09 51 00.pdf
PDF 48 KB Posted
- Attached to
- WVA Fire Station Construction Acquisition Federal contract opportunity
- Solicitation number
- W912DS25RA009
About this file
This document is a technical specification (Section 09 51 00) for Acoustical Ceilings for a WVA Fire Station project, dated August 06, 2025. The specification provides detailed requirements for acoustical ceiling systems, including multiple ceiling tile types with specific performance characteristics such as fire resistance, sound absorption, and indoor air quality certifications. Key requirements include Type III, IV, IX, X, XI, and XII ceiling tiles with recycled content percentages ranging from 25-60%, Noise Reduction Coefficients (NRC) of 0.80, and flame spread ratings of Class A (25 or less).
The specification mandates strict installation guidelines, including suspension system requirements, hanger configurations, and acoustical unit placement. Additional requirements include indoor air quality certifications from UL 2818 (Greenguard) Gold or SCS Global Services, environmental conditions for installation (60-85 degrees F, 70% max humidity), and a ten-year manufacturer's warranty covering defects like sagging, warping, and grid system rusting. The contractor must provide spare tiles at a rate of 5 tiles per 1000 installed, and all materials must be free from visual evidence of biological growth.
View the file
Other files for this federal contract opportunity
Show all 46
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WVA Fire Station WVAFIRESTATION23 Amendment 004 August 06, 2025
SECTION 09 51 00
ACOUSTICAL CEILINGS
08/20
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM A489 (2018; E 2018) Standard Specification for Carbon Steel Eyebolts
ASTM A580/A580M (2018) Standard Specification for Stainless Steel Wire
ASTM A641/A641M (2019) Standard Specification for Zinc-Coated (Galvanized) Carbon Steel Wire
ASTM A653/A653M (2020) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A1008/A1008M (2021a) Standard Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, Solution Hardened, and Bake Hardenable
ASTM B633 (2019) Standard Specification for Electrodeposited Coatings of Zinc on Iron and Steel
ASTM C423 (2009a) Sound Absorption and Sound Absorption Coefficients by the Reverberation Room Method
ASTM C635/C635M (2022) Standard Specification for Manufacture, Performance, and Testing of Metal Suspension Systems for Acoustical Tile and Lay-In Panel Ceilings
ASTM C636/C636M (2013) Standard Practice for Installation of Metal Ceiling Suspension Systems for Acoustical Tile and Lay-In Panels
ASTM C834 (2017) Standard Specification for Latex Sealants
ASTM E84 (2020) Standard Test Method for Surface Burning Characteristics of Building Materials
SECTION 09 51 00 Page 1
ASTM E119 (2020) Standard Test Methods for Fire Tests of Building Construction and Materials
ASTM E413 (2022) Classification for Rating Sound Insulation
ASTM E795 (2016) Standard Practices for Mounting Test Specimens During Sound Absorption Tests
ASTM E1111/E1111M (2014; R 2022) Standard Test Method for Measuring the Interzone Attenuation of Open Office Components
ASTM E1264 (2022) Standard Classification for Acoustical Ceiling Products
ASTM E1414/E1414M (2021a) Standard Test Method for Airborne Sound Attenuation Between Rooms Sharing a Common Ceiling Plenum
ASTM E1477 (1998a; R 2017; E 2018) Standard Test Method for Luminous Reflectance Factor of Acoustical Materials by Use of Integrating-Sphere Reflectometers
CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)
CDPH SECTION 01350 (2010; Version 1.1) Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources using Environmental Chambers
GREEN SEAL (GS)
GS-36 (2013) Adhesives for Commercial Use
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS SCS Global Services (SCS) Indoor Advantage
SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD)
SCAQMD Rule 1168 (2017) Adhesive and Sealant Applications
UNDERWRITERS LABORATORIES (UL)
UL 2818 (2013) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government.
SECTION 09 51 00 Page 2
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Drawings ; G,DO
SD-03 Product Data
Acoustical Ceiling Systems ; G, DO
Fire Resistive Ceilings ; G,DO
Recycled Content for Type III Ceiling Tiles ; S
Recycled Content for Type IV Ceiling Tiles ; S
Recycled Content for Type IX Ceiling Tiles ; S
Recycled Content for Type XII Ceiling Tiles ; S
Recycled Content for Suspension Systems ; S
Acoustical Performance ; G,DO
SD-04 Samples
Acoustical Units ; G,DO
Acoustical Ceiling Tiles ; G,DO
SD-06 Test Reports
Fire Resistive Ceilings ; G
SD-07 Certificates
Indoor Air Quality for Type III Ceiling Tiles ; S
Indoor Air Quality for Type IV Ceiling Tiles ; S
Indoor Air Quality for Type IX Ceiling Tiles ; S
Indoor Air Quality for Type X Ceiling Tiles ; S
Indoor Air Quality for Type XI Ceiling Tiles ; S
Indoor Air Quality for Type XII Ceiling Tiles ; S
Indoor Air Quality for Impact/Abrasion Resistant Ceiling Tiles ; S
Indoor Air Quality for Humidity Resistant Ceiling Tiles ; S
Indoor Air Quality for Adhesives ; S
Indoor Air Quality for Sealants ; S
SECTION 09 51 00 Page 3
1.3 CERTIFICATIONS
1.3.1 Indoor Air Quality Certifications
1.3.1.1 Ceiling Tiles
Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party programs that products meet the requirements of this section. Provide current product certification documentation from certification body.
1.3.1.2 Adhesives and Sealants
Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party programs that products meet the requirements of this Section. Provide current product certification documentation from certification body. When product does not have certification, provide validation that product meets the indoor air quality product requirements cited in this Section.
1.4 DELIVERY, STORAGE. AND HANDLING
Deliver materials to the site in the manufacturer's original unopened containers with brand name and type clearly marked. Carefully handle and store materials in dry, watertight enclosures. Immediately before installation, store acoustical units for not less than 24 hours at the same temperature and relative humidity as the space where they will be installed in order to assure proper temperature and moisture acclimation.
1.5 ENVIRONMENTAL REQUIREMENTS
Maintain a uniform temperature of not less than 60 degrees F nor more than 85 degrees F and a relative humidity of not more than 70 percent for 24 hours before, during, and 24 hours after installation of acoustical units.
1.6 SCHEDULING
Complete and dry interior finish work such as plastering, concrete and terrazzo work before ceiling installation. Complete mechanical, electrical, and other work above the ceiling line; install and start operating heating, ventilating, and air conditioning systems in order to maintain temperature and humidity requirements.
1.7 WARRANTY
Provide manufacturer's warranty to repair or replace defective materials and workmanship including but not limited to, sagging and warping of panels and rusting and of grid systems, for a period of ten yearsfrom date of final acceptance of the work.
1.8 EXTRA MATERIALS
Furnish spare tiles, from the same lot as those installed, of each color at the rate of 5 tiles for each 1000 tiles installed.
SECTION 09 51 00 Page 4
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
Provide sound controlling units mechanically mounted on a ceiling suspension system for acoustical treatment. Provide the unit size, texture, finish, and color as specified. The Contractor has the option to substitute inch-pound (I-P) Recessed Light Fixtures (RLF) for metric RLF.
If the Contractor opts to provide I-P RLF, then provide I-P products for other ceiling elements like acoustical ceiling tiles, air diffusers, air registers and grills. Coordinate the entire ceiling system with other details, like the location of access panels and ceiling penetrations, for instance, shown on the drawings. Submit drawings showing the the location, extent and details of acoustical treatment including suspension system, method of anchoring and fastening, and reflected ceiling plan.
Coordinate with paragraph RECLAMATION PROCEDURES for reclamation of mineral fiber acoustical ceiling panels to be removed from the job site.
2.1.1 Fire Resistive Ceilings
Rate acoustical ceiling systems , indicated as fire resistant, for fire endurance as specified when tested in accordance with ASTM E119. Test suspended ceiling with a specimen roof assembly representative of the indicated construction, including mechanical and electrical work within ceiling space openings for light fixtures, and air outlets, and access panels. Provide ceiling assembly rating for1 hour exposed grid systemor as shown on drawings. Provide acoustical units with a flame spread of 25 or less and smoke development of 50 or less when tested in accordance with
ASTM E84.
Submit manufacturer's catalog showing UL classification of fire-rated ceilings giving materials, construction details, types of floor and roof constructions to be protected, and UL design number and fire protection time rating for each required floor or roof construction and acoustic ceiling assembly.
Submit reports by an independent testing laboratory attesting that acoustical ceiling systems meet specified fire endurance and sound transmission requirements. Data attesting to conformance of the proposed system to Underwriters Laboratories requirements for the fire endurance rating listed in UL Fire Resistance may be submitted in lieu of test reports.
2.1.2 Acoustical Performance
2.1.2.1 Ceiling Sound Transmission
Provide ceiling systems with the specified Ceiling Attenuation Class (CAC) ratings as determined in accordance with ASTM E1414/E1414M and ASTM E413.
Provide sound attenuators over light fixtures, air terminals and other ceiling penetrations, provide acoustical blanket insulation on top of the ceiling or adjacent to partitions to provide lightweight acoustical plenum barriers above partitions as required to achieve the specified CAC ratings. Provide test ceiling continuous at the partition and assembled in the suspension system in the same manner that the ceiling will be installed on the project.
SECTION 09 51 00 Page 5
2.1.2.2 Ceiling Sound Absorption
Determine the Noise Reduction Coefficient (NRC) in accordance with ASTM C423. Determine Articulation Class (AC) in accordance with
ASTM E1111/E1111M .
2.1.3 Light Reflectance
Determine light reflectance factor in accordance with ASTM E1477 test method.
2.2 ACOUSTICAL UNITS
Submit samples of each type of acoustical unit and each type of suspension grid tee section showing texture, finish, and color. Conform acoustical units to ASTM E1264, Class A, and the following requirements:
2.2.1 Units for Exposed-Grid System A
2.2.1.1 Type
III (non-asbestos mineral fiber with painted finish). Provide Type III Acoustical Ceiling Tiles containing a minimum of 30 percent recycled content. Provide data identifying percentage of recycled content for Type III ceiling tiles . Provide certification of indoor air quality for Type III Ceiling Tiles .
IV (non-asbestos mineral fiber with membrane-faced overlay). Provide Type IV Acoustical Ceiling Tiles containing a minimum of 60 percent recycled content. Provide data identifying percentage of recycled content for Type IV ceiling tiles . Provide certification of indoor air quality for Type IV Ceiling Tiles .
IX (mineral fiber with scrubbable finish).Provide Type IX Acoustical Ceiling Tiles containing a minimum 50 percent recycled content. Provide data identifying percentage of recycled content for Type IX ceiling tiles .
Provide certification of indoor air quality for Type IX Ceiling Tiles .
X (mineral composition with plastic membrane).Provide certification of indoor air quality for Type X Ceiling Tiles .
XI (mineral fiber with fabric faced overlay). Provide certification of indoor air quality for Type XI Ceiling Tiles .
XII (fiberglass base with membrane-faced overlay).Provide Type XII Acoustical Ceiling Tiles containing a minimum of 25 percent recycled content. Provide data identifying percentage of recycled content for Type XII ceiling tiles . Provide certification of indoor air quality for Type XII Ceiling Tiles .
2.2.1.2 Flame Spread
Class A, 25 or less
2.2.1.3 Pattern
E
SECTION 09 51 00 Page 6
2.2.1.4 Minimum NRC
0.80 when tested on mounting Type E-400 of ASTM E795.
2.2.1.5 Minimum Light Reflectance Coefficient
LR-1, 0.75 or greater
2.2.1.6 Nominal Size
24 by 24 inch
2.2.1.7 Edge Detail
Manufacturer's standard
2.2.1.8 Finish
Factory-applied standard finish. See paragraph COLORS AND STANDARDS.
2.2.2 Impact/Abrasion Resistant Units
2.2.2.1 Type
Non-asbestos mineral composition with a hardened mineral surface and factory applied white paint finish. Provide a surface resistant to impact and abrasion. Provide certification of indoor air quality for Impact/Abrasion Resistant Ceiling Tiles .
2.2.2.2 Flame Spread
Class A, 25 or less
2.2.2.3 Pattern
E
2.2.2.4 Minimum NRC
0.80 when tested on Mounting Type E-400 of ASTM E795.
2.2.2.5 Minimum Light Reflectance Coefficient
LR-1, 0.75 or greater
2.2.2.6 Nominal Size
24 by 24inch
2.2.2.7 Edge Detail
Manufacturer's standard
2.2.2.8 Joint Detail
Trimmed and butted
2.2.2.9 Finish
Factory-applied standard finish. See paragraph COLORS AND PATTERNS.
SECTION 09 51 00 Page 7
2.2.3 Humidity Resistant Composition Units
2.2.3.1 Type
Non-asbestos mineral or glass fibers bonded with ceramic, moisture resistant thermo-setting resin, or other moisture resistant material and having a factory applied white paint finish. Provide panels that do not sag or warp under conditions of heat, high humidity or chemical fumes.
Provide certification of indoor air quality for Humidity Resistant Ceiling Tiles .
2.2.3.2 Flame Spread
Class: A, 25 or less
2.2.3.3 Pattern
E
2.2.3.4 Minimum NRC0.80when tested on Mounting Type E-400 of ASTM E795.
2.2.3.5 Minimum Light Reflectance Coefficient
LR-1, 0.75 or greater
2.2.3.6 Nominal Size
24 by 24inch
2.2.3.7 Edge Detail
Square
2.2.3.8 Finish
Factory-applied standard finish. See paragraph COLORS AND PATTERNS.
2.2.4 Unit Acoustical Absorbers
Provide individually mounted sound absorbing plaques composed of glass fibers or non-asbestos mineral fibers and having a NRC range of not less than 0.60 - 0.70 when tested in accordance with ASTM C423 and reported as a 4 frequency average.
2.3 SUSPENSION SYSTEM
Provide standard width flange suspension system conforming to ASTM C635/C635M for intermediate-duty systems. Provide surfaces exposed to view of aluminum or steel with a factory-applied white . Provide wall molding having a flange of not less than 15/16 inch . Provide inside and outside corner capsmitered corners. Provide a suspension system with a maximum deflection of 1/360 of the span length capable of supporting the finished ceiling, light fixtures, air diffusers, and accessories, as shown.Conform seismic detailsas indicated.
Provide Suspension System containing a minimum of 15 percent recycled content. Provide data identifying percentage of recycled content for
SECTION 09 51 00 Page 8 suspension systems .
2.4 HANGERS
Provide hangers and attachment capable of supporting a minimum 300 pound ultimate vertical load without failure of supporting material or attachment.
2.4.1 Wires
Conform wires to ASTM A641/A641M , Class 1, 0.08 inch (12 gauge) in diameter. ASTM A580/A580M , composition 302 or 304, condition annealed stainless steel, 0.08 inch (12 gauge) in diameter.
2.4.2 Straps
Provide straps of 1 by 3/16 inch galvanized steel conforming to ASTM A653/A653M , with a light commercial zinc coating or ASTM A1008/A1008M with an electrodeposited zinc coating conforming to ASTM B633, Type RS.
2.4.3 Rods
Provide 3/16 inch diameter threaded steel rods, zinc or cadmium coated.
2.4.4 Eyebolts
Provide eyebolts of weldless, forged-carbon-steel, with a straight-shank in accordance with ASTM A489. Provide minimum 1/4 inch , zinc coated eyebolts.
2.4.5 Masonry Anchorage Devices
Comply with ASTM C636/C636Mfor anchorage devices for eyebolts.
2.5 ADHESIVE
Use adhesive as recommended by tile manufacturer. Provide non-aerosol adhesive products used on the interior of the building (defined as inside of the weatherproofing system) that meet either emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type) or VOC content requirements of SCAQMD Rule 1168 . Provide aerosol adhesives used on the interior of the building that meet either emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type) or VOC content requirements of GS-36. For products located on the interior of the building (inside of the weatherproofing system), provide certification or validation of indoor air quality for adhesives .
2.6 FINISHES
Use manufacturer's standard textures, patterns and finishes as specified for acoustical units and suspension system members. Treat ceiling suspension system components to inhibit corrosion.
2.7 COLORS AND PATTERNS
Use colors and patterns for acoustical units and suspension system components as indicated; colors listed are not intended to limit the selection of equal colors from other manufacturers.
SECTION 09 51 00 Page 9
2.8 ACOUSTICAL SEALANT
Conform acoustical sealant to ASTM C834, nonstaining. Provide sealants used on the interior of the building (defined as inside of the weatherproofing system)in accordance with requirements of Section 07 92 00 JOINT SEALANTS.that meet either emissions requirements of CDPH SECTION 01350 (limit the requirements for either office or classroom spaces regardless of space type) or VOC content requirements of SCAQMD Rule 1168 . For products located on the interior of the building (inside of the weatherproofing system), provide certification of indoor air quality for Sealants .
PART 3 EXECUTION
3.1 INSTALLATION
Do not install building construction materials that show visual evidence of biological growth.
Examine surfaces to receive directly attached acoustical units for unevenness, irregularities, and dampness that would affect quality and execution of the work. Rid areas, where acoustical units will be cemented, of oils, form residue, or other materials that reduce bonding capabilities of the adhesive. Complete and dry interior finish work such as plastering, concrete, and terrazzo work before installation. Complete and approve mechanical, electrical, and other work above the ceiling line prior to the start of acoustical ceiling installation. Provide acoustical work complete with necessary fastenings, clips, and other accessories required for a complete installation. Do not expose mechanical fastenings in the finished work. Lay out hangers for each individual room or space.
Provide hangers to support framing around beams, ducts, columns, grilles, and other penetrations through ceilings. Keep main runners and carrying channels clear of abutting walls and partitions. Provide at least two main runners for each ceiling span. Wherever required to bypass an object with the hanger wires, install a subsuspension system so that all hanger wires will be plumb.
3.1.1 Suspension System
Install suspension system in accordance with ASTM C636/C636M and as specified herein. Do not suspend hanger wires or other loads from underside of steel decking.
3.1.1.1 Plumb Hangers
Install hangers plumb and not pressing against insulation covering ducts and pipes. Where lighting fixtures are supported from the suspended ceiling system, provide hangers at a minimum of four hangers per fixture and located not more than 6 inch from each corner of each fixture.
3.1.1.2 Splayed Hangers
Splay (slope or slant) hangers around obstructions, offsetting the resulting horizontal force by bracing, countersplaying, or other acceptable means.
SECTION 09 51 00 Page 10
3.1.2 Wall Molding
Provide wall molding where ceilings abut vertical surfaces. Miter corners where wall moldings intersect or install corner caps. Secure wall molding not more than 3 inch from ends of each length and not more than 16 inch on centers between end fastenings. Provide wall molding springs at each acoustical unit in semi-exposed or concealed systems.
3.1.3 Acoustical Units
Install acoustical units in accordance with the approved installation instructions of the manufacturer. Ensure that edges of acoustical units are in close contact with metal supports, with each other, and in true alignment. Arrange acoustical units so that units less than one-half width are minimized. Hold units in exposed-grid system in place with manufacturer's standard hold-down clips, if units weigh less than 1 psf or if required for fire resistance rating.
3.1.4 Acoustical Sealant
Seal all joints around pipes, ducts or electrical outlets penetrating the ceiling. Apply a continuous ribbon of acoustical sealant on vertical web of wall or edge moldings.
3.1.5 Adhesive Application
Wipe back of tile to remove accumulated dust. Daub acoustical units on back side with four equal daubs of adhesive. Apply daubs near corners of tiles. Ensure that contact area of each daub is at least 2 inch diameter in final position. Press units into place, aligning joints and abutting units tight and uniform without differences in joint widths.
3.2 CEILING ACCESS PANELS
Locate ceiling access panels directly under the items which require access.
3.3 CLEANING
Following installation, clean dirty or discolored surfaces of acoustical units and leave them free from defects. Remove units that are damaged or improperly installed and provide new units as directed.
-- End of Section --
SECTION 09 51 00 Page 11
| 09 51 00 - ACOUSTICAL CEILINGS |
| PART 1 GENERAL |
| 1.1 REFERENCES |
| 1.2 SUBMITTALS |
| 1.3 CERTIFICATIONS |
| 1.3.1 Indoor Air Quality Certifications |
| 1.3.1.1 Ceiling Tiles |
| 1.3.1.2 Adhesives and Sealants |
| 1.4 DELIVERY, STORAGE. AND HANDLING |
| 1.5 ENVIRONMENTAL REQUIREMENTS |
| 1.6 SCHEDULING |
| 1.7 WARRANTY |
| 1.8 EXTRA MATERIALS |
| PART 2 PRODUCTS |
| 2.1 SYSTEM DESCRIPTION |
| 2.1.1 Fire Resistive Ceilings |
| 2.1.2 Acoustical Performance |
| 2.1.2.1 Ceiling Sound Transmission |
| 2.1.2.2 Ceiling Sound Absorption |
2.1.3 Light Reflectance
| 2.2 ACOUSTICAL UNITS |
| 2.2.1 Units for Exposed-Grid System A |
| 2.2.1.1 Type |
| 2.2.1.2 Flame Spread |
| 2.2.1.3 Pattern |
| 2.2.1.4 Minimum NRC |
| 2.2.1.5 Minimum Light Reflectance Coefficient |
| 2.2.1.6 Nominal Size |
| 2.2.1.7 Edge Detail |
| 2.2.1.8 Finish |
| 2.2.2 Impact/Abrasion Resistant Units |
| 2.2.2.1 Type |
| 2.2.2.2 Flame Spread |
| 2.2.2.3 Pattern |
| 2.2.2.4 Minimum NRC |
| 2.2.2.5 Minimum Light Reflectance Coefficient |
| 2.2.2.6 Nominal Size |
| 2.2.2.7 Edge Detail |
| 2.2.2.8 Joint Detail |
| 2.2.2.9 Finish |
| 2.2.3 Humidity Resistant Composition Units |
| 2.2.3.1 Type |
| 2.2.3.2 Flame Spread |
| 2.2.3.3 Pattern |
| 2.2.3.4 Minimum NRC0.80when tested on Mounting Type E-400 of ASTM E795. |
| 2.2.3.5 Minimum Light Reflectance Coefficient |
| 2.2.3.6 Nominal Size |
| 2.2.3.7 Edge Detail |
| 2.2.3.8 Finish |
2.2.4 Unit Acoustical Absorbers
| 2.3 SUSPENSION SYSTEM |
| 2.4 HANGERS |
| 2.4.1 Wires |
| 2.4.2 Straps |
| 2.4.3 Rods |
| 2.4.4 Eyebolts |
| 2.4.5 Masonry Anchorage Devices |
| 2.5 ADHESIVE |
| 2.6 FINISHES |
| 2.7 COLORS AND PATTERNS |
| 2.8 ACOUSTICAL SEALANT |
| PART 3 EXECUTION |
| 3.1 INSTALLATION |
| 3.1.1 Suspension System |
| 3.1.1.1 Plumb Hangers |
| 3.1.1.2 Splayed Hangers |
| 3.1.2 Wall Molding |
| 3.1.3 Acoustical Units |
| 3.1.4 Acoustical Sealant |
| 3.1.5 Adhesive Application |
| 3.2 CEILING ACCESS PANELS |
| 3.3 CLEANING |
File details come from the government source that posted it. Updated .