40 95 34 a- IOList Table.pdf
PDF 176 KB Posted
- Attached to
- Skytop Lodge Sewage Treatment Plant Improvements Project – Contract : 2026-01- Project Number 005153. 0436
- Solicitation number
- Not on record
- Issued by
- Monroe County, Pennsylvania
About this file
This is an Input/Output (I/O) List document for the SCADA Operating System supporting the Skytop Lodge Sewage Treatment Plant Upgrade Project in Pennsylvania. The document provides detailed technical specifications for control panels and monitoring systems across multiple treatment process areas, including the Influent Screen Control Panel (10-CP-101), Equalization Tank Control Panel (10-CP-102), and Recirculation Wet Well & Secondary Clarifier Control Panel (40-CP-400). The I/O list identifies 67 distinct inputs and outputs encompassing level sensors, float switches, pump and blower controls, flow meters, and alarm systems distributed across influent screening, equalization, recirculation, clarification, post-aeration, and backup power management functions. Each line item specifies equipment tags, signal types (analog or digital), operational ranges, source and destination control panels, and implementation remarks indicating whether data connections are contiguous registers, hardwired, VFD Ethernet parameters, spare holding registers, or Modbus communications.
The document serves as the technical blueprint for systems integration and configuration, with all marked items designated for implementation by the systems integrator or through specified communication protocols. The Autodialer (40-AD-400) and Automatic Transfer Switch (40-ATS-400) inputs provide facility-wide alarm notification and generator backup power monitoring capabilities. The I/O list was prepared as of April 27, 2026, corresponding to the bid opening scheduled for September 18, 2026, with a pre-bid conference held on August 25, 2026 at the Skytop Lodge STP location in Canadensis, Pennsylvania. Bid security of 10 percent is required from contractors responding to Contract 2026-01, Project Number 005153.0436.
View the file
Other files
Show 40 more
Latest 50 of 157 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
I/O List for SCADA Operating System Skytop WWTP Upgrade
Location Letter Number Ind
INFLUENT SCREEN CONTROL PANEL (10-CP-101)
10 LE 101 A INFLUENT CHANNEL UPSTREAM LEVEL LEVEL AI FEET LE-101 10-CP-101 2
10 LE 102 A INFLUENT CHANNEL DOWNSTREAM LEVEL LEVEL AI FEET LE-102 10-CP-101 2
10 SV 101 A AUGER SPRAY SOLENOID VALVE ON DO OFF ON 10-CP-101 10-SV-101 2
10 SV 102 A PRESS ZONE SOLENOID VALVE ON DO OFF ON 10-CP-101 10-SV-102 2
EQUALIZATION TANK CONTROL PANEL (10-CP-102)
10 LE 103 A EQ TANK LEVEL LEVEL AI FEET LE-103 10-CP-102 2
10 LSH 101 A EQ TANK HIGH LEVEL FLOAT SWITCH HIGH LEVEL DI NORMAL HIGH LEVEL LSH-101 10-CP-102 2
10 LSL 102 A EQ TANK LOW LEVEL FLOAT SWITCH LOW LEVEL DI NORMAL LOW LEVEL LSL-101 10-CP-102 2
10 P 101 A EQ TANK PUMP #1 VFD START DO STOP START 10-CP-102 VFD-P-101 2
10 P 101 B EQ TANK PUMP #1 VFD RUNNING DI STOPPED RUNNING VFD-P-101 10-CP-102 2
10 P 101 C EQ TANK PUMP #1 VFD VFD FAIL DI NORMAL FAIL VFD-P-101 10-CP-102 2
10 P 102 A EQ TANK PUMP #2 VFD START DO STOP START 10-CP-102 VFD-P-102 2
10 P 102 B EQ TANK PUMP #2 VFD RUNNING DI STOPPED RUNNING VFD-P-102 10-CP-102 2
10 P 102 C EQ TANK PUMP #2 VFD VFD FAIL DI NORMAL FAIL VFD-P-102 10-CP-102 2
10 B 101 A EQ TANK BLOWER #1 START DO STOP START 10-CP-102 10-B-101 (STARTER) 2
10 B 101 B EQ TANK BLOWER #1 OVERLOAD DI NORMAL OVERLOAD 10-B-101 (STARTER) 10-CP-102 2
10 B 101 C EQ TANK BLOWER #1 MOTOR OVERTEMP DI NORMAL OVERTEMP 10-B-101 10-CP-102 2
10 B 102 A EQ TANK BLOWER #2 START DO STOP START 10-CP-102 10-B-102 (STARTER) 2
10 B 102 B EQ TANK BLOWER #2 OVERLOAD DI NORMAL OVERLOAD 10-B-102 (STARTER) 10-CP-102 2
10 B 102 C EQ TANK BLOWER #2 MOTOR OVERTEMP DI NORMAL OVERTEMP 10-B-102 10-CP-102 2
RECIRCULATION WET WELL & SECONDARY CLARIFIER CONTROL PANEL (40-CP-400)
20 LE 200 A RECIRULATION WET WELL LEVEL LEVEL AI FEET LE-200 40-CP-400 2
20 LSH 200 A RECIRULATION WET WELL HIGH LEVEL FLOAT SWITCH HIGH LEVEL DI NORMAL HIGH LEVEL LSH-200 40-CP-400 2
20 LSL 200 A RECIRULATION WET WELL LOW LEVEL FLOAT SWITCH LOW LEVEL DI NORMAL LOW LEVEL LSL-200 40-CP-400 2
Remarks Equipment Tag
Description Analog/Digital (True)
Condition Signal Range/Off Status Units/On Status Source Destination
4/27/2026 HRG 1
20 P 201 A RECIRCULATION PUMP #1 VFD START DO STOP START 40-CP-400 VFP-P-201 2
20 P 201 B RECIRCULATION PUMP #1 VFD RUNNING DI STOPPED RUNNING VFP-P-201 40-CP-400 2
20 P 201 C RECIRCULATION PUMP #1 VFD VFD FAIL DI NORMAL FAIL VFP-P-201 40-CP-400 2
20 P 202 A RECIRCULATION PUMP #2 VFD START DO STOP START 40-CP-400 VFP-P-202 2
20 P 202 B RECIRCULATION PUMP #2 VFD RUNNING DI STOPPED RUNNING VFP-P-202 40-CP-400 2
20 P 202 C RECIRCULATION PUMP #2 VFD VFD FAIL DI NORMAL FAIL VFP-P-202 40-CP-400 2
30 P 301 A SECONDARY CLARIFIER PUMP #1 VFD START DO STOP START 40-CP-400 VFP-P-301 2
30 P 301 B SECONDARY CLARIFIER PUMP #1 VFD RUNNING DI STOPPED RUNNING VFP-P-301 40-CP-400 2
30 P 301 C SECONDARY CLARIFIER PUMP #1 VFD VFD FAIL DI NORMAL FAIL VFP-P-301 40-CP-400 2
30 P 302 A SECONDARY CLARIFIER PUMP #2 VFD START DO STOP START 40-CP-400 VFP-P-302 2
30 P 302 B SECONDARY CLARIFIER PUMP #2 VFD RUNNING DI STOPPED RUNNING VFP-P-302 40-CP-400 2
30 P 302 C SECONDARY CLARIFIER PUMP #2 VFD VFD FAIL DI NORMAL FAIL VFP-P-302 40-CP-400 2
30 P 303 A SECONDARY CLARIFIER PUMP #3 VFD START DO STOP START 40-CP-400 VFP-P-303 2
30 P 303 B SECONDARY CLARIFIER PUMP #3 VFD RUNNING DI STOPPED RUNNING VFP-P-303 40-CP-400 2
30 P 303 C SECONDARY CLARIFIER PUMP #3 VFD VFD FAIL DI NORMAL FAIL VFP-P-303 40-CP-400 2
30 P 304 A SECONDARY CLARIFIER PUMP #4 VFD START DO STOP START 40-CP-400 VFP-P-304 2
30 P 304 B SECONDARY CLARIFIER PUMP #4 VFD RUNNING DI STOPPED RUNNING VFP-P-304 40-CP-400 2
30 P 304 C SECONDARY CLARIFIER PUMP #4 VFD VFD FAIL DI NORMAL FAIL VFP-P-304 40-CP-400 2
30 LSH 301 A EQ TANK #1 LOW LEVEL FLOAT SWITCH LOW LEVEL DI NORMAL LOW LEVEL LSH-301 40-CP-400 2
30 LSH 302 A EQ TANK #2 LOW LEVEL FLOAT SWITCH LOW LEVEL DI NORMAL LOW LEVEL LSH-302 40-CP-400 2
40 B 301 A POST AERATION BLOWER #1 START DO STOP START 40-CP-400 40-B-301 (STARTER) 2
40 B 301 B POST AERATION BLOWER #1 OVERLOAD DI NORMAL OVERLOAD 40-B-301 (STARTER) 40-CP-400 2
40 B 301 C POST AERATION BLOWER #1 MOTOR OVERTEMP DI NORMAL OVERTEMP 40-B-301 40-CP-400 2
40 B 302 A POST AERATION BLOWER #2 START DO STOP START 40-CP-400 40-B-302 (STARTER) 2
40 B 302 B POST AERATION BLOWER #2 OVERLOAD DI NORMAL OVERLOAD 40-B-302 (STARTER) 40-CP-400 2
40 B 302 C POST AERATION BLOWER #2 MOTOR OVERTEMP DI NORMAL OVERTEMP 40-B-302 40-CP-400 2
AUTODIALER '40-AD-400'
40 CP 400 A 10-CP-101: SYSTEM FAIL FAIL DI NORMAL FAIL 10-CP-101 40-AD-400 2
40 CP 400 B 10-CP-102: EQ TANK HIGH LEVEL HIGH LEVEL DI NORMAL HIGH LEVEL 10-CP-102 40-AD-400 2
40 CP 400 C 40-CP-400: RECIRCULATION WET WELL HIGH LEVEL HIGH LEVEL DI NORMAL HIGH LEVEL 40-CP-400 40-AD-400 2
40 CP 400 D 40-CP-400: SECONDARY CLARIFIER GENERAL ALARM GENERAL ALARM DI NORMAL ALARM 40-CP-400 40-AD-400 2
40 CP 400 E 40-CP-400: INFLUENT FLOW METER FLOW AI GPM 40-CP-400 40-AD-400 2
40 CP 400 F 40-CP-400: EFLUENT FLOW METER FLOW AI GPM 40-CP-400 40-AD-400 2
40 CP 400 G 40-CP-400: EQ TANK LEVEL LEVEL AI FEET 40-CP-400 40-AD-400 2
4/27/2026 HRG 2
40 ATS 400 A 40-ATS-400: UTILITY POWER FAILURE UTILITY OUTAGE DI NORMAL UTILITY OUTAGE 40-ATS-400 40-AD-400 2
40 ATS 400 B 40-ATS-400: ATS TRANSFER FAIL ATS TRANSFER FAIL DI NORMAL FAIL 40-ATS-400 40-AD-400 2
40 ATS 400 C 40-ATS-400: GENERATOR POWER GENERATOR POWER DI NORMAL ON GENERATOR 40-ATS-400 40-AD-400 2
40 GEN 400 A 40-GEN-400: GENERATOR FAULT GENERATOR FAULT DI NORMAL FAIL 40-GEN-400 40-AD-400 2
REMARKS:
1. ITEMS MARKED WITH A '1' IN THE REMARKS COLUMN, DATA TO BE PLACED IN CONTIGUOUS REGISTERS FOR IMPLEMENTATION ONTO THE SCADA SYSTEM BY THE SYSTEMS INTEGRATOR
2. ITEMS MARKED WITH A '2' IN THE REMARKS COLUMN, HARDWIRED
3. ITEMS MARKED WITH A '3' IN THE REMARKS COLUMN, VFD ETHERNET PARAMETERS
4. ITEMS MARKED WITH A '4' IN THE REMARKS COLUMN, SPARE IO HOLDING REGISTERS
5. ITEMS MARKED WITH A '5' IN THE REMARKS COLUMN, MODBUS COMMUNICATION
4/27/2026 HRG 3