255_EP501_R1_AMENDMENT 009.pdf
PDF 393 KB Posted
- Solicitation number
- N6247026R0012
About this file
This document is an electrical one-line diagram and associated notes for Building 60 construction work. The diagram illustrates the electrical distribution system including switchboards, panelboards, transformers, and related equipment connections throughout multiple floors (first floor, mezzanine, and second floor) of the facility.
Key electrical components and requirements include: installation of a fire pump feeder with separate switchboard vertical section below the slab within a concrete encased ductbank, extending to the fire pump room; provision of a Shark 270 meter with associated current transformers mounted on existing steel slotted strut support; Category 6 cable in 1-inch RGS conduit between the meter and existing network switch WCO3004 (approximately 20 feet); connection of existing Duraline connection to a relocated exterior receptacle with ground fault protection; temporary power provision to Building 60 construction trailer via existing transformer (assuming 100A, 120/208V, 3-phase); reinstallation of salvaged exterior receptacle serving existing trailer 2; adjustment of current setting to 1,140A (.95X); provision of service entrance available fault current label; and provision of conduit and wire for generator controls, block heater, monitoring, and battery charger. The document references panelboard schedules (EP601-EP604), electrical site plan (ES101), and mechanical and plumbing equipment wiring schedules (EP503-EP504) for additional specifications. Two Contract Line Items (CLIN 004) address exterior receptacle relocation and reconnection tasks, with coordination required with the Contracting Officer on exact locations.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T1
FIRST FLOOR
250/3 250/3 70/3
MDP, 1200A, 120/208V, 3PH, 4W SWITCHBOARD 42K AIC
PANEL
ML2
INTERIOREXTERIOR
MEZZANINE
600/3 30/3
MSB, 1200A, 480V, 3PH, 3W, 100K AIC, SWITCHBOARDGRADE
1140AT
EXISTING LOAD CENTER 4
M
EXISTING LC4 VAULT AND
MANHOLE AC 801
SECOND FLOOR
PANEL
PH2
PANEL
PL9
T5
FIRE PUMP RM
GRADE
FIRE PUMP
CONTROLLER WITH
INTEGRAL ATS
FIRE PUMP
EXISTING TRAILER 2
EXIST 45KVA, 480V: 120/208V,
TRANSFORMER, PRIMARY AND
SECONDARY DISCONNECTS, AND
SECONDARY CONDUCTORS
SERVING EXISTING TRAILER 2
125KW, 480V, DIESEL
GENERATOR WITH SOUND
ATTENUATING, WEATHERPROOF
ENCLOSURE AND SUB BASE
FUEL TANK
PANEL
AH1
T3
PANEL
AL1
PANEL
PH1
T4
PANEL
PL7
PANEL
TPP2
1200AF
SPD
600/3
1140AT
1200AF
SPD
SPD
PANEL
PL10
PANEL
ML1
T2
PANEL
MH1
PANEL
PL1
PANEL
PL2
400/3
PANEL
PL3
250/3 250/3 125/3
PANEL
PL5
PANEL
PL4
PANEL
PL6
125/3 125/3 60/3
S P
A R
E
S P
A R
E
20/1 20/1
S P
A R
E
S P
A R
E
STS
200A
ELEVATOR
ANNEX
PANEL
FA2
PANEL
PL8
PANEL
FA1
PANEL
TPP1
S P
A R
E
S P
A R
E
S P
A R
E
60/3
CU-4
WP
100/3
EXIST TRAILER 1
T
100/3 225/3 125/3150/3150/3175/3
CR-1(B)
WP
CR-1(A)
WP
P-1BP-1A
30/3 50/3
WP
AHU-1
30/3 15/3 15/3
100/3 100/3100/3
225/3
24 [CLIN 004] 23 [CLIN 004]
100A
1 PHASE
37.5KVA
15 14 17 16 15 18
1000AT
1200AF
10 11
21 S P
A R
E
25 19
JJ
[CLIN 004]
MEZZANINE
SPD
J
RATED CHASE
SPD
SPD
SPD
SPD
SPD
SPD
(TYP)
480 - 208Y/120300
VOLTS
TRANSFORMER SCHEDULE
TAG
T1
KVA
T2
T3
T4
480 - 208Y/120
480 - 208Y/120
480 - 208Y/120
T5 480 - 208Y/120
EXISTING 3 #500, + GROUND3
CABLE
WIRING SCHEDULE
# CONDUIT
EXISTING1
3 #10, 1 #10G1 3/4"2
4 #12, 2 #10N, 2 #12G
2#8, 1#10G
3#4, 1#8G
1"
3/4"
1"C
16 4#1, 1#6G 1-1/2"C
17 3#1/0, 1#6G
18 4#1/0, 1#6G
19 4#6, 1#10G
110 4#1, 1#4G
111 4#4, 1#8G
112 4#250, 1#2G
113 3#1, 1#6G
1-1/2"C
1-1/2"C
1-1/4"C
1"C
1-1/2"C
2-1/2"C
1-1/2"C
114 4#250 1#4G 2-1/2"C
115 4#350, 1#2G
116 4#300, 1#3G
117 4#500, 1#3G 3"C
118 4#3/0, 1#2G 2"C
119 3#4/0, 1#4G 2"C
120 3#3/0, 1#6G 2"C
221 3#350, 1#1G 2-1/2"C
322 4#400, 1#3/0G 3"C
123 3#2, 1#8G 1-1/4"C
124 3#2/0, 1#4G 1-1/2"C
125 3#2/0, 1#1G 2"C
2-1/2"C
2-1/2"C
SATISFACTORY TO DATE
APPROVED
FOR COMMANDER NAVFAC
SEAL
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SHEET
NAVFAC DRAWING NO.
DESIGNER
DRAWN BY
CHECKED BY
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 14 SEP 2023
DESIGN MANAGER
PROJECT MANAGER
FEAD/PM&E
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
P O
R T
S M
O U
T H
N A
V A
L S
H
IP
Y A
R D
K
IT
T
E R
Y M
E
UNCLASSIFIED
UNCLASSIFIED
U N
C L
A S
S
IF
IE
D
ACTIVITY
1740579
T. CARLETON
L. LYONS
S. RUCINSKI
/1
/2
:4
:4
A
M
C U s e rs \b d a ig le \D o c u m e n ts
\2
.2
B
L D
G
E
L E
C -V b d a ig le
Q U
X G
.r v t
EP501
B R
E P
A
IR
S
O N
E -L
IN
E
D
IA
G R
A M
A N
D S
C H
E D
U L E
S
DCL
HRM
BPD
K
IT
T E
R Y
M
E P
O R
T S
M O
U T
H N
A V
A L S
H
IP
Y A
R D
R O
IC
C
-M E
E P
SCALE: NOT TO SCALE
B2
ONE-LINE DIAGRAM
1 INSTALL BELOW SLAB WITHIN CONCRETE ENCASED DUCTBANK. EXTEND FROM
BELOW SLAB TRENCH TO THE FIRE PUMP ROOM IN A RATED CHASE. REFER TO
SHEETS AE101, SB101, AND SB102.
PROVIDE SEPARATE SWITCHBOARD VERTICAL SECTION FOR THE FIRE PUMP FEEDER.
PROVIDE RED LABEL WITH WHITE CENTER CORE INDICATING, "FIRE PUMP FEEDER".
PROVIDE SHARK 270 METER AND ASSOCIATED CURRENT TRANSFORMERS. MOUNT ON
EXISTING STEEL SLOTTED STRUT SUPPORT WITHIN THE LOAD CENTER 4 ENCLOSURE.
COORDINATE EXACT LOCATION WITH THE CONTRACTING OFFICER. PROVIDE
CATEGORY 6 CABLE, IN 1" RGS CONDUIT, BETWEEN METER AND EXISTING NETWORK
SWITCH WCO3004. FOR BIDDING PURPOSES ASSUME 20' OF CONDUIT WITH WIRE.
[CLIN 004]: CONNECT EXISTING DURALINE CONNECTION TO RELOCATED EXTERIOR
RECEPTACLE.
PROVIDE GROUND FAULT PROTECTION.
SPLICE TO EXISTING CONDUCTORS. SEAL INTERIOR PORTION OF EXISTING
CONDUITS.
REFER TO TRANSFORMER GROUNDING DETAIL, C4/EP502.
PROVIDE BREAKER SIZED PER SPD MANUFACTURER'S RECOMMENDATION.
1. REFER TO SHEETS EP601-EP604 FOR PANELBOARD SCHEDULES.
2. REFER TO SHEET ES101 FOR ELECTRICAL SITE PLAN.
3. REFER TO SHEETS EP503 AND EP504 FOR MECHANICAL,
PLUMBING, AND MISCELLANEOUS EQUIPMENT WIRING
SCHEDULE.
EXISTING GE POWER BREAK THC1616SSH LOAD CENTER BREAKER
WITH RMS-9 MICROVERSA TRIP UNIT. CIRCUIT LC4-13. FRAME RATING
IS 1600A, SENSOR RATING IS 1200A.
EXISTING FEEDER BETWEEN LOAD CENTER 4 AND BUILDING 60.
GENERAL NOTES KEYNOTES
COORDINATE WITH THE FIRE ALARM TRADE FOR MONITORING OF THE
GENERATOR.
[CLIN 004]: REINSTALL SALVAGED EXTERIOR RECEPTACLE SERVING EXISTING
TRAILER 2. COORDINATE EXACT LOCATION WITH THE CONTRACTING OFFICER.
PROVIDE TEMPORARY POWER TO BUILDING 60 CONSTRUCTION TRAILER VIA
EXISTING TRANSFORMER. COORDINATE WITH THE CONTRACTING OFFICER. FOR
BIDDING PURPOSES ASSUME 100A, 120/208V, 3 PHASE.
[CLIN 004]: UTILIZE EXISTING TEMPORARY EQUIPMENT SERVING EXISTING
TRAILER 1. REFER TO SHEETS ED102, ES101, EP102, AND G-007 THRU G-009.
ADJUST CURRENT SETTING TO 1,140A (.95X).
PROVIDE SERVICE ENTRANCE AVAILABLE FAULT CURRENT LABEL. REFER TO
SHEET EP601 FOR ADDITIONAL INFORMATION.
PROVIDE JUNCTION BOX IN ACCORDANCE WITH NEC 695.6(H) AND (I).
PROVIDE CONDUIT AND WIRE FOR GENERATOR CONTROLS, BLOCK HEATER,
MONITORING, AND BATTERY CHARGER.
EXISTING KEYNOTES
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
F
IN
A L
S U
B M
IS
S
IO
N
/0
1/
R
S H
A
M E
N D
M E
N T
/1
6/
R
S H
| Sheets |
| EP501 - ONE-LINE DIAGRAM AND SCHEDULES |