PWS RAN FMP Template - v2.2.xlsx

XLSX spreadsheet 126 KB Posted

Attached to
Sources Sought - CEHNC FUELS PROGRAM
Solicitation number
PANHES-25-P-0000-001794
Issued by

About this file

This is a Facility Maintenance Plan (FMP) template for recurring maintenance of fuel facilities at Joint Base San Antonio-Randolph. The template details maintenance requirements for equipment and systems at multiple facilities including a Military Service Station (#179), Operations Building (#1042), Maintenance Shed (#1043), and Tank Truck Offload (#3001).

The plan provides detailed specifications for inspection and maintenance of fuel system components including storage tanks, piping, valves, pumps, filters, meters, hoses, control systems, and safety equipment. It outlines maintenance frequencies (daily, weekly, monthly, quarterly, annually) and specific tasks for each component. Key systems covered include above/underground storage tanks, dispensing equipment, offloading systems, filter separators, emergency shutoff systems, and leak detection equipment. The facility operates 24 hours at 1 Washington Circle, Randolph, TX 78150. The template includes sections for administrative information, communication protocols, safety requirements, and maintenance schedules but does not specify actual maintenance services being procured.

View the file

Other files

File Type Posted
Sources Sought FUELS - Programmatic Rev1 7 May 25.docx DOCX document
3.4 Appendix B - Attachment 4 - SO Tracker-20210628.xlsx XLSX spreadsheet
6.0 - Appendix E ISR 15-Bulk_Fuel_Facilities FY25.xlsx XLSX spreadsheet
2.0 Appendix A RM_SO Process_20241220_PgM Reviewed Incorporated.docx DOCX document
3.1 Appendix B - Attachment 1 - Three Week Look Ahead_20230420.xlsx XLSX spreadsheet
3.2 Appendix B - Attachment 2 - Monthly Report Format 20240910.docx DOCX document
2.2 Appendix A - Attachment 2 Contractor Travel Expense Report_20240910.xlsx XLSX spreadsheet
9.0 Appendix H - Minor Repairs Incidental to Maintenance Activities POJ 20231009.xlsx XLSX spreadsheet
7.0 CUID - v2.1.pdf PDF
8.0 Appendix G_UFC 3-460-03 Maintenance Table- v4.3.pdf PDF
6.0 Appendix E ISR 14_operational_fuel_facilities FY25.xlsx XLSX spreadsheet
3.0 Appendix B Reporting Requirements_20240910.docx DOCX document
4.0 Appendix C Task Order Specifications_202401216.docx DOCX document
5.0 Appendix D Antiterrorism and OPSEC 20230206.docx DOCX document
PWS LEX FMP Template - v2.2.xlsx XLSX spreadsheet
PWS VNC FMP Template - v2.2.xlsx XLSX spreadsheet
PWS KEQ FMP Template - v2.2.xlsx XLSX spreadsheet
PWS CVZ FMP Template - v2.2.xlsx XLSX spreadsheet
PWS SHP FMP Template - v2.2.xlsx XLSX spreadsheet
PWS PBA FMP Template - v2.2.xlsx XLSX spreadsheet
PWS GRB FMP Template - v2.2.xlsx XLSX spreadsheet
PWS BRO FMP Template - v2.2.xlsx XLSX spreadsheet
PWS BAR FMP Template - v2.2.xlsx XLSX spreadsheet
PWS EFS FMP Template - v2.2.xlsx XLSX spreadsheet
PWS LAU FMP Template - v2.2.xlsx XLSX spreadsheet
PWS CHF FMP Template - v2.2.xlsx XLSX spreadsheet
PWS BEU FMP Template - v2.2.xlsx XLSX spreadsheet
PWS GDF FMP Template - v2.2.xlsx XLSX spreadsheet
PWS BLI FMP Template - v2.2.xlsx XLSX spreadsheet
PWS TKR FMP Template - v2.2.xlsx XLSX spreadsheet
PWS RBN FMP Template - v2.2.xlsx XLSX spreadsheet
PWS MAA FMP Template - v2.2.xlsx XLSX spreadsheet
PWS FSH FMP Template - v2.2.xlsx XLSX spreadsheet
PWS FSO FMP Template - v2.2.xlsx XLSX spreadsheet
PWS LRG FMP Template - v2.2.xlsx XLSX spreadsheet
PWS RRT FMP Template - v2.2.xlsx XLSX spreadsheet
PWS ALT FMP Template - v2.2.xlsx XLSX spreadsheet
PWS TUL FMP Template - v2.2.xlsx XLSX spreadsheet
PWS BL2 FMP Template - v2.2.xlsx XLSX spreadsheet
PWS ELL FMP Template - v2.2.xlsx XLSX spreadsheet
PWS WRF FMP Template - v2.2.xlsx XLSX spreadsheet
PWS LLD FMP Template - v2.2.xlsx XLSX spreadsheet
PWS DYE FMP Template - v2.2.xlsx XLSX spreadsheet
12.0 PWS Appendix K Real Property Data_20230420.xlsx XLSX spreadsheet
PWS FSM FMP Template - v2.2.xlsx XLSX spreadsheet
PWS _Fuels RMMR 20241220.docx DOCX document
Show all 46

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Administrative

LocationSite NameJBSA-Randolph
RPSUID3209
DLA Site CodeRAN
Hours of Operation24 Hours of Operation
Address1 Washington Circle, Randolph, TX 78150
ContractContractor
Contract #
Local POCsQAE Name
QAE Phone
QAE Email
Alt QAE Name
Alt QAE Phone
Alt QAE Email
DLA/SCP POCsDLA PM Name
DLA PM Phone
DLA PM Email
SCP PM Name
SCP PM Phone
SCP PM Email
Contractor POCsContractor PM Name
Contractor PM Phone
Contractor PM Email
Contractor QC Name
Contractor QC Phone
Contractor QC Email
Contractor SM Name
Contractor SM Phone
Contractor SM Email
USACE POCsUSACE PM/COR Name
USACE PM/COR Phone
USACE PM/COR Email
USACE PE Name
USACE PE Phone
USACE PE Email
USACE KO Name
USACE KO Phone
USACE KO Email

Facility Maintenance Plan

FMP v2.2 &P of &N

Instructions:

This table shows the minimum information required. Additional details should be included based on site specific requirements. Additional POCs may be required.

General Facility Description Facility Description

Purpose:

This Facility Maintenance Plan provides guidance for Contractor personnel in the operation, inspection, and maintenance of permanently installed fuel facilities operated under the control of the Quality Assurance Evaluators. Federal, state, and local environmental laws and regulations shall be complied with if this plan is in conflict with them.

Scope:

The instructions prescribed by this plan outline general fuels maintenance information associated with fuel storage and dispensing systems and provides the minimum periodic contractor maintenance and inspection criteria requirements for the systems. This plan is to be used in conjunction with other existing directives governing fuel system operations and maintenance requirements. Conotractor will properly maintain and repair federally funded petroleum systems and facilities in order to provide compliance with applicable code, criteria, and federal, state, local and/or host nation regulations.

Fuels Facilities:

Organizational tanks, and associated dispensing equipment are maintained and operated by the owning organization. Fuel system maintenance contractors shall perform all maintenance and associated procurement actions on installed fuel systems.

Each installation under the Southwest Division contract are military land-based facilities who receive, store, distribute, and/or dispense liquid fuels.

Standard fuel system equipment includes:

a) Above Ground Sorage Stanks (AST), Underground Storage Tanks (UST)

b) Filter/separator and other filtration device maintenance access, particularly element removal.

c) Manual valves

d) Meter Registers, and Flow Meters.

e) Control Valves.

f) Pumps

g) Tank Monitoring Equipment and Instruments

h) Alarms

i) Fire Fighting Equipment

Site Specific General Information:

Facility Maintenance Plan

FMP v2.2 &P of &N

Instructions:

Include a general facility overview and description of each fuel system for the sites in accordance with UFC 3-460-01. Examples include: Bulk Storage Facilities, Aircraft Fueling Facilities, Marine and Dispensing Facilities, Ground Products Fueling Facilities, Alternate POL Facilities, and Support Facilities. Also include facility #s, facility names, fuel type, photos, and any other pertinent information.

Include Site Specific Conditions and Restrictions in this tab.

Communication Plan

Facility Maintenance Plan

FMP v2.2 &P of &N

Instructions:

Communication plan shall address in/out briefs, lines of communication, coordination for access, etc.

Safety

Facility Maintenance Plan

FMP v2.2 &P of &N

Instructions:

Site Specific Addendum and Activity Hazard Analysis, which are Attachments to the APP, specific to activities or tasks related to recurring maintenance for this site.

RM Schedule

Facility Maintenance Plan

FMP v2.2 &P of &N

Instructions:

Link RM schedule here

Task Matrix

Applicable Facility AssetsUFC System Level Maintenance FrequencySpecial Considerations
Real Property Unique Identifier
(RPUID)Real Property Facility #Real Property Facility NameOperational AreaComponent TypeBase Asset IDComponent Unique Identifier (CUID)MakeModelCapacity/SizeQSAUFC Section ReferenceAdditional Manufacturer RM RequirementsOperator/ equipment RequirementsSystem availabilityOther ContractComments
20Fuels ManagementFuels ManagementFuel Truck Containment AreasPOL YardN/AN/AN/AXXX11-1.1No Manufacturer Requirements AvailableMonthly - Remove debris from around security fence. Inspect fence grounding points. Ensure connections are not loose or damage.No Mission Impact
20Fuels ManagementFuels ManagementPumphouse/Filter BuildingsFuels ManagementN/AN/AN/AXXX11-2.1No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
20Fuels ManagementFuels ManagementEmergency Eyewash/ShowersLab ShowerWater Saver FaucetUnmarkedUnmarkedXXX11-3Weekly - Equipment installed within 10 seconds from the hazard and on the same plane as the hazard Pathway is clear of obstructions Plumbed equipment activated to ensure compliant operation and to clear any sediment Self-contained equipment checked to determine if the flushing fluid needs to be changed or supplemented Equipment free of broken or missing parts Equipment protected against freezing User protected from scalding waterNo Operator RequirementNo Mission Impact
20Fuels ManagementFuels ManagementVentilation HoodsLab HoodHamiltonNot LabeledNot LabeledXXX11-4.1Daily visual inspection, check the fume hood for visible airflow blockage such as large items or containers near the slot opening. Other daily inspections include holding a tissue at the opening to observe inward airflow, maintaining clean surfaces inside the hood, and keeping the sash at an appropriate height when working and not working in the hood.No Operator RequirementNo Mission Impact
179Military Service StationDispenser IslandPumphouse/Filter BuildingsOperations BuildingN/AN/AN/AXXX11-2.1No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
179Military Service StationDispenser IslandEmergency Eyewash/ShowersEEW/SHawsUnmarkedUnmarkedXXX11-3Weekly - Equipment installed within 10 seconds from the hazard and on the same plane as the hazard Pathway is clear of obstructions Plumbed equipment activated to ensure compliant operation and to clear any sediment Self-contained equipment checked to determine if the flushing fluid needs to be changed or supplemented Equipment free of broken or missing parts Equipment protected against freezing User protected from scalding waterNo Operator RequirementNo Mission Impact
179Military Service StationOffload AreaSignage and MarkingsOffload AreaN/AN/AN/A00X2-7No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
179Military Service StationDispenser IslandSignage and MarkingsDispenser IslandN/AN/AN/A00X2-7No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
179Military Service StationOffload AreaAboveground PipingOffload AreaN/AN/A4.0 in.XXX6-1.3No Manufacturer Requirements AvailableWeekly - Conduct petroleum fuel piping visual inspection in accordance with Section 6-1.5 Pipeline Visual Inspection.No Mission Impact
179Military Service StationOffload AreaSight Flow IndicatorsMOGASPainted OverPainted OverPainted Over0006-12.3Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Partial System OOS
179Military Service StationOffload AreaSight Flow IndicatorsTank 3/4Not LabeledNot LabeledNot Labeled0006-12.3Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Partial System OOS
179Military Service StationOffload AreaSight Flow IndicatorsE85Painted OverPainted OverPainted Over0006-12.3Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Partial System OOS
179Military Service StationOffload AreaBall ValvesDiesel Transition T4 IsolationApolloRF153.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
179Military Service StationOffload AreaBall ValvesDike drainCruvloxM14.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
179Military Service StationOffload AreaBall ValvesDike drainCruvloxM14.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
179Military Service StationOffload AreaBall ValvesDike drainUnknownUnknown1.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
179Military Service StationOffload AreaBall ValvesDike DrainUnknownUnknown1.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
179Military Service StationOffload AreaBall ValvesE85 Transition SumpUnknownUnknown2.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
179Military Service StationOffload AreaBall ValvesDiesel Transition T3 IsolationApolloRF153.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
179Military Service StationOffload AreaBall ValvesMOGASApolloNot legible3.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
179Military Service StationOffload AreaBall ValvesE85DemcoWard 126A4.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
179Military Service StationOffload AreaBall ValvesE85Painted OverPainted Over0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
179Military Service StationOffload AreaBall ValvesV5-NC Tank 4DemcoNot Legible4.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
179Military Service StationOffload AreaBall ValvesV4-NC Tank 3DemcoNot Legible4.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
179Military Service StationOffload AreaBall ValvesTank 3/4 IsolationDemcoNot Legible4.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
179Military Service StationOffload AreaBall ValvesTank 3/4 Sample PortNot Legible600 WOG0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
179Military Service StationOffload AreaBall ValvesV1-NCDemcoWard 126A4.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
179Military Service StationOffload AreaBall ValvesMOGAS Sample PortNot LegiblePainted Over0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
179Military Service StationOffload AreaBall ValvesV6 - NCPainted OverPainted Over4.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactMaybe not used
179Military Service StationOffload AreaDouble Block and Bleed ValvesC-300 FillstandWestern ValveDan-Ex3.0 in.XXX6-6.2.5Valve design must permit sealing slips to be replaced from the bottom with the valve mounted in the piping. Valves must operate from fully open to fully closed by rotation of the handwheel to lift and turn the plug.No Operator RequirementPartial System OOS
179Military Service StationOffload AreaCheck ValvesMOGAS Transition SumpNot LabeledNot Labeled3.0 in.XX06-6.2.8Visual for damage, leaks, tightness.No Operator RequirementPartial System OOS
179Military Service StationDispenser IslandEmergency Shutoff ValvesDispenser 1/2OPWNot Legible1.5 in.00X7-12Inspect fusible link and ensure it is not obstructed. Ensure valve body is clean and free of fuel. Inspect mechanical links of the valve for correct operation. Conduct test of valve to ensure it operates correctly.Monthly - Inspect stabilizer bar to ensure that it is securely mounted below the base of the dispenser. Inspect the mounting bolts that secure the emergency shutoff valve to the stabilizer bar. Inspect fusible link and ensure it is not obstructed. Ensure valve body is clean and free of fuel.Partial System OOS
179Military Service StationDispenser IslandEmergency Shutoff ValvesDispenser 3/4OPWNot Legible1.5 in.00X7-12Inspect fusible link and ensure it is not obstructed. Ensure valve body is clean and free of fuel. Inspect mechanical links of the valve for correct operation. Conduct test of valve to ensure it operates correctly.Monthly - Inspect stabilizer bar to ensure that it is securely mounted below the base of the dispenser. Inspect the mounting bolts that secure the emergency shutoff valve to the stabilizer bar. Inspect fusible link and ensure it is not obstructed. Ensure valve body is clean and free of fuel.Partial System OOS
179Military Service StationDispenser IslandEmergency Shutoff ValvesDispenser 5/6OPWNot Legible1.5 in.00X7-12Inspect fusible link and ensure it is not obstructed. Ensure valve body is clean and free of fuel. Inspect mechanical links of the valve for correct operation. Conduct test of valve to ensure it operates correctly.Monthly - Inspect stabilizer bar to ensure that it is securely mounted below the base of the dispenser. Inspect the mounting bolts that secure the emergency shutoff valve to the stabilizer bar. Inspect fusible link and ensure it is not obstructed. Ensure valve body is clean and free of fuel.Partial System OOS
179Military Service StationDispenser IslandDispenser SumpsDispenser 1/2WayneUnmarkedN/AXXX7-13Inspect sump pipe transition fittings for tears, cracks, or other signs of deterioration. Test sumps and ensure they are liquid tight by using vacuum, pressure, or liquid testing in accordance with 40 CFR 280, Section 43.Monthly - Inspect for signs of water, fuel, trash, and debris inside sumps. Remove and properly dispose of collected water, fuel, trash, and debris. Visually inspect penetration fittings. If fuel or water is detected investigate the source and repair.Partial System OOS
179Military Service StationDispenser IslandDispenser SumpsDispenser 5/6WayneUnmarkedN/AXXX7-13Inspect sump pipe transition fittings for tears, cracks, or other signs of deterioration. Test sumps and ensure they are liquid tight by using vacuum, pressure, or liquid testing in accordance with 40 CFR 280, Section 43.Monthly - Inspect for signs of water, fuel, trash, and debris inside sumps. Remove and properly dispose of collected water, fuel, trash, and debris. Visually inspect penetration fittings. If fuel or water is detected investigate the source and repair.Partial System OOS
179Military Service StationDispenser IslandDispenser SumpsDispenser 3/4WayneUnmarkedN/AXXX7-13Inspect sump pipe transition fittings for tears, cracks, or other signs of deterioration. Test sumps and ensure they are liquid tight by using vacuum, pressure, or liquid testing in accordance with 40 CFR 280, Section 43.Monthly - Inspect for signs of water, fuel, trash, and debris inside sumps. Remove and properly dispose of collected water, fuel, trash, and debris. Visually inspect penetration fittings. If fuel or water is detected investigate the source and repair.Partial System OOS
179Military Service StationOffload AreaTransition SumpsDiesel Transition SumpUnknownUnknownUnknownXXX7-14Inspect sump pipe transition fittings for tears, cracks, or other signs of deterioration. Test sumps and ensure they are liquid tight by using vacuum, pressure, or liquid testing in accordance with 40 CFR 280, Section 43.Monthly - Inspect for signs of water, fuel, trash, and debris inside sumps. Remove and properly dispose of collected water, fuel, trash, and debris. Visually inspect penetration fittings. If fuel or water is detected investigate the source and repair.Partial System OOS
179Military Service StationOffload AreaTransition SumpsMOGASUnknownUnknownUnknownXXX7-14Inspect sump pipe transition fittings for tears, cracks, or other signs of deterioration. Test sumps and ensure they are liquid tight by using vacuum, pressure, or liquid testing in accordance with 40 CFR 280, Section 43.Monthly - Inspect for signs of water, fuel, trash, and debris inside sumps. Remove and properly dispose of collected water, fuel, trash, and debris. Visually inspect penetration fittings. If fuel or water is detected investigate the source and repair.Partial System OOS
179Military Service StationOffload AreaRemote Dispenser PumpsTank 4Red JacketR75513/4 HP GPM/SCFMXX07-15.1No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
179Military Service StationOffload AreaRemote Dispenser PumpsTank 3Red JacketR75513/4 HP GPM/SCFMXX07-15.1No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
179Military Service StationOffload AreaRemote Dispenser PumpsE85Red JacketR75513/4 HP GPM/SCFMXX07-15.1No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
179Military Service StationOffload AreaRemote Dispenser PumpsTank 3Red JacketR75513/4 HP GPM/SCFMXX07-15.1No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
179Military Service StationDispenser IslandEFSO SystemsOps BuildingSafety Technology InternationalSTI-13000UnmarkedXX07-16Proper operation, box seals for integrity. Electrical connections for continuity.No Operator RequirementPartial System OOS
179Military Service StationOffload AreaStage I Vapor RecoveryE85 OffloadUnknownUnknownUnknownXX07-17No Manufacturer Requirements AvailableDaily or Before Use - Inspect vapor recovery hoses for gouges, cuts or outside wear that may result in vapor leaks.No Mission Impact
179Military Service StationDispenser IslandDispenser NozzlesDispenser 2HuskeyNot Labeled0.75 in.00X7-2Start flow into approved test container; place nozzle

in low clip position. Immerse nozzle spout tip in the gasoline in the approved test container. The nozzle tip must be at least three (3) inches from the bottom of the container

to prevent back-pressure in the spout. Nozzle must shut off five consective tests.Daily - Inspect dispenser nozzle spout. Ensure it is tight, round, has no cracks, or excessive wear. Inspect automatic shutoff hole. Ensure the hole is open and free of obstructions. Inspect nozzle hold-open latch. Ensure the latch is straight, moves freely, and the return spring operates correctly. Inspect body of nozzle. Ensure the body is in good condition and that the valve stem is clean and free of fuel. Inspect the nozzle to hose connection and ensure it is clean and free of fuel.
Monthly - Dispenser nozzle handles shall be inspected for an expiration date established by the manufacturer. Nozzles must be replaced before the indicated expiration date.Partial System OOS
179Military Service StationDispenser IslandDispenser NozzlesDispenser 3OPW11BP0.75 in.00X7-2Start flow into approved test container; place nozzle

in low clip position. Immerse nozzle spout tip in the gasoline in the approved test container. The nozzle tip must be at least three (3) inches from the bottom of the container

to prevent back-pressure in the spout. Nozzle must shut off five consective tests.Daily - Inspect dispenser nozzle spout. Ensure it is tight, round, has no cracks, or excessive wear. Inspect automatic shutoff hole. Ensure the hole is open and free of obstructions. Inspect nozzle hold-open latch. Ensure the latch is straight, moves freely, and the return spring operates correctly. Inspect body of nozzle. Ensure the body is in good condition and that the valve stem is clean and free of fuel. Inspect the nozzle to hose connection and ensure it is clean and free of fuel.
Monthly - Dispenser nozzle handles shall be inspected for an expiration date established by the manufacturer. Nozzles must be replaced before the indicated expiration date.Partial System OOS
179Military Service StationDispenser IslandDispenser NozzlesDispenser 4OPW11BP0.75 in.00X7-2Start flow into approved test container; place nozzle

in low clip position. Immerse nozzle spout tip in the gasoline in the approved test container. The nozzle tip must be at least three (3) inches from the bottom of the container

to prevent back-pressure in the spout. Nozzle must shut off five consective tests.Daily - Inspect dispenser nozzle spout. Ensure it is tight, round, has no cracks, or excessive wear. Inspect automatic shutoff hole. Ensure the hole is open and free of obstructions. Inspect nozzle hold-open latch. Ensure the latch is straight, moves freely, and the return spring operates correctly. Inspect body of nozzle. Ensure the body is in good condition and that the valve stem is clean and free of fuel. Inspect the nozzle to hose connection and ensure it is clean and free of fuel.
Monthly - Dispenser nozzle handles shall be inspected for an expiration date established by the manufacturer. Nozzles must be replaced before the indicated expiration date.Partial System OOS
179Military Service StationDispenser IslandDispenser NozzlesDispenser 6OPW77HB0.75 in.00X7-2Start flow into approved test container; place nozzle

in low clip position. Immerse nozzle spout tip in the gasoline in the approved test container. The nozzle tip must be at least three (3) inches from the bottom of the container

to prevent back-pressure in the spout. Nozzle must shut off five consective tests.Daily - Inspect dispenser nozzle spout. Ensure it is tight, round, has no cracks, or excessive wear. Inspect automatic shutoff hole. Ensure the hole is open and free of obstructions. Inspect nozzle hold-open latch. Ensure the latch is straight, moves freely, and the return spring operates correctly. Inspect body of nozzle. Ensure the body is in good condition and that the valve stem is clean and free of fuel. Inspect the nozzle to hose connection and ensure it is clean and free of fuel.
Monthly - Dispenser nozzle handles shall be inspected for an expiration date established by the manufacturer. Nozzles must be replaced before the indicated expiration date.Partial System OOS
179Military Service StationDispenser IslandDispenser NozzlesDispenser 5OPW77BH0.75 in.00X7-2Start flow into approved test container; place nozzle

in low clip position. Immerse nozzle spout tip in the gasoline in the approved test container. The nozzle tip must be at least three (3) inches from the bottom of the container

to prevent back-pressure in the spout. Nozzle must shut off five consective tests.Daily - Inspect dispenser nozzle spout. Ensure it is tight, round, has no cracks, or excessive wear. Inspect automatic shutoff hole. Ensure the hole is open and free of obstructions. Inspect nozzle hold-open latch. Ensure the latch is straight, moves freely, and the return spring operates correctly. Inspect body of nozzle. Ensure the body is in good condition and that the valve stem is clean and free of fuel. Inspect the nozzle to hose connection and ensure it is clean and free of fuel.
Monthly - Dispenser nozzle handles shall be inspected for an expiration date established by the manufacturer. Nozzles must be replaced before the indicated expiration date.Partial System OOS
179Military Service StationDispenser IslandDispenser NozzlesDispenser 1OPW11BP0.75 in.00X7-2Start flow into approved test container; place nozzle

in low clip position. Immerse nozzle spout tip in the gasoline in the approved test container. The nozzle tip must be at least three (3) inches from the bottom of the container

to prevent back-pressure in the spout. Nozzle must shut off five consective tests.Daily - Inspect dispenser nozzle spout. Ensure it is tight, round, has no cracks, or excessive wear. Inspect automatic shutoff hole. Ensure the hole is open and free of obstructions. Inspect nozzle hold-open latch. Ensure the latch is straight, moves freely, and the return spring operates correctly. Inspect body of nozzle. Ensure the body is in good condition and that the valve stem is clean and free of fuel. Inspect the nozzle to hose connection and ensure it is clean and free of fuel.
Monthly - Dispenser nozzle handles shall be inspected for an expiration date established by the manufacturer. Nozzles must be replaced before the indicated expiration date.Partial System OOS
179Military Service StationDispenser IslandDispenser HosesDispenser 5IRPCOSteelFlex0.75 in.0007-3Check for expiration date, and physical condition/damage leaks.Daily - Inspect dispenser hoses and hose whips for gouges, cuts, blisters, or outside wear that may lead to rupture during use. Replace hose or hose whips that show signs of wear. Inspect connection points of hoses and hose whips to the dispenser, breakaways, swivels, and the nozzle and ensure the connection points are clean and free of fuel.Partial System OOS
179Military Service StationDispenser IslandDispenser HosesDispenser 6IRPCOSteelFlex0.75 in.0007-3Check for expiration date, and physical condition/damage leaks.Daily - Inspect dispenser hoses and hose whips for gouges, cuts, blisters, or outside wear that may lead to rupture during use. Replace hose or hose whips that show signs of wear. Inspect connection points of hoses and hose whips to the dispenser, breakaways, swivels, and the nozzle and ensure the connection points are clean and free of fuel.Partial System OOS
179Military Service StationDispenser IslandDispenser HosesDispenser 3IRPCOSteelFlex0.75 in.0007-3Check for expiration date, and physical condition/damage leaks.Daily - Inspect dispenser hoses and hose whips for gouges, cuts, blisters, or outside wear that may lead to rupture during use. Replace hose or hose whips that show signs of wear. Inspect connection points of hoses and hose whips to the dispenser, breakaways, swivels, and the nozzle and ensure the connection points are clean and free of fuel.Partial System OOS
179Military Service StationDispenser IslandDispenser HosesDispenser 4IRPCOSteelFlex0.75 in.0007-3Check for expiration date, and physical condition/damage leaks.Daily - Inspect dispenser hoses and hose whips for gouges, cuts, blisters, or outside wear that may lead to rupture during use. Replace hose or hose whips that show signs of wear. Inspect connection points of hoses and hose whips to the dispenser, breakaways, swivels, and the nozzle and ensure the connection points are clean and free of fuel.Partial System OOS
179Military Service StationDispenser IslandDispenser HosesDispenser 2HuskeyEagleFlex0.75 in.0007-3Check for expiration date, and physical condition/damage leaks.Daily - Inspect dispenser hoses and hose whips for gouges, cuts, blisters, or outside wear that may lead to rupture during use. Replace hose or hose whips that show signs of wear. Inspect connection points of hoses and hose whips to the dispenser, breakaways, swivels, and the nozzle and ensure the connection points are clean and free of fuel.Partial System OOS
179Military Service StationDispenser IslandDispenser HosesDispenser 1HuskeyEagleFlex0.75 in.0007-3Check for expiration date, and physical condition/damage leaks.Daily - Inspect dispenser hoses and hose whips for gouges, cuts, blisters, or outside wear that may lead to rupture during use. Replace hose or hose whips that show signs of wear. Inspect connection points of hoses and hose whips to the dispenser, breakaways, swivels, and the nozzle and ensure the connection points are clean and free of fuel.Partial System OOS
179Military Service StationDispenser IslandBreakawaysDispenser 4HuskeyDVS3800.75 in.0007-4Inspect for expiration date. Inspect for loose connections and signs of damage.Daily - Inspect breakaways for loose connections and signs of damage to poppets. Ensure breakaways are clean and free of fuel.
Monthly - Inspect breakaway for an expiration date established by the manufacturer. Breakaways must be replaced before the indicated expiration date.No Mission Impact
179Military Service StationDispenser IslandBreakawaysDispenser 3HuskyCGB7100.75 in.0007-4Inspect for expiration date. Inspect for loose connections and signs of damage.Daily - Inspect breakaways for loose connections and signs of damage to poppets. Ensure breakaways are clean and free of fuel.
Monthly - Inspect breakaway for an expiration date established by the manufacturer. Breakaways must be replaced before the indicated expiration date.No Mission Impact
179Military Service StationDispenser IslandBreakawaysDispenser 2HuskeyDAJ8800.75 in.0007-4Inspect for expiration date. Inspect for loose connections and signs of damage.Daily - Inspect breakaways for loose connections and signs of damage to poppets. Ensure breakaways are clean and free of fuel.
Monthly - Inspect breakaway for an expiration date established by the manufacturer. Breakaways must be replaced before the indicated expiration date.No Mission Impact
179Military Service StationDispenser IslandBreakawaysDispenser 6CatlowC86NT0.75 in.0007-4Inspect for expiration date. Inspect for loose connections and signs of damage.Daily - Inspect breakaways for loose connections and signs of damage to poppets. Ensure breakaways are clean and free of fuel.
Monthly - Inspect breakaway for an expiration date established by the manufacturer. Breakaways must be replaced before the indicated expiration date.No Mission Impact
179Military Service StationDispenser IslandBreakawaysDispenser 1HuskeyDAJ8800.75 in.0007-4Inspect for expiration date. Inspect for loose connections and signs of damage.Daily - Inspect breakaways for loose connections and signs of damage to poppets. Ensure breakaways are clean and free of fuel.
Monthly - Inspect breakaway for an expiration date established by the manufacturer. Breakaways must be replaced before the indicated expiration date.No Mission ImpactRemove 09/2024
179Military Service StationDispenser IslandBreakawaysDispenser 5OPWDV33800.75 in.0007-4Inspect for expiration date. Inspect for loose connections and signs of damage.Daily - Inspect breakaways for loose connections and signs of damage to poppets. Ensure breakaways are clean and free of fuel.
Monthly - Inspect breakaway for an expiration date established by the manufacturer. Breakaways must be replaced before the indicated expiration date.No Mission Impact
179Military Service StationDispenser IslandSwivelsDispenser 4 / NozzleHuskeyCHT4800.75 in.0007-5Inspect for expiration date. Inspect for loose connections and signs of damage.Daily - Inspect swivel for loose connections and signs of damage. Ensure swivel rotates easily and is clean and free of fuel.
Monthly - Inspect swivel for expiration date established by manufacturer. Swivels must be replaced before the indicated expiration date.Partial System OOSRemove 04/2024
179Military Service StationDispenser IslandSwivelsDispenser 4 / CabinetOPW45 Series0.75 in.0007-5Inspect for expiration date. Inspect for loose connections and signs of damage.Daily - Inspect swivel for loose connections and signs of damage. Ensure swivel rotates easily and is clean and free of fuel.
Monthly - Inspect swivel for expiration date established by manufacturer. Swivels must be replaced before the indicated expiration date.Partial System OOS
179Military Service StationDispenser IslandSwivelsDispenser 3CatlowNot Labeled0.75 in.0007-5Inspect for expiration date. Inspect for loose connections and signs of damage.Daily - Inspect swivel for loose connections and signs of damage. Ensure swivel rotates easily and is clean and free of fuel.
Monthly - Inspect swivel for expiration date established by manufacturer. Swivels must be replaced before the indicated expiration date.Partial System OOS
179Military Service StationDispenser IslandSwivelsDispenser 3OPW45 Series0.75 in.0007-5Inspect for expiration date. Inspect for loose connections and signs of damage.Daily - Inspect swivel for loose connections and signs of damage. Ensure swivel rotates easily and is clean and free of fuel.
Monthly - Inspect swivel for expiration date established by manufacturer. Swivels must be replaced before the indicated expiration date.Partial System OOS
179Military Service StationDispenser IslandSwivelsDispenser 6 / NozzleCatlowNot Labeled0.75 in.0007-5Inspect for expiration date. Inspect for loose connections and signs of damage.Daily - Inspect swivel for loose connections and signs of damage. Ensure swivel rotates easily and is clean and free of fuel.
Monthly - Inspect swivel for expiration date established by manufacturer. Swivels must be replaced before the indicated expiration date.Partial System OOS
179Military Service StationDispenser IslandSwivelsDispenser 2HuskeyDBA7200.75 in.0007-5Inspect for expiration date. Inspect for loose connections and signs of damage.Daily - Inspect swivel for loose connections and signs of damage. Ensure swivel rotates easily and is clean and free of fuel.
Monthly - Inspect swivel for expiration date established by manufacturer. Swivels must be replaced before the indicated expiration date.Partial System OOSRemove 09/2024
179Military Service StationDispenser IslandSwivelsDispenser 6 / CabinetHuskyNot Labeled0.75 in.0007-5Inspect for expiration date. Inspect for loose connections and signs of damage.Daily - Inspect swivel for loose connections and signs of damage. Ensure swivel rotates easily and is clean and free of fuel.
Monthly - Inspect swivel for expiration date established by manufacturer. Swivels must be replaced before the indicated expiration date.Partial System OOS
179Military Service StationDispenser IslandSwivelsDispenser 5 / NozzleCatlowUnmarked0.75 in.0007-5Inspect for expiration date. Inspect for loose connections and signs of damage.Daily - Inspect swivel for loose connections and signs of damage. Ensure swivel rotates easily and is clean and free of fuel.
Monthly - Inspect swivel for expiration date established by manufacturer. Swivels must be replaced before the indicated expiration date.Partial System OOS
179Military Service StationDispenser IslandSwivelsDispenser 1HuskeyDBA7200.75 in.0007-5Inspect for expiration date. Inspect for loose connections and signs of damage.Daily - Inspect swivel for loose connections and signs of damage. Ensure swivel rotates easily and is clean and free of fuel.
Monthly - Inspect swivel for expiration date established by manufacturer. Swivels must be replaced before the indicated expiration date.Partial System OOSRemove 09/2024
179Military Service StationDispenser IslandSwivelsDispenser 5Husky1 VI0.75 in.0007-5Inspect for expiration date. Inspect for loose connections and signs of damage.Daily - Inspect swivel for loose connections and signs of damage. Ensure swivel rotates easily and is clean and free of fuel.
Monthly - Inspect swivel for expiration date established by manufacturer. Swivels must be replaced before the indicated expiration date.Partial System OOS
179Military Service StationDispenser IslandHose RetrieverDispenser 1WayneDresser306347-0040007-6No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
179Military Service StationDispenser IslandHose RetrieverDispenser 2WayneDresser306347-0040007-6No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
179Military Service StationDispenser IslandHose RetrieverDispenser 4WayneDresser306347-0040007-6No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
179Military Service StationDispenser IslandHose RetrieverDispenser 3WayneDresser306347-0040007-6No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
179Military Service StationDispenser IslandHose RetrieverDispenser 6WayneDresser306347-0040007-6No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
179Military Service StationDispenser IslandHose RetrieverDispenser 5WayneDresser306347-0040007-6No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
179Military Service StationDispenser IslandDispenser CabinetDispenser 3/4Wayne3/G7242D/2GHJ/HKN/A00X7-7Inspect for damage, ensure door panels and locks are functional.Monthly - Inspect outside of cabinet and ensure it is free of damage. Inspect for fuel stains on the concrete island around the cabinet and on the outside of the cabinet. Ensure the cabinet is free of dirt and fuel. Open both sides of the cabinet and inspect the inside of the cabinet. Ensure the inside of the cabinet and all of the components inside the cabinet are clean and free of fuel.Partial System OOS
179Military Service StationDispenser IslandDispenser CabinetDispenser 1/2WayneE3/G7202D/2GHJX/HKN/A00X7-7Inspect for damage, ensure door panels and locks are functional.Monthly - Inspect outside of cabinet and ensure it is free of damage. Inspect for fuel stains on the concrete island around the cabinet and on the outside of the cabinet. Ensure the cabinet is free of dirt and fuel. Open both sides of the cabinet and inspect the inside of the cabinet. Ensure the inside of the cabinet and all of the components inside the cabinet are clean and free of fuel.Partial System OOS
179Military Service StationDispenser IslandDispenser CabinetDispenser 5/6Wayne3/37242D/23HJ/HKN/A00X7-7Inspect for damage, ensure door panels and locks are functional.Monthly - Inspect outside of cabinet and ensure it is free of damage. Inspect for fuel stains on the concrete island around the cabinet and on the outside of the cabinet. Ensure the cabinet is free of dirt and fuel. Open both sides of the cabinet and inspect the inside of the cabinet. Ensure the inside of the cabinet and all of the components inside the cabinet are clean and free of fuel.Partial System OOS
179Military Service StationDispenser IslandDispenser MetersDispenser 1WayneDM11-1 LPM - 72 LPM GPM/SCFM00X7-8Inspect for damage, smooth operation and legibility.Monthly - Inspect meter and ensure meter is clean and free of fuel. Ensure calibration mechanism is sealed.Partial System OOS
179Military Service StationDispenser IslandDispenser MetersDispenser 2WayneDM11-1 LPM - 72 LPM GPM/SCFM00X7-8Inspect for damage, smooth operation and legibility.Monthly - Inspect meter and ensure meter is clean and free of fuel. Ensure calibration mechanism is sealed.Partial System OOS
179Military Service StationDispenser IslandDispenser MetersDispenser 4WayneDM 21-1 LPM - 72 LPM GPM/SCFM00X7-8Inspect for damage, smooth operation and legibility.Monthly - Inspect meter and ensure meter is clean and free of fuel. Ensure calibration mechanism is sealed.Partial System OOS
179Military Service StationDispenser IslandDispenser MetersDispenser 3WayneDM 21-1 LPM - 72 LPM GPM/SCFM00X7-8Inspect for damage, smooth operation and legibility.Monthly - Inspect meter and ensure meter is clean and free of fuel. Ensure calibration mechanism is sealed.Partial System OOS
179Military Service StationDispenser IslandDispenser MetersDispenser 6WayneDM 21-1 LPM - 72 LPM GPM/SCFM00X7-8Inspect for damage, smooth operation and legibility.Monthly - Inspect meter and ensure meter is clean and free of fuel. Ensure calibration mechanism is sealed.Partial System OOS
179Military Service StationDispenser IslandDispenser MetersDispenser 5WayneDM 21-1 LPM - 72 LPM GPM/SCFM00X7-8Inspect for damage, smooth operation and legibility.Monthly - Inspect meter and ensure meter is clean and free of fuel. Ensure calibration mechanism is sealed.Partial System OOS
179Military Service StationDispenser IslandDispenser FiltersDispenser 1/2CIM-TEK400HA-017003900X7-9Check exterior for damageNo Operator RequirementPartial System OOS
179Military Service StationDispenser IslandDispenser FiltersDispenser 4Bio-Tek400BMG-107010400X7-9Check exterior for damageNo Operator RequirementPartial System OOS
179Military Service StationDispenser IslandDispenser FiltersDispenser 3Bio-Tek400BMG-107010400X7-9Check exterior for damageNo Operator RequirementPartial System OOS
179Military Service StationDispenser IslandDispenser FiltersDispenser 6Bio-Tek400BHA-017003900X7-9Check exterior for damageNo Operator RequirementPartial System OOS
179Military Service StationDispenser IslandDispenser FiltersDispenser 5Bio-Tek400BHA-017003900X7-9Check exterior for damageNo Operator RequirementPartial System OOS
179Military Service StationOffload AreaPipe PenetrationsAll SumpsUnknownUnknownVarious SizesXX08-10.6No Manufacturer Requirements AvailableNo Operator RequirementPartial System OOSVarious pipe sizes
179Military Service StationOffload AreaUnderground Double-walled Shop-Fabricated TanksTank 1UnknownUnknown10,000 GallonsXXX8-5.4.2No Manufacturer Requirements AvailableMonthly - Monthly External Inspection (Identified as P in Table 8-4): Ensure all tank port covers are present, are in good condition, and seated firmly on the correct tank. Inspect tank stick gauge and ensure markings are legible and that the stick gauge is not warped or broken. Inspect tank for water using ATG or stick gauge with water-finding paste. Remove water found in tank. Open and inspect tank-top containment sumps and ensure no fuel or water is collected in the sumps. Check for and remove obstructions in tank fill pipe.Partial System OOS
179Military Service StationOffload AreaUnderground Double-walled Shop-Fabricated TanksTank 3UnknownUnknown10,000 GallonsXXX8-5.4.2No Manufacturer Requirements AvailableMonthly - Monthly External Inspection (Identified as P in Table 8-4): Ensure all tank port covers are present, are in good condition, and seated firmly on the correct tank. Inspect tank stick gauge and ensure markings are legible and that the stick gauge is not warped or broken. Inspect tank for water using ATG or stick gauge with water-finding paste. Remove water found in tank. Open and inspect tank-top containment sumps and ensure no fuel or water is collected in the sumps. Check for and remove obstructions in tank fill pipe.Partial System OOS
179Military Service StationOffload AreaUnderground Double-walled Shop-Fabricated TanksTank 4UnknownUnknown10,000 GallonsXXX8-5.4.2No Manufacturer Requirements AvailableMonthly - Monthly External Inspection (Identified as P in Table 8-4): Ensure all tank port covers are present, are in good condition, and seated firmly on the correct tank. Inspect tank stick gauge and ensure markings are legible and that the stick gauge is not warped or broken. Inspect tank for water using ATG or stick gauge with water-finding paste. Remove water found in tank. Open and inspect tank-top containment sumps and ensure no fuel or water is collected in the sumps. Check for and remove obstructions in tank fill pipe.Partial System OOS
179Military Service StationOffload AreaUnderground Double-walled Shop-Fabricated TanksTank 2UnknownUnknown10,000 GallonsXXX8-5.4.2No Manufacturer Requirements AvailableMonthly - Monthly External Inspection (Identified as P in Table 8-4): Ensure all tank port covers are present, are in good condition, and seated firmly on the correct tank. Inspect tank stick gauge and ensure markings are legible and that the stick gauge is not warped or broken. Inspect tank for water using ATG or stick gauge with water-finding paste. Remove water found in tank. Open and inspect tank-top containment sumps and ensure no fuel or water is collected in the sumps. Check for and remove obstructions in tank fill pipe.Partial System OOS
179Military Service StationOffload AreaFill PortsGURNot LabeledNot LabeledNot LabeledXXX8-9.12Ensure fill port covers are installed and are not damaged or broken. Ensure fill port covers are identified by fuel type and are installed on the correct tank. Visually inspect the fill port spill bucket to ensure there are no cracks, budges, or holes.Daily - Ensure fill port covers are installed and are not damaged or broken. Ensure fill port covers are identified by fuel type and are installed on the correct tank. Visually inspect the fill port spill bucket to ensure there are no cracks, budges, or holes. Ensure the spill bucket is clean of dirt, trash, water, and fuel.Partial System OOSMaybe not used
179Military Service StationOffload AreaFill PortsTank 3/4Not LabeledNot LabeledNot LabeledXXX8-9.12Ensure fill port covers are installed and are not damaged or broken. Ensure fill port covers are identified by fuel type and are installed on the correct tank. Visually inspect the fill port spill bucket to ensure there are no cracks, budges, or holes.Daily - Ensure fill port covers are installed and are not damaged or broken. Ensure fill port covers are identified by fuel type and are installed on the correct tank. Visually inspect the fill port spill bucket to ensure there are no cracks, budges, or holes. Ensure the spill bucket is clean of dirt, trash, water, and fuel.Partial System OOS
179Military Service StationOffload AreaFill PortsMOGASN/AN/ANot LabeledXXX8-9.12Ensure fill port covers are installed and are not damaged or broken. Ensure fill port covers are identified by fuel type and are installed on the correct tank. Visually inspect the fill port spill bucket to ensure there are no cracks, budges, or holes.Daily - Ensure fill port covers are installed and are not damaged or broken. Ensure fill port covers are identified by fuel type and are installed on the correct tank. Visually inspect the fill port spill bucket to ensure there are no cracks, budges, or holes. Ensure the spill bucket is clean of dirt, trash, water, and fuel.Partial System OOS
179Military Service StationOffload AreaFill PortsE85 OffloadUnknownUnknownNot LabeledXXX8-9.12Ensure fill port covers are installed and are not damaged or broken. Ensure fill port covers are identified by fuel type and are installed on the correct tank. Visually inspect the fill port spill bucket to ensure there are no cracks, budges, or holes.Daily - Ensure fill port covers are installed and are not damaged or broken. Ensure fill port covers are identified by fuel type and are installed on the correct tank. Visually inspect the fill port spill bucket to ensure there are no cracks, budges, or holes. Ensure the spill bucket is clean of dirt, trash, water, and fuel.Partial System OOS
179Military Service StationOffload AreaTank Pressure/ Vacuum VentsTank 1 MOGASOPW623 SeriesOPW623V220300X8-9.3No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
179Military Service StationOffload AreaTank Pressure/ Vacuum VentsTank 2 MOGASOPW624 SeriesOPW623V220400X8-9.3No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
179Military Service StationOffload AreaTank Pressure/ Vacuum VentsTank 3 DieselOPW625 SeriesOPW623V220500X8-9.3No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
179Military Service StationOffload AreaTank Pressure/ Vacuum VentsTank 4 DieselOPW626 SeriesOPW623V220600X8-9.3No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact