This is a technical specification document for thrust restraint systems for utility piping, prepared by Herbert, Rowland & Grubic, Inc., for the Biosolids Project 011139.0465 owned by Ephrata Borough Authority in Pennsylvania. The specification establishes requirements for tied joint restraint systems on pressure pipelines, including mechanical joint restraint systems for ductile iron (DI) pipe with a 235 psi pressure rating. Restrained joints must be installed at each bend, tee, valve, and change in direction throughout the entire force main length, unless the fitting includes a concrete thrust block or integral thrust restraint. Approved manufacturers include Sigma ONE-LOK SLDE, JCM 610 Sur-Grip Restrainer, and Ebaa Iron 1100 Megalug, or approved equivalents. The specification requires a preinstallation meeting to be held minimum one week prior to commencing work, with detailed submittals including product data, shop drawings indicating restrained joint locations and piece numbers, manufacturer's certificates, installation instructions, and qualifications statements from the manufacturer and fabricator. The project involves general construction and electrical construction components, with bids due December 8, 2026 at 10:00 AM, and a pre-bid open house scheduled for November 18, 2026 from 8:00 AM to 10:00 AM at the facility.

The specification requires manufacturers and fabricators to have minimum three years of documented experience in producing and fabricating the specified products. Gland materials shall be either ductile iron complying with ASTM A536 Grade 65-45-12 with epoxy coating or carbon steel with fusion bonded epoxy coating per ANSI/AWWA C213. T-bolts and nuts must be high-strength, low-alloy steel complying with AWWA C111 or ASTM A449 with zinc-plated fluoropolymer coating, or 304/316 stainless steel. Installation shall comply with AWWA C600 and manufacturer's instructions, with joint restraint systems mechanically locked to prevent joint separation. Two coats of coal tar field-applied coating are required on all restraint systems unless components are already epoxy coated, fluoropolymer coated, or stainless steel. Materials must be stored in clean, dry locations protected from moisture and dust according to manufacturer instructions, and field measurements must be verified prior to fabrication with measurements indicated on shop drawings.

View the file

Other files

File Type Posted
26 08 00 - Electrical Field Acceptance Tests.pdf PDF
00 63 25 - Substitution Request Form (During Construction).pdf PDF
40 05 36 - Fiberglass-Reinforced Plastic Process Pipe.pdf PDF
00 01 10 - Table of Contents.pdf PDF
00 60 00 - Project Forms.pdf PDF
26 29 23 - VFDs .pdf PDF
00 73 43 - Wage Rate Requirements.pdf PDF
26 05 19 - Conductors.pdf PDF
01 57 28 - Temporary Flow Control.pdf PDF
00 65 19.19 - Consent of Surety to Final Payment.pdf PDF
05 53 00 - Metal Gratings (VPR).pdf PDF
02 41 19.13 - Selective Building Demolition (VPR).pdf PDF
01 29 00 - Payment Procedures.pdf PDF
00 43 13 - Bid Bond PENAL SUM Form.pdf PDF
00 61 13.16 - Payment Bond.pdf PDF
01 64 00 - Owner Furnished Products.pdf PDF
01 32 33 - Photographic Documentation.pdf PDF
31 25 00 - Erosion And Sedimentation Controls.pdf PDF
40 05 65.23 - Swing Check Valves.pdf PDF
01 74 19 - Construction Waste Management and Disposal.pdf PDF
05 50 00 - Metal Fabrications (VPR).pdf PDF
40 05 19 - Ductile Iron Process Pipe.pdf PDF
26 09 16 - Auxiliary Controls & Relays.pdf PDF
01 10 00 - Project Summary.pdf PDF
05 52 00 - Metal Railings (VPR).pdf PDF
26 24 19 - MCC.pdf PDF
26 05 53 - Electrical System Identification.pdf PDF
01 26 13 - Requests for Interpretation.pdf PDF
01 78 39 - Project Record Documents.pdf PDF
03 60 00 - Grouting (VPR).pdf PDF
01 61 00 - Product Requirements.pdf PDF
32 91 19 - Landscape Grading.pdf PDF
00 45 36 EEO Certificate.pdf PDF
00 31 00a Ephrata Boro Record Drawings.pdf PDF
01 31 19 - Project Meetings.pdf PDF
00 65 19.16 - Affidavit of Release of Liens.pdf PDF
00 63 49 - Work Change Directive Form.pdf PDF
26 27 16 - Control Panels & Enclosures.pdf PDF
26 05 26 - Grounding.pdf PDF
00 65 19.23 - Notice of Acceptability of Work.pdf PDF
00 01 01 - LA Cover.pdf PDF
26 29 13 - Contactors and Motor Starting Equipment.pdf PDF
32 92 19 - Seeding.pdf PDF
00 45 33 Certification of Non-Segregated Facilities and Non-Employment of Illegal Alien Labor.pdf PDF
00 01 07 - Seal Page.pdf PDF
01 73 00 - Execution Requirements.pdf PDF
40 05 53 - Identification For Process Piping.pdf PDF
01 40 00 - Quality Requirements.pdf PDF
05 31 23 - Steel Roof Decking (VPR).pdf PDF
00 52 00b - Agmnt btw Own and Cntr for Const Con Stip Price - Electrical Construction.pdf PDF
Show 40 more

Latest 50 of 125 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

33 05 09.33 - THRUST RESTRAINT FOR UTILITY PIPING

Herbert, Rowland & Grubic, Inc. 33 05 09.33 - 1 011139.0465

SECTION 33 05 09.33 - THRUST RESTRAINT FOR UTILITY PIPING

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Tied joint restraint system.

B. Related Requirements:

1. Section 09 91 00 - Painting.

2. Section 31 23 16.13 - Trenching.

3. Section 33 31 23 - Sanitary Sewerage Force Main Piping.

1.2 REFERENCE STANDARDS

A. American Water Works Association:

1. AWWA C600 - Installation of Ductile-Iron Water Mains and Their Appurtenances.

B. ASME International:

1. ASME B1.1 - Unified Inch Screw Threads, UN and UNR Thread Form.

C. ASTM International:

1. ASTM A36/A36M - Standard Specification for Carbon Structural Steel.

2. ASTM A123/A123M - Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products.

3. ASTM A153/A153M - Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware.

4. ASTM A307 - Standard Specification for Carbon Steel Bolts, Studs, and Threaded Rod 60 000 PSI Tensile Strength.

5. ASTM A325 - Standard Specification for Structural Bolts, Steel, Heat Treated, 120/105 ksi Minimum Tensile Strength.

6. ASTM A563 - Standard Specification for Carbon and Alloy Steel Nuts.

7. ASTM A588/A588M - Standard Specification for High-Strength Low-Alloy Structural Steel, up to 50 ksi Minimum Yield Point, with Atmospheric Corrosion Resistance.

8. ASTM B633 - Standard Specification for Electrodeposited Coatings of Zinc on Iron and Steel.

9. ASTM F436 - Standard Specification for Hardened Steel Washers.

1.3 COORDINATION

A. Section 01 31 13 – Project Coordination: Requirements for coordination.

B. Coordinate Work of this Section with installation of fittings and joints that require restraint.

Herbert, Rowland & Grubic, Inc. 33 05 09.33 - 2 011139.0465

1.4 PREINSTALLATION MEETINGS

A. Section 01 31 19 – Project Meetings: Requirements for preinstallation meeting.

B. Convene minimum one week prior to commencing Work of this Section.

1.5 SUBMITTALS

A. Section 01 33 00 - Submittal Procedures: Requirements for submittals.

B. Product Data: Submit manufacturer catalog information for restrained joint details and installation instructions.

C. Shop Drawings:

1. Indicate restrained joint details and materials being used.

2. Submit layout drawings showing piece numbers and locations.

3. Indicate restrained joint locations.

D. Manufacturer's Certificate: Certify that products meet or exceed specified requirements.

E. Manufacturer Instructions: Submit detailed instructions on installation requirements, including storage and handling procedures.

F. Qualifications Statement:

1. Submit qualifications for manufacturer and fabricator.

1.6 CLOSEOUT SUBMITTALS

A. Section 01 77 00 - Execution and Closeout Requirements: Requirements for submittals.

B. Project Record Documents: Record actual locations of joint restraints.

1.7 QUALIFICATIONS

A. Manufacturer: Company specializing in manufacturing products specified in this Section with minimum three years' documented experience.

B. Fabricator: Company specializing in fabricating products specified in this Section with minimum three years' documented experience.

1.8 DELIVERY, STORAGE, AND HANDLING

A. Section 01 61 00 - Product Requirements: Requirements for transporting, handling, storing, and protecting products.

B. Inspection: Accept materials on Site in manufacturer's original packaging and inspect for damage.

Herbert, Rowland & Grubic, Inc. 33 05 09.33 - 3 011139.0465

C. Store materials according to manufacturer instructions.

D. Protection:

1. Protect materials from moisture and dust by storing in clean, dry location remote from construction operations areas.

2. Provide additional protection according to manufacturer instructions.

1.9 EXISTING CONDITIONS

A. Field Measurements:

1. Verify field measurements prior to fabrication.

2. Indicate field measurements on Shop Drawings.

PART 2 - PRODUCTS

2.1 PERFORMANCE AND DESIGN CRITERIA

A. Provide pressure pipeline with restrained joints at each bend, tee, valve, and change in direction, unless fitting is shown with a concrete thrust block on the Drawing or integral thrust restraint is provided by fittings or couplings. Entire length of force main shall be restrained.

2.2 MECHANICAL JOINT RESTRAINT SYSTEMS – DI PIPE

A. Manufacturers

1. Sigma – ONE-LOK SLDE.

2. JCM – 610 Sur-Grip Restrainer.

3. Ebaa Iron – 1100 Megalug.

4. Or approved Equal.

B. Pressure Rating: 235 psi.

C. Gland:

1. Material:

a. Ductile Iron, comply with ASTM A536, Grade 65-45-12, epoxy coated.

b. Carbon Steel with fusion bonded epoxy coating per ANSI/AWWA C213.

D. T-Bolts and Nuts:

1. Material:

a. High Strength, Low Alloy Steel, comply with AWWA C111 or ASTM A449, zinc-plated with fluoropolymer coating.

b. 304/316 Stainless Steel.

2.3 FIELD APPLIED COATING

A. Material:

1. Coal Tar: See Section 09 91 00 – Painting.

Herbert, Rowland & Grubic, Inc. 33 05 09.33 - 4 011139.0465

PART 3 - EXECUTION

3.1 EXAMINATION

A. Section 01 73 00 - Execution Requirements: Requirements for installation examination.

B. Verify that pipe and fittings are ready to receive Work.

C. Field measure and verify conditions for installation of Work.

3.2 PREPARATION

A. Section 01 73 00 - Execution Requirements: Requirements for installation preparation.

B. Clean surfaces of pipe and fittings that are to receive tied joint restraint systems.

3.3 INSTALLATION

A. According to AWWA C600 and manufacturer’s instructions.

B. Install joint restraint system such that joints are mechanically locked together to prevent joint separation.

C. Apply two (2) coats of field applied coating to all restraint systems:

1. If restraint system component is epoxy coated, fluoropolymer coated, or stainless steel, field applied coating is not required.

3.4 TOLERANCES

A. Section 01 40 00 - Quality Requirements: Requirements for tolerances.

END OF SECTION

PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Tied joint restraint system.
B. Related Requirements:
1. Section 09 91 00 - Painting.
2. Section 31 23 16.13 - Trenching.
3. Section 33 31 23 - Sanitary Sewerage Force Main Piping.
1.2 REFERENCE STANDARDS
A. American Water Works Association:
1. AWWA C600 - Installation of Ductile-Iron Water Mains and Their Appurtenances.
B. ASME International:
1. ASME B1.1 - Unified Inch Screw Threads, UN and UNR Thread Form.
C. ASTM International:
1. ASTM A36/A36M - Standard Specification for Carbon Structural Steel.
2. ASTM A123/A123M - Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products.
3. ASTM A153/A153M - Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware.
4. ASTM A307 - Standard Specification for Carbon Steel Bolts, Studs, and Threaded Rod 60 000 PSI Tensile Strength.
5. ASTM A325 - Standard Specification for Structural Bolts, Steel, Heat Treated, 120/105 ksi Minimum Tensile Strength.
6. ASTM A563 - Standard Specification for Carbon and Alloy Steel Nuts.
7. ASTM A588/A588M - Standard Specification for High-Strength Low-Alloy Structural Steel, up to 50 ksi Minimum Yield Point, with Atmospheric Corrosion Resistance.
8. ASTM B633 - Standard Specification for Electrodeposited Coatings of Zinc on Iron and Steel.
9. ASTM F436 - Standard Specification for Hardened Steel Washers.
1.3 COORDINATION
A. Section 01 31 13 – Project Coordination: Requirements for coordination.
B. Coordinate Work of this Section with installation of fittings and joints that require restraint.
1.4 PREINSTALLATION MEETINGS
A. Section 01 31 19 – Project Meetings: Requirements for preinstallation meeting.
B. Convene minimum one week prior to commencing Work of this Section.
1.5 SUBMITTALS
A. Section 01 33 00 - Submittal Procedures: Requirements for submittals.
B. Product Data: Submit manufacturer catalog information for restrained joint details and installation instructions.
C. Shop Drawings:
1. Indicate restrained joint details and materials being used.
2. Submit layout drawings showing piece numbers and locations.
3. Indicate restrained joint locations.
D. Manufacturer's Certificate: Certify that products meet or exceed specified requirements.
E. Manufacturer Instructions: Submit detailed instructions on installation requirements, including storage and handling procedures.
F. Qualifications Statement:
1. Submit qualifications for manufacturer and fabricator.
1.6 CLOSEOUT SUBMITTALS
A. Section 01 77 00 - Execution and Closeout Requirements: Requirements for submittals.
B. Project Record Documents: Record actual locations of joint restraints.
1.7 QUALIFICATIONS
A. Manufacturer: Company specializing in manufacturing products specified in this Section with minimum three years' documented experience.
B. Fabricator: Company specializing in fabricating products specified in this Section with minimum three years' documented experience.
1.8 DELIVERY, STORAGE, AND HANDLING
A. Section 01 61 00 - Product Requirements: Requirements for transporting, handling, storing, and protecting products.
B. Inspection: Accept materials on Site in manufacturer's original packaging and inspect for damage.
C. Store materials according to manufacturer instructions.
D. Protection:
1. Protect materials from moisture and dust by storing in clean, dry location remote from construction operations areas.
2. Provide additional protection according to manufacturer instructions.
1.9 EXISTING CONDITIONS
A. Field Measurements:
1. Verify field measurements prior to fabrication.
2. Indicate field measurements on Shop Drawings.
PART 2 - PRODUCTS
2.1 PERFORMANCE AND DESIGN CRITERIA
A. Provide pressure pipeline with restrained joints at each bend, tee, valve, and change in direction, unless fitting is shown with a concrete thrust block on the Drawing or integral thrust restraint is provided by fittings or couplings. Entire length...
2.2 MECHANICAL JOINT RESTRAINT SYSTEMS – DI PIPE
A. Manufacturers
1. Sigma – ONE-LOK SLDE.
2. JCM – 610 Sur-Grip Restrainer.
3. Ebaa Iron – 1100 Megalug.
4. Or approved Equal.
B. Pressure Rating: 235 psi.
C. Gland:
1. Material:
a. Ductile Iron, comply with ASTM A536, Grade 65-45-12, epoxy coated.
b. Carbon Steel with fusion bonded epoxy coating per ANSI/AWWA C213.
D. T-Bolts and Nuts:
1. Material:
a. High Strength, Low Alloy Steel, comply with AWWA C111 or ASTM A449, zinc-plated with fluoropolymer coating.
b. 304/316 Stainless Steel.
2.3 FIELD APPLIED COATING
A. Material:
1. Coal Tar: See Section 09 91 00 – Painting.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Section 01 73 00 - Execution Requirements: Requirements for installation examination.
B. Verify that pipe and fittings are ready to receive Work.
C. Field measure and verify conditions for installation of Work.
3.2 PREPARATION
A. Section 01 73 00 - Execution Requirements: Requirements for installation preparation.
B. Clean surfaces of pipe and fittings that are to receive tied joint restraint systems.
3.3 INSTALLATION
A. According to AWWA C600 and manufacturer’s instructions.
B. Install joint restraint system such that joints are mechanically locked together to prevent joint separation.
C. Apply two (2) coats of field applied coating to all restraint systems:
1. If restraint system component is epoxy coated, fluoropolymer coated, or stainless steel, field applied coating is not required.
3.4 TOLERANCES
A. Section 01 40 00 - Quality Requirements: Requirements for tolerances.