26 05 19 - Conductors.pdf
PDF 337 KB Posted
- Attached to
- Biosolids Project 011139.0465
- Solicitation number
- US.260443
- Issued by
- Lancaster County, Pennsylvania
About this file
This is a specification document for conductors and electrical wiring materials for the Biosolids Project 011139.0465 at Ephrata Borough Authority in Pennsylvania. The document establishes detailed technical requirements for building wire and cable, underground feeder and branch circuit cable, wiring connectors and connections, and special wire and cable types including twisted instrumentation cable, telecommunication cable for Ethernet, bonding conductors, VFD motor cable, control panel wire, and Modbus communications cable. The specifications reference compliance with ANSI/NFPA 70 National Electrical Code, ASTM standards, and UL certifications. The project involves coordination and interconnection of two new owner-procured biodryers, demolitions and replacement of dewatered solids conveyor systems, wall demolition and replacement, indoor utility replacements, site piping replacement/relocation, a dumpster loading canopy, and associated electrical improvements. Bidding for the electrical construction contract (EBA26-3) closes on December 8, 2026 at 10:00 AM local time via PennBid, with a pre-bid open house scheduled for November 18, 2026 from 8:00 AM to 10:00 AM.
The specification document provides detailed product requirements and approved manufacturers for each conductor type, with standard "or equal" provisions allowing alternative products meeting specified standards. Installation requirements include conductor sizing minimums (12 AWG for power and lighting, 14 AWG for control circuits), mandatory stranding for certain applications, specific color coding standards for different voltage systems and control circuits, and detailed termination and splicing protocols. Field quality control measures require inspection for physical damage, verification of connection tightness with torque measurements compared to manufacturer recommendations, and continuity testing of branch circuit conductors. The document emphasizes compliance with manufacturer instructions and NEC standards, with restrictions on solder joints and hinged connectors, prohibitions on splices in major power distribution runs or underground wiring, and special requirements for instrumentation cables and intrinsically safe conductors to be installed in separate conduits with labeled barriers.
View the file
Other files
Show 40 more
Latest 50 of 125 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
26 05 19 – CONDUCTORS
Herbert, Rowland & Grubic, Inc. 26 05 19-1 11139.0465
SECTION 26 05 19 - CONDUCTORS
PART 1 GENERAL
1.1 SECTION INCLUDES
A. Building wire and cable.
B. Underground feeder and branch circuit cable.
C. Wiring connectors and connections.
D. Special wire and cable.
1.2 RELATED SECTIONS
A. Section 26 05 00 – Electrical General.
B. Section 26 05 33 – Raceways.
C. Division 40.
1.3 REFERENCES
A. ANSI/NFPA 70 - National Electrical Code.
B. ASTM - American Society of Testing and Materials.
C. U.L. - Underwriters Laboratories.
D. Material construction of copper conductors strands shall be coated or uncoated soft drawn or annealed copper as specified in Part 2 and meet or exceed the following:
1. ASTM B-3 for uncoated strands.
2. ASTM B-33 for tin coated strands.
E. Copper conductor strands shall be combined to form conductors according to the following:
1. ASTM B-8 for concentric-lay-stranded copper conductors.
2. ASTM B-173 for rope-lay-stranded copper conductors.
3. ASTM B-174 for bunch-stranded copper conductors.
F. Insulation:
1. General.
a. All insulation thicknesses shall be in accordance with Section 310 of the National Electric Code.
Herbert, Rowland & Grubic, Inc. 26 05 19-2 11139.0465
b. Maximum operating temperature as noted in Article 3.05.
c. Insulation for specific use shall be as specified herein.
2. Construction - Material construction of insulation shall meet or exceed the following:
a. Ethylene Propylene (EP) - IPECCA S-68-516/NEMA WC 8 and UL 44 standards.
b. Ethylene Propylene Diene (EPD) - IPECA S-68-516/NEMA SC-8 and UL 44
Standards.
c. Cross Linked Polyethylene (XLP) - IPECA S-66-524/NEMA WC-7 and UL 44
Standards.
d. Polyvinyl Chloride (PVC) - UL 83 Standard.
e. High Molecular Weight Polyethylene (HMW-PE) - IPECA S-61-402/NEMA
WC-5 and UL 83 Standards.
G. Jacketing and Covering - Material construction of jacketing shall meet or exceed the following:
1. Chlorosulfonated Polyethylene (CP) - (Hypalon) - IPECA S-19-81/NEMA WC-3 and UL 44 Standards.
2. PVC - IPECA S-19-81/NEMA WC-3, IPECA S-61-402/NEMA WC-5 and UL 83 Standards.
3. Nylon - UL Standard 62 and 758.
1.4 SUBMITTALS
A. Submit under provisions of Sections 01 33 00 – Submittal Procedures and 26 05 00 –
Electrical General.
B. Product Data - Provide for each cable assembly type.
C. Test Reports - Indicate procedures and values obtained.
D. Manufacturer’s Installation Instructions - Indicate application conditions and limitations of use stipulated by product testing agency specified under Article 1.06.
E. Submittals shall contain a material list with manufacturer data describing the material and showing its compliance with specification, associated standards and test requirements.
1.5 QUALIFICATIONS
A. Manufacturer - Company specializing in manufacturing products specified in this section with minimum three years’ documented experience.
Herbert, Rowland & Grubic, Inc. 26 05 19-3 11139.0465
1.6 REGULATORY REQUIREMENTS
A. Conform to requirements of ANSI/NFPA 70.
B. Furnish products listed and classified by Underwriters Laboratories, Inc. or other third-party testing firm acceptable to authority having jurisdiction as suitable for purpose specified and shown.
1.7 PROJECT CONDITIONS
A. Verify that field measurements are as shown on Drawings.
B. Wire and cable routing, if shown on Drawings, is approximate unless dimensioned. Route wire and cable as required to meet project conditions.
C. Where wire and cable routing are not shown, and destination only is indicated, Contractor shall determine exact routing and lengths required.
1.8 COORDINATION
A. Coordinate work under provisions of Section 01 31 13 - Project Coordination.
B. Determine required separation between cable and other work.
C. Determine cable routing to avoid interference with other work.
PART 2 PRODUCTS
2.1 MAJOR POWER DISTRIBUTION
A. Major power distribution is that shown on one-line drawing.
B. Description - ANSI/NFPA 70, Type XHHW.
C. Conductor - Copper.
D. Insulation Voltage Rating - 600 volts.
E. Insulation - Type XLP (cross-linked polyethylene) or EP.
F. Manufacturers:
1. Anixter - Model 3B.
2. Manhattan - Model M8628.
3. Okonite Company - Model 112-32-3.
Herbert, Rowland & Grubic, Inc. 26 05 19-4 11139.0465
4. Or equal.
2.2 BUILDING WIRE AND CABLE
A. Description - Single conductor insulated wire.
B. Conductor - Stranded or solid copper as specified in Part 3 of this section.
C. Insulation Voltage Rating - 600 volts.
D. Insulation - ANSI/NFPA 70; Type XHHW insulation for feeders and branch circuits larger than 4 AWG; Type THHN/THWN insulation for feeders and branch circuits 6 AWG and smaller.
E. Manufacturers:
1. Southwire – THHN or XHHW.
2. Anixter - Model 6G.
3. Okonite - Model 116-67.
4. Or equal.
2.3 TWISTED INSTRUMENTATION CABLE (INTERIOR)
A. Description - Single and multi-pair cable with overall shield.
B. Conductor – Tinned stranded copper, Size 16 AWG (18 AWG 300V in panels).
C. Insulation Voltage Rating - 600 volts.
D. Insulation - PVC/nylon.
E. Shielding – 100 percent overall aluminum or aluminum/polyester foil.
F. Manufacturers:
1. Alpha - Model 2471 (2421).
2. Belden – Model 8719 (8760).
3. Clifford – Multi-pairs.
4. Or equal.
2.4 TELECOMMUNICATION CABLE FOR INSIDE USE (ETHERNET)
A. Description - Multi-conductor cable, insulated conductor are twisted into pairs.
B. Conductor - Minimum size No. 24 solid copper.
C. Insulation - Color-coded, PVC.
Herbert, Rowland & Grubic, Inc. 26 05 19-5 11139.0465
D. Rip Cord - If available.
E. Outer Jacket - PVC. COLOR - BLUE
F. Manufacturers:
1. Anixter - Inside Wiring Cable, Model EX-CM-00224BAG.
2. Triangle PWC, Inc. - Type 123BM; Model TP-610TC.
3. Brand-REX - Model BMD.
4. Or equal.
2.5 BONDING CONDUCTORS
A. Description - Bare copper wire.
B. Conductor - Solid ASTM B-1 for sizes No. 8 and smaller; stranded ASTM B-8 for sizes No.
6 and larger.
C. Manufacturers:
1. Anixter - Model 1A or 1B.
2. Cablec - Model “Bare and coated copper conductors” listed under Section 7
“Special Purpose Cables.”
3. Southwire – Bare copper ground.
4. Or equal.
2.6 VFD MOTOR CABLE
A. Description – Multi-conductor power cable with overall shield.
B. Conductor – High strand tinned copper.
C. Insulation Voltage Rating – 1,000 volts.
D. Individual Conductor Insulation – XLPE with phase indicators.
E. Jacket – PVC.
F. Manufacturers:
1. Belden – 29500 Series.
2. AmerCable – 37-108 Series.
3. Or equal.
2.7 CONTROL PANEL WIRE
A. Description - 90 degrees C Machine Tool Wire (MTW).
B. Conductor - Minimum Size AWG #16, 19 strand.
Herbert, Rowland & Grubic, Inc. 26 05 19-6 11139.0465
C. Insulation - PVC, 2/64-inch for 600 V service.
D. Manufacturers:
1. Carol - Catalog Series 7600.
2. Anixter - Catalog Series 6W.
3. Manhattan – Series MTW.
4. Or equal.
2.8 MODBUS COMMUNICATIONS CABLE
A. Description – Stranded tinned copper multi-conductor, EIA Industrial RS-485 PLTC/CM.
B. Conductor – Stranded tinned copper, Size 22 AWG.
C. Insulation Voltage Rating – 300 volts.
D. Insulation Type – Foam high density polyethylene (FHDPE) with PVC outer jacket.
E. Shielding – Outer, aluminum foil-polyester tape with tinned copper drain wire.
F. Manufacturers
1. Belden 3105A.
2. Anixter 3105A.
3. Clifford Instrumentation and Tray.
4. Or equal.
2.9 WIRING CONNECTORS
A. Terminal Block Manufacturer:
1. Control Wiring:
a. Buchanan - Model 0241.
b. Connection - Model NSS3.
c. Ideal.
d. Or equal.
2. Equipment Power Wiring:
a. Buchanan - Model 416.
b. Connection - Model NC3.
c. Ideal.
d. Or equal.
B. Wire Nuts:
1. For Unclassified Areas - Hexagonal shaped for use with a nut driver, compact swept-wings, ribbed cap, UL-listed for 600V with temperature rating of 105 degrees C (221 degrees F).
a. Ideal - Models 341 and 342.
b. 3M - Models 212, 312, and 512.
c. Buchanan - Models B-1, B-2, and B-4.
Herbert, Rowland & Grubic, Inc. 26 05 19-7 11139.0465
d. Or equal.
2. For Wet and Corrosive Areas - Compact swept-wings, ribbed cap, filled with non-hardening sealant, UL-listed for 600V with temperature rating of 105 degrees C
(221 degrees F).
a. Ideal - Model DB Plus.
b. Buchanan - Models BTS2 and BTS4.
c. 3M.
d. Or equal.
C. Bolted Wire Connectors - Mechanical connectors for all combination of copper and aluminum conductors. It shall be of a compact high-strength design, tin-plated copper alloy, two-piece connector, and shall utilize two hexhead bolts.
1. Burndy - Model KVSU.
2. Ideal.
3. Ilsco.
4. Or equal.
D. Terminal Blocks - 600 VAC continuous ratings, heavy duty nylon and suitable for channel mounting with end caps, jumpers and mounting channels as required.
E. Two-way splices, tubular compression type for conductors 1/0 and larger. Rated 600 VAC and uninsulated.
1. Burndy - Model YS-L “Hylink.”
2. Thomas & Betts Catalog - Model 545.
3. 3M - Model 10000.
4. Or equal.
F. Two-way splices, tubular, compression type for conductors, 1 AWG and smaller, uninsulated and rated 600 VAC.
1. Burndy – Type YSV “Hylink.”
2. Thomas & Betts.
3. 3M.
4. Or equal.
G. Branch Circuit Connector and Fixture Connections - Crimp type, 600 VAC connectors with rubber rap insulator.
1. Ideal Catalog - Series 30; Model 410, 411, and 412 with Model 415 and 417 insulator.
2. Thomas & Betts - Catalog PT66M with PT6 insulator.
3. 3M.
4. Or equal.
H. Bus or Lug Terminals - 600 VAC, crimp type.
Herbert, Rowland & Grubic, Inc. 26 05 19-8 11139.0465
1. Burndy - “HYLUG” Catalog, Series YA.
2. Ideal - Catalog Series CCL and CC.
3. Ilsco.
4. Or equal.
I. Control and Instrumentation - Locking fork, vinyl self-insulated, crimp type connectors.
1. Thomas & Betts - Catalog Series 18RA, 14RB, and 10RC.
2. Burndy - “VINYLUG” Types TP-LF and BA-EL.
3. Ideal - Catalog Series 83-7.
4. Or equal.
2.10 MISCELLANEOUS ACCESSORIES
A. Electrical Tape:
1. Plastic Tape - All weather vinyl electrical tape having a high dielectric strength and resistant to sun, water, oil, acids, and corrosive chemicals. Tape shall be Tomic No. 85; 3M; Thomas & Betts; or equal.
2. High Voltage Electrical Tape - Self bonding polyethylene bond tape. Tape shall be Tomic No. 3; 3M; Thomas & Betts; or equal.
3. High Temperature Tape - A woven glass fabric backing with a thermosetting rubber base adhesive. Tape shall be Tomic No. 77; 3M; Thomas & Betts; or equal.
4. Underground Splice Tape - An inherent positive moisture seal and insulation for 600-volt conductors consisting of a laminate of EPR and Electro-Seal mastic in roll form.
5. Manufacturers - Bishop Electric, 3M, Thomas & Betts, or equal.
B. Wire Pulling Lubricant Manufacturers:
1. Ideal.
2. Tomic Electric.
3. 3M.
4. Or equal.
C. Wire Pulling Lubricant - Wire pulling lubricant shall be non-toxic and contain no solvent to attack wire insulation plastic tape or conduits. Lubricant shall leave no residual in conduit, shall be rust inhibited and be non-combustible.
PART 3 EXECUTION
3.1 EXAMINATION
A. Verify that interior of building has been protected from weather.
B. Verify ductbanks are completed and terminal equipment is in place.
C. Verify that mechanical work likely to damage wire and cable has been completed.
Herbert, Rowland & Grubic, Inc. 26 05 19-9 11139.0465
3.2 PREPARATION
A. Completely and thoroughly swab raceway before installing wire.
3.3 CONDUCTOR SIZING
A. Power and lighting circuits - Minimum number 12 AWG. Quantity as required for proper operation.
B. Control Circuits - Use stranded conductor not smaller than 14 AWG. Quantity as required for proper operation.
C. Neutral Wire - To be equal to ungrounded wires unless specifically otherwise shown.
D. Ground Wire - Minimum size as required by the NEC Table 250.122.
3.4 CONDUCTOR STRANDING
A. Conductors shall be stranded as called for in the following table.
USE SIZE STRANDED REQUIRED
Wiring within MCC All Yes
Control wiring All Yes
Instrumentation All Yes
Major power All Yes
Panelboard circuits #8 and Larger Yes
3.5 WIRING METHODS
A. General - All conductor shall be Type THWN with insulation suitable for use in wet locations and designed for 75 degrees C maximum operating temperature unless otherwise indicated as noted below:
1. Major Power Distribution (as shown on one-line diagram).
a. Use XHHW type-conductor for interior applications.
2. Lighting Circuits - Use THW or THWN-type conductor. Switching control shall be as shown on Drawings. Circuiting approximately as shown; minor variations permitted. Install all required conductors for switching and emergency lighting shown.
3. Receptacle Circuits - Use THW or THWN type conductor. Circuiting approximately as shown; minor variations permitted. Six receptacles per circuit unless indicated otherwise. Special receptacle circuits as shown on Drawings.
Herbert, Rowland & Grubic, Inc. 26 05 19-10 11139.0465
4. Wet and Corrosive Areas - Use nylon jacketed type except for major power distribution.
5. 90 Degrees F High Ambient Areas (i.e., Furnace Room) - Use conductor with insulation rated 90 degrees C for dry areas, in locations with continuous ambient temperature in excess of 90 degrees F.
3.6 COLOR CODING
A. All service, feeder, branch, control, and signaling circuit conductors, shall have color coding throughout the entire run.
B. Grounding Conductors - Shall be green.
C. Neutral Conductors - Shall be white or gray, except where neutrals of more than one system are installed in the same raceway or box, the other neutral shall be white with a colored (not green) stripe.
D. The color of the ungrounded conductors in different voltage systems shall match the existing system. When no existing system exists, color coding shall be as follows:
1. 277/480 volt, 3-phase:
a. Phase A – Brown.
b. Phase B – Orange.
c. Phase C – Yellow.
2. 120/208 volt, 3 phase:
a. Phase A – Black.
b. Phase B – Red.
c. Phase C – Blue.
3. dc Power:
a. Positive Lead – Red.
b. Negative Lead – Black.
4. dc Control: All – Blue.
5. 120V Control Wiring - Single conductor ac control wire shall be Red except a wire entering a motor control center compartment or control panel which is an interlock, shall be color coded Yellow.
6. 24V Control Wiring - Orange.
3.7 INSTALLATION
A. Install products in accordance with manufacturers’ instructions.
B. Use suitable wire pulling lubricant for building wire 4 AWG and larger.
C. Do not pull thermoplastic wire at temperatures below 35 degrees F.
Herbert, Rowland & Grubic, Inc. 26 05 19-11 11139.0465
D. Protect exposed cable from damage. For exterior cables, tape ends watertight if terminations are not to be made up immediately after pulling conductors.
E. Support cables above accessible ceiling, using spring metal clips or metal cable ties to support cables from structure or ceiling suspension system. Do not rest cable on ceiling panels.
F. Neatly train and lace wiring inside boxes, equipment, and panelboards.
G. Circuit arrangements shown on Drawings with regard to electrical loading and design concept shall be followed completely. Actual circuit routing shall be at the electrical installer’s option as approved by the Engineer. Circuit numbers labeling home runs on
Drawings are for count only and not necessarily for directory purposes.
H. Wiring Diagrams:
1. Any wiring diagrams shown on plans for hookup of equipment furnished by others are approximate only.
2. Obtain wiring diagrams, certified correct for the job, from respective supplier for all equipment and systems furnished by them.
3. Install all work in accordance with certified wiring diagrams.
I. Conductors installed in wireways shall be grouped and bundled as they exit each conduit run.
In opened areas such as wireways, manholes, etc., wires and cables shall be tied every
12 inches. Provide plastic laminated labels on conductor groupings wrapped to cables.
J. Electrical trade to provide all power, control and signal wiring and conduits between system components (including installation of any conductors supplied by other trades), including final connections to labeled terminal strips integral in equipment, as shown on
Drawings, and in accordance with approved manufacturer’s wiring diagrams.
K. Where instrumentation cables are installed in panels, etc., arrange wiring to provide maximum clearance between instrumentation cables and other conductors.
Instrumentation cables shall not be installed in the same bundle with conductors of other circuits.
L. Intrinsically safe conductors shall be in separate conduits both inside and outside the enclosure and shall be terminated on separate terminal strips with barriers. Label the conduit as “intrinsically safe.”
Herbert, Rowland & Grubic, Inc. 26 05 19-12 11139.0465
M. Installation in Manholes and Handholes - Neatly bundle conductors and train them around the outside (long way around) of the manhole. Support conductors from hooks inside of manhole or handhole.
N. Multi-conductor VFD motor cables shall be installed such that the cable manufacturer’s minimum bend radius specifications are followed. As required and prior information, obtain this information from the cable manufacturer for each size cable installed.
3.8 SPARE CONDUCTORS
A. As noted on the contract drawings.
3.9 TERMINATIONS CONNECTIONS, SPLICES AND JOINTING
A. General:
1. All accessories that use special tools for proper application as recommended by the manufacturer shall be installed only with those tools and in accordance with the established practices and recommendations of the manufacturers.
2. Solder joints and hinged connectors will not be permitted.
a. The exception of multi bolted direct compression connectors in large wire and cable sizes will be permitted, if compression type fittings are not available or the Engineer determines sufficient space is not available.
3. Make splices only in accessible locations and in junction boxes. No splices in pulling fittings, wireways, or MCC wiring spaces.
4. Make splices, taps, and terminations to carry full ampacity of conductors with no perceptible temperature rise.
5. Clean conductor surfaces before installing lugs and connectors.
6. Splices, taps or terminations shall not be made when conductor ends have missing strands or when ends are mutilated in any way.
B. Splices:
1. No splices will be allowed in any major power distribution runs or in any underground wiring.
2. Insulate the completed splice with insulating putty to approximately match the insulation thickness or approximately 1/8 inch and tape with self-fusing neoprene splicing tape to twice original cable or wire diameter, two half lapped layers minimum. Extend taping at least 1/2 inch over original insulation or two cable diameters, whichever is larger.
3. Exceptions:
a. Lighting and Receptacle Circuits - Splice connections shall be wrapped with plastic electrical tape, or use insulated compression connectors.
b. Fractional horsepower motors wrap splice with plastic electrical tape or insulated compression fillings.
c. For splices in circuits located in high ambient temperature areas, wrap the connection with high temperature tape and cover with plastic tape.
Herbert, Rowland & Grubic, Inc. 26 05 19-13 11139.0465
C. All outdoor splices of 600 volt conductors shall be wrapped with underground splice tape and an outer wrapping of plastic electrical tape.
D. Taps - Make taps similar to splices described above.
E. Lug Connections - Use one- or two-bolt indent compression lugs. Insulate the lug barrel and original insulation as for splices.
F. Motor Connections:
1. Motors Less than 1 HP - Use wire nut appropriate for the environment where the motor is located.
2. Motors from 1 HP to 20 HP - Use branch circuit crimp-type connectors.
G. Terminal Board Terminations - All interconnecting wiring to terminal boards and strips shall be made with insulated crimp type connectors (locking spade type). Stranded wire shall not be directly connected to terminals without the use of connectors unless the terminations are of the locking collar type. No loose strands shall be permitted outside of the connector, whichever is utilized.
H. Connections:
1. Connections of conductors to terminal posts or other conductors shall be made with UL approved compression type connectors. Wire nuts shall not be permitted, except for fractional horsepower, single phase motors or elsewhere where specifically approved by the Engineer.
2. Connections shall insure a thorough connection without damaging the conductor.
3. Connections shall be for proper cable size.
4. Copper to aluminum connection shall be made with UL approved aluminum to copper connectors and compound.
3.10 INTERFACE WITH OTHER PRODUCTS
A. Identify wire and cable under provisions of Section 26 05 53, Electrical System
Identification.
B. Identify each conductor with its circuit number or other designation indicated on
Drawings.
3.11 FIELD QUALITY CONTROL
A. Perform field inspection and testing under provisions of Sections 01 40 00 - Quality
Requirements and 26 05 00 – Electrical General.
B. Inspect wire and cable for physical damage and proper connection.
Herbert, Rowland & Grubic, Inc. 26 05 19-14 11139.0465
C. Measure tightness of bolted connections and compare torque measurements with manufacturer’s recommended values. Torque values can also be found in the NEC
Handbook.
D. Verify continuity of each branch circuit conductor.
END OF SECTION `