Unk | Unk | X | X | 4-4.2.2 | No Manufacturers Data Available. Adjustment not advised unless formal training is received. | No Operator Requirement | |||
| 48125 | 11111 | Biggs Airfield | Filter Seperator Control Valves | Filter House | Unk | Unk | Unk | X | X | 4-4.2.2 | No Manufacturers Data Available. Adjustment not advised unless formal training is received. | No Operator Requirement | |||
| 48125 | 11111 | Biggs Airfield | Above Ground Piping and Equipment Coatings | Unk | Unk | Unk | X | 6-10.1 | No Manufacturer Requirements Available | No Operator Requirement | |||||
| 48125 | 11111 | Biggs Airfield | Gate Valves | Offload 1 | Unk | Unk | Unk | X | X | 6-6.2.3 | Operate from fully open to fully closed . Conduct Tightness test as required for application. | No Operator Requirement | |||
| 48125 | 11111 | Biggs Airfield | Gate Valves | Offload 1 | Unk | Unk | Unk | X | X | 6-6.2.3 | Operate from fully open to fully closed . Conduct Tightness test as required for application. | No Operator Requirement | |||
| 48125 | 11111 | Biggs Airfield | Gate Valves | Offload 1 | Unk | Unk | Unk | X | X | 6-6.2.3 | Operate from fully open to fully closed . Conduct Tightness test as required for application. | No Operator Requirement | |||
| 48125 | 11111 | Biggs Airfield | Gate Valves | Offload 2 | Unk | Unk | Unk | X | X | 6-6.2.3 | Operate from fully open to fully closed . Conduct Tightness test as required for application. | No Operator Requirement | |||
| 48125 | 11111 | Biggs Airfield | Gate Valves | Offload 2 | Unk | Unk | Unk | X | X | 6-6.2.3 | Operate from fully open to fully closed . Conduct Tightness test as required for application. | No Operator Requirement | |||
| 48125 | 11111 | Biggs Airfield | Gate Valves | Fillstand 1 | Unk | Unk | Unk | X | X | 6-6.2.3 | Operate from fully open to fully closed . Conduct Tightness test as required for application. | No Operator Requirement | |||
| 48125 | 11111 | Biggs Airfield | Gate Valves | Fillstand #3 | Unk | Unk | Unk | X | X | 6-6.2.3 | Operate from fully open to fully closed . Conduct Tightness test as required for application. | No Operator Requirement | |||
| 48125 | 11111 | Biggs Airfield | Gate Valves | Fillstand #3 | Unk | Unk | Unk | X | X | 6-6.2.3 | Operate from fully open to fully closed . Conduct Tightness test as required for application. | No Operator Requirement | |||
| 48125 | 11111 | Biggs Airfield | Gate Valves | Fillstand #3 | Unk | Unk | Unk | X | X | 6-6.2.3 | Operate from fully open to fully closed . Conduct Tightness test as required for application. | No Operator Requirement | |||
| 48125 | 11111 | Biggs Airfield | Gate Valves | Fillstand #4 | Unk | Unk | Unk | X | X | 6-6.2.3 | Operate from fully open to fully closed . Conduct Tightness test as required for application. | No Operator Requirement | |||
| 48125 | 11111 | Biggs Airfield | Gate Valves | Fillstand #4 | Unk | Unk | Unk | X | X | 6-6.2.3 | Operate from fully open to fully closed . Conduct Tightness test as required for application. | No Operator Requirement | |||
| 48125 | 11111 | Biggs Airfield | Gate Valves | Fillstand #4 | Unk | Unk | Unk | X | X | 6-6.2.3 | Operate from fully open to fully closed . Conduct Tightness test as required for application. | No Operator Requirement | |||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Fillstand 1 | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Fillstand 1 | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Fillstand 1 | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Fillstand 2 | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Fillstand 2 | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Fillstand 2 | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Fillstand #3 | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Fillstand #3 | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Fillstand #3 | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Fillstand #3 | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Fillstand #3 | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Fillstand #3 | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Fillstand #3 | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Fillstand #3 | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Fillstand #3 | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Fillstand #3 | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Fillstand #4 | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Fillstand #4 | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Fillstand #4 | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Fillstand #4 | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Fillstand #4 | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Fillstand #4 | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Fillstand #4 | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Fillstand #4 | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Fillstand #4 | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Fillstand #4 | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Ball Valves | Filter House | Unk | Unk | Unk | X | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Double Block and Bleed Valves | Filter House | Unk | Unk | Unk | X | X | 6-6.2.5 | Valve design must permit sealing slips to be replaced from the bottom with the valve mounted in the piping. Valves must operate from fully open to fully closed by rotation of the handwheel to lift and turn the plug. | No Operator Requirement | |||
| 48125 | 11111 | Biggs Airfield | Double Block and Bleed Valves | Filter House | Unk | Unk | Unk | X | X | 6-6.2.5 | Valve design must permit sealing slips to be replaced from the bottom with the valve mounted in the piping. Valves must operate from fully open to fully closed by rotation of the handwheel to lift and turn the plug. | No Operator Requirement | |||
| 48125 | 11111 | Biggs Airfield | Double Block and Bleed Valves | Filter House | Unk | Unk | Unk | X | X | 6-6.2.5 | Valve design must permit sealing slips to be replaced from the bottom with the valve mounted in the piping. Valves must operate from fully open to fully closed by rotation of the handwheel to lift and turn the plug. | No Operator Requirement | |||
| 48125 | 11111 | Biggs Airfield | Double Block and Bleed Valves | Filter House | Unk | Unk | Unk | X | X | 6-6.2.5 | Valve design must permit sealing slips to be replaced from the bottom with the valve mounted in the piping. Valves must operate from fully open to fully closed by rotation of the handwheel to lift and turn the plug. | No Operator Requirement | |||
| 48125 | 11111 | Biggs Airfield | Motor Operators | Tank 11113 PRT | Unk | Unk | Unk | X | 6-6.6 | Visually inspect motor operators to ensure smooth movement during opening and closing operation and adjust, if necessary, to ensure that they are opening and closing fully. Listen for and investigate unusual noises during operation. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Motor Operators | Tank 11114 PRT | Unk | Unk | Unk | X | 6-6.6 | Visually inspect motor operators to ensure smooth movement during opening and closing operation and adjust, if necessary, to ensure that they are opening and closing fully. Listen for and investigate unusual noises during operation. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Motor Operators | Filter House PRT | Unk | Unk | Unk | X | 6-6.6 | Visually inspect motor operators to ensure smooth movement during opening and closing operation and adjust, if necessary, to ensure that they are opening and closing fully. Listen for and investigate unusual noises during operation. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Motor Operators | Issue Pump 1 | Unk | Unk | Unk | X | 6-6.6 | Visually inspect motor operators to ensure smooth movement during opening and closing operation and adjust, if necessary, to ensure that they are opening and closing fully. Listen for and investigate unusual noises during operation. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Motor Operators | Issue Pump 2 | Unk | Unk | Unk | X | 6-6.6 | Visually inspect motor operators to ensure smooth movement during opening and closing operation and adjust, if necessary, to ensure that they are opening and closing fully. Listen for and investigate unusual noises during operation. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Motor Operators | Reciept 1 | Unk | Unk | Unk | X | 6-6.6 | Visually inspect motor operators to ensure smooth movement during opening and closing operation and adjust, if necessary, to ensure that they are opening and closing fully. Listen for and investigate unusual noises during operation. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Motor Operators | Reciept 2 | Unk | Unk | Unk | X | 6-6.6 | Visually inspect motor operators to ensure smooth movement during opening and closing operation and adjust, if necessary, to ensure that they are opening and closing fully. Listen for and investigate unusual noises during operation. | No Operator Requirement | ||||
| 48125 | 11111 | Biggs Airfield | Pressure and Pressure Vacuum Gauges | Offload 1 | Palmer | Unk | 0-100 | X | X | X | 6-7.1 | Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use. | Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system. | ||
| 48125 | 11111 | Biggs Airfield | Pressure and Pressure Vacuum Gauges | Offload 1 | Palmer | Unk | 0-160 | X | X | X | 6-7.1 | Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use. | Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system. | ||
| 48125 | 11111 | Biggs Airfield | Pressure and Pressure Vacuum Gauges | Offload 2 | Palmer | Unk | 0-160 | X | X | X | 6-7.1 | Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use. | Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system. | ||
| 48125 | 11111 | Biggs Airfield | Pressure and Pressure Vacuum Gauges | Offload 2 | Palmer | Unk | 0-160 | X | X | X | 6-7.1 | Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use. | Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system. | ||
| 48125 | 11111 | Biggs Airfield | Pressure and Pressure Vacuum Gauges | Fillstand 1 | Palmer | Unk | 0-160 | X | X | X | 6-7.1 | Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use. | Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system. | ||
| 48125 | 11111 | Biggs Airfield | Pressure and Pressure Vacuum Gauges | Fillstand 1 | Palmer | Unk | 0-160 | X | X | X | 6-7.1 | Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use. | Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system. | ||
| 48125 | 11111 | Biggs Airfield | Pressure and Pressure Vacuum Gauges | Filstand 2 | Palmer | Unk | 0-160 | X | X | X | 6-7.1 | Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use. | Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system. | ||
| 48125 | 11111 | Biggs Airfield | Pressure and Pressure Vacuum Gauges | Filstand 2 | Palmer | Unk | 0-160 | X | X | X | 6-7.1 | Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use. | Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system. | ||
| 48125 | 11111 | Biggs Airfield | Pressure and Pressure Vacuum Gauges | Pump 1 | Palmer | Unk | 0-300 | X | X | X | 6-7.1 | Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use. | Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system. | ||
| 48125 | 11111 | Biggs Airfield | Pressure and Pressure Vacuum Gauges | Pump 1 | Palmer | Unk | 0-60 | X | X | X | 6-7.1 | Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use. | Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system. | ||
| 48125 | 11111 | Biggs Airfield | Pressure and Pressure Vacuum Gauges | Pump 2 | Palmer | Unk | 0-300 | X | X | X | 6-7.1 | Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use. | Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system. | ||
| 48125 | 11111 | Biggs Airfield | Pressure and Pressure Vacuum Gauges | Pump 2 | Palmer | Unk | 0-160 | X | X | X | 6-7.1 | Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use. | Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system. | ||
| 48125 | 11111 | Biggs Airfield | Pressure and Pressure Vacuum Gauges | Issue Seperator / top of DP gauge | Palmer | Unk | 0-300 | X | X | X | 6-7.1 | Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use. | Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system. | ||
| 48125 | 11111 | Biggs Airfield | Pressure and Pressure Vacuum Gauges | Issue Seperator / top of DP gauge | Palmer | Unk | 0-300 | X | X | X | 6-7.1 | Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use. | Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system. | ||
| 48125 | 11111 | Biggs Airfield | Pressure and Pressure Vacuum Gauges | Reciept Seperator / top of DP gauge | Palmer | Unk | 0-300 | X | X | X | 6-7.1 | Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use. | Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system. | ||
| 48125 | 11111 | Biggs Airfield | Pressure and Pressure Vacuum Gauges | Reciept Seperator / top of DP gauge | Palmer | Unk | 0-300 | X | X | X | 6-7.1 | Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use. | Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system. | ||
| 48125 | 11111 | Biggs Airfield | Pressure and Pressure Vacuum Gauges | Filter House PRT | Palmer | Unk | 0-300 | X | X | X | 6-7.1 | Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use. | Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system. | ||
| 48125 | 11111 | Biggs Airfield | Pressure and Pressure Vacuum Gauges | Fillstand #3 | Palmer | Unk | 0-160 | X | X | X | 6-7.1 | Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use. | Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system. | ||
| 48125 | 11111 | Biggs Airfield | Pressure and Pressure Vacuum Gauges | Fillstand #3 | Palmer | Unk | 0-160 | X | X | X | 6-7.1 | Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use. | Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system. | ||
| 48125 | 11111 | Biggs Airfield | Pressure and Pressure Vacuum Gauges | Fillstand #4 | Palmer | Unk | 0-160 | X | X | X | 6-7.1 | Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use. | Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system. |