06 17 53 - Shop-Fabricated Wood Trusses.pdf
PDF 245 KB Posted
- Attached to
- Skytop Lodge Sewage Treatment Plant Improvements Project – Contract : 2026-01- Project Number 005153. 0436
- Solicitation number
- Not on record
- Issued by
- Monroe County, Pennsylvania
About this file
This is a specification document for shop-fabricated wood trusses prepared by Herbert, Rowland & Grubic, Inc. for the Skytop Lodge Sewage Treatment Plant Improvements Project (Contract 2026-01, Project Number 005153.0436) in Pennsylvania. The specification establishes requirements for metal-plate-connected wood trusses used in roof framing, bridging, bracing, and anchorage applications. The document mandates compliance with industry standards including TPI 1 (National Design Standard for Metal Plate Connected Wood Truss Construction), ASTM specifications, and APA guidelines. Key performance requirements include structural design loads with maximum vertical deflection of 1/240 of span for roof trusses, fabrication within manufacturing tolerances established by TPI 1, and installation by qualified fabricators participating in recognized quality-assurance programs with third-party inspection. Dimension lumber must comply with DOC PS 20 standards with minimum chord sizes of 2 by 6 inches nominal and maximum moisture content of 19 percent at time of dressing. Metal connector plates must be obtained from a single manufacturer—specifically Alpine Engineered Products, Inc., MiTek Industries, Inc., or approved equivalent—and fabricated to TPI 1 specifications using hot-dip galvanized-steel sheet per ASTM A 653/A 653M with G60 coating designation and minimum thickness of 0.036 inch.
The specification requires submission of detailed shop drawings showing truss location, pitch, span, camber, configuration, spacing, lumber specifications, permanent bracing locations, and metal connector plate details, along with delegated-design submittals signed and sealed by qualified professional engineers. Trusses must be stored flat off the ground, protected from weather with waterproof sheeting, and handled according to TPI BCSI guidelines. Installation requires trusses to be placed plumb, square, and true to line with permanent bracing installed during erection before construction loads are applied; field alterations such as cutting, drilling, notching, or removing truss members are prohibited. Damaged galvanized coatings on exposed surfaces must be repaired with galvanized repair paint complying with ASTM A 780, and wood trusses exposed to moisture despite protection must receive EPA-registered borate treatment. The pre-bid conference is scheduled for August 25, 2026 at 10:30 AM at Skytop Lodge STP in Canadensis, Pennsylvania, with bids due September 18, 2026 at 10:00 AM through PennBid; bid security of at least 10 percent in the form of a certified check or bid bond is required.
View the file
Other files
Show 40 more
Latest 50 of 157 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
06 17 53 - SHOP-FABRICATED WOOD TRUSSES
Herbert, Rowland & Grubic, Inc. 06 17 53 - 1 005153.0436
SECTION 06 17 53 - SHOP-FABRICATED WOOD TRUSSES
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Shop-fabricated wood trusses for:
a. Roof framing.
b. Bridging, bracing, and anchorage.
B. Related Requirements:
1. Section 06 10 00 – Rough Carpentry.
2. Section 06 16 00 – Sheathing.
1.2 REFERENCE STANDARDS
A. American Wood Protection Association:
1. AWPA M4 - Standard for the Care of Preservative-Treated Wood Products.
2. AWPA U1 - Use Category System: User Specification for Treated Wood.
B. APA - The Engineered Wood Association:
1. APA/EWA Plywood Design Specification.
C. ASTM International:
1. ASTM A153 - Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel
Hardware.
2. ASTM A240 - Standard Specification for Chromium and Chromium-Nickel
Stainless Steel Plate, Sheet, and Strip for Pressure Vessels and for General Applications.
3. ASTM A666 - Standard Specification for Annealed or Cold-Worked Austenitic Stainless Steel Sheet, Strip, Plate, and Flat Bar.
4. ASTM B695 - Standard Specification for Coatings of Zinc Mechanically Deposited on Iron and Steel.
5. ASTM E84 - Standard Test Method for Surface Burning Characteristics of Building Materials.
6. ASTM E119 - Standard Test Methods for Fire Tests of Building Construction and Materials.
7. ASTM F1667 - Standard Specification for Driven Fasteners: Nails, Spikes, and Staples.
D. California Department of Public Health:
1. CA/DHS/EHLB/R-174 - Standard Practice for the Testing of Volatile Organic
Emissions from Various Sources Using Small-Scale Environmental Chambers (includes Addendum 2004).
E. Forest Stewardship Council:
1. FSC Guidelines.
Herbert, Rowland & Grubic, Inc. 06 17 53 - 2 005153.0436
F. National Particleboard Association:
1. NPA A208.1 - Particleboard.
G. Redwood Inspection Service:
1. RIS - Standard Specifications for Grades of California Redwood Lumber.
H. Southern Pine Inspection Bureau:
1. SPIB - Standard Grading Rules for Southern Pine Lumber.
I. Truss Plate Institute:
1. TPI - Building Component Safety Information (BCSI): Guide to Good Practice for
Handling, Installing, Restraining & Bracing of Metal Plate Connected Wood Trusses.
2. TPI DSB - Recommended Design Specification for Temporary Bracing of Metal Plate Connected Wood Trusses.
3. TPI 1 - National Design Standard for Metal Plate Connected Wood Truss Construction.
J. U.S. Department of Commerce - National Institute of Standards and Technology:
1. Voluntary Product Standard PS 1 - Structural Plywood.
2. Voluntary Product Standard PS 2 - Performance Standard for Wood-Based
Structural-Use Panels.
3. Voluntary Product Standard PS 20 - American Softwood Lumber Standard.
K. West Coast Lumber Inspection Bureau:
1. WCLIB Standard 17 - Grading Rules for West Coast Lumber.
L. Western Wood Products Association:
1. WWPA G-5 - Western Lumber Grading Rules.
1.3 COORDINATION
A. Coordinate work under provisions of Section 01 31 13.
B. Coordinate placement of sheathing with Work of this Section.
1.4 SUBMITTALS
A. Section 01 33 00 - Submittal Procedures: Requirements for submittals.
B. Shop Drawings: Show fabrication and installation details for trusses:
1. Show location, pitch, span, camber, configuration, and spacing for each type of truss required.
2. Indicate sizes, stress grades, and species of lumber.
3. Indicate locations of permanent bracing required to prevent buckling of individual truss members due to design loads.
4. Indicate locations, sizes, and materials for permanent bracing required to prevent buckling of individual truss members due to design loads.
5. Indicate type, size, material, finish, design values, orientation, and location of metal connector plates.
Herbert, Rowland & Grubic, Inc. 06 17 53 - 3 005153.0436
6. Show splice details and bearing details.
C. Delegated-Design Submittal: For metal-plate-connected wood trusses indicated to comply with performance requirements and design criteria, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation.
D. Qualification Data: For metal connector-plate manufacturer, professional engineer and fabricator.
E. Material Certificates: For dimension lumber specified to comply with minimum specific gravity. Indicate species and grade selected for each use and specific gravity.
F. Product Certificates: For metal-plate-connected wood trusses, signed by officer of truss fabricating firm.
G. Evaluation Reports: For the following, from ICC-ES:
1. Metal-plate connectors.
2. Metal truss accessories.
1.5 QUALITY ASSURANCE
A. Metal Connector-Plate Manufacturer Qualifications: A manufacturer that is a member of TPI and that complies with quality-control procedures in TPI 1 for manufacture of connector plates:
1. Manufacturer's responsibilities include providing professional engineering services needed to assume engineering responsibility.
2. Engineering Responsibility: Preparation of Shop Drawings and comprehensive engineering analysis by a qualified professional engineer.
B. Fabricator Qualifications: Shop that participates in a recognized quality-assurance program that complies with quality-control procedures in TPI 1 and that involves third-party inspection by an independent testing and inspecting agency acceptable to Engineer and authorities having jurisdiction.
C. Testing Agency Qualifications: For testing agency providing classification marking for fire-retardant treated material, an inspection agency acceptable to authorities having jurisdiction that periodically performs inspections to verify that the material bearing the classification marking is representative of the material tested.
1.6 DELIVERY, STORAGE, AND HANDLING
A. Handle and store trusses to comply with recommendations in TPI BCSI, "Building Component Safety Information: Guide to Good Practice for Handling, Installing, Restraining, & Bracing Metal Plate Connected Wood Trusses:"
1. Store trusses flat, off of ground, and adequately supported to prevent lateral bending.
2. Protect trusses from weather by covering with waterproof sheeting, securely anchored.
3. Provide for air circulation around stacks and under coverings.
Herbert, Rowland & Grubic, Inc. 06 17 53 - 4 005153.0436
B. Inspect trusses showing discoloration, corrosion, or other evidence of deterioration.
Discard and replace trusses that are damaged or defective.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Delegated Design: Engage a qualified professional engineer, as defined in Section 01 40 00 "Quality Requirements," to design metal-plate-connected wood trusses.
B. Structural Performance: Provide metal-plate-connected wood trusses capable of withstanding design loads within limits and under conditions indicated. Comply with requirements in TPI 1 unless more stringent requirements are specified below:
1. Design Loads: As indicated.
2. Maximum Deflection Under Design Loads:
a. Roof Trusses: Vertical deflection of 1/240 of span.
C. Comply with applicable requirements and recommendations of the following publications:
1. TPI 1, "National Design Standard for Metal Plate Connected Wood Truss
Construction."
2. TPI DSB, "Recommended Design Specification for Temporary Bracing of Metal
Plate Connected Wood Trusses."
3. TPI BCSI, "Building Component Safety Information: Guide to Good Practice for
Handling, Installing, Restraining, & Bracing Metal Plate Connected Wood Trusses."
D. Wood Structural Design Standard: Comply with applicable requirements in AF&PA's "National Design Specifications for Wood Construction" and its "Supplement."
2.2 DIMENSION LUMBER
A. Lumber: DOC PS 20 and applicable rules of grading agencies indicated. If no grading agency is indicated, provide lumber that complies with the applicable rules of any rules writing agency certified by the ALSC Board of Review. Provide lumber graded by an agency certified by the ALSC Board of Review to inspect and grade lumber under the rules indicated:
1. Factory mark each piece of lumber with grade stamp of grading agency.
2. Provide dressed lumber, S4S.
3. Provide dry lumber with 19 percent maximum moisture content at time of dressing.
B. Minimum Chord Size for Roof Trusses: 2 by 6 inches nominal for both top and bottom chords].
C. Permanent Bracing: Provide wood bracing that complies with requirements for miscellaneous lumber in Section 06 10 00 - Rough Carpentry.
Herbert, Rowland & Grubic, Inc. 06 17 53 - 5 005153.0436
2.3 METAL CONNECTOR PLATES
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Alpine Engineered Products, Inc.; an ITW company.
2. MiTek Industries, Inc.; a subsidiary of Berkshire Hathaway Inc.
3. Or Equal.
B. Source Limitations: Obtain metal connector plates from single manufacturer.
C. General: Fabricate connector plates to comply with TPI 1.
D. Hot-Dip Galvanized-Steel Sheet: ASTM A 653/A 653M; Structural Steel (SS), high-strength low-alloy steel Type A (HSLAS Type A), or high-strength low-alloy steel Type B (HSLAS Type B); G60 coating designation; and not less than 0.036 inch thick:
1. Use for all locations unless otherwise indicated.
2.4 FASTENERS
A. General: Provide fasteners of size and type indicated that comply with requirements specified in this article for material and manufacture:
1. Provide fasteners for use with metal framing anchors that comply with written recommendations of metal framing manufacturer.
2. Where trusses are exposed to weather, in ground contact, made from pressure-preservative treated wood, or in area of high relative humidity, provide fasteners with hot-dip zinc coating complying with ASTM A 153/A 153M.
B. Nails, Brads, and Staples: ASTM F 1667.
2.5 METAL FRAMING ANCHORS AND ACCESSORIES
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Simpson Strong-Tie Co., Inc.
2. USP Structural Connectors.
3. Or Equal.
B. Allowable Design Loads: Provide products with allowable design loads, as published by manufacturer that meet or exceed those indicated. Manufacturer's published values shall be determined from empirical data or by rational engineering analysis and demonstrated by comprehensive testing performed by a qualified independent testing agency.
C. Galvanized-Steel Sheet: Hot-dip, zinc-coated steel sheet complying with ASTM A 653/A 653M, G60 (Z180) coating designation:
1. Use for interior locations unless otherwise indicated.
2.6 MISCELLANEOUS MATERIALS
A. Galvanizing Repair Paint: SSPC-Paint 20, with dry film containing a minimum of 94 percent zinc dust by weight.
Herbert, Rowland & Grubic, Inc. 06 17 53 - 6 005153.0436
2.7 FABRICATION
A. Cut truss members to accurate lengths, angles, and sizes to produce close-fitting joints.
B. Fabricate metal connector plates to sizes, configurations, thicknesses, and anchorage details required to withstand design loads for types of joint designs indicated.
C. Assemble truss members in design configuration indicated; use jigs or other means to ensure uniformity and accuracy of assembly with joints closely fitted to comply with tolerances in TPI 1. Position members to produce design camber indicated:
1. Fabricate wood trusses within manufacturing tolerances in TPI 1.
D. Connect truss members by metal connector plates located and securely embedded simultaneously in both sides of wood members by air or hydraulic press.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Section 01 73 00 - Execution Requirements: Requirements for erection examination.
B. Verify that supports and openings are ready to receive trusses.
3.2 ERECTION
A. Install wood trusses only after supporting construction is in place and is braced and secured.
B. If trusses are delivered to Project site in more than one piece, assemble trusses before installing.
C. Hoist trusses in place by lifting equipment suited to sizes and types of trusses required, exercising care not to damage truss members or joints by out-of-plane bending or other causes.
D. Install and brace trusses according to TPI recommendations and as indicated.
E. Install trusses plumb, square, and true to line and securely fasten to supporting construction.
F. Space trusses as indicated; adjust and align trusses in location before permanently fastening.
G. Anchor trusses securely at bearing points as indicated on the drawings. Install fasteners through each fastener hole in metal framing anchors according to manufacturer's fastening schedules and written instructions.
H. Install and fasten permanent bracing during truss erection and before construction loads are applied. Anchor ends of permanent bracing where terminating at walls or beams:
1. Install bracing to comply with Section 06 10 00 - Rough Carpentry.
Herbert, Rowland & Grubic, Inc. 06 17 53 - 7 005153.0436
2. Install and fasten strongback bracing vertically against vertical web of parallel-chord floor trusses at centers indicated.
I. Install wood trusses within installation tolerances in TPI 1.
J. Do not alter trusses in field. Do not cut, drill, notch, or remove truss members.
K. Replace wood trusses that are damaged or do not meet requirements:
1. Damaged trusses may be repaired according to truss repair details signed and sealed by the qualified professional engineer responsible for truss design, when approved by Engineer.
3.3 REPAIRS AND PROTECTION
A. Protect wood trusses from weather. If, despite protection, wood trusses become wet, apply EPA-registered borate treatment. Apply borate solution by spraying to comply with EPA-registered label.
B. Repair damaged galvanized coatings on exposed surfaces with galvanized repair paint according to ASTM A 780 and manufacturer's written instructions.
END OF SECTION