PWS DYE FMP Template - v2.2.xlsx

XLSX spreadsheet 246 KB Posted

Attached to
Sources Sought - CEHNC FUELS PROGRAM
Solicitation number
PANHES-25-P-0000-001794
Issued by

About this file

This is a Facility Maintenance Plan (FMP) template for fuel system maintenance at Dyess Air Force Base in Abilene, TX. The template provides detailed guidance for contractor personnel regarding the operation, inspection, and maintenance of permanently installed fuel facilities under Quality Assurance Evaluator control.

The plan outlines maintenance requirements for various fuel system components including above/underground storage tanks, filter separators, valves, meters, pumps, monitoring equipment, alarms, and fire fighting equipment. It contains specific maintenance schedules and procedures for the Bravo Fillstand, RTB Header/Alpha facility, Fuels Operations building, Refueler Parking Yard, and Hydrants Operations areas. The template includes sections for administrative information, communication protocols, safety requirements, and a detailed task matrix listing all maintainable assets with their specifications, maintenance frequencies, and operational impact considerations. The document is structured as a working template where site-specific details and requirements can be added.

View the file

Other files

File Type Posted
Sources Sought FUELS - Programmatic Rev1 7 May 25.docx DOCX document
3.4 Appendix B - Attachment 4 - SO Tracker-20210628.xlsx XLSX spreadsheet
6.0 - Appendix E ISR 15-Bulk_Fuel_Facilities FY25.xlsx XLSX spreadsheet
2.0 Appendix A RM_SO Process_20241220_PgM Reviewed Incorporated.docx DOCX document
3.1 Appendix B - Attachment 1 - Three Week Look Ahead_20230420.xlsx XLSX spreadsheet
3.2 Appendix B - Attachment 2 - Monthly Report Format 20240910.docx DOCX document
2.2 Appendix A - Attachment 2 Contractor Travel Expense Report_20240910.xlsx XLSX spreadsheet
9.0 Appendix H - Minor Repairs Incidental to Maintenance Activities POJ 20231009.xlsx XLSX spreadsheet
7.0 CUID - v2.1.pdf PDF
8.0 Appendix G_UFC 3-460-03 Maintenance Table- v4.3.pdf PDF
6.0 Appendix E ISR 14_operational_fuel_facilities FY25.xlsx XLSX spreadsheet
3.0 Appendix B Reporting Requirements_20240910.docx DOCX document
4.0 Appendix C Task Order Specifications_202401216.docx DOCX document
5.0 Appendix D Antiterrorism and OPSEC 20230206.docx DOCX document
PWS LEX FMP Template - v2.2.xlsx XLSX spreadsheet
PWS VNC FMP Template - v2.2.xlsx XLSX spreadsheet
PWS KEQ FMP Template - v2.2.xlsx XLSX spreadsheet
PWS CVZ FMP Template - v2.2.xlsx XLSX spreadsheet
PWS SHP FMP Template - v2.2.xlsx XLSX spreadsheet
PWS PBA FMP Template - v2.2.xlsx XLSX spreadsheet
PWS GRB FMP Template - v2.2.xlsx XLSX spreadsheet
PWS BRO FMP Template - v2.2.xlsx XLSX spreadsheet
PWS BAR FMP Template - v2.2.xlsx XLSX spreadsheet
PWS EFS FMP Template - v2.2.xlsx XLSX spreadsheet
PWS LAU FMP Template - v2.2.xlsx XLSX spreadsheet
PWS CHF FMP Template - v2.2.xlsx XLSX spreadsheet
PWS BEU FMP Template - v2.2.xlsx XLSX spreadsheet
PWS GDF FMP Template - v2.2.xlsx XLSX spreadsheet
PWS BLI FMP Template - v2.2.xlsx XLSX spreadsheet
PWS TKR FMP Template - v2.2.xlsx XLSX spreadsheet
PWS RBN FMP Template - v2.2.xlsx XLSX spreadsheet
PWS MAA FMP Template - v2.2.xlsx XLSX spreadsheet
PWS FSH FMP Template - v2.2.xlsx XLSX spreadsheet
PWS FSO FMP Template - v2.2.xlsx XLSX spreadsheet
PWS LRG FMP Template - v2.2.xlsx XLSX spreadsheet
PWS RRT FMP Template - v2.2.xlsx XLSX spreadsheet
PWS ALT FMP Template - v2.2.xlsx XLSX spreadsheet
PWS TUL FMP Template - v2.2.xlsx XLSX spreadsheet
PWS BL2 FMP Template - v2.2.xlsx XLSX spreadsheet
PWS ELL FMP Template - v2.2.xlsx XLSX spreadsheet
PWS WRF FMP Template - v2.2.xlsx XLSX spreadsheet
PWS LLD FMP Template - v2.2.xlsx XLSX spreadsheet
12.0 PWS Appendix K Real Property Data_20230420.xlsx XLSX spreadsheet
PWS RAN FMP Template - v2.2.xlsx XLSX spreadsheet
PWS FSM FMP Template - v2.2.xlsx XLSX spreadsheet
PWS _Fuels RMMR 20241220.docx DOCX document
Show all 46

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Administrative

LocationSite NameDyess Air Force Base Site #1
RPSUID1672
DLA Site CodeDYE
Hours of Operation24 Hours of Operation
Address710 South Third St., Abilene, TX 79607
ContractContractor
Contract #
Local POCsQAE Name
QAE Phone
QAE Email
Alt QAE Name
Alt QAE Phone
Alt QAE Email
DLA/SCP POCsDLA PM Name
DLA PM Phone
DLA PM Email
SCP PM Name
SCP PM Phone
SCP PM Email
Contractor POCsContractor PM Name
Contractor PM Phone
Contractor PM Email
Contractor QC Name
Contractor QC Phone
Contractor QC Email
Contractor SM Name
Contractor SM Phone
Contractor SM Email
USACE POCsUSACE PM/COR Name
USACE PM/COR Phone
USACE PM/COR Email
USACE PE Name
USACE PE Phone
USACE PE Email
USACE KO Name
USACE KO Phone
USACE KO Email

Facility Maintenance Plan

FMP v2.2 &P of &N

Instructions:

This table shows the minimum information required. Additional details should be included based on site specific requirements. Additional POCs may be required.

General Facility Description Facility Description

Purpose:

This Facility Maintenance Plan provides guidance for Contractor personnel in the operation, inspection, and maintenance of permanently installed fuel facilities operated under the control of the Quality Assurance Evaluators. Federal, state, and local environmental laws and regulations shall be complied with if this plan is in conflict with them.

Scope:

The instructions prescribed by this plan outline general fuels maintenance information associated with fuel storage and dispensing systems and provides the minimum periodic contractor maintenance and inspection criteria requirements for the systems. This plan is to be used in conjunction with other existing directives governing fuel system operations and maintenance requirements. Conotractor will properly maintain and repair federally funded petroleum systems and facilities in order to provide compliance with applicable code, criteria, and federal, state, local and/or host nation regulations.

Fuels Facilities:

Organizational tanks, and associated dispensing equipment are maintained and operated by the owning organization. Fuel system maintenance contractors shall perform all maintenance and associated procurement actions on installed fuel systems.

Each installation under the Southwest Division contract are military land-based facilities who receive, store, distribute, and/or dispense liquid fuels.

Standard fuel system equipment includes:

a) Above Ground Sorage Stanks (AST), Underground Storage Tanks (UST)

b) Filter/separator and other filtration device maintenance access, particularly element removal.

c) Manual valves

d) Meter Registers, and Flow Meters.

e) Control Valves.

f) Pumps

g) Tank Monitoring Equipment and Instruments

h) Alarms

i) Fire Fighting Equipment

Site Specific General Information:

Facility Maintenance Plan

FMP v2.2 &P of &N

Instructions:

Include a general facility overview and description of each fuel system for the sites in accordance with UFC 3-460-01. Examples include: Bulk Storage Facilities, Aircraft Fueling Facilities, Marine and Dispensing Facilities, Ground Products Fueling Facilities, Alternate POL Facilities, and Support Facilities. Also include facility #s, facility names, fuel type, photos, and any other pertinent information.

Include Site Specific Conditions and Restrictions in this tab.

Communication Plan

Facility Maintenance Plan

FMP v2.2 &P of &N

Instructions:

Communication plan shall address in/out briefs, lines of communication, coordination for access, etc.

Safety

Facility Maintenance Plan

FMP v2.2 &P of &N

Instructions:

Site Specific Addendum and Activity Hazard Analysis, which are Attachments to the APP, specific to activities or tasks related to recurring maintenance for this site.

RM Schedule

Facility Maintenance Plan

FMP v2.2 &P of &N

Instructions:

Link RM schedule here

Task Matrix

Applicable Facility AssetsUFC System Level Maintenance FrequencySpecial Considerations
Real Property Unique Identifier
(RPUID)Real Property Facility #Real Property Facility NameOperational AreaComponent TypeBase Asset IDComponent Unique Identifier (CUID)MakeModelCapacity/SizeQSAUFC Section ReferenceAdditional Manufacturer RM RequirementsOperator/ equipment RequirementsSystem availabilityOther ContractComments
909Oil Water SeparatorOil Water SeparatorOil/Water SeparatorsOil Water SeparatorUnmarkedUnmarkedUnmarked GallonsX0X11-5No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
909Oil Water SeparatorOil Water SeparatorElectrical EquipmentAutomatic Tank GaugeInconTS-1000N/AX009-1.2No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
1003Bravo FillstandBravo FillstandCanopiesFillstand Bravo CanopyUnmarkedUnmarkedN/A00011-2.2No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission ImpactFillstand Bravo canop
1003Bravo FillstandBravo FillstandPositive Displacement MetersMeterLCUnmarked30-600 GPM/SCFM0X03-7.1Inspect counter head for unusual noises and smooth operation. Inspect temperature element operation of meters equipped with temperature
compensation featureMonthly - Inspect counter head for unusual noises and smooth operation.Partial System OOS
1003Bravo FillstandBravo FillstandFueling NozzlesNozzleCla-ValD3N/A0004-7.4Quarterly - Inspect the condition of the dust cap at the aircraft adapter end and ensure it is in good working order. Dust caps must be attached to nozzles when they are not is use. Test leak resistance of poppet valve against full pump pressure. Inspect storage racks for moisture or dirt accumulation. Remove nozzle for inspection of content impinged upon the mesh screen. Clean and dry screens before nozzles are returned to service. Tests nozzle interlocks. Check the operation of the manual valve crank assembly for smooth and positive motion on a special test stand.Quarterly - Inspect the condition of the dust cap at the aircraft adapter end and ensure it is in good working order. Dust caps must be attached to nozzles when they are not is use. Test leak resistance of poppet valve against full pump pressure. Inspect storage racks for moisture or dirt accumulation. Remove nozzle for inspection of content impinged upon the mesh screen. Clean and dry screens before nozzles are returned to service. Tests nozzle interlocks. Check the operation of the manual valve crank assembly for smooth and positive motion on a special test stand.Partial System OOSFillstand Bravo
1003Bravo FillstandBravo FillstandSight Flow IndicatorsVisi-FloVisi-Flo1571 F 11.0 in.0006-12.3Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Partial System OOSFillstand Bravo
1003Bravo FillstandBravo FillstandEFSO SystemsFillstand Bravo EFSOKillarkXCS-0MMR3N/AX007-16Proper operation, box seals for integrity. Electrical connections for continuity.No Operator RequirementPartial System OOSFillstand Bravo
1003Bravo FillstandBravo FillstandElectronic Overfill Protection SystemsScullyScullyIntellitrolN/AX009-6Proof Test : Confirm that the control module is indicating a dry condition (output relay closed). Bypass the safety function and take appropriate action to avoid a false trip Remove power from the WX system relay. Confirm that the relay opens within

one (1) second. Reconnect power. Disconnect one of the wires to the sensor. Confirm that the relay opens within one (1) second. Reconnect power. Short the two sensor wires together. Confirm that the relay opens within one (1)

second. Remove short. Remove the bypass and otherwise restore normal operationNo Operator RequirementPartial System OOSCMPFillstand Bravo
1003Bravo FillstandBravo FillstandFuel Truck Containment AreasFillstand Bravo truck containmentUnmarkedUnmarkedN/AX0X11-1.1No Manufacturer Requirements AvailableMonthly - Remove debris from around security fence. Inspect fence grounding points. Ensure connections are not loose or damage.No Mission ImpactFillstand Bravo truck Containment
1003Bravo FillstandBravo FillstandPressure Control ValvesCla-ValCla-Val4-90AF4H-024.0 in.X004-4.2.7No Manufacturers Data Available. Adjustment not advised unless formal training is received.No Operator RequirementPartial System OOS
1003Bravo FillstandBravo FillstandFixed PantographsFillstand Bravo PantographMeyerinckUnmarkedN/AX004-7.1.1No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission ImpactFillstand Bravo
1003Bravo FillstandBravo FillstandBall ValvesBall ValveVelanHB 20001.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactFillstand Bravo
1003Bravo FillstandBravo FillstandBall ValvesBall ValveVelanHB 20000.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1003Bravo FillstandBravo FillstandBall ValvesLow Point DrainJamesburyCF8M2.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1003Bravo FillstandBravo FillstandBall ValvesBall ValveVelanCF8M4.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1003Bravo FillstandBravo FillstandBall ValvesBall ValveVelanCF8M4.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1003Bravo FillstandBravo FillstandBall ValvesBall ValveConbracoApollo0.5 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1003Bravo FillstandBravo FillstandThermal and/or Pressure Relief ValvesPRVTaylorT-8200-10.75 in. 51 - 100 PSIX0X6-6.3Thermal and pressure relief valves shall be inspected for signs of leaks. Inspect valve exterior of thermal and pressure relief valves for corrosion. Repaint as required. Adjustment not reccomended.Monthly for Army, Navy, USMC; Quarterly for AF - Thermal and pressure relief valves shall be inspected for signs of leak-by. Inspect relief valves for leaks by visually inspecting downstream flow indicators (if installed) for flow. If no flow indicators are installed listen for possible leaks. If suspect: isolate and test the relief valve; check opening pressure; and verify re-seating. Malfunctioning valves shall be repaired or replaced.
Monthly for Army, Navy, USMC; Quarterly for AF - Ensure manual isolation valves installed upstream and downstream of thermal and pressure relief valves are open with valve handles are removed, wired open or locked.Partial System OOSFillstand Bravo
1003Bravo FillstandBravo FillstandPressure and Pressure/Vacuum GaugesPressure GaugeTube and SocketUnmarked0.5 in. 0 - 300 PSIXXX6-7.1Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use.Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system.Partial System OOSFillstand Bravo
1003Bravo FillstandBravo FillstandPressure and Pressure/Vacuum GaugesPressure GaugeTube and Socket3160.5 in. 0 - 300 PSIXXX6-7.1Check operation of gauge. Ensure gauge is indicating pressure of the system. Inspect liquid level, and clean exterior glass. Calibrate as required dependent on use.Monthly - Check operation of gauge. Ensure gauge is indicating pressure of the system.Partial System OOS
1003Bravo FillstandBravo FillstandStatic Grounding SystemsGroundN/AN/AN/AX0X9-1.6.2Measure the ground resistance with an instrument designed specifically to measure and document earth/ground resistance, soil resistivity, and current flow. Conduct the test by using the fall-of-potential method as described in the Institute of Electronic and Electrical Engineers (IEEE) Standard 81.If fall-of-potential tests cannot be performed, it is acceptable to measure resistance at each accessible ground rod using a clamp-on ground resistance tester. Provide the Engineer with written, certified test results for each testing location.No Operator RequirementPartial System OOS
1003Bravo FillstandBravo FillstandLightingFillstand Bravo canopy lightingUnmarkedUnmarkedN/AX0X9-1.8No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission ImpactFillstand Bravo
1004RTB Header/AlphaRTB Header/AlphaEFSO SystemsEmergency Fuel Shutoff ButtonUnmarkedUnmarkedN/AX007-16Proper operation, box seals for integrity. Electrical connections for continuity.No Operator RequirementPartial System OOSRTB Header/A
1004RTB Header/AlphaRTB Header/AlphaFuel Truck Containment AreasRTB Header/A truck containmentUnmarkedUnmarkedN/AX0X11-1.1No Manufacturer Requirements AvailableMonthly - Remove debris from around security fence. Inspect fence grounding points. Ensure connections are not loose or damage.No Mission ImpactRTB Header/A
1004RTB Header/AlphaRTB Header/AlphaPressure Control ValvesCla-ValCla-ValIllegible6.0 in.X004-4.2.7No Manufacturers Data Available. Adjustment not advised unless formal training is received.No Operator RequirementPartial System OOSRTB Header/A
1004RTB Header/AlphaRTB Header/AlphaHydrant AdaptersHydrant adapterCla-Val8703246.0 in.X004-7.3Inspect hydrant adapter for proper operation, damage, and wear. Test operation of dry break system.No Operator RequirementPartial System OOSRTB Header/A
1004RTB Header/AlphaRTB Header/AlphaBall ValvesBall ValveConbracoApollo0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission ImpactRTB Header/A
1004RTB Header/AlphaRTB Header/AlphaBall ValvesBall ValveBMC CorpsI-SS-R-SS6.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1004RTB Header/AlphaRTB Header/AlphaBall ValvesBall ValveBMC CorpsI-SS-R-SS6.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1004RTB Header/AlphaRTB Header/AlphaBall ValvesBall ValveBMC CorpsI-SS-R-SS6.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1004RTB Header/AlphaRTB Header/AlphaButterfly ValvesButterfly ValveFlowSealUnmarked6.0 in.X006-6.2.6No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
1004RTB Header/AlphaRTB Header/AlphaStatic Grounding SystemsGroundN/AN/AN/AX0X9-1.6.2Measure the ground resistance with an instrument designed specifically to measure and document earth/ground resistance, soil resistivity, and current flow. Conduct the test by using the fall-of-potential method as described in the Institute of Electronic and Electrical Engineers (IEEE) Standard 81.If fall-of-potential tests cannot be performed, it is acceptable to measure resistance at each accessible ground rod using a clamp-on ground resistance tester. Provide the Engineer with written, certified test results for each testing location.No Operator RequirementPartial System OOS
4111Fuels Operations buildingFuels LabEmergency Eyewash/ShowersEmergency Eyewash/ShowerHawsUnmarkedN/AXXX11-3Weekly - Equipment installed within 10 seconds from the hazard and on the same plane as the hazard Pathway is clear of obstructions Plumbed equipment activated to ensure compliant operation and to clear any sediment Self-contained equipment checked to determine if the flushing fluid needs to be changed or supplemented Equipment free of broken or missing parts Equipment protected against freezing User protected from scalding waterNo Operator RequirementNo Mission ImpactEmergency eyewash
4111Fuels Operations buildingFuels LabVentilation HoodsVent hoodLabconcoUnmarkedN/AXXX11-4.1Daily visual inspection, check the fume hood for visible airflow blockage such as large items or containers near the slot opening. Other daily inspections include holding a tissue at the opening to observe inward airflow, maintaining clean surfaces inside the hood, and keeping the sash at an appropriate height when working and not working in the hood.No Operator RequirementDelay in Performing AnalysisLab vent hood
4111Fuels Operations buildingGeneratorStatic Grounding SystemsGroundN/AN/AN/AX0X9-1.6.2Measure the ground resistance with an instrument designed specifically to measure and document earth/ground resistance, soil resistivity, and current flow. Conduct the test by using the fall-of-potential method as described in the Institute of Electronic and Electrical Engineers (IEEE) Standard 81.If fall-of-potential tests cannot be performed, it is acceptable to measure resistance at each accessible ground rod using a clamp-on ground resistance tester. Provide the Engineer with written, certified test results for each testing location.No Operator RequirementPartial System OOS
4111Fuels Operations buildingFuels LabStatic Grounding SystemsLab groundUnmarkedUnmarkedN/AX0X9-1.6.2Measure the ground resistance with an instrument designed specifically to measure and document earth/ground resistance, soil resistivity, and current flow. Conduct the test by using the fall-of-potential method as described in the Institute of Electronic and Electrical Engineers (IEEE) Standard 81.If fall-of-potential tests cannot be performed, it is acceptable to measure resistance at each accessible ground rod using a clamp-on ground resistance tester. Provide the Engineer with written, certified test results for each testing location.No Operator RequirementPartial System OOSFuels lab grounding
4111Fuels Operations buildingGeneratorBack-Up Power GeneratorsEmergency GeneratorCumminsDKAE-5659777N/AXX0Back-Up Power GeneratorsNo Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
4160Refueler Parking YardRefueler Parking YardAir CompressorsAir compressorIngersoll RandUnmarkedN/AXX0Air CompressorsNo Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission ImpactCompressor
4160Refueler Parking YardRefueler Parking YardEmergency Eyewash/ShowersEmergency EyewashUnmarkedUnmarkedN/AXXX11-3Weekly - Equipment installed within 10 seconds from the hazard and on the same plane as the hazard Pathway is clear of obstructions Plumbed equipment activated to ensure compliant operation and to clear any sediment Self-contained equipment checked to determine if the flushing fluid needs to be changed or supplemented Equipment free of broken or missing parts Equipment protected against freezing User protected from scalding waterNo Operator RequirementNo Mission ImpactEmergency eyewash
4160Refueler Parking YardRefueler Parking YardFuel Truck Containment AreasTruck parkingUnmarkedUnmarkedN/AX0X11-1.1No Manufacturer Requirements AvailableMonthly - Remove debris from around security fence. Inspect fence grounding points. Ensure connections are not loose or damage.No Mission ImpactTruck containment
4160Refueler Parking YardRefueler Parking YardLightingLightingUnmarkedUnmarkedN/AX0X9-1.8No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission ImpactTruck parking lighting
5212Hydrants OpsBravo Pump HouseCanopiesBravo Pump House CanopyUnmarkedUnmarkedN/A00011-2.2No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
5212Hydrants OpsBravo Pump HouseAutomatic Air VentsAir EliminatorArmstrongUnmarked0.75 in.00X3-10.2No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission ImpactReceipt Filter Separator 2
5212Hydrants OpsBravo Pump HouseAutomatic Air VentsAir EliminatorArmstrongUnmarked0.75 in.00X3-10.2No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission ImpactReceipt Filter Separator 3
5212Hydrants OpsBravo Pump HouseAutomatic Air VentsAir EliminatorArmstrongUnmarked0.75 in.00X3-10.2No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission ImpactIssue Filter Separator 9
5212Hydrants OpsBravo Pump HouseAutomatic Air VentsAir EliminatorArmstrongUnmarked0.75 in.00X3-10.2No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission ImpactIssue Filter Separator 10
5212Hydrants OpsBravo Pump HouseAutomatic Air VentsAir EliminatorArmstrongUnmarked0.75 in.00X3-10.2No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission ImpactIssue Filter Separator 11
5212Hydrants OpsBravo Pump HouseAutomatic Air VentsAir EliminatorArmstrongUnmarked0.75 in.00X3-10.2No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission ImpactIssue Filter Separator 12
5212Hydrants OpsBravo Pump HouseAutomatic Air VentsAir EliminatorArmstrongUnmarked0.75 in.00X3-10.2No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission ImpactIssue Filter Separator 13
5212Hydrants OpsBravo Pump HouseBasket StrainersBasket StrainerMuellerB529A8.0 in.0003-6.4Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyDaily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyNo Mission Impact
5212Hydrants OpsBravo Pump HouseBasket StrainersBasket StrainerMueller600 8WP1.0 in.0003-6.4Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyDaily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyNo Mission ImpactIssue Filter Separator 13
5212Hydrants OpsBravo Pump HouseBasket StrainersBasket StrainerMueller600 8WP1.0 in.0003-6.4Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyDaily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyNo Mission ImpactIssue Filter Separator 12
5212Hydrants OpsBravo Pump HouseBasket StrainersBasket StrainerMueller600 8WP1.0 in.0003-6.4Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyDaily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyNo Mission ImpactIssue Filter Separator 11
5212Hydrants OpsBravo Pump HouseBasket StrainersBasket StrainerMueller600 8WP1.0 in.0003-6.4Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyDaily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyNo Mission ImpactIssue Filter Separator 10
5212Hydrants OpsBravo Pump HouseBasket StrainersBasket StrainerMueller600 8WP1.0 in.0003-6.4Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyDaily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyNo Mission ImpactIssue Filter Separator 9
5212Hydrants OpsBravo Pump HouseBasket StrainersBasket StrainerMueller600 8WP1.0 in.0003-6.4Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyDaily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyNo Mission ImpactReceipt Filter Separator 3
5212Hydrants OpsBravo Pump HouseBasket StrainersBasket StrainerMueller600 8WP1.0 in.0003-6.4Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyDaily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations.
Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterlyNo Mission ImpactReceipt Filter Separator 2
5212Hydrants OpsBravo PitsHydrant Fuel PitsFuel PitUnmarkedUnmarkedN/A0006-11.2No Manufacturer Requirements AvailableMonthly, or more often based on local conditions - Hydrant fuel pits shall be inspected to ensure that they are dry and clean and that all fueling components within the pit are clean and in good working order. Check pipe penetrations through pit walls or bottom to ensure that mechanical and boot seals are in good working condition and are allowing no water seepage into the pits. Check for fuel leaks at all flanged and pipe connections.Check pit lids to ensure that seals are in good working order and are preventing water entry into the pits. Inspect hydrant fuel pit bonding cables for corrosion and ensure electrical continuity between bonded equipment.Partial System OOSB22
5212Hydrants OpsBravo PitsHydrant Fuel PitsFuel PitUnmarkedUnmarkedN/A0006-11.2No Manufacturer Requirements AvailableMonthly, or more often based on local conditions - Hydrant fuel pits shall be inspected to ensure that they are dry and clean and that all fueling components within the pit are clean and in good working order. Check pipe penetrations through pit walls or bottom to ensure that mechanical and boot seals are in good working condition and are allowing no water seepage into the pits. Check for fuel leaks at all flanged and pipe connections.Check pit lids to ensure that seals are in good working order and are preventing water entry into the pits. Inspect hydrant fuel pit bonding cables for corrosion and ensure electrical continuity between bonded equipment.Partial System OOSB21
5212Hydrants OpsBravo PitsHydrant Fuel PitsFuel PitUnmarkedUnmarkedN/A0006-11.2No Manufacturer Requirements AvailableMonthly, or more often based on local conditions - Hydrant fuel pits shall be inspected to ensure that they are dry and clean and that all fueling components within the pit are clean and in good working order. Check pipe penetrations through pit walls or bottom to ensure that mechanical and boot seals are in good working condition and are allowing no water seepage into the pits. Check for fuel leaks at all flanged and pipe connections.Check pit lids to ensure that seals are in good working order and are preventing water entry into the pits. Inspect hydrant fuel pit bonding cables for corrosion and ensure electrical continuity between bonded equipment.Partial System OOSB20
5212Hydrants OpsBravo PitsHydrant Fuel PitsFuel PitUnmarkedUnmarkedN/A0006-11.2No Manufacturer Requirements AvailableMonthly, or more often based on local conditions - Hydrant fuel pits shall be inspected to ensure that they are dry and clean and that all fueling components within the pit are clean and in good working order. Check pipe penetrations through pit walls or bottom to ensure that mechanical and boot seals are in good working condition and are allowing no water seepage into the pits. Check for fuel leaks at all flanged and pipe connections.Check pit lids to ensure that seals are in good working order and are preventing water entry into the pits. Inspect hydrant fuel pit bonding cables for corrosion and ensure electrical continuity between bonded equipment.Partial System OOSB19
5212Hydrants OpsBravo PitsHydrant Fuel PitsFuel PitUnmarkedUnmarkedN/A0006-11.2No Manufacturer Requirements AvailableMonthly, or more often based on local conditions - Hydrant fuel pits shall be inspected to ensure that they are dry and clean and that all fueling components within the pit are clean and in good working order. Check pipe penetrations through pit walls or bottom to ensure that mechanical and boot seals are in good working condition and are allowing no water seepage into the pits. Check for fuel leaks at all flanged and pipe connections.Check pit lids to ensure that seals are in good working order and are preventing water entry into the pits. Inspect hydrant fuel pit bonding cables for corrosion and ensure electrical continuity between bonded equipment.Partial System OOSB18
5212Hydrants OpsBravo PitsHydrant Fuel PitsFuel PitUnmarkedUnmarkedN/A0006-11.2No Manufacturer Requirements AvailableMonthly, or more often based on local conditions - Hydrant fuel pits shall be inspected to ensure that they are dry and clean and that all fueling components within the pit are clean and in good working order. Check pipe penetrations through pit walls or bottom to ensure that mechanical and boot seals are in good working condition and are allowing no water seepage into the pits. Check for fuel leaks at all flanged and pipe connections.Check pit lids to ensure that seals are in good working order and are preventing water entry into the pits. Inspect hydrant fuel pit bonding cables for corrosion and ensure electrical continuity between bonded equipment.Partial System OOSB17
5212Hydrants OpsBravo PitsHydrant Fuel PitsFuel PitUnmarkedUnmarkedN/A0006-11.2No Manufacturer Requirements AvailableMonthly, or more often based on local conditions - Hydrant fuel pits shall be inspected to ensure that they are dry and clean and that all fueling components within the pit are clean and in good working order. Check pipe penetrations through pit walls or bottom to ensure that mechanical and boot seals are in good working condition and are allowing no water seepage into the pits. Check for fuel leaks at all flanged and pipe connections.Check pit lids to ensure that seals are in good working order and are preventing water entry into the pits. Inspect hydrant fuel pit bonding cables for corrosion and ensure electrical continuity between bonded equipment.Partial System OOSB16
5212Hydrants OpsBravo PitsHydrant Fuel PitsFuel PitUnmarkedUnmarkedN/A0006-11.2No Manufacturer Requirements AvailableMonthly, or more often based on local conditions - Hydrant fuel pits shall be inspected to ensure that they are dry and clean and that all fueling components within the pit are clean and in good working order. Check pipe penetrations through pit walls or bottom to ensure that mechanical and boot seals are in good working condition and are allowing no water seepage into the pits. Check for fuel leaks at all flanged and pipe connections.Check pit lids to ensure that seals are in good working order and are preventing water entry into the pits. Inspect hydrant fuel pit bonding cables for corrosion and ensure electrical continuity between bonded equipment.Partial System OOSB15
5212Hydrants OpsBravo PitsHydrant Fuel PitsFuel PitUnmarkedUnmarkedN/A0006-11.2No Manufacturer Requirements AvailableMonthly, or more often based on local conditions - Hydrant fuel pits shall be inspected to ensure that they are dry and clean and that all fueling components within the pit are clean and in good working order. Check pipe penetrations through pit walls or bottom to ensure that mechanical and boot seals are in good working condition and are allowing no water seepage into the pits. Check for fuel leaks at all flanged and pipe connections.Check pit lids to ensure that seals are in good working order and are preventing water entry into the pits. Inspect hydrant fuel pit bonding cables for corrosion and ensure electrical continuity between bonded equipment.Partial System OOSB14
5212Hydrants OpsBravo PitsHydrant Fuel PitsFuel PitUnmarkedUnmarkedN/A0006-11.2No Manufacturer Requirements AvailableMonthly, or more often based on local conditions - Hydrant fuel pits shall be inspected to ensure that they are dry and clean and that all fueling components within the pit are clean and in good working order. Check pipe penetrations through pit walls or bottom to ensure that mechanical and boot seals are in good working condition and are allowing no water seepage into the pits. Check for fuel leaks at all flanged and pipe connections.Check pit lids to ensure that seals are in good working order and are preventing water entry into the pits. Inspect hydrant fuel pit bonding cables for corrosion and ensure electrical continuity between bonded equipment.Partial System OOSB13
5212Hydrants OpsBravo PitsHydrant Fuel PitsFuel PitUnmarkedUnmarkedN/A0006-11.2No Manufacturer Requirements AvailableMonthly, or more often based on local conditions - Hydrant fuel pits shall be inspected to ensure that they are dry and clean and that all fueling components within the pit are clean and in good working order. Check pipe penetrations through pit walls or bottom to ensure that mechanical and boot seals are in good working condition and are allowing no water seepage into the pits. Check for fuel leaks at all flanged and pipe connections.Check pit lids to ensure that seals are in good working order and are preventing water entry into the pits. Inspect hydrant fuel pit bonding cables for corrosion and ensure electrical continuity between bonded equipment.Partial System OOSB12
5212Hydrants OpsBravo PitsHydrant Fuel PitsFuel pitUnmarkedUnmarkedN/A0006-11.2No Manufacturer Requirements AvailableMonthly, or more often based on local conditions - Hydrant fuel pits shall be inspected to ensure that they are dry and clean and that all fueling components within the pit are clean and in good working order. Check pipe penetrations through pit walls or bottom to ensure that mechanical and boot seals are in good working condition and are allowing no water seepage into the pits. Check for fuel leaks at all flanged and pipe connections.Check pit lids to ensure that seals are in good working order and are preventing water entry into the pits. Inspect hydrant fuel pit bonding cables for corrosion and ensure electrical continuity between bonded equipment.Partial System OOSB11
5212Hydrants OpsBravo PitsHydrant Fuel PitsFuel pitUnmarkedUnmarkedN/A0006-11.2No Manufacturer Requirements AvailableMonthly, or more often based on local conditions - Hydrant fuel pits shall be inspected to ensure that they are dry and clean and that all fueling components within the pit are clean and in good working order. Check pipe penetrations through pit walls or bottom to ensure that mechanical and boot seals are in good working condition and are allowing no water seepage into the pits. Check for fuel leaks at all flanged and pipe connections.Check pit lids to ensure that seals are in good working order and are preventing water entry into the pits. Inspect hydrant fuel pit bonding cables for corrosion and ensure electrical continuity between bonded equipment.Partial System OOSB10
5212Hydrants OpsBravo PitsHydrant Fuel PitsFuel pitUnmarkedUnmarkedN/A0006-11.2No Manufacturer Requirements AvailableMonthly, or more often based on local conditions - Hydrant fuel pits shall be inspected to ensure that they are dry and clean and that all fueling components within the pit are clean and in good working order. Check pipe penetrations through pit walls or bottom to ensure that mechanical and boot seals are in good working condition and are allowing no water seepage into the pits. Check for fuel leaks at all flanged and pipe connections.Check pit lids to ensure that seals are in good working order and are preventing water entry into the pits. Inspect hydrant fuel pit bonding cables for corrosion and ensure electrical continuity between bonded equipment.Partial System OOSB9
5212Hydrants OpsBravo PitsHydrant Fuel PitsFuel pitUnmarkedUnmarkedN/A0006-11.2No Manufacturer Requirements AvailableMonthly, or more often based on local conditions - Hydrant fuel pits shall be inspected to ensure that they are dry and clean and that all fueling components within the pit are clean and in good working order. Check pipe penetrations through pit walls or bottom to ensure that mechanical and boot seals are in good working condition and are allowing no water seepage into the pits. Check for fuel leaks at all flanged and pipe connections.Check pit lids to ensure that seals are in good working order and are preventing water entry into the pits. Inspect hydrant fuel pit bonding cables for corrosion and ensure electrical continuity between bonded equipment.Partial System OOSB8
5212Hydrants OpsBravo PitsHydrant Fuel PitsFuel pitUnmarkedUnmarkedN/A0006-11.2No Manufacturer Requirements AvailableMonthly, or more often based on local conditions - Hydrant fuel pits shall be inspected to ensure that they are dry and clean and that all fueling components within the pit are clean and in good working order. Check pipe penetrations through pit walls or bottom to ensure that mechanical and boot seals are in good working condition and are allowing no water seepage into the pits. Check for fuel leaks at all flanged and pipe connections.Check pit lids to ensure that seals are in good working order and are preventing water entry into the pits. Inspect hydrant fuel pit bonding cables for corrosion and ensure electrical continuity between bonded equipment.Partial System OOSB7
5212Hydrants OpsBravo PitsHydrant Fuel PitsFuel pitUnmarkedUnmarkedN/A0006-11.2No Manufacturer Requirements AvailableMonthly, or more often based on local conditions - Hydrant fuel pits shall be inspected to ensure that they are dry and clean and that all fueling components within the pit are clean and in good working order. Check pipe penetrations through pit walls or bottom to ensure that mechanical and boot seals are in good working condition and are allowing no water seepage into the pits. Check for fuel leaks at all flanged and pipe connections.Check pit lids to ensure that seals are in good working order and are preventing water entry into the pits. Inspect hydrant fuel pit bonding cables for corrosion and ensure electrical continuity between bonded equipment.Partial System OOSB6
5212Hydrants OpsBravo PitsHydrant Fuel PitsFuel pitUnmarkedUnmarkedN/A0006-11.2No Manufacturer Requirements AvailableMonthly, or more often based on local conditions - Hydrant fuel pits shall be inspected to ensure that they are dry and clean and that all fueling components within the pit are clean and in good working order. Check pipe penetrations through pit walls or bottom to ensure that mechanical and boot seals are in good working condition and are allowing no water seepage into the pits. Check for fuel leaks at all flanged and pipe connections.Check pit lids to ensure that seals are in good working order and are preventing water entry into the pits. Inspect hydrant fuel pit bonding cables for corrosion and ensure electrical continuity between bonded equipment.Partial System OOSB5
5212Hydrants OpsBravo PitsHydrant Fuel PitsFuel pitUnmarkedUnmarkedN/A0006-11.2No Manufacturer Requirements AvailableMonthly, or more often based on local conditions - Hydrant fuel pits shall be inspected to ensure that they are dry and clean and that all fueling components within the pit are clean and in good working order. Check pipe penetrations through pit walls or bottom to ensure that mechanical and boot seals are in good working condition and are allowing no water seepage into the pits. Check for fuel leaks at all flanged and pipe connections.Check pit lids to ensure that seals are in good working order and are preventing water entry into the pits. Inspect hydrant fuel pit bonding cables for corrosion and ensure electrical continuity between bonded equipment.Partial System OOSB4
5212Hydrants OpsBravo PitsHydrant Fuel PitsFuel pitUnmarkedUnmarkedN/A0006-11.2No Manufacturer Requirements AvailableMonthly, or more often based on local conditions - Hydrant fuel pits shall be inspected to ensure that they are dry and clean and that all fueling components within the pit are clean and in good working order. Check pipe penetrations through pit walls or bottom to ensure that mechanical and boot seals are in good working condition and are allowing no water seepage into the pits. Check for fuel leaks at all flanged and pipe connections.Check pit lids to ensure that seals are in good working order and are preventing water entry into the pits. Inspect hydrant fuel pit bonding cables for corrosion and ensure electrical continuity between bonded equipment.Partial System OOSB3
5212Hydrants OpsBravo PitsHydrant Fuel PitsFuel pitUnmarkedUnmarkedN/A0006-11.2No Manufacturer Requirements AvailableMonthly, or more often based on local conditions - Hydrant fuel pits shall be inspected to ensure that they are dry and clean and that all fueling components within the pit are clean and in good working order. Check pipe penetrations through pit walls or bottom to ensure that mechanical and boot seals are in good working condition and are allowing no water seepage into the pits. Check for fuel leaks at all flanged and pipe connections.Check pit lids to ensure that seals are in good working order and are preventing water entry into the pits. Inspect hydrant fuel pit bonding cables for corrosion and ensure electrical continuity between bonded equipment.Partial System OOSB2
5212Hydrants OpsBravo Pump HouseSight Flow IndicatorsVisi-FloVisi-Flo1571 F 11.0 in.0006-12.3Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Partial System OOSIssue Filter Separator 13

1� 5212 Hydrants Ops Bravo Pump House Sight Flow Indicators Visi-Flo Visi-Flo 1571 F 1 1.0 in. 0 0 0 6-12.3 Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. Partial System OOS Issue Filter Separator 13 1� 5212 Hydrants Ops Bravo Pump House Sight Flow Indicators Visi-Flo Visi-Flo 1571 F 1 1.0 in. 0 0 0 6-12.3 Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. Partial System OOS Issue Filter Separator 12 1� 5212 Hydrants Ops Bravo Pump House Sight Flow Indicators Visi-Flo Visi-Flo 1571 F 1 1.0 in. 0 0 0 6-12.3 Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. Partial System OOS Issue Filter Separator 12 1� 5212 Hydrants Ops Bravo Pump House Sight Flow Indicators Visi-Flo Visi-Flo 1571 F 1 1.0 in. 0 0 0 6-12.3 Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. Partial System OOS Issue Filter Separator 11 1� 5212 Hydrants Ops Bravo Pump House Sight Flow Indicators Visi-Flo Visi-Flo 1571 F 1 1.0 in. 0 0 0 6-12.3 Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. Partial System OOS Issue Filter Separator 11 1� 5212 Hydrants Ops Bravo Pump House Sight Flow Indicators Visi-Flo Visi-Flo 1571 F 1 1.0 in. 0 0 0 6-12.3 Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. Partial System OOS Issue Filter Separator 10 1� 5212 Hydrants Ops Bravo Pump House Sight Flow Indicators Visi-Flo Visi-Flo 1571 F 1 1.0 in. 0 0 0 6-12.3 Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. Partial System OOS Issue Filter Separator 10 1� 5212 Hydrants Ops Bravo Pump House Sight Flow Indicators Visi-Flo Visi-Flo 1571 F 1 1.0 in. 0 0 0 6-12.3 Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. Partial System OOS Issue Filter Separator 9 1� 5212 Hydrants Ops Bravo Pump House Sight Flow Indicators Visi-Flo Visi-Flo 1571 F 1 1.0 in. 0 0 0 6-12.3 Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. Partial System OOS Issue Filter Separator 9 1� 5212 Hydrants Ops Bravo Pump House Sight Flow Indicators Visi-Flo Visi-Flo 1571 F 1 1.0 in. 0 0 0 6-12.3 Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. Partial System OOS Receipt Filter Separator 2 1� 5212 Hydrants Ops Bravo Pump House Sight Flow Indicators Visi-Flo Visi-Flo 1571 F 1 1.0 in. 0 0 0 6-12.3 Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. Partial System OOS Receipt Filter Separator 2 1� 5212 Hydrants Ops Bravo Pump House Sight Flow Indicators Visi-Flo Visi-Flo 1571 F 1 1.0 in. 0 0 0 6-12.3 Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. Partial System OOS Receipt Filter Separator 3 1� 5212 Hydrants Ops Bravo Pump House Sight Flow Indicators Visi-Flo Visi-Flo 1571 F 1 1.0 in. 0 0 0 6-12.3 Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. Partial System OOS Receipt Filter Separator 3 1�