PWS LRG FMP Template - v2.2.xlsx
XLSX spreadsheet 146 KB Posted
- Attached to
- Sources Sought - CEHNC FUELS PROGRAM
- Solicitation number
- PANHES-25-P-0000-001794
About this file
This is a Facility Maintenance Plan (FMP) template for recurring maintenance of fuel systems at Little Rock Air Force Base in Arkansas. The template details maintenance requirements for fuel storage and dispensing equipment at a 24-hour facility located at 1250 West Thomas Avenue, including 8 underground storage tanks of 50,000 gallons each, filter separators, pumps, valves, gauges, and electrical components.
The document provides detailed specifications for quarterly, monthly, and annual maintenance tasks for each piece of equipment, including 8 Johnston vertical turbine pumps rated at 600 GPM, Facet filter separators, Cla-Val control valves, various ball/gate/globe valves, pressure gauges, and electrical motors/controls. It includes manufacturer requirements, inspection frequencies, and operational impacts for each component. The template is structured as a comprehensive asset inventory and maintenance scheduling tool, with sections for administrative information, safety protocols, communications plans, and detailed equipment specifications. This appears to be version 2.2 of a standardized template rather than a completed maintenance plan.
View the file
Other files
Show all 46
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Administrative
| Location | Site Name | Little Rock AFB Site #1 |
| RPSUID | 2496 | |
| DLA Site Code | LRG | |
| Hours of Operation | 24 Hours of Operation | |
| Address | 1250 West Thomas Avenue, Little Rock AFB, AR 72136 | |
| Contract | Contractor | |
| Contract # | ||
| Local POCs | QAE Name | |
| QAE Phone | ||
| QAE Email | ||
| Alt QAE Name | ||
| Alt QAE Phone | ||
| Alt QAE Email | ||
| DLA/SCP POCs | DLA PM Name | |
| DLA PM Phone | ||
| DLA PM Email | ||
| SCP PM Name | ||
| SCP PM Phone | ||
| SCP PM Email | ||
| Contractor POCs | Contractor PM Name | |
| Contractor PM Phone | ||
| Contractor PM Email | ||
| Contractor QC Name | ||
| Contractor QC Phone | ||
| Contractor QC Email | ||
| Contractor SM Name | ||
| Contractor SM Phone | ||
| Contractor SM Email | ||
| USACE POCs | USACE PM/COR Name | |
| USACE PM/COR Phone | ||
| USACE PM/COR Email | ||
| USACE PE Name | ||
| USACE PE Phone | ||
| USACE PE Email | ||
| USACE KO Name | ||
| USACE KO Phone | ||
| USACE KO Email |
Facility Maintenance Plan
FMP v2.2 &P of &N
Instructions:
This table shows the minimum information required. Additional details should be included based on site specific requirements. Additional POCs may be required.
General Facility Description Facility Description
Purpose:
This Facility Maintenance Plan provides guidance for Contractor personnel in the operation, inspection, and maintenance of permanently installed fuel facilities operated under the control of the Quality Assurance Evaluators. Federal, state, and local environmental laws and regulations shall be complied with if this plan is in conflict with them.
Scope:
The instructions prescribed by this plan outline general fuels maintenance information associated with fuel storage and dispensing systems and provides the minimum periodic contractor maintenance and inspection criteria requirements for the systems. This plan is to be used in conjunction with other existing directives governing fuel system operations and maintenance requirements. Conotractor will properly maintain and repair federally funded petroleum systems and facilities in order to provide compliance with applicable code, criteria, and federal, state, local and/or host nation regulations.
Fuels Facilities:
Organizational tanks, and associated dispensing equipment are maintained and operated by the owning organization. Fuel system maintenance contractors shall perform all maintenance and associated procurement actions on installed fuel systems.
Each installation under the Southwest Division contract are military land-based facilities who receive, store, distribute, and/or dispense liquid fuels.
Standard fuel system equipment includes:
a) Above Ground Sorage Stanks (AST), Underground Storage Tanks (UST)
b) Filter/separator and other filtration device maintenance access, particularly element removal.
c) Manual valves
d) Meter Registers, and Flow Meters.
e) Control Valves.
f) Pumps
g) Tank Monitoring Equipment and Instruments
h) Alarms
i) Fire Fighting Equipment
Site Specific General Information:
Facility Maintenance Plan
FMP v2.2 &P of &N
Instructions:
Include a general facility overview and description of each fuel system for the sites in accordance with UFC 3-460-01. Examples include: Bulk Storage Facilities, Aircraft Fueling Facilities, Marine and Dispensing Facilities, Ground Products Fueling Facilities, Alternate POL Facilities, and Support Facilities. Also include facility #s, facility names, fuel type, photos, and any other pertinent information.
Include Site Specific Conditions and Restrictions in this tab.
Communication Plan
Facility Maintenance Plan
FMP v2.2 &P of &N
Instructions:
Communication plan shall address in/out briefs, lines of communication, coordination for access, etc.
Safety
Facility Maintenance Plan
FMP v2.2 &P of &N
Instructions:
Site Specific Addendum and Activity Hazard Analysis, which are Attachments to the APP, specific to activities or tasks related to recurring maintenance for this site.
RM Schedule
Facility Maintenance Plan
FMP v2.2 &P of &N
Instructions:
Link RM schedule here
Task Matrix
| Applicable Facility Assets | UFC System Level Maintenance Frequency | Special Considerations | ||||||||||||||||
| Real Property Unique Identifier | ||||||||||||||||||
| (RPUID) | Real Property Facility # | Real Property Facility Name | Operational Area | Component Type | Base Asset ID | Component Unique Identifier (CUID) | Make | Model | Capacity/Size | Q | S | A | UFC Section Reference | Additional Manufacturer RM Requirements | Operator/ equipment Requirements | System availability | Other Contract | Comments |
| 10 | Pump House 1 | Pump Pad | Pumphouse/Filter Buildings | Pumphouse #1 | N/A | N/A | N/A | X | X | X | 11-2.1 | No Additional Manufacturer Requirements | No Operator/equipment Requirements | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Canopies | Pumphouse Canopy | N/A | N/A | N/A | X | X | 0 | 11-2.2 | No Additional Manufacturer Requirements | No Operator/equipment Requirements | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Emergency Eyewash/Showers | Emergency Shower/Eyewash | Haws Corp | Not Labeled | Not Labeled | X | X | X | 11-3 | Weekly - Equipment installed within 10 seconds from the hazard and on the same plane as the hazard Pathway is clear of obstructions Plumbed equipment activated to ensure compliant operation and to clear any sediment Self-contained equipment checked to determine if the flushing fluid needs to be changed or supplemented Equipment free of broken or missing parts Equipment protected against freezing User protected from scalding water | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Signage and Markings | PH1 Signage | N/A | N/A | N/A | 0 | 0 | X | 2-7 | No Additional Manufacturer Requirements | No Operator/equipment Requirements | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Air Eliminator Tanks | Air Eliminator | Armstrong | 11AV | 1.0 In. | X | X | X | 3-10.1 | No Additional Manufacturer Requirements | No Operator/equipment Requirements | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Air Eliminator Tanks | Air Eliminator | Armstrong | 11AV | 1.0 In. | X | X | X | 3-10.1 | No Additional Manufacturer Requirements | No Operator/equipment Requirements | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Air Eliminator Tanks | Air Eliminator | Armstrong | 11AV | 1.0 In. | X | X | X | 3-10.1 | No Additional Manufacturer Requirements | No Operator/equipment Requirements | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Air Eliminator Tanks | Air Eliminator | Armstrong | 11AV | 1.0 In. | X | X | X | 3-10.1 | No Additional Manufacturer Requirements | No Operator/equipment Requirements | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Air Eliminator Tanks | Air Eliminator | Armstrong | 11AV | 1.0 In. | X | X | X | 3-10.1 | No Additional Manufacturer Requirements | No Operator/equipment Requirements | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Air Eliminator Tanks | Air Eliminator | Armstrong | 11AV | 1.0 In. | X | X | X | 3-10.1 | No Additional Manufacturer Requirements | No Operator/equipment Requirements | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Air Eliminator Tanks | Air Eliminator | Armstrong | 11AV | 1.0 In. | X | X | X | 3-10.1 | No Additional Manufacturer Requirements | No Operator/equipment Requirements | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Air Eliminator Tanks | Air Eliminator | Armstrong | 11AV | 1.0 In. | X | X | X | 3-10.1 | No Additional Manufacturer Requirements | No Operator/equipment Requirements | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Filter Separators | Filter Separator 1 | Facet | VCS-543-236 | 600 GPM GPM/SCFM 100 Gallons | X | X | 0 | 3-6.2 | Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. Replace filter cartridges when the acceptable maximum differential pressure is reached, the maximum in-service duration has passed, or the fuel becomes visibly dirty or discolored. | Daily - Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Filter Separators | Filter Separator 2 | Facet | VCS-543-236 | 600 GPM GPM/SCFM 100 Gallons | X | X | 0 | 3-6.2 | Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. Replace filter cartridges when the acceptable maximum differential pressure is reached, the maximum in-service duration has passed, or the fuel becomes visibly dirty or discolored. | Daily - Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Filter Separators | Filter Separator 3 | Facet | VCS-543-236 | 600 GPM GPM/SCFM 100 Gallons | X | X | 0 | 3-6.2 | Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. Replace filter cartridges when the acceptable maximum differential pressure is reached, the maximum in-service duration has passed, or the fuel becomes visibly dirty or discolored. | Daily - Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Filter Separators | Filter Separator 4 | Facet | VCS-543-236 | 600 GPM GPM/SCFM 100 Gallons | X | X | 0 | 3-6.2 | Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. Replace filter cartridges when the acceptable maximum differential pressure is reached, the maximum in-service duration has passed, or the fuel becomes visibly dirty or discolored. | Daily - Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Filter Separators | Filter Separator 5 | Facet | VGS-543-236 | 600 GPM GPM/SCFM 100 Gallons | X | X | 0 | 3-6.2 | Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. Replace filter cartridges when the acceptable maximum differential pressure is reached, the maximum in-service duration has passed, or the fuel becomes visibly dirty or discolored. | Daily - Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Filter Separators | Filter Separator 6 | Facet | VCS-543-236 | 600 GPM GPM/SCFM 100 Gallons | X | X | 0 | 3-6.2 | Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. Replace filter cartridges when the acceptable maximum differential pressure is reached, the maximum in-service duration has passed, or the fuel becomes visibly dirty or discolored. | Daily - Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Filter Separators | Filter Separator 7 | Facet | VCS-543-236 | 600 GPM GPM/SCFM 100 Gallons | X | X | 0 | 3-6.2 | Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. Replace filter cartridges when the acceptable maximum differential pressure is reached, the maximum in-service duration has passed, or the fuel becomes visibly dirty or discolored. | Daily - Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Filter Separators | Filter Separator 8 | Facet | VCS-543-236 | 600 GPM GPM/SCFM 100 Gallons | X | X | 0 | 3-6.2 | Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. Replace filter cartridges when the acceptable maximum differential pressure is reached, the maximum in-service duration has passed, or the fuel becomes visibly dirty or discolored. | Daily - Open drain under flow conditions until clear fuel is observed from the drain valve. Monitor differential pressure of coalescer cartridges. | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Basket Strainers | Basket Strainer | Zurn | 4-150 | 4.0 in. | X | X | 0 | 3-6.4 | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | ||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | |||||||||||||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | No Mission Impact | |||||||||||||||||
| 10 | Pump House 1 | Pump Pad | Basket Strainers | Basket Strainer | Zurn | 272-15-2 | 4.0 in. | X | X | 0 | 3-6.4 | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | ||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | |||||||||||||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | No Mission Impact | |||||||||||||||||
| 10 | Pump House 1 | Pump Pad | Basket Strainers | Basket Strainer | Zurn | 272-15-2 | 4.0 in. | X | X | 0 | 3-6.4 | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | ||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | |||||||||||||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | No Mission Impact | |||||||||||||||||
| 10 | Pump House 1 | Pump Pad | Basket Strainers | Basket Strainer | Zurn | 272-15-2 | 4.0 in. | X | X | 0 | 3-6.4 | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | ||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | |||||||||||||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | No Mission Impact | |||||||||||||||||
| 10 | Pump House 1 | Pump Pad | Basket Strainers | Basket Strainer | Zurn | 272-15-2 | 4.0 in. | X | X | 0 | 3-6.4 | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | ||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | |||||||||||||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | No Mission Impact | |||||||||||||||||
| 10 | Pump House 1 | Pump Pad | Basket Strainers | Basket Strainer | Zurn | 272-15-2 | 4.0 in. | X | X | 0 | 3-6.4 | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | ||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | |||||||||||||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | No Mission Impact | |||||||||||||||||
| 10 | Pump House 1 | Pump Pad | Basket Strainers | Basket Strainer | Zurn | 272-15-2 | 4.0 in. | X | X | 0 | 3-6.4 | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | ||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | |||||||||||||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | No Mission Impact | |||||||||||||||||
| 10 | Pump House 1 | Pump Pad | Basket Strainers | Basket Strainer | Zurn | 24366-2 | 6.0 in. | X | X | 0 | 3-6.4 | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | ||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | |||||||||||||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | No Mission Impact | |||||||||||||||||
| 10 | Pump House 1 | Pump Pad | Basket Strainers | Basket Strainer | Zurn | 24366-2 | 6.0 in. | X | X | 0 | 3-6.4 | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | ||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | |||||||||||||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | No Mission Impact | |||||||||||||||||
| 10 | Pump House 1 | Pump Pad | Basket Strainers | Basket Strainer | Zurn | 4-5150 | 4.0 in. | X | X | 0 | 3-6.4 | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | ||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | Daily - Monitor and chart differential pressure measurements of basket strainers from readings taken during normal operations. | |||||||||||||||||
| Semi-annually if basket strainer is equipped with means to measure differential pressure; otherwise quarterly | No Mission Impact | |||||||||||||||||
| 10 | Pump House 1 | Pump Pad | Vertical Turbine/Submerged Turbine Pumps | Pump #3 | Johnston | Model # Unavailable/No Data Plate | 600 GPM GPM/SCFM | X | X | X | 3-8.1.3 | During routine pump inspections only the easy to monitor factors such as pressure, temperature, vibration etc can be checKed. But during quarterly inspections, shaft alignment and oil levels should also be checked. Change Oil Annually | No Operator/equipment Requirements | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Vertical Turbine/Submerged Turbine Pumps | Pump #2 | Johnston | Model # Unavailable/No Data Plate | 600 GPM GPM/SCFM | X | X | X | 3-8.1.3 | During routine pump inspections only the easy to monitor factors such as pressure, temperature, vibration etc can be checKed. But during quarterly inspections, shaft alignment and oil levels should also be checked. Change Oil Annually | No Operator/equipment Requirements | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Vertical Turbine/Submerged Turbine Pumps | Pump #1 | Johnston | Model # Unavailable/No Data Plate | 600 GPM GPM/SCFM | X | X | X | 3-8.1.3 | During routine pump inspections only the easy to monitor factors such as pressure, temperature, vibration etc can be checKed. But during quarterly inspections, shaft alignment and oil levels should also be checked. Change Oil Annually | No Operator/equipment Requirements | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Vertical Turbine/Submerged Turbine Pumps | Pump #6 | Johnston | Model # Unavailable/No Data Plate | 600 GPM GPM/SCFM | X | X | X | 3-8.1.3 | During routine pump inspections only the easy to monitor factors such as pressure, temperature, vibration etc can be checKed. But during quarterly inspections, shaft alignment and oil levels should also be checked. Change Oil Annually | No Operator/equipment Requirements | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Vertical Turbine/Submerged Turbine Pumps | Pump #7 | Johnston | Model # Unavailable/No Data Plate | 600 GPM GPM/SCFM | X | X | X | 3-8.1.3 | During routine pump inspections only the easy to monitor factors such as pressure, temperature, vibration etc can be checKed. But during quarterly inspections, shaft alignment and oil levels should also be checked. Change Oil Annually | No Operator/equipment Requirements | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Vertical Turbine/Submerged Turbine Pumps | Pump #8 | Johnston | Model # Unavailable/No Data Plate | 600 GPM GPM/SCFM | X | X | X | 3-8.1.3 | During routine pump inspections only the easy to monitor factors such as pressure, temperature, vibration etc can be checKed. But during quarterly inspections, shaft alignment and oil levels should also be checked. Change Oil Annually | No Operator/equipment Requirements | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Vertical Turbine/Submerged Turbine Pumps | Pump #4 | Johnston | Model # Unavailable/No Data Plate | 600 GPM GPM/SCFM | X | X | X | 3-8.1.3 | During routine pump inspections only the easy to monitor factors such as pressure, temperature, vibration etc can be checKed. But during quarterly inspections, shaft alignment and oil levels should also be checked. Change Oil Annually | No Operator/equipment Requirements | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Vertical Turbine/Submerged Turbine Pumps | Pump #5 | Johnston | Model # Unavailable/No Data Plate | 600 GPM GPM/SCFM | X | X | X | 3-8.1.3 | During routine pump inspections only the easy to monitor factors such as pressure, temperature, vibration etc can be checKed. But during quarterly inspections, shaft alignment and oil levels should also be checked. Change Oil Annually | No Operator/equipment Requirements | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | General System Control Valves | Control Valve | Cla-Val | 150/PN16 | 4.0 in. | X | X | X | 4-3.2.1 | No Manufacturers Data Available. Adjustment not advised unless formal training is received. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | General System Control Valves | Control Valve | Cla-Val | 150/PN16 | 6.0 in. | X | X | X | 4-3.2.1 | No Manufacturers Data Available. Adjustment not advised unless formal training is received. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | General System Control Valves | Control Valve | Cla-Val | 150/PN16 | 4.0 in. | X | X | X | 4-3.2.1 | No Manufacturers Data Available. Adjustment not advised unless formal training is received. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | General System Control Valves | Control Valve | Cla-Val | 150/PN16 | 6.0 in. | X | X | X | 4-3.2.1 | No Manufacturers Data Available. Adjustment not advised unless formal training is received. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | General System Control Valves | Control Valve | Cla-Val | 150/PN16 | 4.0 in. | X | X | X | 4-3.2.1 | No Manufacturers Data Available. Adjustment not advised unless formal training is received. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | General System Control Valves | Control Valve | Cla-Val | 150/PN16 | 6.0 in. | X | X | X | 4-3.2.1 | No Manufacturers Data Available. Adjustment not advised unless formal training is received. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | General System Control Valves | Control Valve | Cla-Val | 150/PN16 | 4.0 in. | X | X | X | 4-3.2.1 | No Manufacturers Data Available. Adjustment not advised unless formal training is received. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | General System Control Valves | Control Valve | Cla-Val | 150/PN16 | 6.0 in. | X | X | X | 4-3.2.1 | No Manufacturers Data Available. Adjustment not advised unless formal training is received. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | General System Control Valves | Control Valve | Cla-Val | 150/PN16 | 6.0 in. | X | X | X | 4-3.2.1 | No Manufacturers Data Available. Adjustment not advised unless formal training is received. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | General System Control Valves | Control Valve | Cla-Val | 150/PN16 | 4.0 in. | X | X | X | 4-3.2.1 | No Manufacturers Data Available. Adjustment not advised unless formal training is received. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | General System Control Valves | Control Valve | Cla-Val | 150/PN16 | 6.0 in. | X | X | X | 4-3.2.1 | No Manufacturers Data Available. Adjustment not advised unless formal training is received. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | General System Control Valves | Control Valve | Cla-Val | 150/PN16 | 4.0 in. | X | X | X | 4-3.2.1 | No Manufacturers Data Available. Adjustment not advised unless formal training is received. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | General System Control Valves | Control Valve | Cla-Val | 150/PN16 | 4.0 in. | X | X | X | 4-3.2.1 | No Manufacturers Data Available. Adjustment not advised unless formal training is received. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | General System Control Valves | Control Valve | Cla-Val | 150/PN16 | 6.0 in. | X | X | X | 4-3.2.1 | No Manufacturers Data Available. Adjustment not advised unless formal training is received. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | General System Control Valves | Control Valve | Cla-Val | 150/PN16 | 6.0 in. | X | X | X | 4-3.2.1 | No Manufacturers Data Available. Adjustment not advised unless formal training is received. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Filter Separator Control Valves | FSCV | Cla-Val | 150/PN16 | 6.0 in. | X | X | 0 | 4-4.2.2 | No Manufacturers Data Available. Adjustment not advised unless formal training is received. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Filter Separator Control Valves | FSCV | Cla-Val | 150/PN16 | 6.0 in. | X | X | 0 | 4-4.2.2 | No Manufacturers Data Available. Adjustment not advised unless formal training is received. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Filter Separator Control Valves | FSCV | Cla-Val | 150/PN16 | 6.0 in. | X | X | 0 | 4-4.2.2 | No Manufacturers Data Available. Adjustment not advised unless formal training is received. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Filter Separator Control Valves | FSCV | Cla-Val | 150/PN16 | 6.0 in. | X | X | 0 | 4-4.2.2 | No Manufacturers Data Available. Adjustment not advised unless formal training is received. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Filter Separator Control Valves | FSCV | Cla-Val | 150/PN16 | 6.0 in. | X | X | 0 | 4-4.2.2 | No Manufacturers Data Available. Adjustment not advised unless formal training is received. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Filter Separator Control Valves | FSCV | Cla-Val | 150/PN16 | 6.0 in. | X | X | 0 | 4-4.2.2 | No Manufacturers Data Available. Adjustment not advised unless formal training is received. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Filter Separator Control Valves | FSCV | Cla-Val | 150/PN16 | 6.0 in. | X | X | 0 | 4-4.2.2 | No Manufacturers Data Available. Adjustment not advised unless formal training is received. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Filter Separator Control Valves | FSCV | Cla-Val | 150/PN16 | 4.0 in. | X | X | 0 | 4-4.2.2 | No Manufacturers Data Available. Adjustment not advised unless formal training is received. | No Operator Requirement | Partial System OOS | ||||
| 10 | Fillstand | Fillstand 6 | Fueling Nozzles | Fillstand Nozzle | Cla-Val | D-2 | 3.0 In. | X | X | 0 | 4-7.4 | Quarterly - Inspect the condition of the dust cap at the aircraft adapter end and ensure it is in good working order. Dust caps must be attached to nozzles when they are not is use. Test leak resistance of poppet valve against full pump pressure. Inspect storage racks for moisture or dirt accumulation. Remove nozzle for inspection of content impinged upon the mesh screen. Clean and dry screens before nozzles are returned to service. Tests nozzle interlocks. Check the operation of the manual valve crank assembly for smooth and positive motion on a special test stand. | Quarterly - Inspect the condition of the dust cap at the aircraft adapter end and ensure it is in good working order. Dust caps must be attached to nozzles when they are not is use. Test leak resistance of poppet valve against full pump pressure. Inspect storage racks for moisture or dirt accumulation. Remove nozzle for inspection of content impinged upon the mesh screen. Clean and dry screens before nozzles are returned to service. Tests nozzle interlocks. Check the operation of the manual valve crank assembly for smooth and positive motion on a special test stand. | Partial System OOS | ||||
| 10 | Fillstand | Fillstand 5 | Fueling Nozzles | Fillstand Nozzle | Cla-Val | D-1 | 3.0 In. | X | X | 0 | 4-7.4 | Quarterly - Inspect the condition of the dust cap at the aircraft adapter end and ensure it is in good working order. Dust caps must be attached to nozzles when they are not is use. Test leak resistance of poppet valve against full pump pressure. Inspect storage racks for moisture or dirt accumulation. Remove nozzle for inspection of content impinged upon the mesh screen. Clean and dry screens before nozzles are returned to service. Tests nozzle interlocks. Check the operation of the manual valve crank assembly for smooth and positive motion on a special test stand. | Quarterly - Inspect the condition of the dust cap at the aircraft adapter end and ensure it is in good working order. Dust caps must be attached to nozzles when they are not is use. Test leak resistance of poppet valve against full pump pressure. Inspect storage racks for moisture or dirt accumulation. Remove nozzle for inspection of content impinged upon the mesh screen. Clean and dry screens before nozzles are returned to service. Tests nozzle interlocks. Check the operation of the manual valve crank assembly for smooth and positive motion on a special test stand. | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Sight Flow Indicators | Visi-Flo | Visi-Flo | Model Unavailable/Paint | 3.0 In. | 0 | 0 | 0 | 6-12.3 | Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. | Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Sight Flow Indicators | Visi-Flo | Visi-Flo | Model Unavailable/Paint | 3.0 In. | 0 | 0 | 0 | 6-12.3 | Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. | Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Sight Flow Indicators | Visi-Flo | Visi-Flo | Model Unavailable/Paint | 3.0 In. | 0 | 0 | 0 | 6-12.3 | Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. | Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Sight Flow Indicators | Visi-Flo | Visi-Flo | A217-WC | 3.0 In. | 0 | 0 | 0 | 6-12.3 | Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. | Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Sight Flow Indicators | Visi-Flo | Visi-Flo | Model Unavailable/Paint | 3.0 In. | 0 | 0 | 0 | 6-12.3 | Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. | Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Sight Flow Indicators | Visi-Flo | Visi-Flo | Model Unavailable/Paint | 3.0 In. | 0 | 0 | 0 | 6-12.3 | Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. | Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Sight Flow Indicators | Visi-Flo | Visi-Flo | Model Unavailable/Paint | 3.0 In. | 0 | 0 | 0 | 6-12.3 | Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. | Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Sight Flow Indicators | Visi-Flo | Visi-Flo | Model Unavailable/Paint | 3.0 In. | 0 | 0 | 0 | 6-12.3 | Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. | Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks. | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Gate Valves | Gate Valve | Velan | 4-150 | 4.0 in. | X | X | 0 | 6-6.2.3 | Operate from fully open to fully closed . Conduct Tightness test as required for application. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Gate Valves | Gate Valve | Velan | 4-150 | 4.0 in. | X | X | 0 | 6-6.2.3 | Operate from fully open to fully closed . Conduct Tightness test as required for application. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Gate Valves | Gate Valve | Velan | 4-150 | 4.0 in. | X | X | 0 | 6-6.2.3 | Operate from fully open to fully closed . Conduct Tightness test as required for application. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Gate Valves | Gate Valve | Velan | 4-150 | 4.0 in. | X | X | 0 | 6-6.2.3 | Operate from fully open to fully closed . Conduct Tightness test as required for application. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Jamesbury | CF8M | 4.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Apollo | RF15 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Velan | CF8M | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Apollo | CF8M | 2.5 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Smith | 6-150 | 6.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Valen | CF8M | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Jamesbury | CF8M | 4.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Apollo | RF15 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Velan | CF8M | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Apollo | CF8M | 2.5 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Velan | CF8M | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Velan | 3/4-150 | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Jamesbury | 6-150 | 6.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Jamesbury | CF8M | 4.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Apollo | 4-150 | 4.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Apollo | RF15 | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Velan | CF8M | 1.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Apollo | CF8M | 2.5 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Jamesbury | 6-150 | 6.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Velan | 3/4-150 | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Apollo | CF8M | 4.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Apollo | CF8M | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Velan | RF15 | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Apollo | CF8M | 2.5 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Jamesbury | 6-150 | 6.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Smith | 6-150 | 6.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Velan | RF15 | 0.25 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Apollo | 2-150 | 2.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Smith | 6-150 | 6.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Velan | RF15 | 0.25 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Smith | 6-150 | 6.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Velan | RF15 | 2.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Balon | CF8M | 2.5 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Balon | CF8M | 2.5 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Jamesbury | CF8M | 4.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Jamesbury | CF8M | 4.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Nibco | CF8M | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Apollo | 6-150 | 6.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Smith | 6-150 | 6.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Gammon | GT-1149 | 0.25 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Jamesbury | CF8M | 4.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Gammon | GT-1149 | 0.25 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Apollo | CF8M | 2.5 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Jamesbury | CF8M | 4.0 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Velan | RF15 | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Ball Valves | Ball Valve | Velan | 3/4-150 | 0.75 in. | X | 0 | 0 | 6-6.2.4 | Operate from fully open to fully closed with 90 degree rotation of the ball. | No Operator Requirement | No Mission Impact | ||||
| 10 | Pump House 1 | Pump Pad | Double Block and Bleed Valves | Double Block and Bleed Isolation Valve | Unavailable | 6-150 | 6.0 in. | X | X | X | 6-6.2.5 | Valve design must permit sealing slips to be replaced from the bottom with the valve mounted in the piping. Valves must operate from fully open to fully closed by rotation of the handwheel to lift and turn the plug. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Double Block and Bleed Valves | Double Block and Bleed Isolation Valve | Unavailable | 6-150 | 6.0 in. | X | X | X | 6-6.2.5 | Valve design must permit sealing slips to be replaced from the bottom with the valve mounted in the piping. Valves must operate from fully open to fully closed by rotation of the handwheel to lift and turn the plug. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Double Block and Bleed Valves | Double Block and Bleed Isolation Valve | Unavailable | 8-150 | 8.0 in. | X | X | X | 6-6.2.5 | Valve design must permit sealing slips to be replaced from the bottom with the valve mounted in the piping. Valves must operate from fully open to fully closed by rotation of the handwheel to lift and turn the plug. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Double Block and Bleed Valves | Double Block and Bleed Isolation Valve | General | Tru Seal | 8.0 in. | X | X | X | 6-6.2.5 | Valve design must permit sealing slips to be replaced from the bottom with the valve mounted in the piping. Valves must operate from fully open to fully closed by rotation of the handwheel to lift and turn the plug. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Double Block and Bleed Valves | Double Block and Bleed Isolation Valve | Unavailable | 4-150 | 4.0 in. | X | X | X | 6-6.2.5 | Valve design must permit sealing slips to be replaced from the bottom with the valve mounted in the piping. Valves must operate from fully open to fully closed by rotation of the handwheel to lift and turn the plug. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Double Block and Bleed Valves | Double Block and Bleed | General | 4-150 | 4.0 in. | X | X | X | 6-6.2.5 | Valve design must permit sealing slips to be replaced from the bottom with the valve mounted in the piping. Valves must operate from fully open to fully closed by rotation of the handwheel to lift and turn the plug. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Double Block and Bleed Valves | Double Block and Bleed Isolation Valve | General | 6-150 | 6.0 in. | X | X | X | 6-6.2.5 | Valve design must permit sealing slips to be replaced from the bottom with the valve mounted in the piping. Valves must operate from fully open to fully closed by rotation of the handwheel to lift and turn the plug. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Double Block and Bleed Valves | Double Block and Bleed Isolation Valve | General Twin Seal | 8-150 | 8.0 in. | X | X | X | 6-6.2.5 | Valve design must permit sealing slips to be replaced from the bottom with the valve mounted in the piping. Valves must operate from fully open to fully closed by rotation of the handwheel to lift and turn the plug. | No Operator Requirement | Partial System OOS | ||||
| 10 | Pump House 1 | Pump Pad | Globe Valves | Globe Valve | Kenco | Not Labeled | 0.5 in. | X | X | 0 | 6-6.2.7 | 1. Regular inspection of the valve. ... |
2. If the valve is not operated regularly it is a good idea to cycle the valve to ensure the disc is not bedding itself in the seat.
3. Grease the crossbar by using a grease gun on the grease nipple provided
| 4. Slightly tighten the gland bolts if the packing needs adjustment. | No Operator Requirement | Partial System OOS | Filter separator sight glass | |||||||||||
| 10 | Pump House 1 | Pump Pad | Globe Valves | Globe Valve | Kenco | Not Labeled | 0.5 in. | X | X | 0 | 6-6.2.7 | 1. Regular inspection of the valve. ... |
2. If the valve is not operated regularly it is a good idea to cycle the valve to ensure the disc is not bedding itself in the seat.
3. Grease the crossbar by using a grease gun on the grease nipple provided
| 4. Slightly tighten the gland bolts if the packing needs adjustment. | No Operator Requirement | Partial System OOS | Filter Separator Sight Glass | |||||||||||
| 10 | Fillstand | Transfer Separator pad | Globe Valves | Globe Valve | Kenco | Not Labeled | 0.5 in. | X | X | 0 | 6-6.2.7 | 1. Regular inspection of the valve. ... |
2. If the valve is not operated regularly it is a good idea to cycle the valve to ensure the disc is not bedding itself in the seat.
3. Grease the crossbar by using a grease gun on the grease nipple provided
| 4. Slightly tighten the gland bolts if the packing needs adjustment. | No Operator Requirement | Partial System OOS | F/S Sight Glass | |||||||||||
| 10 | Pump House 1 | Pump Pad | Globe Valves | Globe Valve | Kenco | Not Labeled | 0.5 in. | X | X | 0 | 6-6.2.7 | 1. Regular inspection of the valve. ... |
2. If the valve is not operated regularly it is a good idea to cycle the valve to ensure the disc is not bedding itself in the seat.
3. Grease the crossbar by using a grease gun on the grease nipple provided
| 4. Slightly tighten the gland bolts if the packing needs adjustment. | No Operator Requirement | Partial System OOS | Filter separator sight glass | |||||||||||
| 10 | Pump House 1 | Pump Pad | Globe Valves | Globe Valve | Kenco | Not Labeled | 0.5 in. | X | X | 0 | 6-6.2.7 | 1. Regular inspection of the valve. ... |
2. If the valve is not operated regularly it is a good idea to cycle the valve to ensure the disc is not bedding itself in the seat.
3. Grease the crossbar by using a grease gun on the grease nipple provided
| 4. Slightly tighten the gland bolts if the packing needs adjustment. | No Operator Requirement | Partial System OOS | Filter separator sight glass | |||||||||||
| 10 | Pump House 1 | Pump Pad | Globe Valves | Globe Valve | Kenco | Not Labeled | 0.5 in. | X | X | 0 | 6-6.2.7 | 1. Regular inspection of the valve. ... |
2. If the valve is not operated regularly it is a good idea to cycle the valve to ensure the disc is not bedding itself in the seat.
3. Grease the crossbar by using a grease gun on the grease nipple provided
| 4. Slightly tighten the gland bolts if the packing needs adjustment. | No Operator Requirement | Partial System OOS | Filter separator sight glass | |||||||||||
| 10 | Pump House 1 | Pump Pad | Globe Valves | Globe Valve | Kenco | Not Labeled | 0.5 in. | X | X | 0 | 6-6.2.7 | 1. Regular inspection of the valve. ... |
2. If the valve is not operated regularly it is a good idea to cycle the valve to ensure the disc is not bedding itself in the seat.
3. Grease the crossbar by using a grease gun on the grease nipple provided
| 4. Slightly tighten the gland bolts if the packing needs adjustment. | No Operator Requirement | Partial System OOS | Filter separator sight glass | |||||||||||
| 10 | Pump House 1 | Pump Pad | Globe Valves | Globe Valve | Kenco | Not Labeled | 0.5 in. | X | X | 0 | 6-6.2.7 | 1. Regular inspection of the valve. ... |
2. If the valve is not operated regularly it is a good idea to cycle the valve to ensure the disc is not bedding itself in the seat.
3. Grease the crossbar by using a grease gun on the…