M-702 SCHEDULES.pdf
PDF 212 KB Posted
- Attached to
- Construct Mission Training Center (MTC) Facility Federal contract opportunity
- Solicitation number
- W50S78-24-B-0001
- Issued by
- Department of the Army National Guard
About this file
This document appears to be a federal solicitation for the construction of a 15,200 square foot Mission Training Center (MTC) facility for the Texas Air National Guard at Joint Base San Antonio-Lackland Air Force Base. The solicitation is for a single firm fixed-price contract and includes a base bid as well as eight options such as permeable pavement, landscaping, and additional flooring and signage. The project has a 540-calendar day period of performance and is set aside for small businesses under NAICS code 236220 with a size standard of $45 million. Key brand name items are specified for compatibility with existing systems. The solicitation provides details on the site visit, pre-bid conference, and process for submitting questions and requests for information. No paper copies will be distributed, and amendments will be posted to the government's Contract Opportunities webpage.
View the file
Other files for this federal contract opportunity
Show all 50
Construct Mission Training Center (MTC) Facility has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5801 Broadway Extension, Suite 500 Oklahoma City, OK 73118-7436
405.840.2931 | fsb-ae.com
Frankfurt-Short-Bruza Associates,P.C.
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
C
B
A
D
C
B
A
54321
20190310
NDM
Jo in t B as e S an A nt on io
JB
SA
Ke lly A nn ex , T ex as
Te xa s Ai r N at io na l G ua rd 9t h
FW
F- M iss io n Tr ain in g Ce nt er (M
TC
C :\U sers\njd\O neD rive - FSB Architects +
Engineers\D ocum ents\90310_M ech_23_N
D oolittle8ZBW
T.rvt
9/16/2024 12:52:59 PM
15 AUGUST 2024
SCHEDULES
M-702
RRS
DLC
EAO
CONDENSING HOT WATER BOILER SCHEDULE
MARK TYPE FLUID
DESIGN FLOW
(GPM)
EWT
(°F)
LWT
(°F)
INPUT
(MBH)
MIN. OUTPUT
(MBH)
MAX. WPD
(FT. W.C.) FUEL
ELECTRICAL DATA
NOTESV / ɸ / Hz
BLR-01 CONDENSING FIRE TUBE WATER 50.0 120 150 600 540 0.19 NATURAL GAS 115/1/60 ALL BLR-02 CONDENSING FIRE TUBE WATER 50.0 120 150 600 540 0.19 NATURAL GAS 115/1/60 ALL
EXPANSION TANK SCHEDULE
MARK TYPE SERVICE
MIN. TANK
VOLUME
(GAL)
MIN. VOLUME
ACCEPTANCE
(GAL)
MIN. SYSTEM
FILL PRESSURE
(PSIG)
RELIEF VALVE
WORKING PRES.
(PSIG) NOTES
XT-01 DIAPHRAGM, VERTICAL FLOOR-MOUNTED HEATING WATER 23 10 15 50 1,2
XT-02 DIAPHRAGM, VERTICAL FLOOR-MOUNTED CHILLED WATER 23 10 15 50 1,3
AIR SEPARATOR SCHEDULE
MARK TYPE SERVICE
SYSTEM
CONNECTION
MIN. FLOW
(GPM)
MAX. WPD
(PSIG) NOTES
AS-01 IN-LINE COALESCING AIR/DIRT SEPARATOR HEATING WATER 2 35 1.3 ALL
AS-02 IN-LINE COALESCING AIR/DIRT SEPARATOR CHILLED WATER 4 145 1.7 ALL
BYPASS CHEMICAL FEEDER SCHEDULE
MARK SERVICE
VOLUME
(GAL) NOTES
BCF-01 HEATING WATER 2 ALL
BCF-02 CHILLED WATER 2 ALL
PUMP SCHEDULE
MARK TYPE SERVICE
CONNECTION SIZE DUTY POINT MOTOR
NOTES
INLET
(IN.)
OUTLET
(IN.)
CAPACITY
(GPM)
TDH
(FT. WC.)
MIN.
EFF. BHP RPM HP V / ɸ / Hz
CWP-01 VERTICAL CLOSE-COUPLED IN-LINE CENTRIFUGAL CHILLED WATER 2 2 145 80 76.7 3.82 3600 5 460 / 3 / 60 ALL CWP-02 VERTICAL CLOSE-COUPLED IN-LINE CENTRIFUGAL CHILLED WATER 2 2 145 80 76.7 3.82 3600 5 460 / 3 / 60 ALL HWP-01 VERTICAL CLOSE-COUPLED IN-LINE CENTRIFUGAL HEATING WATER 1.25 1.25 50 40 59.5 0.55 3600 1 460 / 3 / 60 ALL HWP-02 VERTICAL CLOSE-COUPLED IN-LINE CENTRIFUGAL HEATING WATER 1.25 1.25 50 40 59.5 0.55 3600 1 460 / 3 / 60 ALL
1.
2.
3.
NOTES:
PROVIDE BOILER WITH LOW NOX BURNER (<30 PPM CORRECTED FOR 3% OXYGEN).
PROVIDE ASME CSD-1 COMPLIANT AND UL-LISTED FUEL TRAIN.
PROVIDE FACTORY-FURNISHED OR FACTORY-INSTALLED COMPONENTS AND ACCESSORIES TO
INCLUDE BUT NOT BE LIMITED TO: SUPPLY WATER TEMPERATURE SENSOR, RETURN WATER
TEMPERATURE SENSOR, MANUAL RESET HIGH-LIMIT AQUASTAT, SAFETY RELIEF VALVE, AND
LOW WATER CUTOFF.
1.
2.
3.
NOTES:
PROVIDE NEMA MG-1 PREMIUM EFFICIENCY INVERTER-DUTY MOTOR WITH SHAFT GROUNDING RINGS AND
TEFC ENCLOSURE.
PROVIDE UNIT-MOUNTED VARIABLE FREQUENCY DRIVE.
PUMP SELECTION SHALL HAVE A NON-OVERLOADING MOTOR HP.
1.
2.
3.
NOTES:
PROVIDE ASME STAMPED VESSEL RATED FOR 125 PSIG OR GREATER WORKING PRESSURE.
PROVIDE TOP-SIDE THREADED CONNECTION FOR AIR VENT AND BOTTOM-SIDE THREADED CONNECTION FOR DRAIN VALVE.
FLANGED CONNECTIONS.
1.
2.
3.
NOTES:
PROVIDE ASME STAMPED VESSEL RATED FOR 125 PSIG OR GREATER WORKING PRESSURE.
SELECTION BASED ON HEATING WATER SYSTEM VOLUME: 225 GAL.
SELECTION BASED ON CHILLED WATER SYSTEM VOLUME: 450 GAL.
1.
2.
3.
NOTES:
DOME-BOTTOM, ASME STAMPED VESSEL RATED
FOR 125 PSIG OR GREATER WORKING
PRESSURE.
PROVIDE WITH LEGS TO KEEP FEEDER ABOVE
MECHANICAL ROOM FLOOR.
PROVIDE UNIT MANUFACTURER'S FILTER BAG
KIT INCLUDING ONE SPARE FILTER.
BUFFER TANK SCHEDULE
MARK TYPE SERVICE
SYSTEM CONNECTION
(IN.)
VOLUME
(GAL.) NOTES
BT-01 VERTICAL HEATING WATER 2 125 ALL
BT-02 VERTICAL CHILLED WATER 3 100 ALL
1.
2.
3.
NOTES:
ASME STAMPED VESSEL RATED FOR 125 PSIG OR GREATER WORKING PRESSURE.
FLANGED CONNECTIONS.
CONNECTIONS HIGH ON TANK.
FLOW CONTROL VALVE SCHEDULE
MARK ASSOCIATED EQUIPMENT
FLUID
TEMP
(°F)
DESIGN FLOW
RATE
(GPM)
NOMINAL
VALVE SIZE
(IN.)
VALVE MAX.
FLOW RATE
(GPM)
DIFF. PRESSURE
RANGE (ΔPSIG)
VALVE TYPE ACTION NOTESMIN. MAX.
FCV-CW1 CW MIN FLOW BYPASS 42.0 60.0 2 1/2 85 4.4 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8
FCV-CW2 CH-01 ISO VALVE 42.0 92.2 3 - - - BALL VALVE 2-POSITION 2,5,6,7,8
FCV-CW3 CH-02 ISO VALVE 42.0 92.2 3 - - - BALL VALVE 2-POSITION 2,5,6,7,8
FCV-CW4 FCU-01 42.0 5.2 3/4 7.5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-CW5 FCU-02 42.0 1.3 1/2 5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-CW6 FCU-03 42.0 1.3 1/2 5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-CW7 FCU-04 42.0 6.0 3/4 7.5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-CW8 AHU-01 42.0 53.3 2 1/2 85 4.4 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8
FCV-CW9 CRAC-01 42.0 16.0 - - - - - MODULATING 9
FCV-CW10 CRAC-02 42.0 16.0 - - - - - MODULATING 9
FCV-CW11 CRAC-03 42.0 16.0 - - - - - MODULATING 9
FCV-CW12 CRAC-04 42.0 16.0 - - - - - MODULATING 9
FCV-CW13 CRAC-05 42.0 16.0 - - - - - MODULATING 9
FCV-CW14 FCU-05 42.0 6.0 3/4 7.5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-CW15 FCU-06 42.0 6.0 3/4 7.5 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-HW1 HW MIN FLOW BYPASS 150.0 30.0 1 1/2 33 4.4 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8
FCV-HW2 BLR-01 ISO VALVE 150.0 17.0 1 1/2 - - - BALL VALVE 2-POSITION 2,5,6,7,8
FCV-HW3 BLR-02 ISO VALVE 150.0 17.0 1 1/2 - - - BALL VALVE 2-POSITION 2,5,6,7,8
FCV-HW4 VAV-01 150.0 3.3 3/4 7.5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-HW5 VAV-02 150.0 0.9 1/2 5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-HW6 VAV-03 150.0 1.1 1/2 5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-HW7 VAV-04 150.0 5.0 3/4 7.5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-HW8 VAV-05 150.0 2.1 1/2 5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-HW9 VAV-06 150.0 1.2 1/2 5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-HW10 VAV-07 150.0 1.2 1/2 5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-HW11 VAV-08 150.0 1.2 1/2 5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-HW12 VAV-09 150.0 1.8 1/2 5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-HW13 VAV-10 150.0 0.8 1/2 5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-HW14 VAV-11 150.0 0.4 1/2 5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-HW15 PHX-01 150.0 7.2 1 12 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-HW16 UH-01 150.0 1.9 1/2 5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-HW17 UH-03 150.0 1.0 1/2 5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-HW18 FCU-01 150.0 2.1 1/2 5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-HW19 FCU-02 150.0 0.9 1/2 5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-HW20 FCU-03 150.0 0.9 1/2 5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-HW21 FCU-04 150.0 2.0 1/2 5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-HW22 AHU-01 150.0 30.5 1 1/4 28.5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8,10 FCV-HW23 VAV-12 150.0 0.8 1/2 5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-HW24 VAV-13 150.0 0.6 1/2 5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-HW25 VAV-14 150.0 0.6 1/2 5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-HW26 VAV-15 150.0 0.8 1/2 5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8 FCV-HW27 VAV-16 150.0 2.4 1/2 5 5.0 60.0 PRESSURE INDEPENDENT CONTROL VALVE MODULATING 1,2,3,4,8
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
NOTES:
PROVIDE PRESSURE INDEPENDENT CONTROL VALVE IN ACCORDANCE WITH THE SPECIFICATIONS.
PROVIDE ACTUATOR FOR USE WITH 24V POWER SOURCE.
PROVIDE ACTUATOR WITH 0-100% POSITION INDICATOR.
REFER TO CONTROL DIAGRAMS FOR NECESSARY ACTUATOR FAILURE POSITIONS.
PROVIDE ACTUATOR WITH LIMIT SWITCHES.
PROVIDE ACTUATOR WITH NEMA 4X ENCLOSURE.
PROVIDE ACTUATOR WITH 600 IN-LB MINIMUM OUTPUT TORQUE AT 24V.
2-WAY VALVE.
VALVE IS PROVIDED FACTORY-INSTALLED IN ASSOCIATED EQUIPMENT.
VALVE SELECTED TO PROVIDE HIGHER RESOLUTION CONTROL AT SIGNIFICANTLY LOWER THAN DESIGN FLOW RATES.
FLOW METER SCHEDULE
MARK TYPE SERVICE
LINE SIZE
(IN.)
MAX FLOW
(GPM)
MIN FLOW
(GPM) NOTES
FM-CH01 ELECTROMAGNETIC INSERTION FLOW METER CHILLED WATER 4 145 60 1,3,4,5
FM-HW01 ELECTROMAGNETIC INSERTION FLOW METER HEATING WATER 2 35 30 2,3,4,5
1.
2.
3.
4.
5.
NOTES:
FLUID IS WATER WITH EXPECTED MAX TEMP OF 58°F AND MIN TEMP OF 42°F.
FLUID IS WATER WITH EXPECTED MAX TEMP OF 150°F AND MIN TEMP OF 80°F.
PROVIDE ALL ADAPTERS AND FITTINGS NECESSARY FOR INTERFACE WITH A BACNET DDC SYSTEM.
WET CALIBRATED AND ACCURATE TO WITHIN +/- 1% OF READING.
NEMA 4 ENCLOSURE.
AIR-COOLED CHILLER SCHEDULE
MARK TYPE REFRIGERANT
EAT DB
(°F)
EVAPORATOR DATA ELECTRICAL DATA EFFICIENCY REQUIREMENTS
J&A
MANUFACTURER NOTES
FULL LOAD CAPACITY
(TONS)
FLOW
(GPM)
FLUID
TYPE
EWT
(°F)
LWT
(°F)
MAX. WPD
(FT. WC.) FOULING FACTOR KW MCA MOCP V / ɸ / Hz EER NPLV.IP
CH-01 SCROLL 454B 105.0 61.76 92.2 WATER 54.0 42.0 3.1 0.000100 67 129 175 460 / 3 / 60 10.3 16.8 TRANE ALL CH-02 SCROLL 454B 105.0 61.76 92.2 WATER 54.0 42.0 3.1 0.000100 67 129 175 460 / 3 / 60 10.3 16.8 TRANE ALL
1.
2.
3.
4.
NOTES:
SCHEDULED PERFORMANCE BASED ON 409'-0" ELEVATION.
LOW AMBIENT KIT.
HOT GAS BYPASS.
THERMAL DISPERSION FLOW SWITCH.
HEAT EXCHANGER SCHEDULE
MARK SERVICE TYPE
CAPACITY
(MBH)
HOT SIDE COLD SIDE
NOTESFLUID
FLOW
(GPM)
EWT
(°F)
LWT
(°F)
WPD
(PSI) FLUID
FLOW
(GPM)
EWT
(°F)
LWT
(°F)
WPD
(PSI)
PHX-01 DOMESTIC HOT WATER DOUBLE-WALL WITH AIR GAP BRAZED PLATE ONE-PASS 179 BOILER WATER 7.2 135.0 85.0 0.24 DOMESTIC WATER 4.5 50.0 130.0 0.09 ALL
1.
2.
3.
4.
5.
NOTES:
SELECTION SHALL INCLUDE FOULING FACTOR OF 0.00010 HR-FT2-°F/BTU ON BOTH SIDES OF THE HEAT EXCHANGER.
SELECTION SHALL INCLUDE MINIMUM 10% EXCESS SURFACE AREA.
316L STAINLESS STEEL PLATES AND COPPER BRAZING.
PROVIDE ASME SECTION VIII DIV 1 STAMPED VESSEL.
PROVIDE WITH CERTIFICATION FOR USE WITH POTABLE WATER.
DUCT CONSTRUCTION AND LEAKAGE TESTING SCHEDULE
SYSTEM
DUCT PRESSURE CLASS SUPPLY RETURN / OUTSIDE AIR
DUCT TEST PRESSURE:
INCHES OF WATER COLUMN
INCHES OF WATER COLUMN ROUND RECTANGULAR
DUCT SEAL
CLASS
DUCT LEAK
CLASS
SUPPLY
DUCT
RETURN
DUCT
EXHAUST
DUCT
OUTSIDE
AIR DUCT
DUCT SEAL
CLASS
DUCT LEAK
CLASS
DUCT SEAL
CLASS
DUCT LEAK
CLASS
AHU-01 2 A 3 A 6 2.0
-1 A 6 1.0
-1 A 6 1.0
CRAC-01 0.5 A 12 A 24 0.5
-0.5 A 24 0.5 -0.5 A 12 0.5
CRAC-02 0.5 A 12 A 24 0.5
-0.5 A 24 0.5
-0.5 A 12 0.5
CRAC-03 0.5 A 12 A 24 0.5
-0.5 A 24 0.5 -0.5 A 12 0.5
CRAC-04 0.5 A 12 A 24 0.5
-0.5 A 24 0.5
-0.5 A 12 0.5
CRAC-05 0.5 A 12 A 24 0.5
-0.5 A 24 0.5
FCU-01 0.5 A 24 0.5
-0.5 A 24 0.5
FCU-02 0.5 A 24 0.5
-0.5 A 24 0.5
FCU-03 0.5 A 24 0.5
-0.5 A 24 0.5
FCU-04 0.5 A 24 0.5
-0.5 A 24 0.5
EF-01 -1 A 24 1.0
EF-02 -0.5 A 24 0.5
EF-03 -0.5 A 24 0.5
RF-01 -0.5 A 24 0.5
RF-02 -0.5 A 24 0.5
VIBRATION ISOLATOR SCHEDULE
ASSOCIATED EQUIPMENT ISOLATOR
NOTESMARK TYPE
SUPPORT
METHOD
MOTOR
HP RPM DESIGNATION
MIN. STATIC
DEFLECTION
(IN)
AHU-01 AIR HANDLER FLOOR MOUNT 20 2735 TYPE C 1" 1,2
CRAC-05 CRAC UNIT SUSPENDED 2 - TYPE F 1" 1
FCU-01 FAN COIL UNIT SUSPENDED < 1/2 - TYPE F 1" 1
FCU-02 FAN COIL UNIT SUSPENDED < 1/2 - TYPE F 1" 1
FCU-03 FAN COIL UNIT SUSPENDED < 1/2 - TYPE F 1" 1
FCU-04 FAN COIL UNIT SUSPENDED < 1/2 - TYPE F 1" 1
EF-01 INLINE FAN SUSPENDED < 1/2 1550 TYPE F 1" 1
RF-01 INLINE FAN SUSPENDED 3 1140 TYPE F 1" 1
RF-02 INLINE FAN SUSPENDED < 1/2 1354 TYPE F 1" 1
CW PUMPS / PIPING VERT. INLINE PUMP & ASSOC. PIPING SUSPENDED 5 - TYPE F 1" 1
HW PUMPS / PIPING VERT. INLINE PUMP & ASSOC. PIPING SUSPENDED 1 - TYPE F 1" 1
1.
2.
NOTES:
REFER TO SPECIFICATION FOR CHARACTERISTICS OF EACH ISOLATOR TYPE.
ISOLATOR IS FACTORY FURNISHED AND INSTALLED.
1 Addendum 02 09/16/2024
5.
6.
7.
8.
9.
VARIABLE SPEED FANS.
PROVIDE WITH HAIL GUARDS.
PROVIDE WITH CRANKCASE HEATERS.
PROVIDE WITH EVAPORATOR FREEZE PROTECTION TO -20°F AMBIENT.
PROVIDE WITH SINGLE-POINT UNIT MOUNTED CIRCUIT BREAK WITH EXTERNAL LOCKABLE HANDLE.
4.
5.
6.
7.
8.
PROVIDE FACTORY-FURNISHED CONDENSATE TRAP AND CONDENSATE NEUTRALIZER.
BOILER'S PACKAGED CONTROLLER SHALL HAVE NON-VOLATILE MEMORY THAT RETAINS ITS PROGRAMMING
AFTER LOSS OF POWER
CONFIGURED FOR CONDENSING OPERATION.
MINIMUM 10:1 BURNER TURNDOWN RATIO.
PROVIDE DIRECT VENTED BOILER KIT TO DRAW COMBUSTION AIR FROM OUTSIDE.
4.
5.
6.
PROVIDE SUCTION DIFFUSER WITH REMOVABLE STRAINER AND LINE SIZE SYSTEM CONNNECTION.
CAPABLE OF INTEGRATINO INTO BACNET FRONT-END CONTROL SYSTEM.
INTEGRATED SENSORLESS PUMP CONTROL.
File details come from the government source that posted it. Updated .