ET-601 - TELECOMM RISER DIAGRAM.pdf
PDF 93 KB Posted
- Attached to
- WVA Fire Station Construction Acquisition Federal contract opportunity
- Solicitation number
- W912DS25RA009
About this file
This is a Telecomm Riser Diagram detailing the telecommunications infrastructure and cable routing for a multi-floor facility. The diagram shows a comprehensive network design including fiber optic and copper cable services, with specific details such as a 24-strand single-mode fiber optic service, a 12-strand multi-mode fiber optic service for the fire central alarm system, and multiple copper cable backbone connections. Key components include primary and secondary grounding busbars, cable ladder trays, EMT conduit sleeves, protector blocks, 110-type blocks, network/data racks, analog/voice racks, and designated telecom rooms on different floors. The diagram specifies cable routes, transitions, and penetrations through fire-rated partitions, with references to additional grounding and bonding requirements on sheet EG-501. The document is part of a U.S. Army Corps of Engineers project, as indicated by the logo in the bottom right corner.
View the file
Other files for this federal contract opportunity
Show all 46
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROVIDE A 20 FT SERVICE LOOP
FOR FIBER OPTIC CABLES
IN THE BACKBOARD WALL FIELD
4" EMT CONDUIT SLEEVES
PENETRATING FIRE RATED
PARTITION
TYPICAL
FIRE RATED
PARTITION
CABLE LADDER TRAY
SEE SHT. EG-501
FOR GROUNDING AND
BONDING REQUIREMENTS
PRIMARY (MAIN) GROUNDING BUSBARFLOOR
(1) 24 ST OSP RATED SINGLE
MODE FIBER OPTIC SERVICE + (1) 12 ST
MULTI MODE FIBER OPTIC SERVICE (FOR
THE FIRE CENTRAL ALARM SYSTEM)
ENTRANCE CABLES
VIA VERTICAL LADDER RACK TRAY
50-PAIR CAT 3
COPPER BACKBONE
VIA RACKS & CABLE
MANAGEMENT
(1)-600 PAIR TYPE PE-89
#24AWG OUTSIDE PLANT
COPPER SERVICE
ENTRANCE CABLE TO
MANHOLE MH-44.
(SEE SHT. ES-103
FOR CONTINUATION)
600 PAIR
PROTECTOR
BLOCKS
110-TYPE
BLOCKS
100-PAIR
PLYWOOD BACKBOARD
SPARE 4"C, EMT
CAPPED IN
BOTH TER AND
2ND FL TR ROOM
PBB
CABLE TRAY (WIREMESH TYPE)
TRANSITION VERTICAL
OFFSET SECTION
4" 4" 7 8 9 16 10 11
W
ACS/CCTV
RACK
50 PAIR
PROTECTOR
BLOCKS
110-TYPE
BLOCKS
50-PAIR
(1)-50 PAIR TYPE PE-89
#24AWG OUTSIDE PLANT
COPPER SERVICE
FOR FIRE ALARM
REPORTING (OLD FACILITIES
FACP).
TO NEW
FACP
NETWORK/
DATA
RACK
4"
ANALOG/
VOICE RACK
1 1 1
4 4 4
DD FL W
12 12 12
(1)-50 PAIR CAT 3 #24AWG
COPPER CABLE (CMP RATED)
FOR FIRE ALARM REPORTING
(OLD FACILITIES NON-SIMPLEX
FACPs).
4" 4"
SPARE
4" 4"
(3) 4"C
TO 2ND FL
TR ROOM
4" EMT CONDUIT SLEEVES
PENETRATING FIRE RATED
PARTITION
TYPICAL
FIRE RATED
PARTITION
CABLE LADDER TRAY
SEE SHT. EG-501
FOR GROUNDING AND
BONDING REQUIREMENTS
SECONDARY BONDING BUSBAR GROUNDING BUSBARFLOOR
SBB
CABLE TRAY (WIREMESH TYPE)
TRANSITION VERTICAL
OFFSET SECTION
7 8 9 16 10 11
W
NETWORK/
DATA
RACK
ANALOG/
VOICE RACK
1 1
4 4 5
DD FL W
12 12
MAIN TELECOM ROOM (TER)
2ND FL TR ROOM
(TYP)
CABLE TRAY (WIREMESH TYPE)
CABLE TRAY (WIREMESH TYPE)
DISPATCH
AREA
NETWORK
RACK
UPS ROOM
4" 4" 4"
50-PAIR CAT 3
COPPER BACKBONE
FROM MAIN TER
(1)-24 ST SM FOC
FROM MAIN TER RM
DR
DR
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
R :\d m s3
\W
VA
-F S-
D M
M -E
-M D
L.
rv t 8/
4/
:3 9:
P
M
ET601
TE
LE
C O
M M
R
IS
ER
D
IA
G
R
AM
W
AT
ER
VL
IE
T
AR
SE
N
AL
N Y
N
EW
Y O
R K
D
IS
TR
IC
T
F
ED
ER
AL
P
LA
ZA
N
EW
Y
O R
K, N
Y
M .D
AV
IS
M .D
AV
IS
M .D
AV
IS
M .G
IU
R
G
IU
AP
R
IL
9, R
TA
S U
BM
IS
SI
O
N
C
O M
PA
N
Y
FI
R E
ST
AT
IO
N
PN
2-POST 19"WX84"H EQUIPMENT RACK.
BACKBONE FIBER PATCH PANEL, 2 RU, 48 PORT WITH FUSION SPLICED
PIGTAIL (10 FT) CASSETTES.
FIBER PATCH PANEL, 2RU, WITH FUSION SPLICED PIGTAIL CASSETTES
FOR TERMINATION OF THE FIBER OPTIC LOOP FOR THE EXISTING WVA
CENTRAL FIRE ALARM SYSTEM (SIMPLEX),
QUAD AND SPECIAL OUTLETS (110VAC, NEMA L5-20R, NEMA L6-30R,ETC)
FOR EQUIPMENT CABINETS AND RACKS SHALL BE MOUNTED ABOVE
CABINETS. SEE SHT. EP-401 FOR ADDITIONAL INFORMATION.
HORIZONTAL CAT 6 & CAT 6A VOICE AND DATA CABLES ROUTED IN
CABLE TRAY THEN IN CONDUIT TO THE OUTLETS.
COORDINATE SLEEVE PENETRATIONS WITH STRUCTURAL AND ARCH
DISCIPLINES. FIRE SEAL ALL PENETRATIONS THROUGH FIRE RATED
PARTITIONS.
TYPICAL WALL MOUNTED DATA/VOICE CAT 6 OUTLET WITH (3) CAT 6
OUTLETS. PROVIDE WITH (3) CAT 6 CABLES IN 1 1/4"C ROUTED TO THE
OUTLET.
TYPICAL DUAL CAT 6 DATA OUTLET FOR BAS SYSTEM WITH 2 CAT 6
CABLES IN 1 1/4"C.
TYPICAL FLOOR MOUNTED DUAL CAT 6 OUTLET IN COMBINATION
POWER/DATA FLOOR BOX WITH (4) CAT 6 CABLES IN 1 1/4"C TO THE
FLOOR BOX. ALL CAT 6 CABLES SHALL BE WEATHERPROOF
TYPICAL WALL MOUNTED TELEPHONE CAT 6 OUTLET WITH (1) CAT 6
CABLE IN 1"C.
TYPICAL WIRELESS ACCESS POINT OUTLET WITH (2) CAT 6A JACKS.
PROVIDE WITH (2) CAT 6A CABLES IN 1 1/4"C.
PROVIDE VERTICAL RACK MOUNTED POWER DISTRIBUTION UNITS
(RPDUs).
PROVIDE GROUNDING BUSHING AT CONDUIT END,
AND GROUND TO CABLE TRAY WITH #6 AWG CONDUCTOR.
PROVIDE (4) 4-INCH CONDUIT DUCTBANK SYSTEM. PROVIDE THREE (3)
3X3" MULTICELL FABRIC MESH INNERDUCT IN ONE OF THE 4-INCH
CONDUIT FOR FIBER OPTIC CABLE ROUTING. 200# PULL STRING SHALL
BE PROVIDED IN EACH INNERDUCT AND EACH CONDUIT. SEE SHT.
ES-101 FOR CONTINUATION OF SERVICE CONDUIT.
ROUTE THE 50 PR CABLES TO THE NEW FACP PANEL. INSTALLER OF
THE FA SYSTEM WILL BE RESPONSIBLE FOR INTEGRATING THESE
OLDER FACILITY (ALARM AND TROUBLE SIGNALS) INTO THE NEW FACP,
AND INTO THE BASE-WIDE SYSTEM FOR REPORTING. FACP INSTALLING
WILL PROVIDE ALL THE REQUIRED ADDRESSABLE MONITOR MODULES
REQUIRED FOR INCORPORATING THESE OLDER FACILITES (NON-
SIMPLEX SYSTEM) INTO THE BASE-WIDE FA REPORTING SYSTEM.
DORM ROOM WALL MOUNTED DATA/VOICE CAT 6 OUTLET WITH (2) CAT
6 OUTLETS. PROVIDE WITH (2) CAT 6 CABLES IN 1 1/4"C ROUTED TO THE
OUTLET. .
12 ST SM FOC BACKBONE CABLE (PLENUM RATED), TYPE OS-2. ROUTE
IN ORANGE INNERDUCT IN THE CABLE TRAY.
BACKBONE CABLE PATCH PANELS. COPPER BACKBONE SHALL BE
TERMINATED ONE PAIR PER PORT (PINS 4 & 5), EXCEPT FOR PORT #48
TERMINATE 2-PAIR. PROVIDE QUANTITY OF PATCH PANELS AS
REQUIRED TO TERMINATE THE 50 PAIR CABLE.
1.FOR ELECTRICAL NOTES, ABBREVIATIONS, AND SYMBOLS REFER TO
DRAWING E-001, E-002 & ET-001.
2. PROVIDE ALL PATCH PANELS AS REQUIRED TO SUFFICIENTLY
TERMINATE ALL CABLES SPECIFIED.
3. DRAWINGS ARE DIAGRAMMATIC ONLY. EXACT ARRANGEMENT FOR
EQUIPMENT AND PATCH PANELS SHALL BE COORDINATED AND
OPTIMIZED IN THE FIELD.
4. MOST JUNCTION BOXES AND RACEWAYS ARE NOT SHOWN. ALL
INSTALLATION SHALL BE IN ACCORDANCE WITH NATIONAL ELECTRICAL
CODE, UFC 3-580-01 CRITERIA, AND TIA STANDARDS AND
REQUIREMENTS.
5. NOT MORE THAN (2) 90-DEGREE TURNS SHALL BE ALLOWED ON ANY
CABLE ROUTES OR PULLS WITHOUT PROPER INSTALLATION OF PULL
BOXES OR JUNCTION BOXES.
6. ALL BACKBONE CONDUITS FOR TELECOM ASSOCIATED CABLES SHALL
BE PROVIDED WITH 3X3" CELL FABRIC INNERDUCTS, AND WITH PULL
STRINGS IF IT IS A SPARE CONDUIT.
7. WHILE NOT SHOWN, CABLES FROM SERVICE ENTRANCE CONDUITS TO
TELCOM RACKS SHALL BE VIA CABLE TRAYS AND SUPPORT AS
REQUIRED BY UFC 3-580-01 CRITERIA.
8. HORIZONTAL DISTRIBUTION CAT 6 CABLES SHALL BE GROUPED IN
BUNDLES OF 25 CABLES MAXIMUM, AND PROVIDED WITH VELCRO CABLE
TIES IN THE CABLE TRAY. CABLE TIES SHALL BE PROVIDED AT
INTERVALS OF EVERY 25 LF.
9. ALL CATEGORY 6 & 6A CABLES SHALL BE PLENUM RATED.
10. ALL FIBER OPTIC CABLES SHALL BE PLENUM RATED.
11. SEE TELECOMM FLOOR PLAN FOR QUANTITY OF OUTLETS AND
DEVICES.
12. THIS CONTRACTINCLUDES THE INSTALLATION OF THE PATHWAYS,
CABLING, CAT 6A JACKS AND BOXES REQUIRED FOR THE FUTURE
INSTALLATION OF WIRELESS ROUTERS. THE WIRELESS
ROUTERS WILL BE PROVIDED BY OTHERS.
DRAWING KEYED NOTES
GENERAL NOTES
NTSET601
1 TELECOMM RISER DIAGRAM
CROSS CONNECT
BY NEC
(TYP)
R ev is ed p er a m en dm en t
/0 4/
| Sheets |
| ET601 - TELECOMM RISER DIAGRAM |
File details come from the government source that posted it. Updated .