M-701 SCHEDULES.pdf

PDF 211 KB Posted

Attached to
Construct Mission Training Center (MTC) Facility Federal contract opportunity
Solicitation number
W50S78-24-B-0001
Issued by
Department of the Army National Guard

About this file

This document is a set of technical specifications and equipment schedules for the construction of a Mission Training Center (MTC) facility at Joint Base San Antonio, Kelly Annex, Texas for the Texas Air National Guard's 149th Fighter Wing.

The key details include: the facility is approximately 15,200 square feet and includes specialized areas such as a secure area, high bay for simulators, and raised flooring; the contract will be a single firm fixed-price award for non-personal construction services with a period of performance of 540 calendar days; the project has a base bid plus 8 different options such as permeable pavement, landscaping, floor coatings, and specialty equipment; the solicitation will include 5 brand name items for compatibility with existing systems; the contracting opportunity is set-aside 100% for small businesses under NAICS code 236220; a site visit and pre-bid conference are scheduled prior to bid opening. The document provides detailed schedules for mechanical equipment, VAV boxes, unit heaters, fans, louvers, duct silencers, and air distribution devices.

View the file

Other files for this federal contract opportunity

Other files attached to Construct Mission Training Center (MTC) Facility, newest first.
File Type Posted
MTC - ABSTRACT Posted 24 Sep 24.pdf PDF
C-301-REMOVAL PLAN.pdf PDF
S-002-TYPICAL DETAILS.pdf PDF
SF101-LOW ROOF FRAMING PLAN.pdf PDF
S-001-GENERAL NOTES.pdf PDF
New Utilities to East.pdf PDF
M-501 DETAILS.pdf PDF
AE501-SECTION DETAILS.pdf PDF
AE305-WALL SECTIONS.pdf PDF
C-401-PROPOSED PLAN.pdf PDF
C-602-DRAINAGE SCHEDULE AND DETAILS.pdf PDF
ES101-ELECTRICAL SITE PLAN.pdf PDF
AE401-ENLARGED PLANS AND DETAILS.pdf PDF
AE503-SECTION DETAILS.pdf PDF
01 45 00 - Quality Control.pdf PDF
Amendment 0004 - 17 Aug 2024.pdf PDF
MTC RFI log 20240917.pdf PDF
C-201-STORMWATER POLLUTION PREVENTION PLAN.pdf PDF
C-601-UTILITY PLAN.pdf PDF
SF102-HIGH ROOF FRAMING PLAN.pdf PDF
G-003-CODE AND LIFE SAFETY PLAN.pdf PDF
M-702 SCHEDULES.pdf PDF
AE601-ROOM FINISH SCHEDULE AND GLAZING TYPES AND MISC DETAILS.pdf PDF
AE303-WALL SECTIONS.pdf PDF
23 05 48.19 - SEISMIC BRACING FOR HVAC.pdf PDF
23 05 48.00 40 - VIBRATION CONTROLS FOR HAC PIPING AND EQUIPMENT.pdf PDF
11 94 10 - Rooftop Fall Protection Anchors.pdf PDF
W50S78-24-B-0001 - Mission Training Center Amendment 0003.pdf PDF
Attachment 14 - Geotechnical report-TX ANG Mission Training Center B-3.pdf PDF
MTC RFI log.pdf PDF
W50S7824B0001 - MTC - Amendment 02 - 20240829.pdf PDF
Pre-Proposal Site Visit Slides - MTC 27 Aug 24.pptx PPTX presentation
MFR Mission Training Center - 2nd Site Visit Pre-Propsal Conference Minutes.pdf PDF
Pre_Bid_Site Visit_MTC_Attendance_Sheet 27_Aug _2024.pdf PDF
MTC RFI log.pdf PDF
2024.08.21_TX-ANG_149TH MISSION TRAINING CENTER_REVISED B3_VOL 1 SPECIFICATIONS.pdf PDF
ATTACHMENT 9 SPECS V1 ADDENDUM.pdf PDF
Pre-Proposal Site Visit Slides - MTC 20 Aug 24 (002).pptx PPTX presentation
Pre_Bid_Site Visit_MTC_Attendance_Sheet 20_Aug _2024.pdf PDF
Attachment 6_Industrial Security.pdf PDF
Attachment 5_STRUCTURAL INTERIOR DESIGN.pdf PDF
Attachment 7_ACCESS AND STAGING SITE PLAN.pdf PDF
JA Nm Brand DDC Redacted.pdf PDF
JA Nm Brand Falcon Redacted.pdf PDF
2024.08.15_TX-ANG_149TH MISSION TRAINING CENTER_REVISED B3_VOL 1 SPECIFICATIONS.pdf PDF
JA Nm Brand Vindicator Sys Redacted.pdf PDF
W50S78-24-B-0001 - Mission Training Center Solicitation.pdf PDF
2024.08.15_TX-ANG_149TH MISSION TRAINING CENTER_REVISED B3_DRAWINGS.pdf PDF
JA Nm Brand Monaco Redacted.pdf PDF
JA Nm Brand Trane HVAC Redacted.pdf PDF
Show all 50

Construct Mission Training Center (MTC) Facility has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

5801 Broadway Extension, Suite 500 Oklahoma City, OK 73118-7436

405.840.2931 | fsb-ae.com

Frankfurt-Short-Bruza Associates,P.C.

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

20190310

NDM

Jo in t B as e S an A nt on io

JB

SA

Ke lly A nn ex , T ex as

Te xa s Ai r N at io na l G ua rd 9t h

FW

F- M iss io n Tr ain in g Ce nt er (M

TC

C :\U sers\njd\O neD rive - FSB Architects +

Engineers\D ocum ents\90310_M ech_23_N

D oolittle8ZBW

T.rvt

9/16/2024 12:46:58 PM

15 AUGUST 2024

SCHEDULES

M-701

RRS

DLC

EAO

1.

2.

3.

4.

5.

NOTES:

REFER TO ARCHITECTURAL REFLECTED CEILING PLANS AND MECHANICAL DRAWINGS TO

COORDINATE DEVICE MOUNTING AND BORDER TYPE TO MATCH CEILING TYPE OR

SURFACE MOUNT.

REFER TO ARCHITECT FOR FINISH.

PROVIDE INTEGRAL BALANCING DAMPER WHERE AN UPSTREAM BALANCING DAMPER IS

NOT INDICATED ON PLANS.

INSTALL ON SPIRAL DUCTWORK AT 45° ANGLE DOWN FROM HORIZONTAL TOWARDS WALL.

FRONT BLADES PARALLEL TO LONG DIMENSION.

COMPUTER ROOM AIR-CONDITIONING UNIT SCHEDULE

MARK TYPE

SUPPLY FAN DATA COOLING COIL DATA HEATING COIL DATA

HUMIDIFIER

CAPACITY

(LBS/HR)

ELECTRICAL

NOTES

SUPPLY

AIRFLOW

(CFM)

EXTERNAL

STATIC

PRESS.

(IN. H2O)

RETURN

AIR TEMP.

(ºF)

RETURN

AIR RH

TOTAL

CAPACITY

(MBH)

SENSIBLE

CAPACITY

(MBH)

FLOW

(GPM)

WPD

(FT. W.C.) HEATING SOURCE

CAPACITY

(MBH)

POWER

(KW)

WPD

(FT. W.C.) V / Ø / HZ FLA/MOP

CRAC-01 FLOOR MOUNTED - UPFLOW 5850 0.5 72 50 115.0 112.9 16.0 4.6 ELECTRIC 51.2 15 - 11.0 460 / 3 / 60 29.5/40 1,2,3,4,5,6,7,8,9,11,13 CRAC-02 FLOOR MOUNTED - UPFLOW 5850 0.5 72 50 115.0 112.9 16.0 4.6 ELECTRIC 51.2 15 - 11.0 460 / 3 / 60 29.5/40 1,2,3,4,5,6,7,8,9,11,13 CRAC-03 FLOOR MOUNTED - UPFLOW 5850 0.5 72 50 115.0 112.9 16.0 4.6 ELECTRIC 51.2 15 - 11.0 460 / 3 / 60 29.5/40 1,2,3,4,5,6,7,8,9,11,13 CRAC-04 FLOOR MOUNTED - UPFLOW 5850 0.5 72 50 115.0 112.9 16.0 4.6 ELECTRIC 51.2 15 - 11.0 460 / 3 / 60 29.5/40 1,2,3,4,5,6,7,8,9,11,13 CRAC-05 CEILING SUSPENDED 1860 0.5 72 50 49.5 42.7 13.7 29.0 ELECTRIC 36.8 10.8 - 8.0 460 / 3 / 60 8.4/30 5,6,7,8,10,12

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

NOTES:

TOP DISCHARGE, REAR RETURN CONFIGURATION.

3-STAGE ELECTRIC REHEAT.

ELECTRONICALLY COMMUTATED MOTORS.

PLENUM FANS.

DIRTY FILTER DIFFERENTIAL PRESSURE SENSOR.

UNIT SHALL INTERFACE WITH THE BUILDING DDC SYSTEM TO MONITOR UNIT STATUS AND ALARMS. PROVIDE INTERFACE CARD AS REQUIRED.

CONDENSATE OVERFLOW CUT-OFF SWITCH.

CONDENSATE PUMP.

INFRARED HUMIDIFIER.

CANISTER HUMIDIFIER.

MERV 11 FILTER.

FILTER BOX WITH MERV 8 FILTER.

REMOTE TEMPERATURE SENSOR AND HUMIDITY SENSOR.

VAV BOX SCHEDULE

MARK

AIRFLOW HOT WATER COIL

MAX.

RAD. NC

INLET

SIZE NOTES

MAX.

COOLING

AIRFLOW

(CFM)

MAX.

HEATING

AIRFLOW

(CFM)

MIN.

AIRFLOW

(CFM)

CAPACITY

(MBH)

EAT

(°F)

LAT

(°F)

MAX. LAT

SETPOINT

FLOW

(GPM)

MIN.

ROWS

MAX. WPD

(IN. W.C.)

MAX. APD

(IN. W.C.)

VAV-01 325 140 100 6.14 50.0 90.4 83.0 0.50 2 0.10 0.10 19 08 ALL

VAV-02 1030 500 235 18.89 50.0 84.8 83.0 1.30 2 0.10 0.15 13 10 ALL

VAV-03 595 300 135 11.93 50.0 86.7 83.0 0.80 2 0.10 0.10 13 08 ALL

VAV-04 180 180 55 7.31 50.0 87.4 83.0 0.50 2 0.10 0.10 23 06 ALL

VAV-05 275 140 55 6.14 50.0 90.4 83.0 0.50 2 0.10 0.10 16 08 ALL

VAV-06 1160 580 505 24.35 50.0 88.7 83.0 1.60 2 0.20 0.10 16 12 ALL

VAV-07 745 375 195 13.78 50.0 83.9 83.0 0.90 2 0.10 0.15 16 08 ALL

VAV-08 2500 970 500 39.0 50.0 80.0 83.0 3.00 2 0.67 0.37 16 12 ALL

VAV-09 425 215 130 8.24 50.0 85.3 83.0 0.60 2 0.10 0.10 20 08 ALL

VAV-10 425 215 130 8.24 50.0 85.3 83.0 0.60 2 0.10 0.10 11 08 ALL

VAV-11 210 140 50 6.14 50.0 90.4 83.0 0.40 2 0.10 0.10 16 06 ALL

VAV-12 595 300 130 11.93 50.0 86.7 83.0 0.80 2 0.10 0.10 16 08 ALL

VAV-13 425 215 130 8.24 50.0 85.3 83.0 0.60 2 0.10 0.10 16 08 ALL

VAV-14 425 215 130 8.24 50.0 85.3 83.0 0.60 2 0.10 0.10 16 08 ALL

VAV-15 595 300 120 11.93 50.0 86.7 83.0 0.80 2 0.10 0.10 16 10 ALL

VAV-16 1465 1080 300 35.87 50.0 80.6 83.0 2.40 2 0.50 0.30 16 14 ALL

1.

2.

3.

4.

5.

NOTES:

CONTRACTOR SHALL FURNISH AND INSTALL TERMINAL UNIT WITH THE SAME CONFIGURATION (I.E. LOCATION OF COIL

CONNECTIONS, CONTROL ENCLOSURES, ETC.) AS SHOWN ON THE DRAWINGS.

RATED AT 1.25 IN. W.C. INLET PRESSURE AND 0.5 IN. W.C. OUTLET PRESSURE.

VAV CONTROLLERS SHALL BE FURNISHED BY THE CONTRACTOR FOR FACTORY INSTALLATION BY VAV TERMINAL UNIT

MANUFACTURER.

24V TRANSFORMER.

MOUNT SUSPENDED FROM STRUCTURE.

UNIT HEATER SCHEDULE

MARK TYPE HEAT SOURCE

CAPACITY

(BTUH)

AIRFLOW

(CFM)

EAT

(°F)

FLOW

(GPM)

MAX. WPD

(FT. W.C.)

EWT

(°F)

LWT

(°F)

ELECTRICAL DATA

NOTESFLA V / Ø / HZ

UH-01 HORIZONTAL HEATING WATER 13312 500 40 1.9 2.2 150 120 0.15 115 / 1 / 60 1,2

UH-02 HORIZONTAL ELECTRIC 17060 350 40 - - - - 6.22 480 / 3 / 60 1,2

UH-03 HORIZONTAL HEATING WATER 13312 500 40 1.9 2.2 150 120 0.15 115 / 1 / 60 1,2

1.

2.

NOTES:

PROVIDE TYPE 'H1' VIBRATION ISOLATION HANGERS WITHIN 12" OF STRUCTURAL ATTACHMENT.

PROVIDE INTEGRAL MANUFACTURER THERMOSTAT.

FAN SCHEDULE

MARK SERVICE FAN TYPE

CAPACITY

(CFM)

MAX. TSP

(IN. W.C.)

FAN

SPEED

(RPM)

MOTOR

POWER

(BHP)

DRIVE

TYPE

MOTOR DATA INLET

SOUND POWER

(dBA) NOTESHP V / Ø / HZ EF-01 EXHAUST SQUARE CENTRIFUGAL INLINE 400 0.75 1550 0.14 DIRECT 1/4 120 / 1 / 60 59 1,3,4,6,8 RF-01 RELIEF AIR TUBE AXIAL 14600 0.5 1140 2.66 DIRECT 3 460 / 3 / 60 84 1,3,4,5,7,9 RF-02 RELIEF AIR SQUARE CENTRIFUGAL INLINE 800 0.5 1354 0.12 DIRECT 1/4 120 / 1 / 60 55 1,3,4,6,8

1.

2.

3.

4.

5.

6.

7.

8.

9.

NOTES:

MOUNT SUSPENDED FROM STRUCTURE SEE VIBRATION ISOLATION SCHEDULE.

UNIT SHALL BE UL-705 LISTED FOR POWER VENTILATION SERVICE.

PROVIDE WITH INLET AND OULET FLANGE.

FAN SELECTION SHALL HAVE A NON-OVERLOADING MOTOR HP.

VARIABLE FREQUENCY DRIVEN NEMA PREMIUM EFFICIENT MOTOR WITH SHAFT GROUNDING RINGS.

ELECTRONICALLY COMMUTATED MOTOR.

MOTOR RATED FOR 40°C.

BACKWARD INCLINED ALUMINUM FAN WHEEL.

CAST ALUMINUM PROPELLER.

LOUVER SCHEDULE

MARK SERVICE TYPE

WIDTH

(IN.)

HEIGHT

(IN.)

DEPTH

(IN.)

MIN.

FREE AREA

(SQ. FT.)

AIRFLOW

(CFM)

AIR

VELOCITY

(FPM)

APD

(IN. WC) NOTES

LVR-01 EXHAUST EXTRUDED ALUMINUM STATIONARY DRAINABLE LOUVER 24 24 6 1.7 400 302 0.01 ALL LVR-02 EXHAUST EXTRUDED ALUMINUM STATIONARY DRAINABLE LOUVER 80 48 6 14.6 15000 1030 0.14 ALL LVR-03 INTAKE EXTRUDED ALUMINUM STATIONARY DRAINABLE LOUVER 24 24 6 1.7 1200 700 0.08 ALL

1.

2.

NOTES:

PROVIDE 2-COAT AAMA 2605 FINISH. CONTRACTOR SHALL SUBMIT COLOR AND FINISH OPTIONS FOR ARCHITECTURAL APPROVAL TO MATCH SURROUNDING

WALL.

PROVIDE REMOVABLE BIRD SCREEN.

FAN COIL UNIT SCHEDULE

MARK

FAN DATA CHILLED WATER COIL DATA HYDRONIC REHEAT COIL DATA ELECTRICAL DATA

NOTES

AIRFLOW

(CFM)

ESP

(IN. W.C.)

EAT (°F) LAT (°F) TOTAL

CAPACITY

(MBH)

SENSIBLE

CAPACITY

(MBH)

EWT

(°F)

LWT

(°F)

FLOW

(GPM)

WPD

(FT. W.C.)

APD

(IN. W.C.)

EAT/LAT

(°F/°F)

CAPACITY

(MBH)

FLOW

(GPM)

WPD

(FT. W.C.)

APD

(IN. W.C.)

MCA /

MOCP V / Ø / HZDB WB WB WB

FCU-01 1645 0.5 72.0 61.0 53.0 52.0 40.3 33.7 42.0 58.0 5.2 4.9 0.43 68.0/85.8 33.1 2.1 1.2 0.09 11.3 / 15 120 / 1 / 60 1 - 6, 8 FCU-02 430 0.5 72.0 61.0 53.3 52.2 14.7 10.4 42.0 58.0 1.3 4.5 0.12 68.0/97.7 13.1 0.9 3.0 0.03 2.5 / 15 120 / 1 / 60 1 - 6, 8 FCU-03 970 0.5 72.0 61.0 56.2 54.0 25.2 22.5 42.0 58.0 3.4 6.4 0.34 68.0/88.5 31.7 2.0 3.4 0.11 9.6 / 15 120 / 1 / 60 1 - 6, 8 FCU-04 600 0.3 80 67 55.0 54.0 26.5 17.8 42 58.0 6 6.2 0.5 - - - - - 0.8 / 5 120 / 1 / 60 4 ,6 , 7 FCU-05 600 0.3 80 67 55.0 54.0 26.5 17.8 42 58.0 6 6.2 0.5 - - - - - 0.8 / 5 120 / 1 / 60 4 ,6 , 7 FCU-06 600 0.3 80 67 55.0 54.0 26.5 17.8 42 58.0 6 6.2 0.5 - - - - - 0.8 / 5 120 / 1 / 60 4 ,6 , 7

1.

2.

3.

4.

NOTES:

INTEGRAL DISCONNECT.

1" PLEATED MERV 8 FILTER.

ELECTRONICALLY COMMUTATED MOTOR.

CONDENSATE PUMP.

1.

2.

3.

4.

5.

NOTES:

BELT-DRIVE AIRFOIL PLENUM SUPPLY FAN.

NEMA PREMIUM EFFICIENCY MOTOR WITH FACTORY-INSTALLED VFD AND MOTOR SHAFT GROUNDING.

SUPPLY, RETURN, AND OUTSIDE AIR CONNECTIONS SHALL BE IN THE SAME CONFIGURATION AS SHOWN ON PLANS.

2" MERV 8 PRE FILTER, 4" MERV 13 FINAL FILTER.

MANUFACTURER FURNISHED DISCONNECT.

DUCT SILENCER SCHEDULE

MARK SERVICE

DUCT SIZE

(IN. X IN.)

BANK SIZE (IN. X

IN.)

BANK

LENGTH (IN)

AIRFLO

W (CFM)

VELOCITY

(FPM) APD (IN.W.C.) NOTES

SIL-01 SUPPLY 8X8 16X16 120 180 409 < 0.16 ALL

SIL-02 RETURN 8X8 16X16 120 180 409 < 0.16 ALL

SIL-03 SUPPLY 10X10 18X18 120 275 396 < 0.16 ALL

SIL-04 RETURN 10X10 18X18 120 275 396 < 0.16 ALL

SIL-05 SUPPLY 16x16 24x24 120 1160 655 < 0.34 ALL SIL-06 RETURN 16x16 24x24 120 1160 655 < 0.34 ALL SIL-07 SUPPLY 16x16 24x24 120 745 420 < 0.16 ALL SIL-08 RETURN 16x16 24x24 120 745 420 < 0.16 ALL

SIL-09 SUPPLY 24X24 32X32 120 2500 625 < 0.34 ALL

SIL-10 RETURN 24X24 32X32 120 2500 625 < 0.34 ALL

SIL-11 SUPPLY 14x14 22x22 120 425 315 < 0.16 ALL SIL-12 RETURN 14x14 22x22 120 425 315 < 0.16 ALL SIL-13 SUPPLY 14x14 22x22 120 425 315 < 0.16 ALL SIL-14 RETURN 14x14 22x22 120 425 315 < 0.16 ALL SIL-15 SUPPLY 14x14 22x22 120 595 440 < 0.16 ALL SIL-16 RETURN 14x14 22x22 120 595 440 < 0.16 ALL SIL-17 SUPPLY 14x14 22x22 120 425 315 < 0.16 ALL SIL-18 RETURN 14x14 22x22 120 425 315 < 0.16 ALL SIL-19 SUPPLY 14x14 22x22 120 425 315 < 0.16 ALL SIL-20 RETURN 14x14 22x22 120 425 315 < 0.16 ALL SIL-21 SUPPLY 14x14 22x22 120 595 440 < 0.16 ALL SIL-22 RETURN 14x14 22x22 120 595 440 < 0.16 ALL SIL-23 SUPPLY 18x18 26x26 120 1465 652 < 0.34 ALL SIL-24 RETURN 18x18 26x26 120 1465 652 < 0.34 ALL

1.

2.

3.

4.

NOTES:

ACHIEVES STC-50 RATING WHEN DETERMINED ACCORDANCE TO ASTM E413.

ACOUSTIC PERFORMANCE DETERMINED ACCORDING TO ASTM E477-13

ASSUMING IDEAL INLET AND OUTLET CONDITIONS.

DOUBLE-WALL 18 GAUGE CASING.

22 GAUGE PERFORATED LINER.

GRAVITY HOOD

MARK SERVICE

CAPACITY

(CFM)

THROAT SIZE

ESP

(IN. W.C.) NOTES

DIAMETER

(IN.)

WIDTH

(IN.)

LENGTH

(IN.)

GH-01 INTAKE 15000 - 46 60 0.15 1,2,3,4,5

GH-02 INTAKE 80 8 - - 0.01 1,3,4,6

GH-03 INTAKE 80 8 - - 0.01 1,3,4,6

GH-04 INTAKE 80 8 - - 0.01 1,3,4,6

GH-05 INTAKE 80 8 - - 0.01 1,3,4,6

1.

2.

3.

4.

5.

6.

NOTES:

ROOF CURB IAW SPECIFICATION SECTION 07 61 14.00 20.

HINGED HOOD.

INSECT SCREEN.

LOW LEAKAGE CONTROL DAMPER WITH TWO-POSITION 24V DC DAMPER ACTUATOR.

RECTANGULAR FABRICATED HOOD.

SPUN ALUMINUM HOOD.

AHU HYDRONIC COOLING / HYDRONIC HEATING

MARK

MAX. DIMENSIONS (IN.)

MIN.

OUTSIDE AIR

(CFM)

SUPPLY FAN DATA HOT WATER PRE-HEAT COIL DATA CHILLED WATER COIL DATA ELECTRICAL DATA

NOTESL W H TYPE QTY

SUPPLY AIR

(CFM)

ESP

(IN. W.C.)

TSP

(IN. W.C.)

FAN

SPEED

(RPM)

FAN

BPH

SENSIBLE

CAPACITY

(MBH)

EWT

(°F)

LWT

(°F)

FLOW

(GPM)

MAX. WPD

(FT. W.C.)

FACE

VELOCITY

(FPM)

MAX. APD

(IN. W.C.)

EAT (°F) LAT (°F) TOTAL

CAPACITY

(MBH)

SENSIBLE

CAPACITY

(MBH)

EWT

(°F)

LWT

(°F)

FLOW

(GPM)

MAX. WPD

(FT. W.C.)

FACE

VELOCITY

(FPM)

MAX. APD

(IN. W.C.) V / Ø / HZ FLA MCA MOCPDB WB DB WB

AHU-01 171 72 108 1,235 PLENUM 2 18,700 2.0 5.20 2,265 12.41 564 150 120 38.2 1.0 504 0.15 71.3 62.4 52.5 52.3 540 380 42 58 67.2 3.3 504 0.93 460 / 3 / 60 34.6 38.9 50 ALL

AIR DISTRIBUTION DEVICE SCHEDULE

MARK TYPE SERVICE

FACE SIZE

(IN.xIN.)

NECK SIZE

(IN.) NOTES

E-1 LOUVERED EXHAUST GRILLE EXHAUST 12X12 PER MFG 1,2,3,5

E-2 LOUVERED EXHAUST GRILLE EXHAUST 24x24 PER MFG 1,2,3,5 R-2 LOUVERED RETURN GRILLE RETURN 24x24 PER MFG 1,2,3,5 R-3 LOUVERED RETURN GRILLE RETURN 24x12 PER MFG 1,2,3,5 R-4 LOUVERED RETURN GRILLE RETURN 48x24 PER MFG 1,2,3,5 S-1 SQUARE PLAQUE DIFFUSER SUPPLY 24x24 6 1,2,3 S-2 SQUARE PLAQUE DIFFUSER SUPPLY 24x24 8 1,2,3 S-3 SQUARE PLAQUE DIFFUSER SUPPLY 24x24 10 1,2,3 S-4 SQUARE PLAQUE DIFFUSER SUPPLY 24x24 12 1,2,3 S-5 SINGLE DEFLECTION SUPPLY GRILLE SUPPLY 24x12 PER MFG 1,2,3,5 S-6 DOUBLE DEFLECTION SUPPLY GRILLE SUPPLY 18x12 PER MFG 1,2,3,4,5 S-7 DOUBLE DEFLECTION SUPPLY GRILLE SUPPLY 24x24 PER MFG 1,2,3

1 Addendum 02 09/16/2024

5.

6.

7.

8.

AUXILARY DRIP PAN.

CONDENSATE OVERFLOW SWITCH TO AUTOMATICALLY SHUT DOWN UNIT UPON

CONDENSATE OVERFLOW CONDITION.

WALL MOUNTED DUCTLESS TWO-PIPE COOLING ONLY FAN COIL.

CEILING MOUNTED SUSPENDED FROM STRUCTURE SEE VIBRATION ISOLATOR SCHEDULE.

File details come from the government source that posted it. Updated .