41 22 23.16 - Portable Hoists.pdf

PDF 222 KB Posted

Attached to
Skytop Lodge Sewage Treatment Plant Improvements Project – Contract : 2026-01- Project Number 005153. 0436
Solicitation number
Not on record
Issued by
Monroe County, Pennsylvania

About this file

This is a specification document for portable hoists required for the Skytop Lodge Sewage Treatment Plant Improvements Project in Pennsylvania, a municipal wastewater treatment facility upgrade project. The scope of work requires the provision of one (1) portable Davit crane with a minimum loading rating of 1,000 pounds to be used for the Equalization Tank Pumps and the Recirculation Pump Station Pumps. The hoist must feature an adjustable boom angle with 360-degree rotation constructed of 304 stainless steel, a 40-foot stainless steel cable, a stainless steel swivel hook, and a manual winch. Acceptable manufacturers include Thern, Inc., ProWinch, or equal products. The project bidding deadline is September 18, 2026 at 10:00 AM, with a pre-bid conference scheduled for August 25, 2026 at 10:30 AM at the Skytop Lodge STP facility in Canadensis, Pennsylvania. Bid security of no less than 10% in the form of a certified check or bid bond is required.

The specification requires compliance with multiple ASME standards (B30.5, B30.7, B30.16, HST series standards), ASTM standards for materials, NEMA electrical standards, and OSHA regulations for overhead cranes. Contractors must submit comprehensive product data, manufacturer certifications, assembly instructions, and certified load test results. The equipment must be tested in the presence of the engineer and demonstrated to the owner's personnel, with all limit switches and hoist controls verified for proper operation. Equipment must comply with ASME B30.16 and OSHA 1910.179 standards for installation and testing. The document does not specify pricing terms, set-asides, or contract duration details within its technical specification scope.

View the file

Other files

File Type Posted
33 05 97 - Identification And Signage For Utilities.pdf PDF
26 29 13 - Contactors and Motor Starting Equipment.pdf PDF
26 05 10 - Basic Electrical Materials & Methods.pdf PDF
01 78 36 - Warranties.pdf PDF
26 12 19.01 - Liquid Filled Medium Voltage Pad Mounted Transformers.pdf PDF
01 61 00 - Product Requirements.pdf PDF
03 39 00 - Concrete Curing.pdf PDF
00 01 07 - Seal Page.pdf PDF
01 78 39 - Project Record Documents.pdf PDF
01 29 00 - Payment Procedures.pdf PDF
01 73 00 - Execution Requirements.pdf PDF
43 26 13 - Submersible Sewage Pumps.pdf PDF
33 05 77 Packaged Metering Manhole.pdf PDF
01 10 00 - Project Summary.pdf PDF
26 05 73 - Power System Study and Testing.pdf PDF
00 65 19.16 - Affidavit of Release of Liens.pdf PDF
02 41 19.13 - SELECTIVE BUILDING DEMOLITION.pdf PDF
33 05 05.36 - Vacuum Testing.pdf PDF
40 05 51 - Common Requirements For Process Valves.pdf PDF
01 26 13 - Requests for Interpretation.pdf PDF
00 73 36 - Equal Employment Opportunity Requirements.pdf PDF
40 05 62 - Plug Valves.pdf PDF
26 24 16 - Panelboards.pdf PDF
00 45 36 EEO Certificate.pdf PDF
46 66 16 - Trojan Open Channel UV Disinfection System.pdf PDF
00 72 00 - General Conditions 2018.pdf PDF
40 23 23 - Potable Water Process Piping.pdf PDF
31 23 19 - Dewatering.pdf PDF
40 95 34 a- IOList Table.pdf PDF
01 50 00 - Temporary Facilities and Controls.pdf PDF
00 31 32 - Geotechnical Data.pdf PDF
01 57 28 - Temporary Flow Control.pdf PDF
31 05 16 - Aggregate for Earthwork.pdf PDF
00 65 19.23 - Notice of Acceptability of Work.pdf PDF
00 60 00 - Project Forms.pdf PDF
01 22 00 - Unit Prices.pdf PDF
06 10 00 - Rough Carpentry.pdf PDF
40 05 53 - Identification For Process Piping.pdf PDF
06 17 53 - Shop-Fabricated Wood Trusses.pdf PDF
00 45 19 Non Collusion Affidavit.pdf PDF
40 05 23 - Stainless Steel Process Pipe And Tubing.pdf PDF
26 05 33.16 - Boxes.pdf PDF
26 05 29 - Electrical Supports, Anchors and Fasteners.pdf PDF
26 32 13 - Packaged Engine Generator Systems.pdf PDF
31 23 16.13 - Trenching.pdf PDF
01 33 00 - Submittal Procedures.pdf PDF
46 43 21 Packaged Wastewater Treatment Plant Equipment.pdf PDF
13 34 00 - Pre-engineered Post Frame Structures.pdf PDF
01 41 26 - Permit Requirements.pdf PDF
33 14 16 - Site Water Utility Distribution Piping.pdf PDF
Show 40 more

Latest 50 of 157 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

41 22 23.16 - PORTABLE HOISTS

Herbert, Rowland & Grubic, Inc. 41 22 23.16 - 1 005153.0436

SECTION 41 22 23.16 - PORTABLE HOISTS

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Portable floor hoists.

1.2 SYSTEM DESCRIPTION

A. General:

1. Provide one (1) portable Davit Crane to be moved and used for the Equalization

Tank Pumps and the Recirculation Pump Station Pumps.

1.3 REFERENCE STANDARDS

A. ASME International:

1. ASME B30.5 - Mobile and Locomotive Cranes.

2. ASME B30.7 - Winches.

3. ASME B30.16 - Overhead Hoists (Underhung).

4. ASME HST-1 - Performance Standard for Electric Chain Hoists.

5. ASME HST-2 - Performance Standard for Hand Chain Manually Operated Chain

Hoists.

6. ASME HST-3 - Performance Standard for Manually Lever Operated Chain Hoists.

7. ASME HST-4 - Performance Standard for Overhead Electric Wire Rope Hoists.

8. ASME HST-5 - Performance Standard for Air Chain Hoists.

9. ASME PALD - Safety Standard for Portable Automotive Lifting Devices.

B. ASTM International:

1. ASTM A580/A580M - Standard Specification for Stainless Steel Wire.

2. ASTM A1023/A1023M - Standard Specification for Stranded Carbon Steel Wire

Ropes for General Purposes.

C. National Electrical Manufacturers Association:

1. NEMA 250 - Enclosures for Electrical Equipment (1000 Volts Maximum).

2. NEMA 535 - Safety Alerting Standards.

D. Occupational Safety and Health Administration:

1. OSHA 1910.179 - Overhead and Gantry Cranes.

1.4 SUBMITTALS

A. Section 01 33 00 - Submittal Procedures: Requirements for submittals.

B. Product Data: Submit manufacturer catalog information for the hoist, including materials, weights, dimensions, and capacities.

Herbert, Rowland & Grubic, Inc. 41 22 23.16 - 2 005153.0436

C. Submittals shall also consist of the following:

1. Descriptive literature, bulletins, or other data supportive of the crane equipment’s capability of fulfilling the requirements of this specification.

2. Complete list of equipment with the Manufacturer’s name and model numbers.

3. Operation and Maintenance Data: As defined in Section 01 78 23 “Operation and

Maintenance Data.”

4. Submit assembly instruction when shipping equipment.

5. Submit certified test results of load tests for cranes.

1.5 CLOSEOUT SUBMITTALS

A. Section 01 77 00 - Closeout Procedures: Requirements for submittals.

B. Project Record Documents: Record actual locations of portable hoists.

C. Operation and Maintenance Data:

1. Submit assembly views.

2. Submit replacement part numbers and availability.

1.6 QUALIFICATIONS

A. Manufacturer:

1. Company specializing in manufacturing products specified in this Section with minimum three years' documented experience.

1.7 QUALITY ASSURANCE

A. Verify hook and lift heights for each application to assure each system is completely operational over range intended.

1.8 WARRANTY

A. Section 01 78 36 - Warranties: Requirements for warranties.

PART 2 - PRODUCTS

2.1 PORTABLE FLOOR HOISTS

A. Manufacturers:

1. Thern, Inc.

2. ProWinch.

3. Or equal.

B. Loading Rating: 1,000 pounds (minimum).

C. Crane: Adjustable Boom Angle, 360 degree rotation, 304 stainless steel.

D. Cable: 40 feet, ¼-inch 304 stainless steel.

E. Hook: SS swivel hook.

Herbert, Rowland & Grubic, Inc. 41 22 23.16 - 3 005153.0436

F. Winch: Manual Winch.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Section 01 73 00 - Execution Requirements: Requirements for installation examination.

B. Verify that field dimensions are as indicated on Shop Drawings.

C. Verify that items provided by other Sections of Work are ready to receive Work of this Section.

3.2 INSTALLATION

A. According to manufacturer instructions and as indicated on Drawings.

B. Comply with ASME B30.16 and OSHA 1910.179.

3.3 FIELD QUALITY CONTROL

A. Section 01 40 00 - Quality Requirements: Requirements for inspecting and testing.

B. Testing:

1. Verify that hoist and controls operate as required.

2. Verify that limit switches operate as required.

3. Test Load Certification:

a. Comply with OSHA 1910.179.

b. Test in presence of Engineer.

C. Equipment Acceptance:

1. Adjust, repair, modify, or replace components failing to perform as specified and rerun tests.

2. Make final adjustments to equipment under direction of manufacturer's representative.

D. Repair damaged coatings with material equal to original coating.

3.4 DEMONSTRATION

A. Section 01 73 00 - Execution Requirements: Requirements for demonstration and training.

B. Demonstrate hoist operation, routine maintenance, and emergency repair procedures to Owner's personnel.

END OF SECTION