23 05 48.19 - SEISMIC BRACING FOR HVAC.pdf

PDF 178 KB Posted

Attached to
Construct Mission Training Center (MTC) Facility Federal contract opportunity
Solicitation number
W50S78-24-B-0001
Issued by
Department of the Army National Guard

About this file

This document is a section of the technical specifications for a federal construction contract to build a Mission Training Center (MTC) facility for the Texas Air National Guard at Kelly Field Annex, Joint Base San Antonio, Lackland Air Force Base.

The specifications outline the requirements for seismic bracing and restraints for the mechanical equipment and systems, including HVAC equipment, piping, ductwork, and other components. Key details include the design requirements, materials specifications, installation procedures, and testing/inspection criteria. The contractor must submit detailed drawings, calculations, and product data for the seismic restraint system, which must be designed and stamped by a registered structural engineer. The project includes a base bid along with eight option items related to site work, finishes, and specialty equipment. The contract will be awarded to a small business, with a period of performance of 540 calendar days.

View the file

Other files for this federal contract opportunity

Other files attached to Construct Mission Training Center (MTC) Facility, newest first.
File Type Posted
MTC - ABSTRACT Posted 24 Sep 24.pdf PDF
C-301-REMOVAL PLAN.pdf PDF
S-002-TYPICAL DETAILS.pdf PDF
SF101-LOW ROOF FRAMING PLAN.pdf PDF
S-001-GENERAL NOTES.pdf PDF
New Utilities to East.pdf PDF
M-501 DETAILS.pdf PDF
AE501-SECTION DETAILS.pdf PDF
AE305-WALL SECTIONS.pdf PDF
SB102-SLAB AND WALL PLAN.pdf PDF
M-502 DETAILS.pdf PDF
AE001-PARTITION TYPES ANNOTATION SYMBOLS ABBREVIATIONS AND ACCESSIBILITY MOUNTING HEIGHTS.pdf PDF
AE603-DOOR DETAILS.pdf PDF
AE502-SECTION DETAILS.pdf PDF
AE101-FLOOR PLAN.pdf PDF
AE304-WALL SECTIONS.pdf PDF
C-401-PROPOSED PLAN.pdf PDF
C-602-DRAINAGE SCHEDULE AND DETAILS.pdf PDF
ES101-ELECTRICAL SITE PLAN.pdf PDF
AE401-ENLARGED PLANS AND DETAILS.pdf PDF
AE503-SECTION DETAILS.pdf PDF
01 45 00 - Quality Control.pdf PDF
Amendment 0004 - 17 Aug 2024.pdf PDF
MTC RFI log 20240917.pdf PDF
W50S78-24-B-0001 - Mission Training Center Amendment 0003.pdf PDF
Attachment 14 - Geotechnical report-TX ANG Mission Training Center B-3.pdf PDF
MTC RFI log.pdf PDF
W50S7824B0001 - MTC - Amendment 02 - 20240829.pdf PDF
Pre-Proposal Site Visit Slides - MTC 27 Aug 24.pptx PPTX presentation
MFR Mission Training Center - 2nd Site Visit Pre-Propsal Conference Minutes.pdf PDF
W50S78-24-B-0001 - Mission Training Center Amendment 0001.pdf PDF
MTC RFI log.pdf PDF
2024.08.21_TX-ANG_149TH MISSION TRAINING CENTER_REVISED B3_VOL 1 SPECIFICATIONS.pdf PDF
ATTACHMENT 9 SPECS V1 ADDENDUM.pdf PDF
MFR Mission Training Center - Site Visit Pre-Propsal Conference Minutes.pdf PDF
Pre-Proposal Site Visit Slides - MTC 20 Aug 24 (002).pptx PPTX presentation
Pre_Bid_Site Visit_MTC_Attendance_Sheet 20_Aug _2024.pdf PDF
Attachment 6_Industrial Security.pdf PDF
Attachment 1_SOW.pdf PDF
Attachment 5_STRUCTURAL INTERIOR DESIGN.pdf PDF
Attachment 7_ACCESS AND STAGING SITE PLAN.pdf PDF
JA Nm Brand DDC Redacted.pdf PDF
JA Nm Brand Falcon Redacted.pdf PDF
2024.08.15_TX-ANG_149TH MISSION TRAINING CENTER_REVISED B3_VOL 2 SPECIFICATIONS.pdf PDF
2024.08.15_TX-ANG_149TH MISSION TRAINING CENTER_REVISED B3_VOL 1 SPECIFICATIONS.pdf PDF
JA Nm Brand Vindicator Sys Redacted.pdf PDF
W50S78-24-B-0001 - Mission Training Center Solicitation.pdf PDF
2024.08.15_TX-ANG_149TH MISSION TRAINING CENTER_REVISED B3_DRAWINGS.pdf PDF
JA Nm Brand Monaco Redacted.pdf PDF
JA Nm Brand Trane HVAC Redacted.pdf PDF
Show all 50

Construct Mission Training Center (MTC) Facility has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NGBJV- TX ANG MI SSI ON TRAI NI NG CENTER PN KELL189014

KELLY FI ELD ANNEX 100% CONTRACT DOCUMENTS, 15 AUGUST 2024

SECTI ON 23 05 48. 19

SEI SMI C BRACI NG FOR HVAC

05/ 18

PART 1 GENERAL

1. 1 REFERENCES

The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.

AMERI CAN CONCRETE I NSTI TUTE ( ACI )

ACI 355. 2 ( 2007) Qual i f i cat i on of Post - I nst al l ed Mechani cal Anchor s i n Concr et e and Comment ar y

ACI 355. 4 ( 2011) Qual i f i cat i on of Post - I nst al l ed Adhesi ve Anchor s i n Concr et e ( ACI 355. 4) and Comment ar y

AMERI CAN SOCI ETY OF CI VI L ENGI NEERS ( ASCE)

ASCE 7- 16 ( 2017; Er r at a 2018; Supp 1 2018) Mi ni mum Desi gn Loads and Associ at ed Cr i t er i a f or Bui l di ngs and Ot her St r uct ur es

ASTM I NTERNATI ONAL ( ASTM)

ASTM A36/ A36M ( 2019) St andar d Speci f i cat i on f or Car bon St r uct ur al St eel

ASTM A53/ A53M ( 2022) St andar d Speci f i cat i on f or Pi pe, St eel , Bl ack and Hot - Di pped, Zi nc- Coat ed, Wel ded and Seaml ess

ASTM A153/ A153M ( 2023) St andar d Speci f i cat i on f or Zi nc Coat i ng ( Hot - Di p) on I r on and St eel Har dwar e

ASTM A325 ( 2014) St andar d Speci f i cat i on f or St r uct ur al Bol t s, St eel , Heat Tr eat ed, 120/ 105 ksi Mi ni mum Tensi l e St r engt h

ASTM A490 ( 2014a) St andar d Speci f i cat i on f or St r uct ur al Bol t s, Al l oy St eel , Heat Tr eat ed, 150 ksi Mi ni mum Tensi l e St r engt h

ASTM A500/ A500M ( 2023) St andar d Speci f i cat i on f or Col d- For med Wel ded and Seaml ess Car bon St eel St r uct ur al Tubi ng i n Rounds and Shapes

ASTM A563 ( 2021; E 2022a) St andar d Speci f i cat i on f or Car bon and Al l oy St eel Nut s

SECTI ON 23 05 48. 19 Page 1

Entire Section Removed.

Addendum #02 09/16/2024

Doolittle, Nicholas J.

Rectangle

Doolittle, Nicholas J.

Rectangle

Doolittle, Nicholas J.

Arrow

Doolittle, Nicholas J.

Arrow

Doolittle, Nicholas J.

Arrow

Doolittle, Nicholas J.

Arrow

Doolittle, Nicholas J.

Rectangle

ASTM A603 ( 2019) St andar d Speci f i cat i on f or Zi nc- Coat ed St eel St r uct ur al Wi r e Rope

ASTM F1554 ( 2020) St andar d Speci f i cat i on f or Anchor Bol t s, St eel , 36, 55, and 105- ksi Yi el d St r engt h

METAL FRAMI NG MANUFACTURERS ASSOCI ATI ON ( MFMA)

MFMA- 4 ( 2004) Met al Fr ami ng St andar ds Publ i cat i on

SHEET METAL AND AI R CONDI TI ONI NG CONTRACTORS' NATI ONAL ASSOCI ATI ON

( SMACNA)

SMACNA 1981 ( 2008) Sei smi c Rest r ai nt Manual Gui del i nes f or Mechani cal Syst ems, 3r d Edi t i on

U. S. DEPARTMENT OF DEFENSE ( DOD)

UFC 3- 301- 01 ( 2023; wi t h Change 1, 2023) St r uct ur al Engi neer i ng

UFC 4- 010- 01 ( 2018) DoD Mi ni mum Ant i t er r or i sm St andar ds f or Bui l di ngs

VI BRATI ON I SOLATI ON AND SEI SMI C CONTROL MANUFACTURERS ASSOCI ATI ON

( VI SCMA)

VI SCMA 412 ( 2014) I nst al l i ng Sei smi c Rest r ai nt s f or Mechani cal Equi pment

1. 2 SYSTEM DESCRI PTI ON

1. 2. 1 Gener al Requi r ement s

Appl y t he r equi r ement s f or sei smi c pr ot ect i on measur es descr i bed i n t hi s sect i on and on t he dr awi ngs t o t he mechani cal equi pment and mechani cal syst ems bot h i nsi de and out si de of t he bui l di ng al ong wi t h ext er i or ut i l i t i es and syst ems l i s t ed bel ow. Wher e t her e i s a conf l i c t bet ween t he speci f i cat i ons and t he dr awi ngs, t he speci f i cat i ons wi l l t ake pr ecedence.

Accompl i sh r esi st ance t o l at er al f or ces i nduced by ear t hquakes wi t hout consi der at i on of f r i c t i on r esul t i ng f r om gr avi t y l oads.

1. 2. 2 Mechani cal Equi pment

Mechani cal equi pment t o be sei smi cal l y pr ot ect ed must i ncl ude, but not be l i mi t ed t o, t he f ol l owi ng i t ems t o t he ext ent r equi r ed on t he dr awi ngs or i n ot her sect i ons of t hese speci f i cat i ons:

Boi l er s Ai r Handl i ng Uni t s

Domest i c Wat er Heat Exchanger Expansi on Ai r Separ at or Tanks

Ther mal St or age Uni t s Val ves and Fi t t i ngs f or Pi pi ng

SECTI ON 23 05 48. 19 Page 2

Doolittle, Nicholas J.

Arrow

Doolittle, Nicholas J.

Arrow

Comput er Room Ai r Condi t i oner s Pumps wi t h Mot or s

Uni t Heat er s Exhaust , Ret ur n and Mi sc. Fans

Ai r Ter mi nal Uni t s Fan Coi l Uni t s

Humi di f i er s I nst r ument at i on and Cont r ol f or HVAC

St acks Duct Si l encer s

Ai r Duct s Sani t ar y and Wast e Pi pi ng

Uni t Heat er s Hydr oni c and Domest i c Wat er , Gas Pi pi ng

1. 2. 3 Mechani cal Syst ems

Mechani cal syst ems t o be sei smi cal l y pr ot ect ed must i ncl ude t he f ol l owi ng i t ems t o t he ext ent r equi r ed on t he dr awi ngs or i n t hi s or ot her sect i ons of t hese speci f i cat i ons:

a. Al l Pi pi ng and Duct s I nsi de t he Bui l di ng Except as Speci f i cal l y St at ed i n Ar t i c l e " I t ems Not Cover ed By Thi s Sect i on" .

b. Chi l l ed Wat er Di st r i but i on Syst ems.

c. Gas Pi pi ng Out si de of Bui l di ngs.

d. Al l Wat er Suppl y Syst ems.

e. St or m and Sani t ar y Sewer Syst ems.

f . Al l Pr ocess Pi pi ng.

g. Heat i ng Wat er Di st r i but i on Syst ems.

h. St acks.

1. 2. 4 Cont r act or Desi gned Br aci ng

Submi t copi es of t he desi gn cal cul at i ons wi t h t he dr awi ngs. Cal cul at i ons must be appr oved, cer t i f i ed, st amped and si gned by a r egi st er ed Pr of essi onal St r uct ur al Engi neer . Cal cul at i ons must ver i f y t he capabi l i t y of st r uct ur al member s t o whi ch br aci ng i s at t ached f or car r y i ng t he l oad f r om t he br ace. Desi gn t he br aci ng i n accor dance wi t h UFC 3- 301- 01, UFC 4- 010- 01 and addi t i onal dat a f ur ni shed by t he Cont r act i ng Of f i cer .

Resi st ance t o l at er al f or ces i nduced by ear t hquakes must be accompl i shed wi t hout consi der at i on of f r i c t i on r esul t i ng f r om gr avi t y l oads.

UFC 3- 301- 01 uses par amet er s f or t he bui l di ng, not f or t he equi pment i n t he bui l di ng; t her ef or e, cor r espondi ng adj ust ment s t o t he f or mul as must be r equi r ed. Loadi ngs det er mi ned usi ng UFC 3- 301- 01 ar e based on st r engt h desi gn. Pr ovi de sei smi c br aci ng desi gn dr awi ngs and engi neer i ng cal cul at i ons f or equi pment and syst ems l i s t ed i n t hi s speci f i cat i on and as r equi r ed by t he cont r act document s.

SECTI ON 23 05 48. 19 Page 3

Doolittle, Nicholas J.

Arrow

Doolittle, Nicholas J.

Arrow

1. 2. 5 I t ems Not Cover ed By Thi s Sect i on

1. 2. 5. 1 Fi r e Pr ot ect i on Syst ems

I nst al l sei smi c pr ot ect i on of pi pi ng f or f i r e pr ot ect i on syst ems as speci f i ed i n Sect i on 21 13 13. 00 10 WET PI PE SPRI NKLER SYSTEM, FI RE

PROTECTI ON.

1. 2. 5. 2 I t ems Requi r i ng No Sei smi c Rest r ai nt s

Sei smi c r est r ai nt s ar e not r equi r ed f or t he f ol l owi ng i t ems:

a. Gas pi pi ng l ess t han 1 i nch nomi nal pi pe s i ze.

b. Pi pi ng i n boi l er and mechani cal equi pment r ooms l ess t han 1- 1/ 4 i nches nomi nal pi pe s i ze.

c. Al l ot her pi pi ng equal t o or l ess t han 3i nches nomi nal pi pe s i ze.

d. Rect angul ar ai r handl i ng duct s l ess t han 6 squar e f eet i n cr oss sect i onal ar ea.

e. Round ai r handl i ng duct s l ess t han 28 i nches i n di amet er .

f . Pi pi ng suspended by i ndi v i dual hanger s 12 i nches or l ess i n l engt h f r om t he t op of pi pe t o t he bot t om of t he suppor t i ng st r uct ur al member wher e t he hanger i s at t ached, except as not ed bel ow.

g. Duct s suspended by hanger s 12 i nches or l ess i n l engt h f r om t he t op of t he duct t o t he bot t om of t he suppor t i ng st r uct ur al member , except as not ed bel ow.

I n exempt i ons f . and g. al l hanger s must meet t he l engt h r equi r ement s. I f t he l engt h r equi r ement i s exceeded by one hanger i n t he r un, br ace t he ent i r e r un. Sei smi cal l y pr ot ect i nt er i or pi pi ng and duct s not l i s t ed above i n accor dance wi t h t he pr ovi s i ons of t hi s speci f i cat i on.

1. 3 SUBMI TTALS

Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on;

submi t t al s not havi ng a " G" desi gnat i on ar e f or i nf or mat i on onl y. When used, a desi gnat i on f ol l owi ng t he " G" desi gnat i on i dent i f i es t he of f i ce t hat wi l l r evi ew t he submi t t al f or t he Gover nment . Submi t t al s wi t h an " S" ar e f or i ncl usi on i n t he Sust ai nabi l i t y eNot ebook, i n conf or mance t o Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG. When shown i n t hi s speci f i cat i on, det ai l ed shop dr awi ngs f or al l r equi r ed equi pment , pi pi ng and duct wor k wi t h cal cul at i ons cer t i f i ed by a r egi st er ed st r uct ur al engi neer wi l l be pr ovi ded. Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:

SD- 02 Shop Dr awi ngs

Coupl i ng and Br aci ng

Fl exi bl e Coupl i ngs or Joi nt s

Equi pment Rest r ai nt

Cont r act or Desi gned Br aci ng ( I ncl udi ng Cal cul at i ons) ; G

SECTI ON 23 05 48. 19 Page 4

Doolittle, Nicholas J.

Arrow

Doolittle, Nicholas J.

Arrow

SD- 03 Pr oduct Dat a

Coupl i ng and Br aci ng; G

Equi pment Rest r ai nt ; G

Cont r act or Desi gned Br aci ng ( I ncl udi ng Cal cul at i ons) ; G

Vi br at i on I sol at or s

SD- 05 Desi gn Dat a

Desi gn Cal cul at i ons

PART 2 PRODUCTS

2. 1 GENERAL DESI GN REQUI REMENTS

Submi t det ai l ed sei smi c r est r ai nt dr awi ngs f or mechani cal equi pment , duct syst ems, pi pi ng syst ems and any ot her mechani cal syst ems al ong wi t h cal cul at i ons, cat al og cut s, t empl at es, and er ect i on and i nst al l at i on det ai l s, as appr opr i at e, f or t he i t ems l i s t ed bel ow. I ndi cat e t hi ckness, t ype, gr ade, c l ass of met al , and di mensi ons; and show const r uct i on det ai l s, r ei nf or cement , anchor age, and i nst al l at i on wi t h r el at i on t o t he bui l di ng const r uct i on. Cal cul at i ons must be st amped, by a r egi st er ed st r uct ur al engi neer , and ver i f y t he capabi l i t y of st r uct ur al member s t o whi ch br aci ng i s at t ached f or car r y i ng t he l oad f r om t he br ace. I ncl ude dr awi ng f or Mi ssi on Cr i t i cal Equi pment i ndi cat i ng t he equi pment l ocat i on i n t he f aci l i t y suf f i c i ent t o be used f or t he i nst al l at i on. Desi gn must be based on act ual equi pment and syst em l ayout . Desi gn must i ncl ude cal cul at ed dead l oads, st at i c sei smi c l oads and capaci t y of mat er i al s ut i l i zed f or t he connect i on of t he equi pment or syst em t o t he st r uct ur e.

Anal ysi s must det ai l anchor i ng met hods.

2. 2 EQUI PMENT RESTRAI NT

Equi pment must be r i gi dl y or f l exi bl y mount ed as i ndi cat ed i n t he speci f i cat i ons and/ or dr awi ngs dependi ng on vi br at i on i sol at i on r equi r ement s as f ol l ows bel ow.

Roof mount ed equi pment , bot h v i br at i on i sol at ed and noni sol at ed, must have suppor t member s desi gned and anchor ed t o bui l di ng st r uct ur al st eel or concr et e as r equi r ed f or sei smi c r est r ai nt and wi nd l oads.

2. 2. 1 Ri gi dl y ( Base and Suspended) Mount ed Equi pment

HVAC equi pment f ur ni shed under t hi s cont r act must be r i gi dl y mount ed i n accor dance wi t h ACI 355. 2 and ACI 355. 4. Anchor bol t s must conf or m t o ASTM F1554. For any r i gi d equi pment whi ch i s r i gi dl y anchor ed, pr ovi de f l exi bl e j oi nt s f or pi pi ng, duct wor k, el ect r i cal condui t , et c. , t hat ar e capabl e of accommodat i ng di spl acement s equal t o t he f ul l wi dt h of t he j oi nt i n bot h or t hogonal di r ect i ons. Suspended equi pment br aci ng at t achment s shoul d be l ocat ed j ust above t he cent er of gr avi t y t o mi ni mi ze swi ngi ng. Use t he r at i o of t he over t ur ni ng moment f r om sei smi c f or ces t o t he r esi st i ng moment due t o gr avi t y l oads t o det er mi ne i f over t ur ni ng f or ces need t o be consi der ed i n t he s i z i ng of anchor bol t s. Pr ovi de cal cul at i ons t o ver i f y t he adequacy of t he anchor bol t s f or combi ned shear

SECTI ON 23 05 48. 19 Page 5

Doolittle, Nicholas J.

Arrow

Doolittle, Nicholas J.

Arrow and over t ur ni ng.

Roof mount ed HVAC equi pment r oof cur bs, f r ami ng and at t achment t o equi pment and st r uct ur e must be desi gned and br aced t o wi t hst and sei smi c l oads. Desi gnat ed Sei smi c Syst ems ( DSS) assi gned t o Sei smi c Desi gn Cat egor y ( SDC) C, D, E, or F and Ri sk Cat egor y I V component s needed f or cont i nued oper at i on af t er an ear t hquake must have t wo nut s pr ovi ded on each anchor bol t .

2. 2. 2 Nonr i gi d or Fl exi bl y- Mount ed Equi pment

Sel ect v i br at i on i sol at i on devi ces so t hat t he maxi mum movement of equi pment f r om t he st at i c def l ect i on poi nt i s 1/ 4 i nch. Equi pment f l exi bl y mount ed on vi br at i on i sol at or s must have a bumper r est r ai nt or snubber i n each hor i zont al di r ect i on and ver t i cal r est r ai nt s must be pr ovi ded wher e r equi r ed t o r esi st over t ur ni ng. I sol at or housi ng and r est r ai nt s must be const r uct ed of duct i l e mat er i al s. A v i scoel ast i c pad or s i mi l ar mat er i al of appr opr i at e t hi ckness must be used bet ween t he bumper and component s t o l i mi t t he i mpact l oad. Rest r ai nt s must be desi gned t o r esi st t he cal cul at ed hor i zont al l at er al and ver t i cal f or ces.

Spr i ng v i br at i on i sol at or s must be sei smi cal l y r at ed, r est r ai ned i sol at or s f or equi pment subj ect t o l oad var i at i ons and l ar ge ext er nal f or ces. The sei smi cal l y r at ed housi ng must be si zed t o meet or exceed t he f or ce r equi r ement s appl i cabl e t o t he pr oj ect and meet t he r equi r ed i sol at i on cr i t er i a. Spr i ng v i br at i on i sol at or manuf act ur er ' s wi l l be a member of VI SCMA. Desi gn f or ce, Fp, must be doubl ed f or v i br at i on i sol at or s wi t h an ai r gap gr eat er t han 0. 25 i nches as speci f i ed i n ASCE 7- 16, Chapt er 13.

Housed spr i ngs must not be used f or sei smi c r est r ai nt appl i cat i ons because t hey cannot r esi st upl i f t .

2. 3 BOLTS AND NUTS

Hex head bol t s, and heavy hexagon nut s must be ASTM A325 or ASTM A490 bol t s and ASTM A563 nut s. Pr ovi de bol t s and nut s gal vani zed i n accor dance wi t h ASTM A153/ A153M when used under gr ound or exposed t o weat her .

2. 4 FLEXI BLE JOI NTS

Fl exi bl e j oi nt s must have same pr essur e and t emper at ur e r at i ngs as adj oi ni ng pi pe. Br ai ded hoses must not be used wher e t her e i s t or s i onal or axi al movement unl ess manuf act ur er al l ows i t .

2. 5 SWAY BRACI NG MATERI ALS

Mat er i al used f or member s l i s t ed i n Cont r act Document s, must be st r uct ur al st eel conf or mi ng wi t h t he f ol l owi ng:

a. Pl at es, r ods, and r ol l ed shapes, ASTM A36/ A36M.

b. Wi r e r ope, ASTM A603 pr e- st r et ched. Cl ass B gal v coat i ng Fer r ul e c l amps must be qual i f i ed by t est i ng f or use i n sei smi c appl i cat i ons per VI SCMA 412. A mi ni mum of t wo cl amps ar e r equi r ed on each end of wi r e r ope.

c. Tubes, ASTM A500/ A500M, Gr ade B.

d. Pi pes, ASTM A53/ A53M, Gr ade B.

SECTI ON 23 05 48. 19 Page 6

Doolittle, Nicholas J.

Arrow

Doolittle, Nicholas J.

Arrow

e. Angl es, ASTM A36/ A36M.

f . Channel s ( St r ut s) wi t h i n- t ur ned l i ps and associ at ed har dwar e f or f ast eni ng t o channel s at r andom poi nt s conf or mi ng t o MFMA- 4

PART 3 EXECUTI ON

3. 1 COUPLI NG AND BRACI NG

a. Submi t det ai l dr awi ngs, as speci f i ed her e and t hr oughout t hi s speci f i cat i on, al ong wi t h cat al og cut s, t empl at es, and er ect i on and i nst al l at i on det ai l s, as appr opr i at e, f or t he i t ems l i s t ed.

Submi t t al s must be compl et e i n det ai l ; must i ndi cat e t hi ckness, t ype, gr ade, c l ass of met al , and di mensi ons; and must show const r uct i on det ai l s, r ei nf or cement , anchor age, and i nst al l at i on wi t h r el at i on t o t he bui l di ng const r uct i on.

b. Pr ovi de coupl i ng i nst al l at i on conf or mi ng t o t he det ai l s shown on t he dr awi ngs. Pr ovi s i ons of t hi s par agr aph appl y t o al l pi pi ng wi t hi n a 5 f oot l i ne ar ound out si de of bui l di ng unl ess bur i ed i n t he gr ound.

Pi pi ng gr ouped f or suppor t on t r apeze- t ype hanger s must be br aced at t he most f r equent i nt er val as det er mi ned by appl y i ng t he r equi r ement s of t hi s speci f i cat i on t o each pi pi ng r un on t he common suppor t .

c. Si ze br aci ng component s as r equi r ed f or t he t ot al l oad car r i ed by t he common suppor t s. Br aci ng r i gi dl y at t ached t o pi pe f l anges, or s i mi l ar , must not be used wher e i t woul d i nt er f er e wi t h t her mal expansi on of pi pi ng.

d. Adj ust i sol at or s and r est r ai nt s af t er pi pi ng syst ems has been f i l l ed and equi pment i s at i t s oper at i ng wei ght , f ol l owi ng t he manuf act ur er ' s wr i t t en i nst r uct i ons.

e. I nst al l cabl es at a 45- degr ee sl ope. Wher e i nt er f er ence i s pr esent , t he s l ope may be mi ni mum of 30 degr ees or a maxi mum of 60 degr ees per

VI SCMA 412.

3. 2 BUI LDI NG DRI FT

Pr ovi de j oi nt s capabl e of accommodat i ng sei smi c di spl acement s f or ver t i cal pi pi ng bet ween f l oor s of t he bui l di ng, wher e pi pes pass t hr ough a bui l di ng sei smi c or expansi on j oi nt , or wher e r i gi dl y suppor t ed pi pes connect t o equi pment wi t h v i br at i on i sol at or s. Pr ovi de hor i zont al pi pi ng acr oss expansi on j oi nt s t o accommodat e t he r esul t ant of t he dr i f t s of each bui l di ng uni t i n each or t hogonal di r ect i on. For t hr eaded pi pi ng, pr ovi de swi ng j oi nt s made of t he same pi pi ng mat er i al . For pi pi ng wi t h manuf act ur ed bal l j oi nt s t he sei smi c dr i f t must be 0. 0198 f eet per f oot of hei ght above t he base wher e t he sei smi c separ at i on occur s; t hi s dr i f t val ue must be used i n pl ace of t he expansi on gi ven i n t he manuf act ur er ' s sel ect i on t abl e.

3. 3 FLEXI BLE COUPLI NGS OR JOI NTS

3. 3. 1 Bui l di ng Pi pi ng

Pr ovi de f l exi bl e coupl i ngs or j oi nt s i n bui l di ng pi pi ng at bot t om of al l pi pe r i ser s f or pi pe l ar ger t han 3- 1/ 2 i nches i n di amet er . Lat er al l y br ace f l exi bl e coupl i ngs or j oi nt s wi t hout i nt er f er i ng wi t h t he act i on of t he f l exi bl e coupl i ng or j oi nt . Cast i r on wast e and vent pi pi ng need onl y

SECTI ON 23 05 48. 19 Page 7

Doolittle, Nicholas J.

Arrow

Doolittle, Nicholas J.

Arrow compl y wi t h t hese pr ovi s i ons when caul ked j oi nt s ar e used. Fl exi bl e bel l and spi got pi pe j oi nt s usi ng r ubber gasket s may be used at each br anch adj acent t o t ees and el bows f or under gr ound wast e pi pi ng i nsi de of bui l di ng t o sat i sf y t hese r equi r ement s.

3. 3. 2 Under gr ound Pi pi ng

I nst al l f l exi bl e coupl i ng i n under gr ound pi pi ng and 4 i nch or l ar ger condui t , except heat di st r i but i on syst em, wher e t he pi pi ng ent er s t he bui l di ng. Pr ovi de coupl i ngs t hat accommodat e 1 i nch of r el at i ve movement bet ween t he pi pe and t he bui l di ng i n any di r ect i on. Pr ovi de addi t i onal f l exi bl e coupl i ngs wher e shown on t he dr awi ngs.

3. 4 PI PE SLEEVES

Si ze pi pe sl eeves i n i nt er i or non- f i r e r at ed wal l s as i ndi cat ed on t he dr awi ngs t o pr ovi de cl ear ances t hat wi l l per mi t di f f er ent i al movement of pi pi ng wi t hout t he pi pi ng st r i k i ng t he pi pe sl eeve. Pi pe sl eeves i n f i r e r at ed wal l s must conf or m t o t he r equi r ement s i n Sect i on 07 84 00

FI RESTOPPI NG.

3. 5 SPREADERS

Pr ovi de spr eader s bet ween adj acent pi pi ng r uns t o pr event cont act dur i ng sei smi c act i v i t y whenever pi pe or i nsul at ed pi pe sur f aces ar e l ess t han 4 i nches apar t . Appl y spr eader s at same i nt er val as sway br aces at an equal di st ance bet ween t he sway br aces. I f r ack t ype hanger s ar e used wher e t he pi pes ar e r est r ai ned f r om cont act by mount i ng t o t he r ack, spr eader s ar e not r equi r ed f or pi pes mount ed i n t he r ack. Appl y spr eader s t o sur f ace of bar e pi pe and over i nsul at i on on i nsul at ed pi pes ut i l i z i ng hi gh- densi t y i nser t s and pi pe pr ot ect i on shi el ds i n accor dance wi t h t he r equi r ement s of Sect i on 23 07 00 THERMAL I NSULATI ON FOR MECHANI CAL SYSTEMS.

3. 6 SWAY BRACES FOR PI PI NG

Pr ovi de sway br aces t o pr event movement of t he pi pes under sei smi c l oadi ng. Pr ovi de br aces i n bot h t he l ongi t udi nal and t r ansver se di r ect i ons, r el at i ve t o t he axi s of t he pi pe. Pr ovi de suf f i c i ent br aces f or equi pment t o r esi st a hor i zont al f or ce as speci f i ed i n UFC 3- 301- 01 wi t hout exceedi ng saf e wor ki ng st r ess of br aci ng component s. Pr ovi de br aci ng t hat does not i nt er f er e wi t h t her mal expansi on r equi r ement s f or t he pi pes as descr i bed i n ot her sect i ons of t hese speci f i cat i ons. For sei smi c anal ysi s of hor i zont al pi pes, t he equi val ent st at i c f or ce shoul d be consi der ed t o act concur r ent l y wi t h t he f ul l dead l oad of t he pi pe, i ncl udi ng cont ent s.

3. 6. 1 Tr ansver se Sway Br aci ng

Pr ovi de t r ansver se sway br aci ng f or st eel and copper pi pe at i nt er val s not t o exceed t hose shown on t he dr awi ngs. Al l r uns ( l engt h of pi pe bet ween end j oi nt s) must have a mi ni mum of t r ansver se br aci ng at each end.

Pr ovi de t r ansver se sway br aci ng f or pi pes of mat er i al s ot her t han st eel and copper at i nt er val s not t o exceed t he hanger spaci ng as speci f i ed i n Sect i on 22 00 00 PLUMBI NG, GENERAL PURPOSE.

3. 6. 2 Longi t udi nal Sway Br aci ng

Pr ovi de l ongi t udi nal sway br aci ng at 40 f oot i nt er val s unl ess ot her wi se i ndi cat ed. Al l r uns ( l engt h of pi pe bet ween end j oi nt s) must have one

SECTI ON 23 05 48. 19 Page 8

Doolittle, Nicholas J.

Arrow

Doolittle, Nicholas J.

Arrow l ongi t udi nal br ace mi ni mum. Const r uct sway br aces i n accor dance wi t h t he dr awi ngs. Do not use br anch l i nes, wal l s, or f l oor s as sway br aces.

3. 6. 3 Ver t i cal Runs

Run i s def i ned as l engt h of pi pe bet ween end j oi nt s. Do not br ace ver t i cal r uns of pi pi ng no mor e t han 10 f oot ver t i cal i nt er val s. Br aces f or ver t i cal r uns must be above t he cent er of gr avi t y of t he segment bei ng br aced. Fl exi bl e coupl i ngs shoul d be pr ovi ded at t he bot t oms of r i ser s f or pi pes l ar ger t han 3. 5 i n. ( 89 mm) i n di amet er . Fl exi bl e coupl i ngs and expansi on j oi nt s shoul d be br aced l at er al l y and l ongi t udi nal l y unl ess such br aci ng woul d i nt er f er e wi t h t he act i on of t he coupl i ngs or j oi nt s. When pi pes ent er bui l di ngs, f l exi bl e coupl i ngs shoul d be pr ovi ded t o al l ow f or r el at i ve movement bet ween t he soi l and bui l di ng. Const r uct al l sway br aces i n accor dance wi t h t he dr awi ngs. At t ach sway br aces t o t he st r uct ur al syst em. Do not connect t o br anch l i nes, wal l s, or f l oor s.

3. 6. 4 Cl amps and Hanger s

Appl y c l amps or hanger s on uni nsul at ed pi pes di r ect l y t o pi pe. I nsul at ed pi pi ng must have cl amps or hanger s appl i ed over i nsul at i on i n accor dance wi t h Sect i on 23 07 00 THERMAL I NSULATI ON FOR MECHANI CAL SYSTEMS.

Hanger r od st i f f ener angl e or st r ut br aci ng must be secur el y at t ached by a ser i es of at t achment c l amps manuf act ur ed f r om a one pi ece met al st ampi ng and must i ncl ude al l r equi r e at t achment har dwar e and l ocki ng nut s.

At t achment c l amps made f r om al umi num or cast i r on must not be used i n sei smi c appl i cat i ons. Do not wel d ver t i cal br aces t o hanger r ods.

3. 7 SWAY BRACES FOR DUCTS

3. 7. 1 Br aced Duct s

Pr ovi de br aci ng det ai l s and spaci ng f or r ect angul ar and r ound duct s i n accor dance wi t h SMACNA 1981. However , t he desi gn sei smi c l oadi ngs f or t hese i t ems must not be l ess t han l oadi ngs obt ai ned usi ng t he pr ocedur es i n UFC 3- 301- 01. Br aci ng must not at t ach t o duct j oi nt s. Use shor t est scr ews possi bl e when penet r at i ng duct wor k t o mi ni mi ze ai r f l ow noi se i nsi de duct .

3. 7. 2 Unbr aced Duct s

At t ach hanger s f or unbr aced duct s t o t he duct wi t hi n 2 i nches of t he t op of t he duct wi t h a mi ni mum of t wo #10 sheet met al scr ews. I nst al l unbr aced duct s wi t h a 6 i nch mi ni mum cl ear ance t o ver t i cal cei l i ng hanger wi r es.

- - End of Sect i on - -

SECTI ON 23 05 48. 19 Page 9