ET601 - TELECOMM RISER DIAGRAM.pdf
PDF 93 KB Posted
- Attached to
- WVA Fire Station Construction Acquisition Federal contract opportunity
- Solicitation number
- W912DS25RA009
About this file
This document is a Telecomm Riser Diagram detailing the telecommunications infrastructure and cable routing for a multi-floor facility. The diagram illustrates comprehensive cable management, including fiber optic and copper cable installations across different rooms such as the Main Telecom Room (TER), 2nd Floor TR Room, UPS Room, and Dispatch Area. Key specifications include: (1) 24-strand single mode and (1) 12-strand multi-mode fiber optic service entrance cables, a 50-pair CAT 3 copper backbone, a 600-pair outside plant copper service entrance cable to manhole MH-44, and multiple 4" EMT conduit sleeves penetrating fire-rated partitions. The diagram also shows grounding requirements with primary and secondary bonding busbars, cable ladder trays, network/data racks, analog/voice racks, and provisions for spare conduits, ensuring a structured and organized telecommunications infrastructure design.
View the file
Other files for this federal contract opportunity
Show all 46
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROVIDE A 20 FT SERVICE LOOP
FOR FIBER OPTIC CABLES
IN THE BACKBOARD WALL FIELD
4" EMT CONDUIT SLEEVES
PENETRATING FIRE RATED
PARTITION
TYPICAL
FIRE RATED
PARTITION
CABLE LADDER TRAY
SEE SHT. EG-501
FOR GROUNDING AND
BONDING REQUIREMENTS
PRIMARY (MAIN) GROUNDING BUSBARFLOOR
(1) 24 ST OSP RATED SINGLE
MODE FIBER OPTIC SERVICE + (1) 12 ST
MULTI MODE FIBER OPTIC SERVICE (FOR
THE FIRE CENTRAL ALARM SYSTEM)
ENTRANCE CABLES
VIA VERTICAL LADDER RACK TRAY
50-PAIR CAT 3
COPPER BACKBONE
VIA RACKS & CABLE
MANAGEMENT
(1)-600 PAIR TYPE PE-89
#24AWG OUTSIDE PLANT
COPPER SERVICE
ENTRANCE CABLE TO
MANHOLE MH-44.
(SEE SHT. ES-103
FOR CONTINUATION)
600 PAIR
PROTECTOR
BLOCKS
110-TYPE
BLOCKS
100-PAIR
PLYWOOD BACKBOARD
SPARE 4"C, EMT
CAPPED IN
BOTH TER AND
2ND FL TR ROOM
PBB
CABLE TRAY (WIREMESH TYPE)
TRANSITION VERTICAL
OFFSET SECTION
4" 4" 7 8 9 16 10 11
W
ACS/CCTV
RACK
NETWORK/
DATA
RACK
4"
ANALOG/
VOICE RACK
1 1 1
4 4 4
DD FL W
12 12 12
4" 4"
SPARE
4" 4"
(3) 4"C
TO 2ND FL
TR ROOM
4" EMT CONDUIT SLEEVES
PENETRATING FIRE RATED
PARTITION
TYPICAL
FIRE RATED
PARTITION
CABLE LADDER TRAY
SEE SHT. EG-501
FOR GROUNDING AND
BONDING REQUIREMENTS
SECONDARY BONDING BUSBAR GROUNDING BUSBARFLOOR
SBB
CABLE TRAY (WIREMESH TYPE)
TRANSITION VERTICAL
OFFSET SECTION
7 8 9 16 10 11
W
NETWORK/
DATA
RACK
ANALOG/
VOICE RACK
1 1
4 4 5
DD FL W
12 12
MAIN TELECOM ROOM (TER)
2ND FL TR ROOM
(TYP)
CABLE TRAY (WIREMESH TYPE)
CABLE TRAY (WIREMESH TYPE)
DISPATCH
AREA
NETWORK
RACK
UPS ROOM
4" 4" 4"
50-PAIR CAT 3
COPPER BACKBONE
FROM MAIN TER
(1)-24 ST SM FOC
FROM MAIN TER RM
DR
DRSPARE
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
R :\d m s3
\W
VA
-F S-
D M
M -E
-M D
L.
rv t 9/
/2
3:
:3
PM
ET601
TE
LE
C O
M M
R
IS
ER
D
IA
G
R
AM
W
AT
ER
VL
IE
T
AR
SE
N
AL
N Y
N
EW
Y O
R K
D
IS
TR
IC
T
F
ED
ER
AL
P
LA
ZA
N
EW
Y
O R
K, N
Y
M .D
AV
IS
M .D
AV
IS
M .D
AV
IS
M .G
IU
R
G
IU
AP
R
IL
9, R
TA
S U
BM
IS
SI
O
N
C
O M
PA
N
Y
FI
R E
ST
AT
IO
N
PN
2-POST 19"WX84"H EQUIPMENT RACK.
BACKBONE FIBER PATCH PANEL, 2 RU, 48 PORT WITH FUSION SPLICED
PIGTAIL (10 FT) CASSETTES.
FIBER PATCH PANEL, 2RU, WITH FUSION SPLICED PIGTAIL CASSETTES
FOR TERMINATION OF THE FIBER OPTIC LOOP FOR THE EXISTING WVA
CENTRAL FIRE ALARM SYSTEM (SIMPLEX),
QUAD AND SPECIAL OUTLETS (110VAC, NEMA L5-20R, NEMA L6-30R,ETC)
FOR EQUIPMENT CABINETS AND RACKS SHALL BE MOUNTED ABOVE
CABINETS. SEE SHT. EP-401 FOR ADDITIONAL INFORMATION.
HORIZONTAL CAT 6 & CAT 6A VOICE AND DATA CABLES ROUTED IN
CABLE TRAY THEN IN CONDUIT TO THE OUTLETS.
COORDINATE SLEEVE PENETRATIONS WITH STRUCTURAL AND ARCH
DISCIPLINES. FIRE SEAL ALL PENETRATIONS THROUGH FIRE RATED
PARTITIONS.
TYPICAL WALL MOUNTED DATA/VOICE CAT 6 OUTLET WITH (3) CAT 6
OUTLETS. PROVIDE WITH (3) CAT 6 CABLES IN 1 1/4"C ROUTED TO THE
OUTLET.
TYPICAL DUAL CAT 6 DATA OUTLET FOR BAS SYSTEM WITH 2 CAT 6
CABLES IN 1 1/4"C.
TYPICAL FLOOR MOUNTED DUAL CAT 6 OUTLET IN COMBINATION
POWER/DATA FLOOR BOX WITH (4) CAT 6 CABLES IN 1 1/4"C TO THE
FLOOR BOX. ALL CAT 6 CABLES SHALL BE WEATHERPROOF
TYPICAL WALL MOUNTED TELEPHONE CAT 6 OUTLET WITH (1) CAT 6
CABLE IN 1"C.
TYPICAL WIRELESS ACCESS POINT OUTLET WITH (2) CAT 6A JACKS.
PROVIDE WITH (2) CAT 6A CABLES IN 1 1/4"C.
PROVIDE VERTICAL RACK MOUNTED POWER DISTRIBUTION UNITS
(RPDUs).
PROVIDE GROUNDING BUSHING AT CONDUIT END,
AND GROUND TO CABLE TRAY WITH #6 AWG CONDUCTOR.
PROVIDE (4) 4-INCH CONDUIT DUCTBANK SYSTEM. PROVIDE THREE (3)
3X3" MULTICELL FABRIC MESH INNERDUCT IN ONE OF THE 4-INCH
CONDUIT FOR FIBER OPTIC CABLE ROUTING. 200# PULL STRING SHALL
BE PROVIDED IN EACH INNERDUCT AND EACH CONDUIT. SEE SHT.
ES-101 FOR CONTINUATION OF SERVICE CONDUIT.
DORM ROOM WALL MOUNTED DATA/VOICE CAT 6 OUTLET WITH (2) CAT
6 OUTLETS. PROVIDE WITH (2) CAT 6 CABLES IN 1 1/4"C ROUTED TO THE
OUTLET. .
12 ST SM FOC BACKBONE CABLE (PLENUM RATED), TYPE OS-2. ROUTE
IN ORANGE INNERDUCT IN THE CABLE TRAY.
BACKBONE CABLE PATCH PANELS. COPPER BACKBONE SHALL BE
TERMINATED ONE PAIR PER PORT (PINS 4 & 5), EXCEPT FOR PORT #48
TERMINATE 2-PAIR. PROVIDE QUANTITY OF PATCH PANELS AS
REQUIRED TO TERMINATE THE 50 PAIR CABLE.
1.FOR ELECTRICAL NOTES, ABBREVIATIONS, AND SYMBOLS REFER TO
DRAWING E-001, E-002 & ET-001.
2. PROVIDE ALL PATCH PANELS AS REQUIRED TO SUFFICIENTLY
TERMINATE ALL CABLES SPECIFIED.
3. DRAWINGS ARE DIAGRAMMATIC ONLY. EXACT ARRANGEMENT FOR
EQUIPMENT AND PATCH PANELS SHALL BE COORDINATED AND
OPTIMIZED IN THE FIELD.
4. MOST JUNCTION BOXES AND RACEWAYS ARE NOT SHOWN. ALL
INSTALLATION SHALL BE IN ACCORDANCE WITH NATIONAL ELECTRICAL
CODE, UFC 3-580-01 CRITERIA, AND TIA STANDARDS AND
REQUIREMENTS.
5. NOT MORE THAN (2) 90-DEGREE TURNS SHALL BE ALLOWED ON ANY
CABLE ROUTES OR PULLS WITHOUT PROPER INSTALLATION OF PULL
BOXES OR JUNCTION BOXES.
6. ALL BACKBONE CONDUITS FOR TELECOM ASSOCIATED CABLES SHALL
BE PROVIDED WITH 3X3" CELL FABRIC INNERDUCTS, AND WITH PULL
STRINGS IF IT IS A SPARE CONDUIT.
7. WHILE NOT SHOWN, CABLES FROM SERVICE ENTRANCE CONDUITS TO
TELCOM RACKS SHALL BE VIA CABLE TRAYS AND SUPPORT AS
REQUIRED BY UFC 3-580-01 CRITERIA.
8. HORIZONTAL DISTRIBUTION CAT 6 CABLES SHALL BE GROUPED IN
BUNDLES OF 25 CABLES MAXIMUM, AND PROVIDED WITH VELCRO CABLE
TIES IN THE CABLE TRAY. CABLE TIES SHALL BE PROVIDED AT
INTERVALS OF EVERY 25 LF.
9. ALL CATEGORY 6 & 6A CABLES SHALL BE PLENUM RATED.
10. ALL FIBER OPTIC CABLES SHALL BE PLENUM RATED.
11. SEE TELECOMM FLOOR PLAN FOR QUANTITY OF OUTLETS AND
DEVICES.
12. THIS CONTRACTINCLUDES THE INSTALLATION OF THE PATHWAYS,
CABLING, CAT 6A JACKS AND BOXES REQUIRED FOR THE FUTURE
INSTALLATION OF WIRELESS ROUTERS. THE WIRELESS
ROUTERS WILL BE PROVIDED BY OTHERS.
DRAWING KEYED NOTES
GENERAL NOTES
NTSET601
1 TELECOMM RISER DIAGRAM
(TYP)
R ev is ed p er a m en dm en t
/0 4/
R ev is ed p er a m en dm en t
/1 1/
| Sheets |
| ET601 - TELECOMM RISER DIAGRAM |
File details come from the government source that posted it. Updated .