MI703.pdf
PDF 91 KB Posted
- Attached to
- WVA Fire Station Construction Acquisition Federal contract opportunity
- Solicitation number
- W912DS25RA009
About this file
This document is a Mechanical Controls drawing (Sheet MI703) for a US Army Corps of Engineers project at the Watervliet Arsenal in New York, specifically for a 3 Company Fire Station. The drawing details the control sequences and specifications for Variable Air Volume (VAV) terminal units and a 2-speed exhaust fan (EF-5).
Key technical specifications include zone temperature control with cooling setpoints at 78°F and heating setpoints at 68°F, with occupant-adjustable ranges of +/- 2°F. The exhaust fan is designed to operate 24/7, with speed variations based on carbon monoxide (CO) and nitrogen oxide (NOx) sensor inputs. Additional monitoring requirements cover gas, power, and water usage, with data to be reported to the building's digital control system and displayed graphically, including daily, monthly, and annual consumption trends. The project is part of solicitation W912D25S0017, with a drawing issue date of April 29, 2025.
View the file
Other files for this federal contract opportunity
Show all 46
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SEQUENCE OF OPERATIONS:
RUN CONDITIONS - SCHEDULED:
THE UNIT SHALL RUN ACCORDING TO THE OCCUPANCY SCHEDULE OF THE SPACES SERVED IN THE FOLLOWING MODES:
OCCUPIED MODE: THE UNIT SHALL MAINTAIN
• A 78°F (ADJ.) COOLING SETPOINT
• A 68°F (ADJ.) HEATING SETPOINT
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER THAN THE COOLING SETPOINT BY A USER DEFINABLE AMOUNT (ADJ.).
• LOW ZONE TEMP: IF THE ZONE TEMPERATURE IS LESS THAN THE HEATING SETPOINT BY A USER DEFINABLE AMOUNT (ADJ.).
ZONE SETPOINT ADJUST:
THE OCCUPANT SHALL BE ABLE TO ADJUST THE ZONE TEMPERATURE HEATING AND COOLING SETPOINTS AT THE ZONE SENSOR AS
FOLLOWS:
• HEATING 68°F (ADJ.) +/- 2°F (ADJ.)
• COOLING 78°F (ADJ.) +/- 2°F (ADJ.).
THE UNIT SHALL MAINTAIN ZONE SETPOINTS BY CONTROLLING THE AIRFLOW THROUGH THE FOLLOWING:
OCCUPIED:
• WHEN ZONE TEMPERATURE IS GREATER THAN ITS COOLING SETPOINT, THE ZONE DAMPER SHALL MODULATE BETWEEN THE
MINIMUM OCCUPIED AIRFLOW (ADJ.) AND THE MAXIMUM COOLING AIRFLOW (ADJ.) UNTIL THE ZONE IS SATISFIED.
• WHEN THE ZONE TEMPERATURE IS BETWEEN THE COOLING SETPOINT AND THE HEATING SETPOINT, THE ZONE DAMPER SHALL
MAINTAIN THE MINIMUM OCCUPIED AIRFLOW.
• WHEN ZONE TEMPERATURE IS LESS THAN ITS HEATING SETPOINT, THE CONTROLLER SHALL ENABLE HEATING TO MAINTAIN THE
ZONE TEMPERATURE AT ITS HEATING SETPOINT. ADDITIONALLY, THE ZONE DAMPER SHALL MODULATE BETWEEN THE MINIMUM OCCUPIED AIRFLOW (ADJ.) AND THE MAXIMUM HEATING AIRFLOW (ADJ.) UNTIL THE ZONE IS SATISFIED.
REHEATING COIL VALVE:
THE CONTROLLER SHALL MEASURE THE ZONE TEMPERATURE AND MODULATE THE REHEATING COIL VALVE OPEN ON DROPPING
TEMPERATURE TO MAINTAIN ITS HEATING SETPOINT.
WHEN COLD AIR IS AVAILABLE FROM THE AHU, THE ZONE DAMPER SHALL MODULATE TO THE MINIMUM OCCUPIED AIRFLOW (ADJ.). IF MORE HEAT IS REQUIRED, THE ZONE DAMPER SHALL MODULATE TO THE AUXILIARY HEATING AIRFLOW (ADJ.).
REHEATING - HIGH DISCHARGE AIR TEMPERATURE LIMIT:
THE CONTROLLER SHALL MEASURE THE DISCHARGE AIR TEMPERATURE AND LIMIT REHEATING IF THE DISCHARGE AIR TEMPERATURE IS
MORE THAN 105°F (ADJ.).
DISCHARGE AIR TEMPERATURE:
THE CONTROLLER SHALL MONITOR THE DISCHARGE AIR TEMPERATURE.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS GREATER THAN 110°F (ADJ.).
• LOW DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS LESS THAN 50°F (ADJ.).
HW
SASA
M T
T
NOTE: PROVIDE 2-WAY OR 3-WAY VALVE PER CONTROL VALVE SCHEDULE
AO 06
AI 01 AI 03
AI 02
AI 04
AI 05
DI 08
HWS
HWR
AI 06
EXHAUST FAN SHALL OPERATE 24/7.
EXHAUST FAN SPEED SHALL BE SET THROUGH BAS TO MAINTAIN SCHEDULED LOW-SPEED
EXHAUST AIRFLOW. UPON INPUT FROM CO OR NOX SENSOR, SETPOINTS BELOW, THE FAN WILL
BE COMMANDED TO RUN AT SCHEDULED HIGH-SPEED EXHAUST AIRFLOW.
WHEN ASSOCIATED LEVELS OF CO OR NOX FALL BELOW SETPOINT (ADJ.), THE REVERSE SHALL
RETURN.
EXHAUST FAN STATUS SHALL BE MONITORED BY BAS VIA CURRENT TRANSDUCER ON INCOMING
POWER LEG.
IF FAN STATUS DOES NOT MATCH COMMAND FROM BAS, AN ALARM SHALL BE GENERATED.
IF CO LEVELS IN APPARATUS BAY EXCEED 50 PPM, EXHAUST FAN WILL GO TO HIGH SPEED, THE VEHICLE EXHAUST SYSTEM WILL ACTIVATE, AND AN ALARM SHALL BE GENERATED AT THE BAS.
IF NOX LEVELS IN APPARATUS BAY EXCEED 25 PPM, EXHAUST FAN WILL GO TO HIGH SPEED, THE VEHICLE EXHAUST SYSTEM WILL ACTIVATE, AND AN ALARM SHALL BE GENERATED AT THE BAS.
ALARMS SHALL REQUIRE MANUAL RESET AT THE UNIT.
FAN CONTROLLER
EXHAUST FAN
DO 01
DI 01 CT
EP
SEQUENCE OF OPERATION:
DI 09SPACE CARBON MONOXIDE
DI 09SPACE NITROGEN OXIDE
CO
NOX
EMERGENCY HVAC SHUTDOWN SOO:
1. CONTROLS CONTRACTOR TO PROVIDE MUSHROOM BOTTOM TYPE
SWITCHES WHERE INDICATED ON M SHEETS. SWITCHES SHALL
INCLUDE COVER TO PREVENT ACCIDENTAL ACTIVATION.
2. PRESSING THE SWITCH SHALL CAUSE ALL HVAC FANS TO
DEENERGIZE AND ALL OUTDOOR AIR DAMPERS TO CLOSE WITHIN 30
SECONDS, REGARDLESS OF HAND-OFF-ON POSITION OF STARTER OR
VFD. EXCEPTION FOR KITCHEN EXHAUST FAN, VEHICLE EXHAUST FAN
AND BOTH MAKEUP AIR UNITS
3. CLEARLY LABEL SHUTDOWN SWITCHES "EMERGENCY HVAC
SHUTDOWN". SWITCHES SHALL BE BLUE IN COLOR.
S-3
DI
GAS USE MONITORING:
1. PLUMBING CONTRACTOR TO PROVIDE GAS METER AS INDICATED ON
THE PLUMBING SHEETS. GAS METER SHALL BE COORDINATED AND
INSTALLED IN COORDINATION WITH OTHER TRADES.
2. REPORT THE FOLLOWING DATA TO THE DDC AND
DISPLAY IT GRAPHICALLY AT THE OPERATOR'S
WORKSTATION: DAILY GAS CONSUMED, MONTHLY
GAS CONSUMED, ANNUAL GAS CONSUMED.
3. TREND THE FOLLOWING: DAILY CONSUMPTION,
ANNUAL CONSUMPTION.
GM-1
AI
GM-2
AI
GAS METER
POWER METER (TYPICAL, REFER
TO ELECTRICAL FOR QUANTITIES
AND LOCATIONS)
POWER USE MONITORING:
1. ELECTRICAL CONTRACTOR TO PROVIDE POWER METERS. POWER METERS
SHALL BE INSTALLED BY ELECTRICAL CONTRACTOR IN COORDINATION WITH
ELECTRICAL EQUIPMENT. COORDINATE PROVISION OF METERS AMONG THE
VARIOUS TRADES.
2. REPORT THE FOLLOWING DATA TO THE DDC AND DISPLAY IT
GRAPHICALLY AT THE OPERATOR'S WORKSTATION: INSTANTANEOUS KW
DEMAND, HIGHEST KW DEMAND FOR THE PAST MONTH, AVERAGE
HOURLY KWH, AVERAGE DAILY KWH, TOTAL ANNUAL KWH. THE INTERVAL
OF EACH OF THESE ITEMS SHALL BE CONFIGURABLE BY THE USER.
3. TREND THE FOLLOWING: HOURLY CONSUMPTION, DAILY CONSUMPTION,
ANNUAL CONSUMPTION.
PM-1
AI
PM-2
AI
PM-3
AI
WATER USE MONITORING:
1. PLUMBING CONTRACTOR TO PROVIDE WATER METER AS INDICATED
ON THE PLUMBING SHEETS. WATER METER SHALL BE COORDINATED
BY GENERAL CONTRACTOR AND INSTALLED IN COORDINATION WITH
OTHER TRADES.
2. REPORT THE FOLLOWING DATA TO THE DDC AND DISPLAY IT
GRAPHICALLY AT THE OPERATOR'S WORKSTATION: DAILY WATER
CONSUMED, MONTHLY WATER CONSUMED, ANNUAL WATER
CONSUMED.
3. TREND THE FOLLOWING: DAILY CONSUMPTION, ANNUAL
CONSUMPTION.
WM-1
AI
WM-2
AI
WATER METER
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
C
U s e rs
\S k in n e rP
\D o c u m e n ts
\W V
A -F
S -D
M M
-M -M
D L P a rk e r.
s k in n e r.
rv t
/1
/2
:1
:0
P
M
MI703
M E
C H
A N
IC
A
L C
O N
T R
O L S
II
I
W A
T E
R V
L
IE
T A
R S
E N
A L N
Y N
E W
Y O
R K
D
IS
T R
IC
T
F
E D
E R
A L P
L A
Z A
N E
W Y
O R
K N
Y
K .M
IL
L E
R
C .H
IO
T
A K
Y
S .B
E C
C
IA
A P
R
IL
W D
S
C
O M
P A
N Y
F
IR
E S
T A
T
IO
N
SCALE: N.T.S.
A9
VAV TERMINAL UNITS CONTROL DIAGRAM
R
E V
IS
E
D P
E R
A M
E N
D M
E N
T
/0
/2
2. THIS POINT IS ONLY FOR VAVS WITH REHEAT PER SCHEDULE.
L - LAST POSITION
C - CLOSED
O - OPEN
1. FAILURE MODE
NOTES:
TOTALS 0 1 2 5 12 10 4
LOW ZONE TEMP 18 X 1-2
LOW DISCHARGE AIR TEMP 17 X
HIGH ZONE TEMP 16 X
HIGH DISCHARGE AIR TEMP 15 X
SCHEDULE 14
HEATING MODE 13 X X
HEATING SETPOINT 12 X X
DAT HEATING LIMIT 11
COOLING SETPOINT 10 X X
AIRFLOW SETPOINT 09 X X
ZONE OVERRIDE 08 X X X
ZONE DAMPER 07 X X X L
REHEATING VALVE 06 X X X C
ZONE TEMPERATURE 05 X X X
ZONE SETPOINT ADJUST 04 X X
DISCHARGE AIR TEMP 03 X X X
DAMPER POSITION 02 X X
AIRFLOW 01 X X X
DO DI AO AI AV TREND ALARM
POINT NAME POINT NUMBER
HARDWARE POINTS SOFTWARE POINTS FAILURE
POSITION
NOTES
VAV SYSTEM POINTS LIST
SCALE: N.T.S.
L8
2-SPEED EXHAUST FAN (EF-5) CONTROL SCHEMATIC
2. SCHEDULES AND ROUTINES SHALL RESIDE ON THE BAS.
1. EXHAUST FAN WILL BE INTERLOCKED TO WITH HWDH-1.
NOTES:
TOTALS 2 3 0 0 2 2 3
FAN RUNTIME EXCEEDED 08 X
FAN IN HAND 07 X
FAN FAILURE 06 X
FAN SPEED 05 X
NO2 SENSOR INPUT 04 X
CO SENSOR INPUT 03 X
FAN START/STOP 02 X X X
FAN STATUS 01 X X X
DO DI AO AI AV TREND ALARM
POINT NAME POINT NUMBER
HARDWARE POINTS SOFTWARE POINTS
NOTES
2-SPEED EXHAUST FAN (EF-5) POINT LIST
| Sheets |
| MI703 - MECHANICAL CONTROLS - III |
File details come from the government source that posted it. Updated .