AE304-WALL SECTIONS.pdf

PDF 202 KB Posted

Attached to
Construct Mission Training Center (MTC) Facility
Solicitation number
W50S78-24-B-0001
Issued by

About this file

This document is a set of wall section drawings for a construction project. The drawings provide detailed specifications for the wall assembly, including the use of steel standing seam roofing, insulated metal wall panels, spray foam air barrier, brick veneer, and gypsum wall board with RF shielding.

The related federal contract opportunity is for the construction of a 15,200 square foot Mission Training Center (MTC) facility for the Texas Air National Guard at Joint Base San Antonio Lackland Air Force Base. The project has a base bid as well as eight options, including items such as permeable pavement, landscaping, epoxy floor coating, and additional under floor drains. The contract will be a single firm fixed-price award set aside for small businesses, with a projected value between $10-25 million and a 540 calendar day period of performance. The solicitation will be available through SAM.gov, with a site visit, pre-bid conference, and deadline for questions and RFIs prior to bid opening.

View the file

Other files

File Type Posted
MTC - ABSTRACT Posted 24 Sep 24.pdf PDF
SF101-LOW ROOF FRAMING PLAN.pdf PDF
S-002-TYPICAL DETAILS.pdf PDF
01 45 35 - Special Inspections.pdf PDF
M-702 SCHEDULES.pdf PDF
23 05 48.19 - SEISMIC BRACING FOR HVAC.pdf PDF
SB102-SLAB AND WALL PLAN.pdf PDF
AE501-SECTION DETAILS.pdf PDF
AE502-SECTION DETAILS.pdf PDF
AE303-WALL SECTIONS.pdf PDF
23 05 48.00 40 - VIBRATION CONTROLS FOR HAC PIPING AND EQUIPMENT.pdf PDF
M-701 SCHEDULES.pdf PDF
AE601-ROOM FINISH SCHEDULE AND GLAZING TYPES AND MISC DETAILS.pdf PDF
AE101-FLOOR PLAN.pdf PDF
S-001-GENERAL NOTES.pdf PDF
AE305-WALL SECTIONS.pdf PDF
M-502 DETAILS.pdf PDF
AE001-PARTITION TYPES ANNOTATION SYMBOLS ABBREVIATIONS AND ACCESSIBILITY MOUNTING HEIGHTS.pdf PDF
C-301-REMOVAL PLAN.pdf PDF
New Utilities to East.pdf PDF
11 94 10 - Rooftop Fall Protection Anchors.pdf PDF
C-201-STORMWATER POLLUTION PREVENTION PLAN.pdf PDF
AE603-DOOR DETAILS.pdf PDF
C-601-UTILITY PLAN.pdf PDF
000 TABLE OF CONTENTS.pdf PDF
M-501 DETAILS.pdf PDF
SF102-HIGH ROOF FRAMING PLAN.pdf PDF
G-003-CODE AND LIFE SAFETY PLAN.pdf PDF
01 45 00 - Quality Control.pdf PDF
MTC RFI log 20240917.pdf PDF
AE401-ENLARGED PLANS AND DETAILS.pdf PDF
ES101-ELECTRICAL SITE PLAN.pdf PDF
AE503-SECTION DETAILS.pdf PDF
Amendment 0004 - 17 Aug 2024.pdf PDF
C-401-PROPOSED PLAN.pdf PDF
C-602-DRAINAGE SCHEDULE AND DETAILS.pdf PDF
W50S78-24-B-0001 - Mission Training Center Amendment 0003.pdf PDF
MTC RFI log.pdf PDF
W50S7824B0001 - MTC - Amendment 02 - 20240829.pdf PDF
Attachment 14 - Geotechnical report-TX ANG Mission Training Center B-3.pdf PDF
MFR Mission Training Center - 2nd Site Visit Pre-Propsal Conference Minutes.pdf PDF
Pre_Bid_Site Visit_MTC_Attendance_Sheet 27_Aug _2024.pdf PDF
Pre-Proposal Site Visit Slides - MTC 27 Aug 24.pptx PPTX presentation
W50S78-24-B-0001 - Mission Training Center Amendment 0001.pdf PDF
2024.08.21_TX-ANG_149TH MISSION TRAINING CENTER_REVISED B3_VOL 1 SPECIFICATIONS.pdf PDF
ATTACHMENT 9 SPECS V1 ADDENDUM.pdf PDF
MTC RFI log.pdf PDF
Pre-Proposal Site Visit Slides - MTC 20 Aug 24 (002).pptx PPTX presentation
Pre_Bid_Site Visit_MTC_Attendance_Sheet 20_Aug _2024.pdf PDF
MFR Mission Training Center - Site Visit Pre-Propsal Conference Minutes.pdf PDF
Show 40 more

Latest 50 of 63 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GROUND FLOOR

100' - 0"

A

(SSSR1) STEEL

STANDING

SEAM ROOFING

(MV1) MODULAR

BRICK VENEER

CONCRETE

FOUNDATION

CONCRETE SLAB

6" CFMF AT 16" OC

FLUID APPLIED AIR

AND WATER

BARRIER

STEEL

STRUCTURE

STEEL

STRUCTURE

SCHEDULED

CEILING

(FWP1) 2"

INSULATED METAL

WALL PANEL

FALL PROTECTION

SYSTEM

NOM 4" SPRAY FOAM

AIR BARRIER - OPEN

CELL (R-17 MIN.) WITH

ASTM E84 COMPLIANT

FIRE RETARDANT

SURFACE FILM

C3

AE501

4" 2'

8"

1'

4"

1/2" EXT GYPSUM

SHEATHING

A3

AE501

C4

AE501

OH

4 LAYERS 2"

RIGID

INSULATION

1/2" COVER

BOARD

STEEL DECK

1" / 1'-0"

1'-7 7/8"

16 GA 3" HORIZ Z-

CHANNEL AT 48"

VERTICALLY

2 LAYERS OF 5/8” GYSUM

WALL BOARD (GWB) WITH

PERFORATED RF

SHIELDING/ FOIL MEMBRANE

ADHERED BETWEEN

LAYERS

SIM 2

GROUND FLOOR

100' - 0"

HIGH EAVE (LOW) DB

123' - 0"

(SSSR1) STEEL

STANDING SEAM

ROOFING

(FWP1) 2"

INSULATED METAL

WALL PANEL

CONCRETE

FOUNDATION

CONCRETE SLAB

6" CFMF AT 16" OC

FLUID APPLIED AIR

AND WATER

BARRIER

STEEL

STRUCTURE

SCHEDULED

CEILING

NOM 4" SPRAY FOAM

AIR BARRIER - OPEN

CELL (R-17 MIN.) WITH

ASTM E84 COMPLIANT

FIRE RETARDANT

SURFACE FILM

STEEL

STRUCTURE

2'

8" 4"

2'

8" 4"

2'

8" 4"

2'

8" 4"

1/2" EXT GYPSUM

SHEATHING

A3

AE501

C1

AE501

FALL PROTECTION

SYSTEM

4 LAYERS 2" RIGID

INSULATION

1/2" COVER BOARD

STEEL DECK

1" / 1'-0"

'-0

1'

-4

G

(MV1) MODULAR

BRICK VENEER

2" CAVITY WALL

INSULATION

BOARD

C4

AE501

SIM

1'-7 7/8"

SNOW GUARD

SYSTEM

16 GA 3" HORIZ Z-

CHANNEL AT 48"

VERTICALLY

2 LAYERS OF 5/8” GYSUM

WALL BOARD (GWB)

WITH PERFORATED RF

SHIELDING/ FOIL

MEMBRANE ADHERED

BETWEEN LAYERS

SIM 1

OH

GROUND FLOOR

100' - 0"

LOW EAVE (LOW) DB

115' - 0"

F

(SSSR1) STEEL

STANDING SEAM

ROOFING

BRICK ROWLOCK

COURSE

CONCRETE

FOUNDATION

CONCRETE SLAB

6" CFMF AT 16" OC

FLUID APPLIED

MEMBRANE AIR

BARRIER

STEEL

STRUCTURE

SCHEDULED

CEILING

(FWP1) 2" INSULATED

METAL WALL PANEL

FALL PROTECTION

SYSTEM

NOM 4" SPRAY

FOAM AIR

BARRIER - OPEN

CELL (R-17 MIN.)

WITH ASTM E84

COMPLIANT FIRE

RETARDANT

SURFACE FILM

C1

AE501

1/2" EXT GYPSUM

SHEATHING

C4

AE501

PREFINISHED

METAL GUTTER

AND DOWNSPOUT

2' -8

4"

'-0

2" CAVITY WALL

INSULATION

BOARD(MV1) MODULAR

BRICK VENEER

1'-7 7/8"

1" / 1'-0"

A3

AE501

SNOW GUARD

SYSTEM

16 GA 3" HORIZ Z-

CHANNEL AT 48"

VERTICALLY

2 LAYERS OF 5/8” GYSUM

WALL BOARD (GWB)

WITH PERFORATED RF

SHIELDING/ FOIL

MEMBRANE ADHERED

BETWEEN LAYERSCLASSROOM

OH

GROUND FLOOR

100' - 0"

LOW EAVE (LOW) DB

115' - 0"

F

(SSSR1) STEEL

STANDING SEAM

ROOFING

CONCRETE

FOUNDATION

ACCESS

FLOORING

6" CFMF AT 16" OC

FLUID APPLIED

MEMBRANE AIR

BARRIER

STEEL STRUCTURE

(FWP1) 2"

INSULATED METAL

WALL PANEL

C1

AE501

1/2" EXT GYPSUM

SHEATHING

C4

AE501

SIM

FALL PROTECTION

SYSTEM

PREFINISHED

METAL GUTTER

AND DOWNSPOUT

3' -0

4"

2' -8

4"

2' -8

4"

2' -8

4"

2' -8

1' -4

'-0

1'

6"

CONCRETE SLAB

2" CAVITY WALL

INSULATION

BOARD

(MV1) MODULAR

BRICK VENEER

NOM 4" SPRAY FOAM

AIR BARRIER - OPEN

CELL (R-17 MIN.) WITH

ASTM E84 COMPLIANT

FIRE RETARDANT

SURFACE FILM

1'-7 7/8"

1" / 1'-0"

SNOW GUARD

SYSTEM

2 LAYERS OF 5/8” GYSUM

WALL BOARD (GWB) WITH

PERFORATED RF

SHIELDING/ FOIL

MEMBRANE ADHERED

BETWEEN LAYERS

AREA 1

COMM

5801 Broadway Extension, Suite 500 Oklahoma City, OK 73118-7436

405.840.2931 | fsb-ae.com

Frankfurt-Short-Bruza Associates,P.C.

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

20190310

NDM

Jo int

B as e S an

A nto nio

JB

SA

Ke lly

A nn ex , T ex as

Te xa s A ir

Na tio na l G ua rd

9t h

FW

F-1

6 M iss ion Tr ain ing

C en ter (M

TC

C :\U sers\keisner\D ocum ents\90310_Arch_keisnerU

7YM

G .rvt

9/16/2024 10:19:29 AM

15 AUGUST 2024

WALL SECTIONS

AE304

MJT

BKG

GMD

SCALE: 1/2" = 1'-0"

WALL SECTIONA4SCALE: 1/2" = 1'-0"

WALL SECTIONA3

5801 Broadway Extension, Suite 500 Oklahoma City, OK 73118-7436

405.840.2931 | fsb-ae.com

Frankfurt-Short-Bruza Associates,P.C.

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

20190310

NDM

Jo int

B as e S an

A nto nio

JB

SA

Ke lly

A nn ex , T ex as

Te xa s A ir

Na tio na l G ua rd

9t h

FW

F-1

6 M iss ion Tr ain ing

C en ter (M

TC

0 1' 2' 4'

1/2" = 1'-0"

C :\U sers\keisner\D ocum ents\90310_Arch_keisnerU

7YM

G .rvt

9/16/2024 10:19:29 AM

15 AUGUST 2024

WALL SECTIONS

AE304

MJT

BKG

GMD

LEGEND GRAPHIC VISUAL PLANE OF CONT AIR

BARRIER WHERE SHOWN ALL SHEETS

SCALE: 1/2" = 1'-0"

WALL SECTIONA1 SCALE: 1/2" = 1'-0"

WALL SECTIONA2

NOTE: REFERENCE SPECIFICATION SECTIONS

07 05 23 AND 07 27 10.00 10 FOR DESCRIPTION

OF AIR BARRIER SYSTEM

AREA 1 - GENERAL NOTES

1 Addendum 02 09/16/20241 Addendum 02 09/16/2024

1. APPLY MINIMUM 2” WIDE FOIL TAPE CENTERED

OVER ALL EXPOSED BED AND HEAD JOINTS NO

DRYWALL COMPOUND (LAP 1/2” DOWN HORIZONTALLY

ONTO FLOOR SLAB AND GENEROUSLY LAP AT THE

HEAD OF THE WALL PER DETAIL CONDITION)

2. APPLY MINIMUM 2” WIDE FOIL TAPE CENTERED

OVER ALL VERTICAL FASTENERS HEADS.

3. APPLY MINIMUM 12” WIDE FOIL TAPE CENTERED ON

EACH CORNER INTERSECTION. (6” LAP EACH WAY)

REFER TO SHEET AE002 FOR "AREA 1" PERIMETER

WALL. REFER TO SHEET AE520 FOR TYPICAL RF

SHIELDING/FOIL MEMBRANE NOTES AND DETAILS.

File details come from the government source that posted it. Updated .