M-701 SCHEDULES.pdf
PDF 211 KB Posted
- Attached to
- Construct Mission Training Center (MTC) Facility Federal contract opportunity
- Solicitation number
- W50S78-24-B-0001
- Issued by
- Department of the Army National Guard
About this file
This document is a set of technical specifications and equipment schedules for the construction of a Mission Training Center (MTC) facility at Joint Base San Antonio, Kelly Annex, Texas for the Texas Air National Guard's 149th Fighter Wing.
The key details include: the facility is approximately 15,200 square feet and includes specialized areas such as a secure area, high bay for simulators, and raised flooring; the contract will be a single firm fixed-price award for non-personal construction services with a period of performance of 540 calendar days; the project has a base bid plus 8 different options such as permeable pavement, landscaping, floor coatings, and specialty equipment; the solicitation will include 5 brand name items for compatibility with existing systems; the contracting opportunity is set-aside 100% for small businesses under NAICS code 236220; a site visit and pre-bid conference are scheduled prior to bid opening. The document provides detailed schedules for mechanical equipment, VAV boxes, unit heaters, fans, louvers, duct silencers, and air distribution devices.
View the file
Other files for this federal contract opportunity
Show all 50
Construct Mission Training Center (MTC) Facility has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5801 Broadway Extension, Suite 500 Oklahoma City, OK 73118-7436
405.840.2931 | fsb-ae.com
Frankfurt-Short-Bruza Associates,P.C.
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
C
B
A
D
C
B
A
54321
20190310
NDM
Jo in t B as e S an A nt on io
JB
SA
Ke lly A nn ex , T ex as
Te xa s Ai r N at io na l G ua rd 9t h
FW
F- M iss io n Tr ain in g Ce nt er (M
TC
C :\U sers\njd\O neD rive - FSB Architects +
Engineers\D ocum ents\90310_M ech_23_N
D oolittle8ZBW
T.rvt
9/16/2024 12:46:58 PM
15 AUGUST 2024
SCHEDULES
M-701
RRS
DLC
EAO
1.
2.
3.
4.
5.
NOTES:
REFER TO ARCHITECTURAL REFLECTED CEILING PLANS AND MECHANICAL DRAWINGS TO
COORDINATE DEVICE MOUNTING AND BORDER TYPE TO MATCH CEILING TYPE OR
SURFACE MOUNT.
REFER TO ARCHITECT FOR FINISH.
PROVIDE INTEGRAL BALANCING DAMPER WHERE AN UPSTREAM BALANCING DAMPER IS
NOT INDICATED ON PLANS.
INSTALL ON SPIRAL DUCTWORK AT 45° ANGLE DOWN FROM HORIZONTAL TOWARDS WALL.
FRONT BLADES PARALLEL TO LONG DIMENSION.
COMPUTER ROOM AIR-CONDITIONING UNIT SCHEDULE
MARK TYPE
SUPPLY FAN DATA COOLING COIL DATA HEATING COIL DATA
HUMIDIFIER
CAPACITY
(LBS/HR)
ELECTRICAL
NOTES
SUPPLY
AIRFLOW
(CFM)
EXTERNAL
STATIC
PRESS.
(IN. H2O)
RETURN
AIR TEMP.
(ºF)
RETURN
AIR RH
TOTAL
CAPACITY
(MBH)
SENSIBLE
CAPACITY
(MBH)
FLOW
(GPM)
WPD
(FT. W.C.) HEATING SOURCE
CAPACITY
(MBH)
POWER
(KW)
WPD
(FT. W.C.) V / Ø / HZ FLA/MOP
CRAC-01 FLOOR MOUNTED - UPFLOW 5850 0.5 72 50 115.0 112.9 16.0 4.6 ELECTRIC 51.2 15 - 11.0 460 / 3 / 60 29.5/40 1,2,3,4,5,6,7,8,9,11,13 CRAC-02 FLOOR MOUNTED - UPFLOW 5850 0.5 72 50 115.0 112.9 16.0 4.6 ELECTRIC 51.2 15 - 11.0 460 / 3 / 60 29.5/40 1,2,3,4,5,6,7,8,9,11,13 CRAC-03 FLOOR MOUNTED - UPFLOW 5850 0.5 72 50 115.0 112.9 16.0 4.6 ELECTRIC 51.2 15 - 11.0 460 / 3 / 60 29.5/40 1,2,3,4,5,6,7,8,9,11,13 CRAC-04 FLOOR MOUNTED - UPFLOW 5850 0.5 72 50 115.0 112.9 16.0 4.6 ELECTRIC 51.2 15 - 11.0 460 / 3 / 60 29.5/40 1,2,3,4,5,6,7,8,9,11,13 CRAC-05 CEILING SUSPENDED 1860 0.5 72 50 49.5 42.7 13.7 29.0 ELECTRIC 36.8 10.8 - 8.0 460 / 3 / 60 8.4/30 5,6,7,8,10,12
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
NOTES:
TOP DISCHARGE, REAR RETURN CONFIGURATION.
3-STAGE ELECTRIC REHEAT.
ELECTRONICALLY COMMUTATED MOTORS.
PLENUM FANS.
DIRTY FILTER DIFFERENTIAL PRESSURE SENSOR.
UNIT SHALL INTERFACE WITH THE BUILDING DDC SYSTEM TO MONITOR UNIT STATUS AND ALARMS. PROVIDE INTERFACE CARD AS REQUIRED.
CONDENSATE OVERFLOW CUT-OFF SWITCH.
CONDENSATE PUMP.
INFRARED HUMIDIFIER.
CANISTER HUMIDIFIER.
MERV 11 FILTER.
FILTER BOX WITH MERV 8 FILTER.
REMOTE TEMPERATURE SENSOR AND HUMIDITY SENSOR.
VAV BOX SCHEDULE
MARK
AIRFLOW HOT WATER COIL
MAX.
RAD. NC
INLET
SIZE NOTES
MAX.
COOLING
AIRFLOW
(CFM)
MAX.
HEATING
AIRFLOW
(CFM)
MIN.
AIRFLOW
(CFM)
CAPACITY
(MBH)
EAT
(°F)
LAT
(°F)
MAX. LAT
SETPOINT
FLOW
(GPM)
MIN.
ROWS
MAX. WPD
(IN. W.C.)
MAX. APD
(IN. W.C.)
VAV-01 325 140 100 6.14 50.0 90.4 83.0 0.50 2 0.10 0.10 19 08 ALL
VAV-02 1030 500 235 18.89 50.0 84.8 83.0 1.30 2 0.10 0.15 13 10 ALL
VAV-03 595 300 135 11.93 50.0 86.7 83.0 0.80 2 0.10 0.10 13 08 ALL
VAV-04 180 180 55 7.31 50.0 87.4 83.0 0.50 2 0.10 0.10 23 06 ALL
VAV-05 275 140 55 6.14 50.0 90.4 83.0 0.50 2 0.10 0.10 16 08 ALL
VAV-06 1160 580 505 24.35 50.0 88.7 83.0 1.60 2 0.20 0.10 16 12 ALL
VAV-07 745 375 195 13.78 50.0 83.9 83.0 0.90 2 0.10 0.15 16 08 ALL
VAV-08 2500 970 500 39.0 50.0 80.0 83.0 3.00 2 0.67 0.37 16 12 ALL
VAV-09 425 215 130 8.24 50.0 85.3 83.0 0.60 2 0.10 0.10 20 08 ALL
VAV-10 425 215 130 8.24 50.0 85.3 83.0 0.60 2 0.10 0.10 11 08 ALL
VAV-11 210 140 50 6.14 50.0 90.4 83.0 0.40 2 0.10 0.10 16 06 ALL
VAV-12 595 300 130 11.93 50.0 86.7 83.0 0.80 2 0.10 0.10 16 08 ALL
VAV-13 425 215 130 8.24 50.0 85.3 83.0 0.60 2 0.10 0.10 16 08 ALL
VAV-14 425 215 130 8.24 50.0 85.3 83.0 0.60 2 0.10 0.10 16 08 ALL
VAV-15 595 300 120 11.93 50.0 86.7 83.0 0.80 2 0.10 0.10 16 10 ALL
VAV-16 1465 1080 300 35.87 50.0 80.6 83.0 2.40 2 0.50 0.30 16 14 ALL
1.
2.
3.
4.
5.
NOTES:
CONTRACTOR SHALL FURNISH AND INSTALL TERMINAL UNIT WITH THE SAME CONFIGURATION (I.E. LOCATION OF COIL
CONNECTIONS, CONTROL ENCLOSURES, ETC.) AS SHOWN ON THE DRAWINGS.
RATED AT 1.25 IN. W.C. INLET PRESSURE AND 0.5 IN. W.C. OUTLET PRESSURE.
VAV CONTROLLERS SHALL BE FURNISHED BY THE CONTRACTOR FOR FACTORY INSTALLATION BY VAV TERMINAL UNIT
MANUFACTURER.
24V TRANSFORMER.
MOUNT SUSPENDED FROM STRUCTURE.
UNIT HEATER SCHEDULE
MARK TYPE HEAT SOURCE
CAPACITY
(BTUH)
AIRFLOW
(CFM)
EAT
(°F)
FLOW
(GPM)
MAX. WPD
(FT. W.C.)
EWT
(°F)
LWT
(°F)
ELECTRICAL DATA
NOTESFLA V / Ø / HZ
UH-01 HORIZONTAL HEATING WATER 13312 500 40 1.9 2.2 150 120 0.15 115 / 1 / 60 1,2
UH-02 HORIZONTAL ELECTRIC 17060 350 40 - - - - 6.22 480 / 3 / 60 1,2
UH-03 HORIZONTAL HEATING WATER 13312 500 40 1.9 2.2 150 120 0.15 115 / 1 / 60 1,2
1.
2.
NOTES:
PROVIDE TYPE 'H1' VIBRATION ISOLATION HANGERS WITHIN 12" OF STRUCTURAL ATTACHMENT.
PROVIDE INTEGRAL MANUFACTURER THERMOSTAT.
FAN SCHEDULE
MARK SERVICE FAN TYPE
CAPACITY
(CFM)
MAX. TSP
(IN. W.C.)
FAN
SPEED
(RPM)
MOTOR
POWER
(BHP)
DRIVE
TYPE
MOTOR DATA INLET
SOUND POWER
(dBA) NOTESHP V / Ø / HZ EF-01 EXHAUST SQUARE CENTRIFUGAL INLINE 400 0.75 1550 0.14 DIRECT 1/4 120 / 1 / 60 59 1,3,4,6,8 RF-01 RELIEF AIR TUBE AXIAL 14600 0.5 1140 2.66 DIRECT 3 460 / 3 / 60 84 1,3,4,5,7,9 RF-02 RELIEF AIR SQUARE CENTRIFUGAL INLINE 800 0.5 1354 0.12 DIRECT 1/4 120 / 1 / 60 55 1,3,4,6,8
1.
2.
3.
4.
5.
6.
7.
8.
9.
NOTES:
MOUNT SUSPENDED FROM STRUCTURE SEE VIBRATION ISOLATION SCHEDULE.
UNIT SHALL BE UL-705 LISTED FOR POWER VENTILATION SERVICE.
PROVIDE WITH INLET AND OULET FLANGE.
FAN SELECTION SHALL HAVE A NON-OVERLOADING MOTOR HP.
VARIABLE FREQUENCY DRIVEN NEMA PREMIUM EFFICIENT MOTOR WITH SHAFT GROUNDING RINGS.
ELECTRONICALLY COMMUTATED MOTOR.
MOTOR RATED FOR 40°C.
BACKWARD INCLINED ALUMINUM FAN WHEEL.
CAST ALUMINUM PROPELLER.
LOUVER SCHEDULE
MARK SERVICE TYPE
WIDTH
(IN.)
HEIGHT
(IN.)
DEPTH
(IN.)
MIN.
FREE AREA
(SQ. FT.)
AIRFLOW
(CFM)
AIR
VELOCITY
(FPM)
APD
(IN. WC) NOTES
LVR-01 EXHAUST EXTRUDED ALUMINUM STATIONARY DRAINABLE LOUVER 24 24 6 1.7 400 302 0.01 ALL LVR-02 EXHAUST EXTRUDED ALUMINUM STATIONARY DRAINABLE LOUVER 80 48 6 14.6 15000 1030 0.14 ALL LVR-03 INTAKE EXTRUDED ALUMINUM STATIONARY DRAINABLE LOUVER 24 24 6 1.7 1200 700 0.08 ALL
1.
2.
NOTES:
PROVIDE 2-COAT AAMA 2605 FINISH. CONTRACTOR SHALL SUBMIT COLOR AND FINISH OPTIONS FOR ARCHITECTURAL APPROVAL TO MATCH SURROUNDING
WALL.
PROVIDE REMOVABLE BIRD SCREEN.
FAN COIL UNIT SCHEDULE
MARK
FAN DATA CHILLED WATER COIL DATA HYDRONIC REHEAT COIL DATA ELECTRICAL DATA
NOTES
AIRFLOW
(CFM)
ESP
(IN. W.C.)
EAT (°F) LAT (°F) TOTAL
CAPACITY
(MBH)
SENSIBLE
CAPACITY
(MBH)
EWT
(°F)
LWT
(°F)
FLOW
(GPM)
WPD
(FT. W.C.)
APD
(IN. W.C.)
EAT/LAT
(°F/°F)
CAPACITY
(MBH)
FLOW
(GPM)
WPD
(FT. W.C.)
APD
(IN. W.C.)
MCA /
MOCP V / Ø / HZDB WB WB WB
FCU-01 1645 0.5 72.0 61.0 53.0 52.0 40.3 33.7 42.0 58.0 5.2 4.9 0.43 68.0/85.8 33.1 2.1 1.2 0.09 11.3 / 15 120 / 1 / 60 1 - 6, 8 FCU-02 430 0.5 72.0 61.0 53.3 52.2 14.7 10.4 42.0 58.0 1.3 4.5 0.12 68.0/97.7 13.1 0.9 3.0 0.03 2.5 / 15 120 / 1 / 60 1 - 6, 8 FCU-03 970 0.5 72.0 61.0 56.2 54.0 25.2 22.5 42.0 58.0 3.4 6.4 0.34 68.0/88.5 31.7 2.0 3.4 0.11 9.6 / 15 120 / 1 / 60 1 - 6, 8 FCU-04 600 0.3 80 67 55.0 54.0 26.5 17.8 42 58.0 6 6.2 0.5 - - - - - 0.8 / 5 120 / 1 / 60 4 ,6 , 7 FCU-05 600 0.3 80 67 55.0 54.0 26.5 17.8 42 58.0 6 6.2 0.5 - - - - - 0.8 / 5 120 / 1 / 60 4 ,6 , 7 FCU-06 600 0.3 80 67 55.0 54.0 26.5 17.8 42 58.0 6 6.2 0.5 - - - - - 0.8 / 5 120 / 1 / 60 4 ,6 , 7
1.
2.
3.
4.
NOTES:
INTEGRAL DISCONNECT.
1" PLEATED MERV 8 FILTER.
ELECTRONICALLY COMMUTATED MOTOR.
CONDENSATE PUMP.
1.
2.
3.
4.
5.
NOTES:
BELT-DRIVE AIRFOIL PLENUM SUPPLY FAN.
NEMA PREMIUM EFFICIENCY MOTOR WITH FACTORY-INSTALLED VFD AND MOTOR SHAFT GROUNDING.
SUPPLY, RETURN, AND OUTSIDE AIR CONNECTIONS SHALL BE IN THE SAME CONFIGURATION AS SHOWN ON PLANS.
2" MERV 8 PRE FILTER, 4" MERV 13 FINAL FILTER.
MANUFACTURER FURNISHED DISCONNECT.
DUCT SILENCER SCHEDULE
MARK SERVICE
DUCT SIZE
(IN. X IN.)
BANK SIZE (IN. X
IN.)
BANK
LENGTH (IN)
AIRFLO
W (CFM)
VELOCITY
(FPM) APD (IN.W.C.) NOTES
SIL-01 SUPPLY 8X8 16X16 120 180 409 < 0.16 ALL
SIL-02 RETURN 8X8 16X16 120 180 409 < 0.16 ALL
SIL-03 SUPPLY 10X10 18X18 120 275 396 < 0.16 ALL
SIL-04 RETURN 10X10 18X18 120 275 396 < 0.16 ALL
SIL-05 SUPPLY 16x16 24x24 120 1160 655 < 0.34 ALL SIL-06 RETURN 16x16 24x24 120 1160 655 < 0.34 ALL SIL-07 SUPPLY 16x16 24x24 120 745 420 < 0.16 ALL SIL-08 RETURN 16x16 24x24 120 745 420 < 0.16 ALL
SIL-09 SUPPLY 24X24 32X32 120 2500 625 < 0.34 ALL
SIL-10 RETURN 24X24 32X32 120 2500 625 < 0.34 ALL
SIL-11 SUPPLY 14x14 22x22 120 425 315 < 0.16 ALL SIL-12 RETURN 14x14 22x22 120 425 315 < 0.16 ALL SIL-13 SUPPLY 14x14 22x22 120 425 315 < 0.16 ALL SIL-14 RETURN 14x14 22x22 120 425 315 < 0.16 ALL SIL-15 SUPPLY 14x14 22x22 120 595 440 < 0.16 ALL SIL-16 RETURN 14x14 22x22 120 595 440 < 0.16 ALL SIL-17 SUPPLY 14x14 22x22 120 425 315 < 0.16 ALL SIL-18 RETURN 14x14 22x22 120 425 315 < 0.16 ALL SIL-19 SUPPLY 14x14 22x22 120 425 315 < 0.16 ALL SIL-20 RETURN 14x14 22x22 120 425 315 < 0.16 ALL SIL-21 SUPPLY 14x14 22x22 120 595 440 < 0.16 ALL SIL-22 RETURN 14x14 22x22 120 595 440 < 0.16 ALL SIL-23 SUPPLY 18x18 26x26 120 1465 652 < 0.34 ALL SIL-24 RETURN 18x18 26x26 120 1465 652 < 0.34 ALL
1.
2.
3.
4.
NOTES:
ACHIEVES STC-50 RATING WHEN DETERMINED ACCORDANCE TO ASTM E413.
ACOUSTIC PERFORMANCE DETERMINED ACCORDING TO ASTM E477-13
ASSUMING IDEAL INLET AND OUTLET CONDITIONS.
DOUBLE-WALL 18 GAUGE CASING.
22 GAUGE PERFORATED LINER.
GRAVITY HOOD
MARK SERVICE
CAPACITY
(CFM)
THROAT SIZE
ESP
(IN. W.C.) NOTES
DIAMETER
(IN.)
WIDTH
(IN.)
LENGTH
(IN.)
GH-01 INTAKE 15000 - 46 60 0.15 1,2,3,4,5
GH-02 INTAKE 80 8 - - 0.01 1,3,4,6
GH-03 INTAKE 80 8 - - 0.01 1,3,4,6
GH-04 INTAKE 80 8 - - 0.01 1,3,4,6
GH-05 INTAKE 80 8 - - 0.01 1,3,4,6
1.
2.
3.
4.
5.
6.
NOTES:
ROOF CURB IAW SPECIFICATION SECTION 07 61 14.00 20.
HINGED HOOD.
INSECT SCREEN.
LOW LEAKAGE CONTROL DAMPER WITH TWO-POSITION 24V DC DAMPER ACTUATOR.
RECTANGULAR FABRICATED HOOD.
SPUN ALUMINUM HOOD.
AHU HYDRONIC COOLING / HYDRONIC HEATING
MARK
MAX. DIMENSIONS (IN.)
MIN.
OUTSIDE AIR
(CFM)
SUPPLY FAN DATA HOT WATER PRE-HEAT COIL DATA CHILLED WATER COIL DATA ELECTRICAL DATA
NOTESL W H TYPE QTY
SUPPLY AIR
(CFM)
ESP
(IN. W.C.)
TSP
(IN. W.C.)
FAN
SPEED
(RPM)
FAN
BPH
SENSIBLE
CAPACITY
(MBH)
EWT
(°F)
LWT
(°F)
FLOW
(GPM)
MAX. WPD
(FT. W.C.)
FACE
VELOCITY
(FPM)
MAX. APD
(IN. W.C.)
EAT (°F) LAT (°F) TOTAL
CAPACITY
(MBH)
SENSIBLE
CAPACITY
(MBH)
EWT
(°F)
LWT
(°F)
FLOW
(GPM)
MAX. WPD
(FT. W.C.)
FACE
VELOCITY
(FPM)
MAX. APD
(IN. W.C.) V / Ø / HZ FLA MCA MOCPDB WB DB WB
AHU-01 171 72 108 1,235 PLENUM 2 18,700 2.0 5.20 2,265 12.41 564 150 120 38.2 1.0 504 0.15 71.3 62.4 52.5 52.3 540 380 42 58 67.2 3.3 504 0.93 460 / 3 / 60 34.6 38.9 50 ALL
AIR DISTRIBUTION DEVICE SCHEDULE
MARK TYPE SERVICE
FACE SIZE
(IN.xIN.)
NECK SIZE
(IN.) NOTES
E-1 LOUVERED EXHAUST GRILLE EXHAUST 12X12 PER MFG 1,2,3,5
E-2 LOUVERED EXHAUST GRILLE EXHAUST 24x24 PER MFG 1,2,3,5 R-2 LOUVERED RETURN GRILLE RETURN 24x24 PER MFG 1,2,3,5 R-3 LOUVERED RETURN GRILLE RETURN 24x12 PER MFG 1,2,3,5 R-4 LOUVERED RETURN GRILLE RETURN 48x24 PER MFG 1,2,3,5 S-1 SQUARE PLAQUE DIFFUSER SUPPLY 24x24 6 1,2,3 S-2 SQUARE PLAQUE DIFFUSER SUPPLY 24x24 8 1,2,3 S-3 SQUARE PLAQUE DIFFUSER SUPPLY 24x24 10 1,2,3 S-4 SQUARE PLAQUE DIFFUSER SUPPLY 24x24 12 1,2,3 S-5 SINGLE DEFLECTION SUPPLY GRILLE SUPPLY 24x12 PER MFG 1,2,3,5 S-6 DOUBLE DEFLECTION SUPPLY GRILLE SUPPLY 18x12 PER MFG 1,2,3,4,5 S-7 DOUBLE DEFLECTION SUPPLY GRILLE SUPPLY 24x24 PER MFG 1,2,3
1 Addendum 02 09/16/2024
5.
6.
7.
8.
AUXILARY DRIP PAN.
CONDENSATE OVERFLOW SWITCH TO AUTOMATICALLY SHUT DOWN UNIT UPON
CONDENSATE OVERFLOW CONDITION.
WALL MOUNTED DUCTLESS TWO-PIPE COOLING ONLY FAN COIL.
CEILING MOUNTED SUSPENDED FROM STRUCTURE SEE VIBRATION ISOLATOR SCHEDULE.