The document provides standardized sketches and installation requirements for four primary electrical components: arc flash warning labels, slotted channel rack systems for panelboard mounting, roof deck conduit and box installations, and electrical device box mounting details. Arc flash warning labels must be self-adhesive vinyl, minimum 2" x 3" for indoor equipment and 3" x 4.5" for outdoor equipment, positioned visibly on panelboards, disconnects, starters, HVAC control panels, and lighting control panels. Slotted channel rack systems require steel support anchored to floor and wall framing with bolted connections, 1/2" clear slip joints for structural deflection, and additional vertical channels every 20 inches for wider installations. Roof deck installations mandate minimum 2-inch clearance between roof decking and conduits, boxes, and fixtures using slotted channel support spanning trusses and beam clamps. Electrical device box mounting uses telescoping rigid box supports located per plan specifications at office desks, door frames, and similar locations, with mounting heights requiring verification from the contracting officer. All specifications reference compliance with NEC standards and include provisions for ground rods, plates, and grounding details. A downloadable Windows Metafile template is available on the Whole Building Design Guide website for label creation.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AF-1APRIL 2015
GENERAL ARC FLASH WARNING LABEL
SKETCH DATE STYLE
NOTES:
1. PROVIDE SELF-ADHESIVE VINYL LABEL TO AFFIX TO ELECTRICAL EQUIPMENT TO
WARN OF ARC FLASH HAZARDS.
2. THE LABEL FORMAT AND TEXT SHALL BE IN ACCORDANCE WITH THE FIGURE.
3. THE LABEL SHALL BE LOCATED ON THE EQUIPMENT TO BE CLEARLY VISIBLE TO
QUALIFIED PERSONS BEFORE EXAMINATION, ADJUSTMENT, SERVICING, OR
MAINTENANCE OF THE EQUIPMENT.
4. THE SIZE OF THE LABEL SHALL BE MINIMUM:
EQUIPMENT TYPE HEIGHT WIDTH
INDOOR 2" 3"
OUTDOOR 3" 4.5"
5. A DOWNLOADABLE WINDOWS METAFILE IS AVAILABLE ON THE WHOLE BUILDING
DESIGN GUIDE WEBSITE ( WWW.WDBG.ORG ) FOR USE IN A LABEL MAKING MACHINE.
A. THE FILE IS LOCATED ON THE "NAVFAC CADD DETAILS" PAGE. TO
NAVIGATE TO THIS LOCATION,
FOLLOW: HOME > DOCUMENTS & REFERENCES > CCB > CADD LIBRARY > NAVFAC CADD
RESOURCES > NAVFAC CADD DETAILS.
B. ALTERNATIVELY, TYPE IN THE FOLLOWING ADDRESS IN INTERNET EXPLORER:
HTTP://WWW.WBDG.ORG/CCB/BROWSE_CAT.PHP?C=232
WIDTH
HEIGHT
ARC FLASH WARNING LABEL DETAIL NOTE:
1. PROVIDE AT EACH PANELBOARD, DISCONNECT, STARTER, HVAC CONTROL PANEL, AND
LIGHTING CONTROL PANEL.
2' -0
M
A X
WIDTH OF
PANEL SLIP JOINT NOTES 3 & 7 (TYP)
SLOTTED CHANNEL SYSTEM
WALL/FLOOR ANCHORS (TYP)
SLOTTED CHANNEL RACK DETAIL NOTES:
SLOTTED CHANNEL ANGLE
ACCESSORIES (TYP)
DECK HEIGHT VARIES
REFER TO A-SERIES SHEETS
ELEVATION SECTION
BUILDING FRAMING
1. ANCHOR TO FLOOR AND WALL FRAMING.
2. PROVIDE BOLTED CONNECTIONS BETWEEN STRUT PIECES AND BETWEEN STRUT AND EQUIPMENT.
3. PROVIDE 1/2" CLEAR SLIP JOINT AT VERTICAL SLOTTED CHANNEL TO ALLOW FOR
STRUCTURAL DEFLECTION. SECURELY ANCHOR SLIP JOINT TO STRUCTURE.
4. DO NOT SECURE TOP OF VERTICAL SLOTTED CHANNEL TO CEILING OR WALL.
5. PROVIDE ADDITIONAL VERTICAL SLOTTED CHANNEL EVERY 20 INCHES FOR WIDER
PANELBOARDS OR CONTROL PANELS OR GROUPS OF PANELBOARDS OR CONTROL PANELS.
INCLUDE ADDITIONAL HORIZONTAL SLOTTED CHANNEL PER DETAIL.
6. PROVIDE STEEL SLOTTED CHANNEL SUPPORT FOR MOUNTING PANELBOARDS, CONTROL
PANELS, VFD'S, STARTERS AND DISCONNECT SWITCHES.
7. PROVIDE SLIP JOINT TIGHTEN BOLT THROUGH SLOTTED CHANNEL HAND TIGHT. PROVIDE
LOCKNUT AND DOUBLE NUT. TIGHTEN NUTS AGAINST EACH OTHER.
8. PROVIDE MANUFACTURER'S NON-METALLIC END CAPS AT CHANNEL ENDS WHERE EXPOSED.
JUMPERS
NOTE 5: GROUNDING
ELECTRODE CONDUCTOR
SUPPLY-SIDE
BONDING
TERMINAL
ISOLATED NEUTRAL
208/120V WYE
EQUIPMENT GROUNDING
CONDUCTOR
480V DELTA
TRANSFORMER
BONDING JUMPER
PROVIDE SYSTEM
CBA
DRY TYPE
MAIN BREAKER
PANEL
NOTE 3
GN
NEUTRAL
1. PROVIDE AT DRY-TYPE TRANSFORMER.
2. PROVIDE GROUNDING ELECTRODE SIZED PER NEC FOR TRANSFORMER SIZE AND SECONDARY PANELBOARD
MAIN CIRCUIT BREAKER.
3.
4. PROVIDE SECONDARY CONDUCTORS AS PER NEC FOR SEPARATELY DERIVED SYSTEM.
5. PROVIDE EMT WITH ANTI-CHOKE BONDING CONNECTORS AT EACH END OF GROUNDING ELECTRODE
CONDUIT IN ACCORDANCE WITH NEC 250.64(E)(1).
TRANSFORMER GROUNDING DETAIL NOTES:
TO NEAREST GROUNDING
ELECTRODE. REFER TO
DETAIL A4/EP502.
PROVIDE ENGRAVED INFORMATIONAL LABEL AT TRANSFORMER. INCLUDE SOURCE, TRANSFORMER
DESIGNATION, LOAD SERVED, VOLTAGE, AND KVA RATING. PROVIDE ENGRAVED INFORMATIONAL LABEL AT
GROUNDING ELECTRODE CONNECTION LOCATION. COORDINATE WITH CONTRACTING OFFICER.
1. PROVIDE SUPPORT TO MAINTAIN MIN OF 2 INCHES OF CLEARANCE BETWEEN THE
BOTTOM OF ROOF DECK AND THE TOP OF CONDUITS, BOXES, FIXTURES, AND
DEVICES TO AVOID DAMAGE FROM ROOFING SCREWS.
2. PROVIDE SLOTTED CHANNEL SUPPORT TO SPAN ACROSS TRUSSES.
3. COMPLY WITH NEC 300.4(E). PROVIDE AT LEAST 2-INCH SPACING INSTEAD OF
NEC MINIMUM 1.5 INCHES.
4. PROVIDE BEAM CLAMPS AT TOP FLANGE OF BEAM OR TOP CHORD OF ROOF
JOISTS OR TRUSSES.
ROOF DECK INSTALLATION DETAIL NOTES
ROOF ASSEMBLY
JUNCTION BOX, TYPICAL
CONDUIT, TYPICAL
STEEL DECKING, WHERE EXIST
2" MIN
CLEARANCE
CONDUIT AND BOXES BELOW
3/8" ROD
BEAM CLAMPS (TYP) WHERE BEAMS EXIST
1. COMPLY WITH NEC, SPECIFICALLY NEC 250.50 AND 250.52.
2. PROVIDE THERMAL WELDED OR IRREVERSIBLE COMPRESSION CONNECTIONS.
3. MINIMUM CONDUCTOR SIZE TO GROUNDING ELECTRODES MUST BE #4/0 COPPER.
4. GROUND PLATE CONNECTION MUST BE UL LISTED, SUITABLE FOR DIRECT BURIAL, THERMAL WELD.
5. WATER PIPE CLAMPS MUST BE BRONZE, UL LISTED FOR WATER OR GAS PIPE SIZE AND INCLUDE LUG
WHICH IS UL LISTED FOR GROUNDING ELECTRODE CONDUCTOR SIZE.
6. PROVIDE ENGRAVED WARNING SIGN. INTENDED TEXT: "WARNING: GROUNDING SYSTEM CONNECTION - DO
NOT REMOVE".
7. PROVIDE GROUND WIRE WITHIN CONCRETE ENCASED DUCTBANK.
8. FIELD VERIFY AND PROVIDE CONNECTION TO EXISTING BUILDING GROUNDING SYSTEM.
9. SIZE IN ACCORDANCE WITH THE IMMEDIATE APPLICATION REQUIREMENTS AND WITH CONDISERATION FOR
FUTURE GROWTH.
10. PROVIDE AT EACH LOCATION INDICATED IN SHOP 111. PROVIDE A SEPARATE GROUND WIRE FROM EACH
GROUND BUS BACK TO THE SERVICE GROUND ("STAR PATTERN").
ELECTRIC SERVICE GROUNDING DETAIL NOTES
MAIN GROUND BUS, COPPER
MAIN SWITCHBOARD, MSB
METAL WATER PIPE
BUILDING STEEL
GROUND RODS /
PLATES
WATER ENTRANCE
FIRE PROTECTION MAIN
POWER SYSTEM
GROUNDING BAR (TYP)
NOTE 6 (TYP AT EACH BUS BAR)
NOTE 6
NOTE 6
NOTE 6
PBBSBBNOTE 7
BRIDGE CRANE STRUCTURE
(TYP 3 CRANES)
NOTE 8
IN ELEC 114
IN SHOP
111 (TYP)NOTE 9
NOTE 10
1. PROVIDE TELESCOPING RIGID BOX SUPPORT TO LOCATE DEVICES BOXES AT LOCATION INDICATED ON PLANS.
2. PROVIDE AT LOCATIONS WHERE TEMPERATURE SENSORS, POWER ,PHONE, COMMUNICATIONS, SECURITY, AND
DATA OUTLETS ARE SHOWN IN THE SAME AREA.
3. PROVIDE AT OFFICE DESKS, SYSTEMS FURNITURE, AND SIMILAR LOCATIONS.
4. PROVIDE TO LOCATE LIGHT SWITCHES, FIRE ALARM PULL STATIONS, RECEPTACLES, EMERGENCY SHUT DOWN
SWITCHES AND SIMILAR ITEMS ADJACENT TO DOOR FRAMES.
5. PROVIDE WHERE DEVICES ARE INDICATED AS BEING "CENTERED" WITH RESPECT TO OTHER BUILDINGI
FEATURES.
6. PROVIDE TO LOCATE DEVICES AS INDICATED ON ELEVATIONS. REFER TO AE SHEETS.
7. PROVIDE IN LOCATIONS WHERE FRAMING MEMBER LOCATIONS, SPACING OR QUANTITY IS NOT SUFFICIENT TO
LOCATE DEVICES OR GROUPS OF DEVICES AS INDICATED.
8. COORDINATE WITH FRAMING INSTALLER TO ADJUST WALL STUDS FOR CENTERING DEVICE BOXES. PROVIDE
ADDITIONAL FRAMING STUD AT LOCATIONS WHERE FRAMING SPACING IS ADJUSTED.
9. DEVICE BOXES TO BE BACK MOUNTED ON PLATE. DEVICE RAISED RINGS TO BE FRONT MOUNTED ON PLATE.
10. VERIFY MOUNTING HEIGHTS AT EACH LOCATION WITH CONTRACTING OFFICER.
ELECTRIC DEVICE BOX MOUNTING DETAIL NOTES:
FLOOR
ELEVATION
TYPICAL FRAMING MEMBER
TELESCOPING RIGID BOX
SUPPORT
NOTE 8
ET502
SATISFACTORY TO DATE
APPROVED
FOR COMMANDER NAVFAC
SEAL
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SHEET
NAVFAC DRAWING NO.
DESIGNER
DRAWN BY
CHECKED BY
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 14 SEP 2023
DESIGN MANAGER
PROJECT MANAGER
FEAD/PM&E
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
P O
R T
S M
O U
T H
N A
V A
L S
H
IP
Y A
R D
K
IT
T
E R
Y M
E
UNCLASSIFIED
UNCLASSIFIED
U N
C L
A S
S
IF
IE
D
ACTIVITY
1740579
T. CARLETON
L. LYONS
S. RUCINSKI
/1
/2
:1
:4
P
M
C U s e rs \b d a ig le \D o c u m e n ts
\2
.2
B
L D
G
E
L E
C -V b d a ig le
Q U
X G
.r v t
EP502
B R
E P
A
IR
S
E L E
C T
R
IC
A L P
O W
E R
D E
T A
IL
S
DCL
HRM
BPD
K
IT
T E
R Y
M
E P
O R
T S
M O
U T
H N
A V
A L S
H
IP
Y A
R D
R O
IC
C
-M E
E P
SCALE: NOT TO SCALE
B1
ARC FLASH LABEL
SCALE: NOT TO SCALE
C2
SLOTTED CHANNEL RACK DETAIL
SCALE: NOT TO SCALE
C4
TRANSFORMER GROUNDING DETAIL
SCALE: NOT TO SCALE
A1
CONDUIT AND BOXES BELOW ROOF DECK INSTALLATION DETAIL
EP501
SCALE: NOT TO SCALE
A4
ELECTRIC SERVICE GROUNDING DETAIL
EP102, EP502SCALE: NOT TO SCALE
A3
ELECTRICAL DEVICE BOX MOUNTING DETAIL
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
F
IN
A L
S U
B M
IS
S
IO
N
/0
1/
R
S H
A
M E
N D
M E
N T
/1
6/
R
S H
| Sheets |
| EP502 - ELECTRICAL POWER DETAILS |
File details come from the government source that posted it. Updated .