33 05 97 - Identification And Signage For Utilities.pdf
PDF 217 KB Posted
- Attached to
- Skytop Lodge Sewage Treatment Plant Improvements Project – Contract : 2026-01- Project Number 005153. 0436
- Solicitation number
- Not on record
- Issued by
- Monroe County, Pennsylvania
About this file
This is a technical specification document for identification and signage for utilities prepared by Herbert, Rowland & Grubic, Inc., in support of the Skytop Lodge Sewage Treatment Plant Improvements Project (Project Number 005153.0436) in Pennsylvania. The specification outlines requirements for pipeline marker posts, metal and plastic utility markers, marking flags, plastic ribbon tape, and trace wire to be installed as part of sewage treatment plant upgrades. The project includes installation of an influent screening system, equalization tank, chemical feed system, two clarifier tanks, post aeration tank, UV disinfection system, and related infrastructure. A pre-bid conference is scheduled for August 25, 2026, at 10:30 AM at Skytop Lodge STP in Canadensis, Pennsylvania, with bid opening on September 18, 2026, at 10:00 AM through PennBid. Bid security of not less than 10% in the form of a certified check or bid bond is required.
The specification details product requirements including stencils with semigloss enamel paint, flexible plastic pipe markers from manufacturers such as Seton Identification Products or Craftmark Pipe Markers, polyethylene ribbon tape minimum 6 inches wide by 4 mils thick with caution imprints for sanitary sewer, water, gas, and storm sewer applications, and 10-AWG Type THWN insulated copper tracer wire. Manufacturers must have minimum three years of documented experience. Installation requirements include placement of ribbon tape continuously over pipe, coordination with trenching operations per specification Section 31 23 16.13, and recording of actual valve locations in project record documents. Bidding documents are available exclusively through the PennBid website at https://pennbid.bonfirehub.com/, with periodic updates to addenda and other project information provided through this designated platform.
View the file
Other files
Show 40 more
Latest 50 of 157 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
33 05 97 - IDENTIFICATION AND SIGNAGE FOR UTILITIES
Herbert, Rowland & Grubic, Inc. 33 05 97 - 1 005153.0436
SECTION 33 05 97 - IDENTIFICATION AND SIGNAGE FOR UTILITIES
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Pipeline marker posts.
2. Metal utility markers.
3. Plastic utility markers.
4. Marking flags.
5. Plastic ribbon tape for placement above direct-buried utility.
6. Trace wire for placement above direct-buried utility.
B. Related Requirements:
1. Section 31 23 16.13 - Trenching: Backfilling considerations for installation of underground pipe markers.
2. Section 33 14 16 - Site Water Utility Distribution Piping: Piping, valves, and appurtenances requiring identification marking.
3. Section 33 31 11 - Sanitary Sewerage Gravity Piping: Piping, valves, and appurtenances requiring identification marking.
1.2 SUBMITTALS
A. Section 01 33 00 - Submittal Procedures: Requirements for submittals.
B. Product Data: Submit manufacturer catalog information for each specified product.
C. Manufacturer's Certificate: Certify that products meet or exceed specified requirements.
D. Qualifications Statement:
1. Submit qualifications for manufacturer.
1.3 CLOSEOUT SUBMITTALS
A. Section 01 77 00 - Closeout Procedures: Requirements for submittals.
B. Project Record Documents: Record actual locations of tagged valves.
1.4 QUALIFICATIONS
A. Manufacturer: Company specializing in manufacturing products specified in this Section with minimum three years' documented experience.
Herbert, Rowland & Grubic, Inc. 33 05 97 - 2 005153.0436
PART 2 - PRODUCTS
2.1 STENCILS
A. Description:
1. Quality: Clean-cut symbols.
2. Letters:
a. Up to 2-Inch OD of Insulation or Pipe: 1/2-inch-high letters.
b. b. 2-1/2- to 6-Inch OD of Insulation or Pipe: 1-inch-high letters.
c. c. More Than 6-Inch OD of Insulation or Pipe: 1-3/4-inch high letters.
B. Stencil Paint:
1. Description: Semigloss enamel.
2. As specified in Section 09 90 00 – Painting and Coating.
2.2 PIPE MARKERS
A. Plastic Pipe Markers:
1. Manufacturers:
a. Seton Identification Products.
b. Craftmark Pipe Markers.
c. Or equal.
2. Description:
a. Factory-fabricated, flexible, and semi-rigid plastic.
b. Preformed to fit around pipe or pipe covering.
c. Larger sizes may be of maximum sheet size, with spring fastener.
B. Plastic Tape Pipe Markers:
1. Description: Flexible, vinyl film tape with pressure-sensitive adhesive backing and printed markings.
2.3 RIBBON TAPE
A. Description:
1. Material: PE.
2. Brightly colored, continuously printed.
3. Minimum Size: 6 inches wide by 4 mils thick.
4. Manufactured for direct burial service.
5. Imprint:
a. CAUTION - SANITARY SEWER BELOW” in large letters.
b. “CAUTION – WATER BELOW” in large letters.
c. “CAUTION – GAS BELOW” in large letters.
d. “CAUTION – STORM SEWER BELOW” in large letters.
Herbert, Rowland & Grubic, Inc. 33 05 97 - 3 005153.0436
2.4 TRACER WIRE
A. Description:
1. Wire: Unshielded 10-AWG Type THWN insulated copper.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Pipeline Marker Posts, Utility Markers, and Marking Flags: According to manufacturer instructions.
B. Ribbon Tape:
1. Continuous over top of pipe.
2. If multiple pipes occur in common trench, locate tape above centerline of trench.
3. Coordinate with trench Work as specified in Section 31 23 16.13 – Trenching.
END OF SECTION