26 05 53 - Electrical System Identification.pdf
PDF 271 KB Posted
- Attached to
- Biosolids Project 011139.0465
- Solicitation number
- US.260443
- Issued by
- Lancaster County, Pennsylvania
About this file
This file is a specification section (26 05 53 - Electrical System Identification) prepared by Herbert, Rowland & Grubic, Inc. for the Biosolids Project 011139.0465 at Ephrata Borough Authority in Pennsylvania. The specification details comprehensive electrical system identification requirements including nameplates, signs, labels, directory cards, wire and cable markers, conduit markers, underground warning tape, and arc flash labeling. Products specified include three-layer laminated plastic nameplates with white letters on black backgrounds, self-adhesive aluminum foil labels for equipment enclosures, polyolefin wire marker sleeves with clear tape overwrap, flexible plastic conduit markers in various colors corresponding to voltage systems (red for 480V, blue for 208V and 277V, green for telephone), four-inch wide yellow detectable underground warning tape, and arc flash labels compliant with NFPA 70E standards. The specification requires a portable label maker to be maintained in the contractor's field office trailer. Installation requirements specify that all electrical enclosures, operating devices, wall switches, and dedicated receptacles receive appropriate identification, with nameplates secured using stainless steel rivets on NEMA 1, 1A, and 12 equipment, and industrial-grade adhesive or glue on NEMA 4X and 7 equipment. Wire markers must be applied at each conductor end, junction box, panelboard gutter, pullbox, and load connection, with conduit markers placed at devices, junction boxes with multiple connections, room entry/exit points, and at fifty-foot intervals on runs exceeding one hundred feet.
The specification mandates compliance with ANSI/NFPA 70 (National Electrical Code) and NFPA 70E standards, with products required to be listed and classified by Underwriters Laboratories or acceptable testing firms. Approved manufacturers for various components include Thomas & Betts, Brady, Seton, and EMED Company, Inc., with equal products permitted. Additional safety signage requirements include up to twenty operational safety and warning signs with specific wording to be provided by the contractor, warning signs on motor control center main circuit breaker compartments, and high-voltage warning signs at electrical distribution equipment identifying voltage levels. The specification requires arc flash labeling and signage in accordance with approved arc flash studies, with label preparation following ANSI Z535.4-1998 standards and displaying hazard risk categories and required personal protective equipment. Letter sizes for identification vary by equipment type, ranging from 5/16-inch for individual equipment to 2-inch for panelboards, motor control centers, transformers, and switchboards. All conductors, including spares, must be labeled with power and lighting circuits identified by branch circuit or feeder numbers and control circuits matching schematic and interconnection diagrams on shop drawings.
View the file
Other files
Show 40 more
Latest 50 of 125 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
26 05 53 – ELECTRICAL SYSTEM IDENTIFICATION
Herbert, Rowland & Grubic, Inc. 26 05 53-1 11139.0465
SECTION 26 05 53 - ELECTRICAL SYSTEM IDENTIFICATION
PART 1 GENERAL
1.1 SECTION INCLUDES
A. Nameplates, signs and labels.
B. Directory cards.
C. Wire and cable markers.
D. Conduit markers.
E. Underground warning tape.
1.2 RELATED SECTIONS
A. Division 09.
B. Division 26.
1.3 REFERENCES
A. ANSI/NFPA 70 - National Electrical Code.
1.4 SUBMITTALS
A. Submit representative samples on all nameplates, signs, markers, and labels for the Owner’s approval prior to ordering.
1.5 REGULATORY REQUIREMENTS
A. Conform to requirements of ANSI/NFPA 70.
B. Furnish products listed and classified by Underwriters Laboratories, Inc. or testing firm acceptable to authority having jurisdiction as suitable for purpose specified and shown.
PART 2 PRODUCTS
2.1 NAMEPLATES AND SIGNS
A. Nameplates and Signs.
1. Nameplates - Engraved three-layer laminated plastic, white letters on black background.
2. Warning Signs - Engraved three-layer laminated plastic, white letters on red background.
Herbert, Rowland & Grubic, Inc. 26 05 53-2 11139.0465
B. Letter Size.
1. 5/16-inch letters for identifying individual equipment and loads.
2. 3/8-inch letters for identifying grouped equipment and loads.
3. 2-inch letters for identifying panelboards, motor control centers, transformers, and switchboards.
2.2 LABELS - EQUIPMENT IN ENCLOSURES
A. Self-debossing, aluminum foil type.
B. Material - 0.0002-inch thick aluminum foil.
C. Typewritten or machine impressed.
D. Permanent pressure-sensitive adhesive; high temperature adhesive for labels on heat producing devices.
E. Letter Size - All upper case, minimum 0.1-inch high.
F. Embossed adhesive strip labels from hand-held dispenser devices are not permitted.
G. Manufacturer - Seton, Brady, EMED Company, Inc., or equal.
2.3 DIRECTORY CARDS
A. Typewritten or machine printed in upper-case letters on extra heavyweight paper or card stock.
B. Locations:
1. Panelboards.
2. Load centers.
3. Distribution panels.
2.4 WIRE AND CABLE MARKERS
A. Manufacturers:
1. Thomas & Betts.
2. Brady.
3. Seton.
4. Or equal.
B. Description - Machine printed polyolefin wire marker sleeves with clear tape overwrap, or sleeve type wire markers. Black print on white background. Each label shall be a single adhesive film or shrink wrap sleeve. Printing that is capable of being rubbed off the wire label is not acceptable.
Herbert, Rowland & Grubic, Inc. 26 05 53-3 11139.0465
C. Legend:
1. Power and Lighting Circuits - Branch circuit or feeder number indicated on drawings.
2. Control Circuits - Control wire number shall match that indicated on schematic and interconnection diagrams on shop drawings.
D. All conductors, including spares, shall be labeled.
2.5 CONDUIT MARKERS
A. Manufacturers:
1. Seton.
2. Brady.
3. EMED Company, Inc.
4. Or equal.
B. Description:
1. Standard preprinted, flexible or semi-rigid, permanent, plastic sheet extending
360 degrees around conduit; designed for attachment to conduit by adhesive backing, matching adhesive plastic tape, cover with plastic laminate or pretensioned acrylic plastic sheet formed to wrap around conduit and grip without adhesive or mechanical attachment.
2. Emergency Powered Circuit Conduit - Black lettering on red background.
3. General Conduit 120 Volt System - Black lettering on white background.
4. Conduit Up to and including 2-Inch Diameter - Marker color field shall be 8 inches long.
5. Conduit Larger Than 2-Inch Diameter - Marker color field shall be 12 inches long.
6. Letter Size.
CONDUIT DIAMETER LETTER HEIGHT
1/2" through 1-3/8" 1/2"
1-1/2" through 2-3/8" 3/4"
2-1/2" and larger 1-1/4"
7. All lettering shall be upper case.
C. Color:
1. 480 Volt System - Red.
2. 208 Volt System - Blue.
3. 277 Volt System - Blue.
4. Telephone System – Green.
Herbert, Rowland & Grubic, Inc. 26 05 53-4 11139.0465
2.6 UNDERGROUND WARNING TAPE
A. Description - 4 -inch wide plastic tape, detectable type, colored yellow with suitable warning legend describing buried electrical lines as manufactured by Seton, EMED Company, Inc., Brady, or equal.
2.7 ARC FLASH LABELING
A. Labeling shall be in accordance with NFPA 70E.
B. Labels shall be prepared in accordance with ANSI Z535.4-1998, Product – Safety Signs and Labels.
C. Labels shall display the Hazard Risk Category #, along with the proper PPE required.
D. Labels shall be provided per the approved arc flash study required by Section 26 05 73 - Power System Study and Testing.
2.8 PORTABLE LABEL MAKER
A. Provide a portable label maker in the Contractor’s field office trailer.
PART 3 EXECUTION
3.1 APPLICATION SCHEDULE, SIGNS, NAMEPLATES AND LABELS
A. Signs - As specified herein or as shown on the Contract Drawings and as required by
NFPA 70.
B. Nameplates - All electrical enclosures and operating devices, such as:
1. Power distribution equipment.
2. Transformers.
3. Distribution panels.
4. Panelboards and load centers.
5. Transfer switches.
6. Equipment control panels.
7. Motor starting switches.
8. Safety switches.
9. Disconnect switches.
10. Instrumentation and PLC enclosures.
11. All control panels.
C. Labels - All electrical devices inside enclosures and control panels, wall switches (where the operated device is not readily identifiable), control stations, and dedicated receptacles.
Herbert, Rowland & Grubic, Inc. 26 05 53-5 11139.0465
D. Label - All dedicated receptacles indicating the full load amps, voltage, and appliance name.
3.2 NAMEPLATES AND LABELS
A. Install nameplate and label parallel to equipment lines.
B. On NEMA 1, 1A and 12 equipment, secure plastic laminate nameplate to equipment front using stainless steel rivets. Adhesive mounting is not acceptable.
C. On NEMA 4X and 7 equipment, use industrial grade double face adhesive tape or glue to permanently bond the nameplate to the mounting surface.
D. On surface-mounted panelboards, install nameplates on the front of the door centered above or below manufacturer’s nameplate.
E. Labels Inside of Enclosures - Center beneath respective components, clearly visible and readily associated with the equipment which they are intended to identify.
F. Inside enclosures and wireways indicate the origin or destination of all connected conduit.
3.3 DIRECTORY CARDS
A. Permanently fasten directory card in place behind protecting glass or clear plastic cover.
Remote equipment names must match directory.
3.4 CONDUIT SYSTEM
A. Identify conduit numbers as shown on motor control center or power distribution schedule or diagrams and as shown on Contract Drawings.
B. Provide markers on exposed conduit.
1. At each device.
2. At junction boxes with more than one incoming and outgoing conduit.
3. At each point of entry to or exit from a room.
4. At 50 feet on center in runs exceeding 100 feet.
3.5 WIRE MARKERS
A. All wiring except primary service conductors and motor power conductors, including spares, shall be labeled at each end of the conductor. Wires shall also be labeled at each junction box, panelboard gutter, pullbox, and load connection.
B. Contractor shall have a portable label maker in the field at all times.
Herbert, Rowland & Grubic, Inc. 26 05 53-6 11139.0465
3.6 OPERATIONAL SAFETY AND WARNING SIGNS
A. Where detailed instructions or explanations are needed, provide sign with clearly-written messages appropriate for the situation (i.e., at automatically started equipment, sign to read: “Danger, This Equipment Automatically Starts - Stay Back”). Contractor shall provide up to 20 such signs. Actual number and specific wording will be provided to the Contractor.
B. Provide the following sign on each motor control center’s main circuit breaker compartment: “Warning - Circuit Breaker Line Terminals May Be Energized with Circuit Breaker Open.”
C. Provide a warning sign at each motor control center, switchboard, load center, distribution panelboard, or similar device “Danger - High Voltage - Keep Out - Authorized Personnel Only.” Add the voltage in a separate sign.
3.7 UNDERGROUND WARNING TAPE
A. Provide continuous underground warning tape above all ductbank(s) or individual conduits in accordance with ductbank detail.
3.8 ARC FLASH SIGNS
A. Provide signs at locations required by NFPA 70, NFPA 110.16, and NFPA 70E; and in accordance with the approved arc flash study required by Section 26 05 73 - Power System Study and Testing.
END OF SECTION
File details come from the government source that posted it. Updated .