This is a specification document for Auxiliary Controls and Relays prepared by Herbert, Rowland & Grubic, Inc. for the Biosolids Project 011139.0465 at Ephrata Borough Authority in Pennsylvania. The specification details the products and equipment required for control systems, including pushbuttons, selector switches, indicating pilot lights, contact blocks, control power transformers, fuse blocks, limit switches, timers, time delay relays, control relays, uninterruptible power supplies, and alarm horns. The project encompasses the coordination and interconnection of two new biodryers, demolition and replacement of conveyor systems, wall demolition and replacement, utility replacements, site piping work, a dumpster loading canopy, and associated electrical improvements. Bids for the Electrical Construction (Contract No. EBA26-3) are due December 8, 2026 at 10:00 AM through PennBid. A pre-bid open house will be held on November 18, 2026 from 8:00 AM to 10:00 AM for bidders to view the facility.
The specification establishes detailed product standards and requirements for all auxiliary control components, including NEMA classifications for different environmental areas (NEMA 13 for non-classified areas, NEMA 4 and 13 for wet or exterior areas, and NEMA 4X for corrosive areas), voltage ratings, contact ratings, and approved manufacturers such as General Electric, Schneider Electric (Square D), Allen-Bradley, and Cutler-Hammer. The document requires shop drawings, product data, manufacturer installation instructions, and operation and maintenance data as submittals. All pilot devices must be industrial-type, heavy-duty construction with 30-millimeter diameter configurations, and controls and relays should be from a single manufacturer where possible. The specification includes no pricing information, set-asides, or incumbent contractor details within the document itself.
View the file
Other files
Show 40 more
Latest 50 of 125 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
26 09 16 – AUXILIARY CONTROLS AND RELAYS
Herbert, Rowland & Grubic, Inc. 26 09 16 -1 011139.0465
SECTION 26 09 16 - AUXILIARY CONTROLS AND RELAYS
PART 1 - GENERAL
1.1 SECTION INCLUDES
A. Pushbutton.
B. Selector switches.
C. Indicating pilot lights.
D. Contact blocks.
E. Control power transformers.
F. Fuse blocks.
G. Limit switches.
H. All timers.
I. Time delay relays.
J. Relays.
K. Liquid level sensors (floats).
L. Uninterruptible power supplies.
M. Alarm horn.
1.2 RELATED SECTIONS
A. Division 26.
1.3 REFERENCES
A. NEMA ICS 1 - General Standards for Industrial Control Systems.
B. NEMA ICS 2 - Standards for Industrial Control Devices, Controllers and Assemblies.
C. NEMA ICS 6 - Enclosures for Industrial Controls and Systems.
D. NEMA ST 1 - Standard for Specialty Transformers (Except General Purpose Type).
Herbert, Rowland & Grubic, Inc. 26 09 16 -2 011139.0465
1.4 SUBMITTALS
A. Submit shop drawings under provisions, Submittals.
B. Submit shop drawings to NEMA ICS 1 indicating control panel layouts, wiring connections and diagrams, dimensions, support points.
C. Submit product data under provisions of, Submittals.
D. Submit product data for each component specified. The submittal shall be included as part of the system in which the component is specified.
E. Submit manufacturer’s installation instructions under provisions of Submittals.
F. Submit samples as requested by the Engineer.
1.5 PROJECT RECORD DOCUMENTS
A. Submit record documents under provisions of 01 78 39 - Project Record Documents.
B. Accurately record actual locations of control equipment. Revise diagrams included in Drawings to reflect actual control device connections.
1.6 OPERATION AND MAINTENANCE DATA
A. Submit operation data under provisions of 01 78 39 - Project Record Documents.
B. Include instructions for adjusting and resetting time delay relays, timers, and counters.
C. Submit maintenance data under provisions of Record Documents.
D. Include recommended preventive maintenance procedures and materials.
PART 2 - PRODUCTS
2.1 PILOT DEVICES
A. General:
1. Pilot devices shall include indicating light, pushbuttons, and selector switches.
2. Heavy-duty, industrial type, construction.
3. Area Classification:
a. Non-Classified Area Device Rating - NEMA 13 oil-tight.
b. Wet Area or Exterior Device Rating - NEMA 4 and NEMA 13 oil-tight and watertight.
c. Corrosive Area Device Rating - NEMA 4X, non-metallic.
4. Provide extra-large nameplates in accordance with Section 26 05 53 Electrical System Identification, for all door or enclosure front-mounted devices.
Herbert, Rowland & Grubic, Inc. 26 09 16 -3 011139.0465
5. Controls and relays shall be by one manufacturer wherever possible.
6. Provide enclosure for field mounted devices and individual controls in accordance with Section 26 27 16 - Control Panels and Enclosures.
7. 30-millimeter diameter.
8. Retaining ring and boot type.
B. Pushbuttons and Selector Switches (PB) and (SEL SW):
1. Lockout feature as indicated.
2. Color – Red for stop or terminate function; black for all others.
3. Operators:
a. Provide “gloved hand” knobs for selector switches.
b. Provide “mushroom head” button on emergency stop pushbuttons.
c. Emergency stop pushbuttons shall be of the push-pull type unless specifically noted otherwise. Provide clear protective flip-up covers over emergency stop pushbuttons. Provide stackable NO/NC contacts as required.
4. Stackable contact blocks as required.
5. Devices shall be either momentary, maintained, spring return, push-pull, or other operational types as shown or otherwise specified.
6. Manufacturer NEMA 4 and 13 Oil and Water Tight – General Electric, Schneider
Electric (Square D) Type K, Cutler-Hammer, or equal.
7. Manufacturer NEMA 4X, Non-Metallic – Allen-Bradley Type 800H, Schneider
Electric (Square D) Type SK, Cutler-Hammer, or equal.
C. Indicating Pilot Lights (IL):
1. Glass or plastic lens.
2. 120-volt LED transformer type.
3. Push-to-test type. When six or more pilot lights are used in control panels, a single lamp test switch can be used in lieu of all lamps being push-to-test.
4. Lens color shall be as follows:
Function Color
Motor running Green
Malfunction/alarm Amber
Ready Red
Power On White
5. Manufacturers – General Electric, Schneider Electric (Square D), Crouse-Hinds, Allen-Bradley, Cutler-Hammer, or equal.
2.2 CONTACT BLOCKS
A. Molded of an amorphous transparent polyamide material with high impact resistance and resistant to carbon tracking.
B. Contacts – Double break silver type rated at 10 amp at 120 VAC continuous.
Herbert, Rowland & Grubic, Inc. 26 09 16 -4 011139.0465
2.3 CONTROL POWER TRANSFORMER (CPT)
A. Standard industrial control type, VA size as required for the powered load.
B. Dual voltage primary, with 120V ac, single phase secondary. All primary connections fused; size as required for the transformer.
C. Secondary control fuse with capacity for the control circuit indicated.
D. Can be DIN-rail mounted type in control panels.
E. Manufacturer – Schneider Electric (Square D), General Electric, Acme, or equal.
2.4 FUSE BLOCKS
A. General purpose Class H, K, and R phenolic fuse block for dual-element cartridge fuses.
B. Can be DIN-rail mounted in control panels.
C. Manufacturer – Buchanan, Connectron, 3M, or equal.
2.5 LIMIT SWITCHES (LS)
A. Contacts – Silver-to-silver snap-acting where practicable and in all cases where the motion is slow.
B. Switches – Operated by levers, plungers, or pushrods, depending on the application.
C. Rollers – Provided where excessive wear due to a sliding action would result.
D. Manufacturer – General Electric Class CR215G, Schneider Electric (Square D) Class 9007 Type C, Allen-Bradley, or equal.
2.6 ELAPSED TIME METERS (ETM)
A. Minimum six-digit, non-resettable hour meter panel mounted.
B. For operation on 120 volts.
C. Manufacturer – General Electric, Yokagowa, Schneider Electric (Square D), or equal.
2.7 PROGRAMMABLE TIMERS
A. Microprocessor-based digital controller with two channels with up to 20 on/off setpoints, repeatable every day.
B. Program entries shall be made by mechanical pushbutton and an acknowledgement of each entry into the unit shall be by audible signal.
Herbert, Rowland & Grubic, Inc. 26 09 16 -5 011139.0465
C. Override switches shall be provided for continuous On or Off, automatic and visual indicators for each channel.
D. Controller shall provide 7-day, 24-hour programming.
E. Maintained output contacts.
F. Plain English self-prompting display.
G. Timing sequences shall be fully detailed in the operations and maintenance manuals for the respective equipment controlled.
H. Timer shall be Tork EWZ201 or equal.
2.8 TIME DELAY RELAYS (TR)
A. Solid-state type with calibrated dial head or dip switch adjustment, encapsulated coil, snap-action switch assembly of number of poles indicated.
B. “On-Delay,” “Off-Delay,” or “On-Off Delay” dual head type as indicated; timing range intervals as shown or specified.
C. Bases shall have captive screws for locking fork solderless connectors, single tier design, with relay retainer clips.
D. Dust-tight construction.
E. Provide auxiliary contacts where indicated.
F. Contacts rated 10 amps resistive at 120 VAC.
G. Manufacturer - Diversified Electronics Series “TD;” Schneider Electric (Square D), Type JCK; Timemark 300 Series; or equal.
2.9 GENERAL PURPOSE CONTROL RELAYS (CR)
A. Units shall be plug-in type.
B. Use in all control panels.
C. Number of poles and arrangement as shown or specified.
D. Contacts:
1. Shall be rated 10 amps at 240 volts AC.
2. Material shall be silver cadmium oxide.
E. Coils shall be rated continuous duty.
Herbert, Rowland & Grubic, Inc. 26 09 16 -6 011139.0465
F. Sockets:
1. Supply with relay retainer clip.
2. Terminal connections with captive screw to accept locking fork solderless connectors.
3. Single tier design.
G. Manufacturers – Schneider Electric (Square D) Class 8501 Type K relay and Type NR socket; Potter-Brumfield; or equal.
2.10 INDUSTRIAL CONTROL RELAYS (ICR)
A. Industrial machine tool type.
B. Use – Shall be used in motor control centers or used to control equipment with power requirements, such as solenoid valves.
C. Contacts:
1. Double break field convertible.
2. Rated 10 amps at 600 volts AC.
3. Rated 5 amps at 250 volts DC.
D. Coil shall be encapsulated, continuously rated of the voltage rating indicated on the plans.
E. Number of poles as indicated on Contract Drawings, but not less than four.
F. Holding and Operating Mechanism:
1. Electrically held, electrically operated, General Electric Company CR-120A;
Schneider Electric (Square D) Class 8501, Type X; Cutler-Hammer; or equal.
2. Mechanically held/electrically held relay with mechanically-held attachment.
3. Time Delay - Pneumatic timer attachment for electrically-held delay; “on delay” or “off delay” as indicated on plans.
2.11 UNINTERRUPTIBLE POWER SUPPLY (UPS)
A. Minimum Watt Capacity – As required to maintain power to equipment for normal operation for a period of 1/2 hour.
B. Battery energy storage.
C. Automatic recharging of batteries.
D. Four 120-volt, 5-15R, output receptacles.
E. Alarms – Battery backup operation, low run time remaining, and overload.
F. Automatic current and overvoltage output protection.
G. Operating Input Voltage – 88 VAC - 138 VAC.
Herbert, Rowland & Grubic, Inc. 26 09 16 -7 011139.0465
H. No interruption (no transfer time for normal power to battery backup) of power to the connected true “on-line” load.
I. Efficiency – 95 percent.
J. Brown-out protection for input voltages of 88 VAC without the use of the batteries.
K. Lightning and Surge Protection – ANSI/IEEE C62.41 Categories A and B with 0.3 percent to 0.7 percent.
L. Radio Frequency Noise Isolation – 38 Db common mode, 47 Db normal mode.
M. Provide a minimum of a NEMA 4 wall-mounted enclosure for external mounted UPS.
N. Manufacturer – Best, Liebert, Sola/Hevi-Duty, or equal.
2.12 ALARM HORN
A. Lightweight, compact, wall-mounted, signal device with gain control. UL listed for indoor and outdoor use.
B. Operating on 120-volt, 60 Hertz, with a maximum current draw of 0.5 amps.
C. Signal Type – Horn, 110 dB at 10 feet.
D. Housing – Speaker cone and projector made of spun aluminum. Internal amplification circuitry including gain control contained in diecast aluminum housing.
PART 3 - EXECUTION
3.1 GENERAL
A. Mount all individual controls in a suitable enclosure as specified per Section 26 27 16 - Control Panels and Enclosures.
B. Identify all auxiliary controls per Section 26 05 53 - Electrical System Identification.
C. General purpose control relays shall be used in manufactured or custom-built control panels. Their use in motor control centers is prohibited. The Contractor shall use control relays as described in Article 2.10 to control equipment with power requirements, such as solenoid valves.
3.2 CONTROL POWER TRANSFORMER
A. Provide individual control power transformers for each control circuit.
B. Size as required by control circuit.
Herbert, Rowland & Grubic, Inc. 26 09 16 -8 011139.0465
3.3 FUSE BLOCKS
A. Size as indicated on Drawings or as required.
3.4 LIMIT SWITCHES
A. Limit switches shall be provided where specified and where it is required to convert a mechanical motion into the control of an electric circuit.
3.5 PUSHBUTTONS AND SELECTOR SWITCHES
A. Units shall be back-mounted wherever possible.
END OF SECTION