26 24 16 - Panelboards.pdf

PDF 269 KB Posted

Attached to
Skytop Lodge Sewage Treatment Plant Improvements Project – Contract : 2026-01- Project Number 005153. 0436
Solicitation number
Not on record
Issued by
Monroe County, Pennsylvania

About this file

This is a technical specification document for panelboards prepared by Herbert, Rowland & Grubic, Inc. for the Skytop Lodge Sewage Treatment Plant Improvements Project (Project Number 005153.0436) in Pennsylvania. The specification establishes requirements for three types of electrical panelboards: 480/277 VAC three-phase Power Panelboards (PP), 208/120 VAC three-phase Power Panelboards (PP), and 240/120 VAC single-phase panelboards (LP), with integral surge protection devices rated at 120 kA for all 240/120 panelboards. The project includes installation of sewage treatment plant upgrades with a public bid opening scheduled for Friday, September 18, 2026, at 10:00 AM through PennBid. A pre-bid conference is scheduled for August 25, 2026, at 10:30 AM at the Skytop Lodge STP facility in Canadensis, Pennsylvania. Panelboards must be completely factory assembled with UL listings per NEMA Standard PB-1 and Federal Specifications W-P-115b, double-row construction, full-sized copper buses, and moldcase circuit breakers with appropriate amperage ratings based on voltage classification.

Installation requirements mandate that panelboards be mounted with the top not exceeding 66 inches in height, that circuit loads be balanced evenly across phases within 10 percent imbalance tolerance, and that contractors provide field time to install or replace circuit breakers to accommodate coordination with process and HVAC equipment. The specification requires comprehensive submittals including shop drawings detailing main bus ampacity, construction characteristics, UL listings, protective and withstand ratings, and circuit breaker specifications. Contractors must furnish spare circuit breakers per panel schedules shown in contract drawings and provide two keys for each panelboard. Acceptable manufacturers include Square D and Eaton or equivalent products. Bid security of not less than 10 percent in the form of a certified check or bid bond is required, with all official notifications and bidding documents available exclusively through the PennBid website at https://pennbid.bonfirehub.com/.

View the file

Other files

File Type Posted
33 05 97 - Identification And Signage For Utilities.pdf PDF
26 29 13 - Contactors and Motor Starting Equipment.pdf PDF
26 05 10 - Basic Electrical Materials & Methods.pdf PDF
01 78 36 - Warranties.pdf PDF
26 12 19.01 - Liquid Filled Medium Voltage Pad Mounted Transformers.pdf PDF
01 61 00 - Product Requirements.pdf PDF
03 39 00 - Concrete Curing.pdf PDF
00 01 07 - Seal Page.pdf PDF
01 78 39 - Project Record Documents.pdf PDF
01 29 00 - Payment Procedures.pdf PDF
01 73 00 - Execution Requirements.pdf PDF
43 26 13 - Submersible Sewage Pumps.pdf PDF
33 05 77 Packaged Metering Manhole.pdf PDF
01 10 00 - Project Summary.pdf PDF
26 05 73 - Power System Study and Testing.pdf PDF
00 65 19.16 - Affidavit of Release of Liens.pdf PDF
02 41 19.13 - SELECTIVE BUILDING DEMOLITION.pdf PDF
33 05 05.36 - Vacuum Testing.pdf PDF
40 05 51 - Common Requirements For Process Valves.pdf PDF
01 26 13 - Requests for Interpretation.pdf PDF
00 73 36 - Equal Employment Opportunity Requirements.pdf PDF
40 05 62 - Plug Valves.pdf PDF
00 45 36 EEO Certificate.pdf PDF
46 66 16 - Trojan Open Channel UV Disinfection System.pdf PDF
00 72 00 - General Conditions 2018.pdf PDF
40 23 23 - Potable Water Process Piping.pdf PDF
31 23 19 - Dewatering.pdf PDF
40 95 34 a- IOList Table.pdf PDF
01 50 00 - Temporary Facilities and Controls.pdf PDF
00 31 32 - Geotechnical Data.pdf PDF
01 57 28 - Temporary Flow Control.pdf PDF
31 05 16 - Aggregate for Earthwork.pdf PDF
00 65 19.23 - Notice of Acceptability of Work.pdf PDF
00 60 00 - Project Forms.pdf PDF
01 22 00 - Unit Prices.pdf PDF
06 10 00 - Rough Carpentry.pdf PDF
40 05 53 - Identification For Process Piping.pdf PDF
06 17 53 - Shop-Fabricated Wood Trusses.pdf PDF
00 45 19 Non Collusion Affidavit.pdf PDF
40 05 23 - Stainless Steel Process Pipe And Tubing.pdf PDF
26 05 33.16 - Boxes.pdf PDF
26 05 29 - Electrical Supports, Anchors and Fasteners.pdf PDF
41 22 23.16 - Portable Hoists.pdf PDF
26 32 13 - Packaged Engine Generator Systems.pdf PDF
31 23 16.13 - Trenching.pdf PDF
01 33 00 - Submittal Procedures.pdf PDF
46 43 21 Packaged Wastewater Treatment Plant Equipment.pdf PDF
13 34 00 - Pre-engineered Post Frame Structures.pdf PDF
01 41 26 - Permit Requirements.pdf PDF
33 14 16 - Site Water Utility Distribution Piping.pdf PDF
Show 40 more

Latest 50 of 157 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

26 24 16 - PANELBOARDS

Herbert, Rowland & Grubic, Inc. 26 24 16 -1 005153.0436

SECTION 26 24 16 - PANELBOARDS

PART 1 - GENERAL

1.1 SECTION INCLUDES

A. Power Panelboards (PP).

B. General Panelboards (GP).

C. Integral surge protection (SPD) devices.

1.2 RELATED SECTIONS

A. Division 26.

1.3 REFERENCES

A. UL listed panelboards and panelboard enclosures shall meet or exceed NEMA Standard

PB-1 and Federal Specifications W-P-115b, Type 1, Class 1, and be listed as service entrance equipment when used as such.

B. The following specifications and standards are incorporated by reference:

1. Underwriters Laboratories, Inc. (UL) Publications:

No. 50 Cabinets and Boxes, Electrical

No. 67 Panelboards

No. 489 Molded Case Circuit Breakers and Circuit Breaker Enclosures

2. National Electrical Manufacturers Association (NEMA) Publications:

No. PB1 Panelboards

No. AB1 Molded Case Circuit Breakers

1.4 SUBMITTALS

A. Submittals shall be made in accordance with Section 26 05 00 - Electrical-General.

B. Submit shop drawings for all panelboards in this Section.

C. Include all construction and device characteristics to show compliance with specifications.

Submittal shall include, but not be limited to, the following:

1. Main bus ampacity.

2. Construction details.

Herbert, Rowland & Grubic, Inc. 26 24 16 -2 005153.0436

3. UL listing.

4. Protective ratings and withstand ratings.

5. Circuit Breakers:

a. Type.

b. Ratings and withstand ratings.

6. Enclosure NEMA type.

7. Integral TVSS Equipment.

1.5 PROJECT RECORD DOCUMENTS

A. Record actual locations of products; indicate actual branch circuit arrangement, and loadings for each panelboard.

B. Provide a directory for each panelboard giving the circuit breaker number and the name or description for the load on that circuit.

1.6 OPERATION AND MAINTENANCE DATA

A. Maintenance Data - Include spare parts data listing; source and current prices of replacement parts and supplies; and recommended maintenance procedures and schedules.

1.7 QUALITY ASSURANCE

A. Perform work in accordance with National Electrical Contractors Association Standard of

Installation.

1.8 FIELD MEASUREMENTS

A. Verify that the panelboard will fit in the space allocated on the plans.

1.9 EXTRA MATERIALS

A. Spare Circuit Breakers:

1. Refer to panel schedules within the contract drawings for quantities and trip ratings of spare circuit breakers to be provided.

B. Provide two of each panelboard key.

PART 2 - PRODUCTS

2.1 PANELBOARDS - GENERAL

A. Interiors:

Herbert, Rowland & Grubic, Inc. 26 24 16 -3 005153.0436

1. Completely factory assembled.

2. Independent switching and protective devices.

3. Replaceable circuit breakers with machining, drilling, or tapping.

4. Double row construction.

5. Full-sized, insulated, copper, neutral bars.

6. In subfed panels, provide neutral isolated from ground.

7. Arrange bus bar taps for panels with single pole branches for “distributed phase” or “phase sequencing.”

8. Full-sized copper, ground bus.

B. Panelboard Boxes:

1. NEMA rating in accordance with Section 26 27 16 - Control Panels and Enclosures.

2. Minimum 20 inches wide.

3. Without knockouts.

4. At least minimum gutter space per NEC.

5. At least four interior mounting studs with adjustable nuts.

C. Trim conforming to the following:

1. Accessible switching device handles.

2. Barriers for completely dead-front construction.

3. Concealed door hinges.

4. Chrome plated, minimum projection latch.

5. Key lock on panelboards; all locks keyed alike.

6. Three-point closure on doors over 48 inches high.

7. Permanent directory with heavy plastic cover.

8. Flush panel trim with 3/4-inch overlap on all four sides.

9. Trim clamps inaccessible when door is closed.

D. Bus Bars:

1. Main bus bars in tin plated copper.

2. Sized in accordance with UL Standards.

3. Limit of temperature rise on any current carrying part - 50 degrees above air ambient of 40 degrees C maximum.

E. Surge Protection (SPD) Devices:

1. Provide 120 kA integral SPD for all 240/120 panelboards shown on the contract drawings.

2.2 480/277 VAC, 3 PHASE PANELBOARDS (PP)

A. General:

1. Definition - Panelboards are to operate on 480Y/277 volt, 3 phase power. The panel may contain circuit breakers to power lighting.

2. Panelboard Breakers - Molded case, thermal magnetic trip, bolt-on connection, quick-make, quick-break, toggle handle circuit breakers. Two- and three-pole units to be internal common trip type with silver alloy contacts.

Herbert, Rowland & Grubic, Inc. 26 24 16 -4 005153.0436

3. Main Circuit Breakers - Rated at 35,000 A.I.C. (or 65,000 A.I.C. where noted on the Contract Drawings)

4. Panelboards for use at 480 or 600 volts AC maximum to incorporate branch circuit breakers as shown or scheduled rated at 35,000 A.I.C. symmetrical at 480 volts.

2.3 208/120VAC, 3 PHASE PANELBOARDS (PP)

A. Application - Provide panelboards as indicated in the Contract Documents.

B. Description:

1. Operating Voltage - 208Y/120 volts, 3 phase power as scheduled.

2. The panelboards may contain circuit breakers to power equipment other than lighting and receptacles.

C. Circuit breakers shall be:

1. Molded case, thermal magnetic trip, bolt-on connection.

2. Quick make, quick break, toggle handle.

3. Silver alloy contacts.

4. Two- and three-pole units shall have internal common trip.

5. Rating - 22,000 A.I.C. (or 14,000 A.I.C. where noted on the Contract Drawings).

D. For panelboards up to 240 volts, incorporate branch circuit breakers rated at 10k A.I.S.

symmetrical at 240 volts.

E. Provide panelboards with circuit protective devices as scheduled on the Contract

Drawings.

F. Manufacturers:

1. Square D

2. Eaton

3. Or equal.

2.4 240/120VAC, 1 PHASE PANELBOARDS (LP)

A. Application - Provide panelboards as indicated in the Contract Documents.

B. Description:

1. Operating Voltage – 240/120 volts, 1 phase power as scheduled.

2. The panelboards may contain circuit breakers to power equipment other than lighting and receptacles.

C. Circuit breakers shall be:

1. Molded case, thermal magnetic trip, bolt-on connection.

2. Quick make, quick break, toggle handle.

3. Silver alloy contacts.

Herbert, Rowland & Grubic, Inc. 26 24 16 -5 005153.0436

4. Two-pole units shall have internal common trip.

5. Rating - 22,000 A.I.C. (or 14,000 A.I.C. where noted on the Contract Drawings).

D. Provide panelboards with circuit protective devices as scheduled on the Contract

Drawings.

PART 3 - EXECUTION

3.1 PANELBOARDS

A. Incorporate panelboard within box. Increase box width as required for additional space for auxiliary equipment, subfeeds or controls. Minimum depth 5-3/4 inches; increase if required to maintain 2 inches between edge of knockouts and front edge of cabinet. Height of cabinet as required. Maximum mounting height to top of cabinet is

72 inches. Locate panels as shown on the Contract Drawings.

B. Contractor shall include field time to install/replace panelboard circuit breakers with the spare parts to accommodate coordination issues with the process, HVAC, or other equipment ratings for the project.

3.2 IDENTIFICATION

A. Identification shall be in accordance with Section 26 05 53 - Electrical System

Identification.

3.3 LOADING

A. Panelboards shall be loaded evenly on each phase. Maximum imbalance shall be limited between phases (i.e., 3-4-5 is not acceptable; 4-5-4 is acceptable). Contractor shall measure steady state load currents at each panelboard feeder and rearrange circuits in the panelboard to balance phase loads within 10% of each other.

3.4 MOUNTING

A. Top of panel not to exceed 66 inches.

B. Methods and Materials - Per Section 26 05 29 - Electrical Supports, Anchors, and

Fasteners and manufacturer’s requirements.

END OF SECTION