PWS ELL FMP Template - v2.2.xlsx

XLSX spreadsheet 68 KB Posted

Attached to
Sources Sought - CEHNC FUELS PROGRAM
Solicitation number
PANHES-25-P-0000-001794
Issued by

About this file

This file is a Facility Maintenance Plan (FMP) template spreadsheet containing detailed maintenance requirements for fuel storage and dispensing systems at Ellington Field in Houston, TX. The template includes tabs for administrative information, general facility description, communication plans, safety requirements, recurring maintenance schedules, and component tracking.

The document provides comprehensive maintenance tracking for fuel system components including above-ground storage tanks (10,000 gallon capacities for both MOGAS and diesel), ball valves, breakaways, card readers, containment systems, dispenser cabinets, filters, hoses, meters, nozzles, pumps, static grounding systems, and associated equipment. For each component, it specifies inspection frequencies (daily/weekly/monthly/annual), maintenance requirements per UFC 3-460-03, manufacturer requirements, operator requirements, and system availability impacts. The template is designed to ensure compliance with federal, state and local environmental regulations while maintaining proper operation of permanently installed fuel facilities under Quality Assurance Evaluator control.

View the file

Other files

File Type Posted
Sources Sought FUELS - Programmatic Rev1 7 May 25.docx DOCX document
3.4 Appendix B - Attachment 4 - SO Tracker-20210628.xlsx XLSX spreadsheet
6.0 - Appendix E ISR 15-Bulk_Fuel_Facilities FY25.xlsx XLSX spreadsheet
2.0 Appendix A RM_SO Process_20241220_PgM Reviewed Incorporated.docx DOCX document
3.1 Appendix B - Attachment 1 - Three Week Look Ahead_20230420.xlsx XLSX spreadsheet
3.2 Appendix B - Attachment 2 - Monthly Report Format 20240910.docx DOCX document
2.2 Appendix A - Attachment 2 Contractor Travel Expense Report_20240910.xlsx XLSX spreadsheet
9.0 Appendix H - Minor Repairs Incidental to Maintenance Activities POJ 20231009.xlsx XLSX spreadsheet
7.0 CUID - v2.1.pdf PDF
8.0 Appendix G_UFC 3-460-03 Maintenance Table- v4.3.pdf PDF
6.0 Appendix E ISR 14_operational_fuel_facilities FY25.xlsx XLSX spreadsheet
3.0 Appendix B Reporting Requirements_20240910.docx DOCX document
4.0 Appendix C Task Order Specifications_202401216.docx DOCX document
5.0 Appendix D Antiterrorism and OPSEC 20230206.docx DOCX document
PWS LEX FMP Template - v2.2.xlsx XLSX spreadsheet
PWS VNC FMP Template - v2.2.xlsx XLSX spreadsheet
PWS KEQ FMP Template - v2.2.xlsx XLSX spreadsheet
PWS CVZ FMP Template - v2.2.xlsx XLSX spreadsheet
PWS SHP FMP Template - v2.2.xlsx XLSX spreadsheet
PWS PBA FMP Template - v2.2.xlsx XLSX spreadsheet
PWS GRB FMP Template - v2.2.xlsx XLSX spreadsheet
PWS BRO FMP Template - v2.2.xlsx XLSX spreadsheet
PWS BAR FMP Template - v2.2.xlsx XLSX spreadsheet
PWS EFS FMP Template - v2.2.xlsx XLSX spreadsheet
PWS LAU FMP Template - v2.2.xlsx XLSX spreadsheet
PWS CHF FMP Template - v2.2.xlsx XLSX spreadsheet
PWS BEU FMP Template - v2.2.xlsx XLSX spreadsheet
PWS GDF FMP Template - v2.2.xlsx XLSX spreadsheet
PWS BLI FMP Template - v2.2.xlsx XLSX spreadsheet
PWS TKR FMP Template - v2.2.xlsx XLSX spreadsheet
PWS RBN FMP Template - v2.2.xlsx XLSX spreadsheet
PWS MAA FMP Template - v2.2.xlsx XLSX spreadsheet
PWS FSH FMP Template - v2.2.xlsx XLSX spreadsheet
PWS FSO FMP Template - v2.2.xlsx XLSX spreadsheet
PWS LRG FMP Template - v2.2.xlsx XLSX spreadsheet
PWS RRT FMP Template - v2.2.xlsx XLSX spreadsheet
PWS ALT FMP Template - v2.2.xlsx XLSX spreadsheet
PWS TUL FMP Template - v2.2.xlsx XLSX spreadsheet
PWS BL2 FMP Template - v2.2.xlsx XLSX spreadsheet
PWS WRF FMP Template - v2.2.xlsx XLSX spreadsheet
PWS LLD FMP Template - v2.2.xlsx XLSX spreadsheet
PWS DYE FMP Template - v2.2.xlsx XLSX spreadsheet
12.0 PWS Appendix K Real Property Data_20230420.xlsx XLSX spreadsheet
PWS RAN FMP Template - v2.2.xlsx XLSX spreadsheet
PWS FSM FMP Template - v2.2.xlsx XLSX spreadsheet
PWS _Fuels RMMR 20241220.docx DOCX document
Show all 46

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Administrative

LocationSite NameEllington Field Site #1
RPSUID1708
DLA Site CodeELL
Hours of Operation24 Hours of Operation
Address14657 Sneider Street, Houston, TX 77034
ContractContractor
Contract #
Local POCsQAE Name
QAE Phone
QAE Email
Alt QAE Name
Alt QAE Phone
Alt QAE Email
DLA/SCP POCsDLA PM Name
DLA PM Phone
DLA PM Email
SCP PM Name
SCP PM Phone
SCP PM Email
Contractor POCsContractor PM Name
Contractor PM Phone
Contractor PM Email
Contractor QC Name
Contractor QC Phone
Contractor QC Email
Contractor SM Name
Contractor SM Phone
Contractor SM Email
USACE POCsUSACE PM/COR Name
USACE PM/COR Phone
USACE PM/COR Email
USACE PE Name
USACE PE Phone
USACE PE Email
USACE KO Name
USACE KO Phone
USACE KO Email

Facility Maintenance Plan

FMP v2.2 &P of &N

Instructions:

This table shows the minimum information required. Additional details should be included based on site specific requirements. Additional POCs may be required.

General Facility Description Facility Description

Purpose:

This Facility Maintenance Plan provides guidance for Contractor personnel in the operation, inspection, and maintenance of permanently installed fuel facilities operated under the control of the Quality Assurance Evaluators. Federal, state, and local environmental laws and regulations shall be complied with if this plan is in conflict with them.

Scope:

The instructions prescribed by this plan outline general fuels maintenance information associated with fuel storage and dispensing systems and provides the minimum periodic contractor maintenance and inspection criteria requirements for the systems. This plan is to be used in conjunction with other existing directives governing fuel system operations and maintenance requirements. Conotractor will properly maintain and repair federally funded petroleum systems and facilities in order to provide compliance with applicable code, criteria, and federal, state, local and/or host nation regulations.

Fuels Facilities:

Organizational tanks, and associated dispensing equipment are maintained and operated by the owning organization. Fuel system maintenance contractors shall perform all maintenance and associated procurement actions on installed fuel systems.

Each installation under the Southwest Division contract are military land-based facilities who receive, store, distribute, and/or dispense liquid fuels.

Standard fuel system equipment includes:

a) Above Ground Sorage Stanks (AST), Underground Storage Tanks (UST)

b) Filter/separator and other filtration device maintenance access, particularly element removal.

c) Manual valves

d) Meter Registers, and Flow Meters.

e) Control Valves.

f) Pumps

g) Tank Monitoring Equipment and Instruments

h) Alarms

i) Fire Fighting Equipment

Site Specific General Information:

Facility Maintenance Plan

FMP v2.2 &P of &N

Instructions:

Include a general facility overview and description of each fuel system for the sites in accordance with UFC 3-460-01. Examples include: Bulk Storage Facilities, Aircraft Fueling Facilities, Marine and Dispensing Facilities, Ground Products Fueling Facilities, Alternate POL Facilities, and Support Facilities. Also include facility #s, facility names, fuel type, photos, and any other pertinent information.

Include Site Specific Conditions and Restrictions in this tab.

Communication Plan

Facility Maintenance Plan

FMP v2.2 &P of &N

Instructions:

Communication plan shall address in/out briefs, lines of communication, coordination for access, etc.

Safety

Facility Maintenance Plan

FMP v2.2 &P of &N

Instructions:

Site Specific Addendum and Activity Hazard Analysis, which are Attachments to the APP, specific to activities or tasks related to recurring maintenance for this site.

RM Schedule

Facility Maintenance Plan

FMP v2.2 &P of &N

Instructions:

Link RM schedule here

Task Matrix

Applicable Facility AssetsUFC System Level Maintenance FrequencySpecial Considerations
Real Property Unique Identifier
(RPUID)Real Property Facility #Real Property Facility NameOperational AreaComponent TypeBase Asset IDComponent Unique Identifier (CUID)MakeModelCapacity/SizeQSAUFC Section ReferenceAdditional Manufacturer RM RequirementsOperator/ equipment RequirementsSystem availabilityOther ContractComments
1145MOGAS Tank / SSTAMOGAS Tank / SSTAAboveground PipingMOGAS OffloadN/AN/A3.0 in.XXX6-1.3No Manufacturer Requirements AvailableWeekly - Conduct petroleum fuel piping visual inspection in accordance with Section 6-1.5 Pipeline Visual Inspection.No Mission Impact
1145MOGAS Tank / SSTAMOGAS Tank / SSTAAboveground PipingMOGAS IssueN/AN/A2.0 in.XXX6-1.3No Manufacturer Requirements AvailableWeekly - Conduct petroleum fuel piping visual inspection in accordance with Section 6-1.5 Pipeline Visual Inspection.No Mission Impact
15011SSTA Above Ground PipingSSTA Above Ground PipingAboveground PipingDispenser PipingN/AN/A2.0 in.XXX6-1.3No Manufacturer Requirements AvailableWeekly - Conduct petroleum fuel piping visual inspection in accordance with Section 6-1.5 Pipeline Visual Inspection.No Mission Impact
15011SSTA Above Ground PipingSSTA Above Ground PipingAboveground PipingOffload PipingN/AN/A3.0 in.XXX6-1.3No Manufacturer Requirements AvailableWeekly - Conduct petroleum fuel piping visual inspection in accordance with Section 6-1.5 Pipeline Visual Inspection.No Mission Impact
1146Diesel Tank / SSTADiesel Tank / SSTAAboveground Shop Fabricated TanksDiesel TankSouthwest Research Institute96040-03-0310,000 GallonsXXX8-5.1No Manufacturer Requirements AvailableMonthly - Visually inspect for evidence of leaks; shell distortions; signs of settlement; corrosion, condition of tank foundation, condition of coating, insulation systems, and appurtenances. Inspection shall include all components and equipment located inside the containment area such as piping, pipe supports, containment valves, and product saver tanks. Items noted during the inspection will be documented for follow-up action by an authorized inspector. See Appendix F for the Field-Erected Tank Monthly Inspection Checklist. Visually inspect chime to ringwall sealant. Seal should be maintained in good working order to prevent corrosion of the underside of the tank bottom.Partial System OOS
1145MOGAS Tank / SSTAMOGAS Tank / SSTAAboveground Shop Fabricated TanksMOGAS TankSouthwest Research Institute96040-03-0310,000 GallonsXXX8-5.1No Manufacturer Requirements AvailableMonthly - Visually inspect for evidence of leaks; shell distortions; signs of settlement; corrosion, condition of tank foundation, condition of coating, insulation systems, and appurtenances. Inspection shall include all components and equipment located inside the containment area such as piping, pipe supports, containment valves, and product saver tanks. Items noted during the inspection will be documented for follow-up action by an authorized inspector. See Appendix F for the Field-Erected Tank Monthly Inspection Checklist. Visually inspect chime to ringwall sealant. Seal should be maintained in good working order to prevent corrosion of the underside of the tank bottom.Partial System OOS
1145MOGAS Tank / SSTAMOGAS Tank / SSTABall ValvesDispenser 3 Issue LineNot LegibleNot Legible2.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1145MOGAS Tank / SSTAMOGAS Tank / SSTABall ValvesDispenser 4 Issue LineNot LegibleNot Legible2.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1145MOGAS Tank / SSTAMOGAS Tank / SSTABall ValvesMOGAS Sample CockGammonGTP-11490.66 (1/8th) in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1145MOGAS Tank / SSTAMOGAS Tank / SSTABall ValvesMOGAS OffloadNot LegibleNot Legible2.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1145MOGAS Tank / SSTAMOGAS Tank / SSTABall ValvesDispenser 3 Sump Drain ValveFNW200A0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1145MOGAS Tank / SSTAMOGAS Tank / SSTABall ValvesDispenser 4 Sump Drain ValveFNW200A0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1146Diesel Tank / SSTADiesel Tank / SSTABall ValvesDiesel OffloadRBDN803.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1145MOGAS Tank / SSTAMOGAS Tank / SSTABall ValvesO NCRBDN803.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1146Diesel Tank / SSTADiesel Tank / SSTABall ValvesDiesel Sample CockGammonUnknown0.25 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1146Diesel Tank / SSTADiesel Tank / SSTABall ValvesDiesel OffloadDover CorpNot Labeled2.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1146Diesel Tank / SSTADiesel Tank / SSTABall ValvesDispenser 1 IsolationPaintedPainted2.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1146Diesel Tank / SSTADiesel Tank / SSTABall ValvesDispenser 2 IsolationPaintedPainted2.0 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1146Diesel Tank / SSTADiesel Tank / SSTABall ValvesDispenser 2 Sump DrainFNWCF8M0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1146Diesel Tank / SSTADiesel Tank / SSTABall ValvesDispenser 1 Sump DrainFNWCF8M0.75 in.X006-6.2.4Operate from fully open to fully closed with 90 degree rotation of the ball.No Operator RequirementNo Mission Impact
1145MOGAS Tank / SSTAMOGAS Tank / SSTABreakawaysDispenser 4OPW68EZR-75750.75 in.0007-4Inspect for expiration date. Inspect for loose connections and signs of damage.Daily - Inspect breakaways for loose connections and signs of damage to poppets. Ensure breakaways are clean and free of fuel.
Monthly - Inspect breakaway for an expiration date established by the manufacturer. Breakaways must be replaced before the indicated expiration date.No Mission Impact
1146Diesel Tank / SSTADiesel Tank / SSTABreakawaysDispenser 2OPW66V1.0 in.0007-4Inspect for expiration date. Inspect for loose connections and signs of damage.Daily - Inspect breakaways for loose connections and signs of damage to poppets. Ensure breakaways are clean and free of fuel.
Monthly - Inspect breakaway for an expiration date established by the manufacturer. Breakaways must be replaced before the indicated expiration date.No Mission Impact
1146Diesel Tank / SSTADiesel Tank / SSTABreakawaysDispenser 1OPW66V1.0 in.0007-4Inspect for expiration date. Inspect for loose connections and signs of damage.Daily - Inspect breakaways for loose connections and signs of damage to poppets. Ensure breakaways are clean and free of fuel.
Monthly - Inspect breakaway for an expiration date established by the manufacturer. Breakaways must be replaced before the indicated expiration date.No Mission Impact
1145MOGAS Tank / SSTAMOGAS Tank / SSTABreakawaysDispenser 3OPW68EZR-75750.75 in.0007-4Inspect for expiration date. Inspect for loose connections and signs of damage.Daily - Inspect breakaways for loose connections and signs of damage to poppets. Ensure breakaways are clean and free of fuel.
Monthly - Inspect breakaway for an expiration date established by the manufacturer. Breakaways must be replaced before the indicated expiration date.No Mission Impact
1146Diesel Tank / SSTADiesel Tank / SSTACard and Key LocksDispensersFuel MasterFMU 2400Faded00X9-3No Manufacturer Requirements AvailableNo Operator RequirementNo Mission Impact
1145MOGAS Tank / SSTAMOGAS Tank / SSTAContainment SystemsMOGAS DispensersN/AN/AN/A0008-10.1No Manufacturer Requirements AvailableDaily - Inspect containment systems for cleanliness, if accessible.No Mission Impact
1146Diesel Tank / SSTADiesel Tank / SSTAContainment SystemsDiesel DispensersN/AN/AN/A0008-10.1No Manufacturer Requirements AvailableDaily - Inspect containment systems for cleanliness, if accessible.No Mission Impact
1145MOGAS Tank / SSTAMOGAS Tank / SSTADispenser CabinetDispenser 4Wayne3/07203P/289HJ/JW39384D00X7-7Inspect for damage, ensure door panels and locks are functional.Monthly - Inspect outside of cabinet and ensure it is free of damage. Inspect for fuel stains on the concrete island around the cabinet and on the outside of the cabinet. Ensure the cabinet is free of dirt and fuel. Open both sides of the cabinet and inspect the inside of the cabinet. Ensure the inside of the cabinet and all of the components inside the cabinet are clean and free of fuel.Partial System OOS
1146Diesel Tank / SSTADiesel Tank / SSTADispenser CabinetDispenser 2Wayne3/G7203P/289HJ/JW39386D00X7-7Inspect for damage, ensure door panels and locks are functional.Monthly - Inspect outside of cabinet and ensure it is free of damage. Inspect for fuel stains on the concrete island around the cabinet and on the outside of the cabinet. Ensure the cabinet is free of dirt and fuel. Open both sides of the cabinet and inspect the inside of the cabinet. Ensure the inside of the cabinet and all of the components inside the cabinet are clean and free of fuel.Partial System OOS
1146Diesel Tank / SSTADiesel Tank / SSTADispenser CabinetDispenser 1Wayne3/G7203P/289HJ/JW39387D00X7-7Inspect for damage, ensure door panels and locks are functional.Monthly - Inspect outside of cabinet and ensure it is free of damage. Inspect for fuel stains on the concrete island around the cabinet and on the outside of the cabinet. Ensure the cabinet is free of dirt and fuel. Open both sides of the cabinet and inspect the inside of the cabinet. Ensure the inside of the cabinet and all of the components inside the cabinet are clean and free of fuel.Partial System OOS
1145MOGAS Tank / SSTAMOGAS Tank / SSTADispenser CabinetDispenser 3Wayne3/G7203P/289HJ/JW39385DA1800X7-7Inspect for damage, ensure door panels and locks are functional.Monthly - Inspect outside of cabinet and ensure it is free of damage. Inspect for fuel stains on the concrete island around the cabinet and on the outside of the cabinet. Ensure the cabinet is free of dirt and fuel. Open both sides of the cabinet and inspect the inside of the cabinet. Ensure the inside of the cabinet and all of the components inside the cabinet are clean and free of fuel.Partial System OOS
1146Diesel Tank / SSTADiesel Tank / SSTADispenser FiltersDispenser 1CIM-TEK50109Series 80000X7-9Check exterior for damageNo Operator RequirementPartial System OOS
1145MOGAS Tank / SSTAMOGAS Tank / SSTADispenser FiltersDispenser 4CIM-TEK70012300-3000X7-9Check exterior for damageNo Operator RequirementPartial System OOS
1146Diesel Tank / SSTADiesel Tank / SSTADispenser FiltersDispenser 2CIM-TEK50109Series 80000X7-9Check exterior for damageNo Operator RequirementPartial System OOS
1145MOGAS Tank / SSTAMOGAS Tank / SSTADispenser FiltersDispenser 3Bio Tek70122300MB-1000X7-9Check exterior for damageNo Operator RequirementPartial System OOS
1145MOGAS Tank / SSTAMOGAS Tank / SSTADispenser HosesDispenser 3Unmarked559N0.75 in.0007-3Check for expiration date, and physical condition/damage leaks.Daily - Inspect dispenser hoses and hose whips for gouges, cuts, blisters, or outside wear that may lead to rupture during use. Replace hose or hose whips that show signs of wear. Inspect connection points of hoses and hose whips to the dispenser, breakaways, swivels, and the nozzle and ensure the connection points are clean and free of fuel.Partial System OOSWorn and needs to be replaced
1145MOGAS Tank / SSTAMOGAS Tank / SSTADispenser HosesDispenser 4Unmarked559N0.75 in.0007-3Check for expiration date, and physical condition/damage leaks.Daily - Inspect dispenser hoses and hose whips for gouges, cuts, blisters, or outside wear that may lead to rupture during use. Replace hose or hose whips that show signs of wear. Inspect connection points of hoses and hose whips to the dispenser, breakaways, swivels, and the nozzle and ensure the connection points are clean and free of fuel.Partial System OOS
1146Diesel Tank / SSTADiesel Tank / SSTADispenser HosesDispenser 2Not Labeled559N1.0 in.0007-3Check for expiration date, and physical condition/damage leaks.Daily - Inspect dispenser hoses and hose whips for gouges, cuts, blisters, or outside wear that may lead to rupture during use. Replace hose or hose whips that show signs of wear. Inspect connection points of hoses and hose whips to the dispenser, breakaways, swivels, and the nozzle and ensure the connection points are clean and free of fuel.Partial System OOS
1146Diesel Tank / SSTADiesel Tank / SSTADispenser HosesDispenser 1Not Labeled559N1.0 in.0007-3Check for expiration date, and physical condition/damage leaks.Daily - Inspect dispenser hoses and hose whips for gouges, cuts, blisters, or outside wear that may lead to rupture during use. Replace hose or hose whips that show signs of wear. Inspect connection points of hoses and hose whips to the dispenser, breakaways, swivels, and the nozzle and ensure the connection points are clean and free of fuel.Partial System OOS
1145MOGAS Tank / SSTAMOGAS Tank / SSTADispenser MetersDispenser 3WayneDM11-1 LPM - 72 LPM00X7-8Inspect for damage, smooth operation and legibility.Monthly - Inspect meter and ensure meter is clean and free of fuel. Ensure calibration mechanism is sealed.Partial System OOS
1145MOGAS Tank / SSTAMOGAS Tank / SSTADispenser MetersDispenser 4WayneDM11-1 LPM - 72 LPM00X7-8Inspect for damage, smooth operation and legibility.Monthly - Inspect meter and ensure meter is clean and free of fuel. Ensure calibration mechanism is sealed.Partial System OOS
1146Diesel Tank / SSTADiesel Tank / SSTADispenser MetersDispenser 2WayneDM11-1 LPM - 72 LPM00X7-8Inspect for damage, smooth operation and legibility.Monthly - Inspect meter and ensure meter is clean and free of fuel. Ensure calibration mechanism is sealed.Partial System OOSDual Dispensing / Second Meter Disabled
1146Diesel Tank / SSTADiesel Tank / SSTADispenser MetersDispenser 1WayneDM11-1 LPM - 72 LPM00X7-8Inspect for damage, smooth operation and legibility.Monthly - Inspect meter and ensure meter is clean and free of fuel. Ensure calibration mechanism is sealed.Partial System OOSDual Dispensing / One Meter Disabled
1145MOGAS Tank / SSTAMOGAS Tank / SSTADispenser NozzlesDispenser 3OPW11 BP1.0 in.00X7-2Start flow into approved test container; place nozzle

in low clip position. Immerse nozzle spout tip in the gasoline in the approved test container. The nozzle tip must be at least three (3) inches from the bottom of the container

to prevent back-pressure in the spout. Nozzle must shut off five consective tests.Daily - Inspect dispenser nozzle spout. Ensure it is tight, round, has no cracks, or excessive wear. Inspect automatic shutoff hole. Ensure the hole is open and free of obstructions. Inspect nozzle hold-open latch. Ensure the latch is straight, moves freely, and the return spring operates correctly. Inspect body of nozzle. Ensure the body is in good condition and that the valve stem is clean and free of fuel. Inspect the nozzle to hose connection and ensure it is clean and free of fuel.
Monthly - Dispenser nozzle handles shall be inspected for an expiration date established by the manufacturer. Nozzles must be replaced before the indicated expiration date.Partial System OOS
1146Diesel Tank / SSTADiesel Tank / SSTADispenser NozzlesDispenser 2OPW7-HB1.0 in.00X7-2Start flow into approved test container; place nozzle

in low clip position. Immerse nozzle spout tip in the gasoline in the approved test container. The nozzle tip must be at least three (3) inches from the bottom of the container

to prevent back-pressure in the spout. Nozzle must shut off five consective tests.Daily - Inspect dispenser nozzle spout. Ensure it is tight, round, has no cracks, or excessive wear. Inspect automatic shutoff hole. Ensure the hole is open and free of obstructions. Inspect nozzle hold-open latch. Ensure the latch is straight, moves freely, and the return spring operates correctly. Inspect body of nozzle. Ensure the body is in good condition and that the valve stem is clean and free of fuel. Inspect the nozzle to hose connection and ensure it is clean and free of fuel.
Monthly - Dispenser nozzle handles shall be inspected for an expiration date established by the manufacturer. Nozzles must be replaced before the indicated expiration date.Partial System OOS
1145MOGAS Tank / SSTAMOGAS Tank / SSTADispenser NozzlesDispenser 4OPW11 BP0.75 in.00X7-2Start flow into approved test container; place nozzle

in low clip position. Immerse nozzle spout tip in the gasoline in the approved test container. The nozzle tip must be at least three (3) inches from the bottom of the container

to prevent back-pressure in the spout. Nozzle must shut off five consective tests.Daily - Inspect dispenser nozzle spout. Ensure it is tight, round, has no cracks, or excessive wear. Inspect automatic shutoff hole. Ensure the hole is open and free of obstructions. Inspect nozzle hold-open latch. Ensure the latch is straight, moves freely, and the return spring operates correctly. Inspect body of nozzle. Ensure the body is in good condition and that the valve stem is clean and free of fuel. Inspect the nozzle to hose connection and ensure it is clean and free of fuel.
Monthly - Dispenser nozzle handles shall be inspected for an expiration date established by the manufacturer. Nozzles must be replaced before the indicated expiration date.Partial System OOS
1146Diesel Tank / SSTADiesel Tank / SSTADispenser NozzlesDispenser 1HuskyNot Labeled1.0 in.00X7-2Start flow into approved test container; place nozzle

in low clip position. Immerse nozzle spout tip in the gasoline in the approved test container. The nozzle tip must be at least three (3) inches from the bottom of the container

to prevent back-pressure in the spout. Nozzle must shut off five consective tests.Daily - Inspect dispenser nozzle spout. Ensure it is tight, round, has no cracks, or excessive wear. Inspect automatic shutoff hole. Ensure the hole is open and free of obstructions. Inspect nozzle hold-open latch. Ensure the latch is straight, moves freely, and the return spring operates correctly. Inspect body of nozzle. Ensure the body is in good condition and that the valve stem is clean and free of fuel. Inspect the nozzle to hose connection and ensure it is clean and free of fuel.
Monthly - Dispenser nozzle handles shall be inspected for an expiration date established by the manufacturer. Nozzles must be replaced before the indicated expiration date.Partial System OOS
1145MOGAS Tank / SSTAMOGAS Tank / SSTADispenser SumpsDispenser 3WayneNot LabeledNot LabeledXXX7-13Inspect sump pipe transition fittings for tears, cracks, or other signs of deterioration. Test sumps and ensure they are liquid tight by using vacuum, pressure, or liquid testing in accordance with 40 CFR 280, Section 43.Monthly - Inspect for signs of water, fuel, trash, and debris inside sumps. Remove and properly dispose of collected water, fuel, trash, and debris. Visually inspect penetration fittings. If fuel or water is detected investigate the source and repair.Partial System OOS
1145MOGAS Tank / SSTAMOGAS Tank / SSTADispenser SumpsDispenser 4WayneNot LabeledNot LabeledXXX7-13Inspect sump pipe transition fittings for tears, cracks, or other signs of deterioration. Test sumps and ensure they are liquid tight by using vacuum, pressure, or liquid testing in accordance with 40 CFR 280, Section 43.Monthly - Inspect for signs of water, fuel, trash, and debris inside sumps. Remove and properly dispose of collected water, fuel, trash, and debris. Visually inspect penetration fittings. If fuel or water is detected investigate the source and repair.Partial System OOS
1146Diesel Tank / SSTADiesel Tank / SSTADispenser SumpsDispenser 2WayneNot LabeledNot LabeledXXX7-13Inspect sump pipe transition fittings for tears, cracks, or other signs of deterioration. Test sumps and ensure they are liquid tight by using vacuum, pressure, or liquid testing in accordance with 40 CFR 280, Section 43.Monthly - Inspect for signs of water, fuel, trash, and debris inside sumps. Remove and properly dispose of collected water, fuel, trash, and debris. Visually inspect penetration fittings. If fuel or water is detected investigate the source and repair.Partial System OOS
1146Diesel Tank / SSTADiesel Tank / SSTADispenser SumpsDispenser 1WayneNot LabeledNot LabeledXXX7-13Inspect sump pipe transition fittings for tears, cracks, or other signs of deterioration. Test sumps and ensure they are liquid tight by using vacuum, pressure, or liquid testing in accordance with 40 CFR 280, Section 43.Monthly - Inspect for signs of water, fuel, trash, and debris inside sumps. Remove and properly dispose of collected water, fuel, trash, and debris. Visually inspect penetration fittings. If fuel or water is detected investigate the source and repair.Partial System OOS
1146Diesel Tank / SSTAElectrical PanelsEFSO SystemsEmergency Shut-OffFederal SignalNot LabeledNot LabeledXX07-16Proper operation, box seals for integrity. Electrical connections for continuity.No Operator RequirementPartial System OOS
1146Diesel Tank / SSTADiesel Tank / SSTAElectric MotorsDispenser 1Bluffton1111017470Not LegibleXXX9-1.7(1) Inadequate ventilation or air flow

(2) Unbalanced voltage or an overload

(3) Bearing failure

(4) Insulation failure

(5) Shaft misalignmentNo Operator RequirementPartial System OOS
1146Diesel Tank / SSTADiesel Tank / SSTAElectric MotorsDispenser 2Bluffton1111017470Not LegibleXXX9-1.7(1) Inadequate ventilation or air flow

(2) Unbalanced voltage or an overload

(3) Bearing failure

(4) Insulation failure

(5) Shaft misalignmentNo Operator RequirementPartial System OOS
1145MOGAS Tank / SSTAMOGAS Tank / SSTAElectric MotorsDispenser 4Bluffton1111017470Not LegibleXXX9-1.7(1) Inadequate ventilation or air flow

(2) Unbalanced voltage or an overload

(3) Bearing failure

(4) Insulation failure

(5) Shaft misalignmentNo Operator RequirementPartial System OOS
1145MOGAS Tank / SSTAMOGAS Tank / SSTAElectric MotorsDispenser 3Bluffton1111017470Not LegibleXXX9-1.7(1) Inadequate ventilation or air flow

(2) Unbalanced voltage or an overload

(3) Bearing failure

(4) Insulation failure

(5) Shaft misalignmentNo Operator RequirementPartial System OOS
35011Refueler Parking YardRefueler Parking YardEmergency Eyewash/ShowersRefueler ParkingHawsNot LabeledNot LabeledXXX11-3Weekly - Equipment installed within 10 seconds from the hazard and on the same plane as the hazard Pathway is clear of obstructions Plumbed equipment activated to ensure compliant operation and to clear any sediment Self-contained equipment checked to determine if the flushing fluid needs to be changed or supplemented Equipment free of broken or missing parts Equipment protected against freezing User protected from scalding waterNo Operator/equipment RequirementsNo Mission Impact
1250Fuels Management BuildingFuels Management BuildingEmergency Eyewash/ShowersEmergency ShowerBradleyNot LabeledNot LabeledXXX11-3Weekly - Equipment installed within 10 seconds from the hazard and on the same plane as the hazard Pathway is clear of obstructions Plumbed equipment activated to ensure compliant operation and to clear any sediment Self-contained equipment checked to determine if the flushing fluid needs to be changed or supplemented Equipment free of broken or missing parts Equipment protected against freezing User protected from scalding waterNo Operator/equipment RequirementsNo Mission Impact
1145MOGAS Tank / SSTAMOGAS Tank / SSTAEmergency Shutoff ValvesDispenser 3 MOGAS Tank TopNot accessibleNo Fall Protection2.0 in.00X7-12Inspect fusible link and ensure it is not obstructed. Ensure valve body is clean and free of fuel. Inspect mechanical links of the valve for correct operation. Conduct test of valve to ensure it operates correctly.Monthly - Inspect stabilizer bar to ensure that it is securely mounted below the base of the dispenser. Inspect the mounting bolts that secure the emergency shutoff valve to the stabilizer bar. Inspect fusible link and ensure it is not obstructed. Ensure valve body is clean and free of fuel.Partial System OOS
1145MOGAS Tank / SSTAMOGAS Tank / SSTAEmergency Shutoff ValvesDispenser 4 MOGAS Tank TopNot accessibleNo Fall Protection2.0 in.00X7-12Inspect fusible link and ensure it is not obstructed. Ensure valve body is clean and free of fuel. Inspect mechanical links of the valve for correct operation. Conduct test of valve to ensure it operates correctly.Monthly - Inspect stabilizer bar to ensure that it is securely mounted below the base of the dispenser. Inspect the mounting bolts that secure the emergency shutoff valve to the stabilizer bar. Inspect fusible link and ensure it is not obstructed. Ensure valve body is clean and free of fuel.Partial System OOS
1146Diesel Tank / SSTADiesel Tank / SSTAEmergency Shutoff ValvesDispenser 1 / Top of TankNot accessibleNo Fall Protection2.0 in.00X7-12Inspect fusible link and ensure it is not obstructed. Ensure valve body is clean and free of fuel. Inspect mechanical links of the valve for correct operation. Conduct test of valve to ensure it operates correctly.Monthly - Inspect stabilizer bar to ensure that it is securely mounted below the base of the dispenser. Inspect the mounting bolts that secure the emergency shutoff valve to the stabilizer bar. Inspect fusible link and ensure it is not obstructed. Ensure valve body is clean and free of fuel.Partial System OOS
1146Diesel Tank / SSTADiesel Tank / SSTAEmergency Shutoff ValvesDispenser 2 / Top of TankNot accessibleNo Fall Protection2.0 in.00X7-12Inspect fusible link and ensure it is not obstructed. Ensure valve body is clean and free of fuel. Inspect mechanical links of the valve for correct operation. Conduct test of valve to ensure it operates correctly.Monthly - Inspect stabilizer bar to ensure that it is securely mounted below the base of the dispenser. Inspect the mounting bolts that secure the emergency shutoff valve to the stabilizer bar. Inspect fusible link and ensure it is not obstructed. Ensure valve body is clean and free of fuel.Partial System OOS
1145MOGAS Tank / SSTAMOGAS Tank / SSTAEmergency VentsMOGAS Tank TopMorrison BrothersFIg 244Not Legible00X8-9.4No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
1146Diesel Tank / SSTADiesel Tank / SSTAEmergency VentsDiesel TankMorrison BrothersFIg 244Not Legible00X8-9.4No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
1146Diesel Tank / SSTAElectrical PanelsExternally Mounted Level AlarmsHigh Level AlarmsVeeder-Root790091-001Not Labled0008-9.9.1Lift the manual test lever of internally mounted float valve (if equipped). Ensure that the HLSO closes when the float of the float valve is raised.No Operator RequirementPartial System OOS
1145MOGAS Tank / SSTAMOGAS Tank / SSTAFill PortsMOGAS OffloadOPW523Not LabledXXX8-9.12Ensure fill port covers are installed and are not damaged or broken. Ensure fill port covers are identified by fuel type and are installed on the correct tank. Visually inspect the fill port spill bucket to ensure there are no cracks, budges, or holes.Daily - Ensure fill port covers are installed and are not damaged or broken. Ensure fill port covers are identified by fuel type and are installed on the correct tank. Visually inspect the fill port spill bucket to ensure there are no cracks, budges, or holes. Ensure the spill bucket is clean of dirt, trash, water, and fuel.Partial System OOS
1146Diesel Tank / SSTADiesel Tank / SSTAFill PortsDiesel TankDover CorpNot LabeledNot LabledXXX8-9.12Ensure fill port covers are installed and are not damaged or broken. Ensure fill port covers are identified by fuel type and are installed on the correct tank. Visually inspect the fill port spill bucket to ensure there are no cracks, budges, or holes.Daily - Ensure fill port covers are installed and are not damaged or broken. Ensure fill port covers are identified by fuel type and are installed on the correct tank. Visually inspect the fill port spill bucket to ensure there are no cracks, budges, or holes. Ensure the spill bucket is clean of dirt, trash, water, and fuel.Partial System OOS
35011Refueler Parking YardRefueler Parking YardFuel Truck Containment AreasRefueler ParkingN/AN/AN/AXXX11-1.1No Manufacturer Requirements AvailableMonthly - Remove debris from around security fence. Inspect fence grounding points. Ensure connections are not loose or damage.No Mission Impact
35005Vehicle Parking AreaVehicle Parking AreaFuel Truck Containment AreasVehicle Parking YardN/AN/AN/AXXX11-1.1No Manufacturer Requirements AvailableMonthly - Remove debris from around security fence. Inspect fence grounding points. Ensure connections are not loose or damage.No Mission Impact
25020SSTA Catch BasinSSTA Catch BasinGate ValvesCatch Basin DrainMueller12566.0 in.XX06-6.2.3Operate from fully open to fully closed . Conduct Tightness test as required for application.No Operator RequirementPartial System OOS
1145MOGAS Tank / SSTAMOGAS Tank / SSTAHose RetrieverDispenser 4ZeppiniZS4Not Labeled0007-6No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
1146Diesel Tank / SSTADiesel Tank / SSTAHose RetrieverDispenser 2ZeppiniZS4Not Labeled0007-6No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
1146Diesel Tank / SSTADiesel Tank / SSTAHose RetrieverDispenser 1ZeppiniZS4Not Labeled0007-6No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
1145MOGAS Tank / SSTAMOGAS Tank / SSTAHose RetrieverDispenser 3ZeppiniZS4Not Labeled0007-6No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
35011Refueler Parking YardRefueler Parking YardLightingRefueler ParkingNot LabeledNot LabeledNot LabeledXXX9-1.8No Manufacturer Requirements AvailableNo Operator RequirementNo Mission Impact11 light Poles
1145MOGAS Tank / SSTAMOGAS Tank / SSTALightingMOGAS DispensersNot LabeledNot LabeledNot LabeledXXX9-1.8No Manufacturer Requirements AvailableNo Operator RequirementNo Mission Impact
1146Diesel Tank / SSTADiesel Tank / SSTALightingDiesel DispensersNot LabeledNot LabeledNot LabeledXXX9-1.8No Manufacturer Requirements AvailableNo Operator RequirementNo Mission Impact
15008Oil Water SeparatorOil Water SeparatorOil/Water SeparatorsRefueler Parking YardEnquipNot LabeledNot LabeledXXX11-5No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
1146Diesel Tank / SSTAElectrical PanelsPanelboardsPanel BoardsNot LabeledNot LabeledNot LabeledXXX9-1.5No Manufacturer Requirements AvailableQuarterly - Verify that there are no physical obstructions blocking access to the panelboard. Remove physical obstructions.Partial System OOS
1250Fuels Management BuildingFuels Management BuildingPumphouse/Filter BuildingsFuels Management BuidingN/AN/AN/AXXX11-2.1No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
25020SSTA Catch BasinSSTA Catch BasinRemote Spill ContainmentSSTA Catch BasinN/AN/AN/AXXX11-1.2No Manufacturer Requirements AvailableAnnually - Secondary containment systems degrade and will collect debris which can clog drainage inlets or prevent drain valves from sealing properly. Test drain valves for leakage through the valve.Partial System OOS
1145MOGAS Tank / SSTAMOGAS Tank / SSTASelf-Contained Dispenser PumpsDispenser 3WayneW710480181-1 LPM - 72 LPMXX07-15.2No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission ImpactTwo pumps but one not used.
1145MOGAS Tank / SSTAMOGAS Tank / SSTASelf-Contained Dispenser PumpsDispenser 4WayneW710480181-1 LPM - 72 LPMXX07-15.2No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
1146Diesel Tank / SSTADiesel Tank / SSTASelf-Contained Dispenser PumpsDispenser 2WayneW710480181-1 LPM - 72 LPMXX07-15.2No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
1146Diesel Tank / SSTADiesel Tank / SSTASelf-Contained Dispenser PumpsDispenser 1WayneW710480181-1 LPM - 72 LPMXX07-15.2No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
1145MOGAS Tank / SSTAMOGAS Tank / SSTASight Flow IndicatorsMOGAS OffloadVisi FlowE-78-D1Faded0006-12.3Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Partial System OOS
1146Diesel Tank / SSTADiesel Tank / SSTASight Flow IndicatorsDiesel OffloadVisi-FlowE-78-D1Faded0006-12.3Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Daily or at each use - Verify there are no leaks around pipe connection fittings and glass seals. Also check glass for indications of cracks.Partial System OOS
35011Refueler Parking YardRefueler Parking YardSignage and MarkingsRefueler Parking FenceN/AN/AN/A00X2-7No Manufacturer Requirements AvailableMonthly - Check permanent signs and markings for adequacy and readability. Repair or replace deteriorated or illegible signs and markings.No Mission Impact
1145MOGAS Tank / SSTAMOGAS Tank / SSTASignage and MarkingsMOGAS Tank and PipingN/AN/AN/A00X2-7No Manufacturer Requirements AvailableMonthly - Check permanent signs and markings for adequacy and readability. Repair or replace deteriorated or illegible signs and markings.No Mission Impact
1146Diesel Tank / SSTADiesel Tank / SSTASignage and MarkingsDiesel TankN/AN/AN/A00X2-7No Manufacturer Requirements AvailableMonthly - Check permanent signs and markings for adequacy and readability. Repair or replace deteriorated or illegible signs and markings.No Mission Impact
1145MOGAS Tank / SSTAMOGAS Tank / SSTAStatic Grounding SystemsMOGAS / Tank Foot Offload SideN/AN/AN/AXXX9-1.6.2Measure the ground resistance with an instrument designed specifically to measure and document earth/ground resistance, soil resistivity, and current flow. Conduct the test by using the fall-of-potential method as described in the Institute of Electronic and Electrical Engineers (IEEE) Standard 81.If fall-of-potential tests cannot be performed, it is acceptable to measure resistance at each accessible ground rod using a clamp-on ground resistance tester. Provide the Engineer with written, certified test results for each testing location.No Operator RequirementPartial System OOS
1145MOGAS Tank / SSTAMOGAS Tank / SSTAStatic Grounding SystemsMOGAS Tank Foot / EastN/AN/AN/AXXX9-1.6.2Measure the ground resistance with an instrument designed specifically to measure and document earth/ground resistance, soil resistivity, and current flow. Conduct the test by using the fall-of-potential method as described in the Institute of Electronic and Electrical Engineers (IEEE) Standard 81.If fall-of-potential tests cannot be performed, it is acceptable to measure resistance at each accessible ground rod using a clamp-on ground resistance tester. Provide the Engineer with written, certified test results for each testing location.No Operator RequirementPartial System OOS
1146Diesel Tank / SSTAElectrical PanelsStatic Grounding SystemsPanelN/AN/AN/AXXX9-1.6.2Measure the ground resistance with an instrument designed specifically to measure and document earth/ground resistance, soil resistivity, and current flow. Conduct the test by using the fall-of-potential method as described in the Institute of Electronic and Electrical Engineers (IEEE) Standard 81.If fall-of-potential tests cannot be performed, it is acceptable to measure resistance at each accessible ground rod using a clamp-on ground resistance tester. Provide the Engineer with written, certified test results for each testing location.No Operator RequirementPartial System OOS
1146Diesel Tank / SSTADiesel Tank / SSTAStatic Grounding SystemsDiesel Tank Foot / EastN/AN/AN/AXXX9-1.6.2Measure the ground resistance with an instrument designed specifically to measure and document earth/ground resistance, soil resistivity, and current flow. Conduct the test by using the fall-of-potential method as described in the Institute of Electronic and Electrical Engineers (IEEE) Standard 81.If fall-of-potential tests cannot be performed, it is acceptable to measure resistance at each accessible ground rod using a clamp-on ground resistance tester. Provide the Engineer with written, certified test results for each testing location.No Operator RequirementPartial System OOS
1146Diesel Tank / SSTADiesel Tank / SSTAStatic Grounding SystemsDiesel Tank Foot /Offload SideN/AN/AN/AXXX9-1.6.2Measure the ground resistance with an instrument designed specifically to measure and document earth/ground resistance, soil resistivity, and current flow. Conduct the test by using the fall-of-potential method as described in the Institute of Electronic and Electrical Engineers (IEEE) Standard 81.If fall-of-potential tests cannot be performed, it is acceptable to measure resistance at each accessible ground rod using a clamp-on ground resistance tester. Provide the Engineer with written, certified test results for each testing location.No Operator RequirementPartial System OOS
1146Diesel Tank / SSTADiesel Tank / SSTAStatic Grounding SystemsTank Grounds #2N/AN/AN/AXXX9-1.6.2Measure the ground resistance with an instrument designed specifically to measure and document earth/ground resistance, soil resistivity, and current flow. Conduct the test by using the fall-of-potential method as described in the Institute of Electronic and Electrical Engineers (IEEE) Standard 81.If fall-of-potential tests cannot be performed, it is acceptable to measure resistance at each accessible ground rod using a clamp-on ground resistance tester. Provide the Engineer with written, certified test results for each testing location.No Operator RequirementPartial System OOS
1146Diesel Tank / SSTADiesel Tank / SSTAStatic Grounding SystemsTank Grounds #1N/AN/AN/AXXX9-1.6.2Measure the ground resistance with an instrument designed specifically to measure and document earth/ground resistance, soil resistivity, and current flow. Conduct the test by using the fall-of-potential method as described in the Institute of Electronic and Electrical Engineers (IEEE) Standard 81.If fall-of-potential tests cannot be performed, it is acceptable to measure resistance at each accessible ground rod using a clamp-on ground resistance tester. Provide the Engineer with written, certified test results for each testing location.No Operator RequirementPartial System OOS
1145MOGAS Tank / SSTAMOGAS Tank / SSTASwivelsDispenser 4OPW24TTPS0.75 in.0007-5Inspect for expiration date. Inspect for loose connections and signs of damage.Daily - Inspect swivel for loose connections and signs of damage. Ensure swivel rotates easily and is clean and free of fuel.
Monthly - Inspect swivel for expiration date established by manufacturer. Swivels must be replaced before the indicated expiration date.Partial System OOS
1146Diesel Tank / SSTADiesel Tank / SSTASwivelsDispenser 2OPW24 ITPS1.0 in.0007-5Inspect for expiration date. Inspect for loose connections and signs of damage.Daily - Inspect swivel for loose connections and signs of damage. Ensure swivel rotates easily and is clean and free of fuel.
Monthly - Inspect swivel for expiration date established by manufacturer. Swivels must be replaced before the indicated expiration date.Partial System OOS
1146Diesel Tank / SSTADiesel Tank / SSTASwivelsDispenser 1OPW24 ITPS1.0 in.0007-5Inspect for expiration date. Inspect for loose connections and signs of damage.Daily - Inspect swivel for loose connections and signs of damage. Ensure swivel rotates easily and is clean and free of fuel.
Monthly - Inspect swivel for expiration date established by manufacturer. Swivels must be replaced before the indicated expiration date.Partial System OOS
1145MOGAS Tank / SSTAMOGAS Tank / SSTASwivelsDispenser 3OPW24TTPS0.75 in.0007-5Inspect for expiration date. Inspect for loose connections and signs of damage.Daily - Inspect swivel for loose connections and signs of damage. Ensure swivel rotates easily and is clean and free of fuel.
Monthly - Inspect swivel for expiration date established by manufacturer. Swivels must be replaced before the indicated expiration date.Partial System OOSRemove by 10-2022
1146Diesel Tank / SSTADiesel Tank / SSTATank Pressure/ Vacuum VentsDiesel TankDover CorpOPW Division10.0 In.00X8-9.3No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
1145MOGAS Tank / SSTAMOGAS Tank / SSTATank Pressure/ Vacuum VentsMOGAS TankOPW52310.0 In.00X8-9.3No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
1250Fuels Management BuildingFuels Management BuildingVentilation HoodsFume HoodLabconco47711N/AXXX11-4.1Daily visual inspection, check the fume hood for visible airflow blockage such as large items or containers near the slot opening. Other daily inspections include holding a tissue at the opening to observe inward airflow, maintaining clean surfaces inside the hood, and keeping the sash at an appropriate height when working and not working in the hood.No Operator RequirementNo Mission Impact
1146Diesel Tank / SSTADiesel Tank / SSTAVisual Leak DetectionDiesel Tank / Interstitial Monitor WellN/AN/AN/AXX08-9.13.4No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact
1145MOGAS Tank / SSTAMOGAS Tank / SSTAVisual Leak DetectionMOGAS / Interstitial Monitor WellN/AN/AN/AXX08-9.13.4No Additional Manufacturer RequirementsNo Operator/equipment RequirementsNo Mission Impact

&"Times New Roman,Bold"&14Facility Maintenance Plan

FMP v2.2 2

Instructions:

1. Input all data as indicated on the sheet.

2. Additional documents referred to in the Special Considerations column shall be included as an appendix to this FMP.

3. The contractor shall generate a Component Unique Identifier (CUID) for each component utilizing the Component Acronym Sheet within this Work Book. The unique identifier must use the following:

Three letter Site Code - Facility # - Component Acronym - Sequential number Example: AAD-00063A-RCVL-0001

If component acronym is not listed, the contractor shall request an acronym be established through the HNC Project Manager and Project Engineer via email. Contractors may utilize other means of tracking/labeling assets such as QR codes in addition to the required CUID however, tracking/labeling must correlate with the CUID. This CUID shall be the standard for all DLA capitalized equipment. Base Asset ID if used by site shall be cross referenced with CUID appropriately.

4. Utilize the UFC Section Reference Work Category as noted on the Component Acronym Sheet.

5. Enter any applicable manufacturer requirements not stated in the UFC. References are acceptable with attachments.

6. Enter any applicable operator support or government owned equipment required to complete the RM task.

7. Enter impact on system availability by performing the RM task. This could include shutdown, lockout, or similar impacts.

8. Enter contract information for any other contract, contractor, or government personnel performing the…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .