AE601-ROOM FINISH SCHEDULE AND GLAZING TYPES AND MISC DETAILS.pdf
PDF 167 KB Posted
- Attached to
- Construct Mission Training Center (MTC) Facility
- Solicitation number
- W50S78-24-B-0001
- Issued by
-
Department of the Army National Guard
About this file
This document appears to be a federal government construction solicitation for a Mission Training Center (MTC) facility at Joint Base San Antonio (JBSA) Lackland Air Force Base for the Texas Air National Guard.
The solicitation is for a firm fixed-price contract for construction services to build a 15,200 square foot FTU 4-ship F-16 MTC facility. The work includes demolition, site work, utilities, building construction, and various specialty systems. The solicitation includes a base bid and 8 options for additional scope. It also lists 5 brand name items required for compatibility with existing systems. The project is set aside 100% for small businesses under NAICS code 236220. The contract duration is 540 calendar days after notice to proceed. Pre-bid site visits are scheduled for August 20th and August 27th, and all questions must be submitted 5 days before bid opening.
View the file
Other files
Show 40 more
Latest 50 of 63 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
7 1/2" 6 1/2" 1 5/8"
BRICK ROWLOCK
COURSE
MASONRY ANCHORS
(MV1) MODULAR BRICK
VENEER
2" CAVITY WALL
INSULATION BOARD
FLUID APPLIED
MEMBRANE AIR
BARRIER
16" GA - 6" CFMF
AT 16" OC
5/8" GWB
1/2" HORIZONTAL
RESILIENT
CHANNEL AT 24"
OC VERTICALLY
ALUMINUM FRAME
STOREFRONT AND
GLAZING
PRE-FINISHED METAL
FLASHING AND DRIP
EDGE
1/2" EXT GYPSUM
SHEATHING
NOM 4" SPRAY
FOAM AIR
BARRIER
SEALANT
103'-0"
SILL RO
1/2" PLYWOOD
VISUAL PLANE
OF AIR BARRIER
5/8"1/2"6"1/2"2"3 1/2"3 5/8"
1/2"
1/2" SOLID
SURFACE
MATERAL
1 5/8"
16" GA - 6" CFMF
CHANNEL
5/8" GWB
6" CFMF BOX
BEAM HEADER
1/2" HORIZONTAL
RESILIENT
CHANNEL AT 24"
OC VERTICALLY
ALUMINUM FRAMED
STOREFRONT
PREFIN METAL WALL
PANEL TRIM
FWP1 2" INSULATED
METAL WALL PANEL
3" 16 GA HORIZ
FURRING CHANNEL AT
48" OC VERTICALLY
FLUID APPLIED
MEMBRANE AIR
BARRIER
1/2" EXT GYPSUM
SHEATHING
16 GA PREFIN METAL
FLASHING
107'-4" AT GLAZING
HEAD RO
108'-8" AT ENTRY
INSULATED LAMINATED
GLASS UNIT
SELF-ADHERED
UNDERLAYMENT
FLASHING
3/ 8"
2"
MINIMAL EXPANDING
FOAM INFILL
SEALANT AND
BACKER ROD
2" 3"
1/2" 6" 1/2" 5/8" 7 1/4"
VISUAL PLANE
OF AIR BARRIER
3 7/8" 1 5/8" 6"
1/2" PLYWOOD
9 1/2"
NOM 4" SPRAY FOAM
AIR BARRIER
TYP NOTE
HEAD
JAMB
SILL
HEAD
JAMB
SILL
EX2
D1/AE601
C1/AE601
B1/AE601
1, 2, 3
TYP NOTE
HEAD
JAMB
SILL
HEAD
JAMB
SILL
EX1
A1/AE502
C1/AE601
A1/AE601
1, 2, 4
SIM.
A4/AE602
3' -0
2"
2' -7
2"
1' -3
2"
4' -4
" R .O
2" 1'-6" 2" 3'-0" 2"
5'-0" R.O.
8' -8
5'-4"
2" 1'-8 1/2" 2"
3'-1 1/2" 2"
2" 2'
-1 0"
2" 3'
-1 0" 2
1/ 2"
1' -3
/2
2"
GROUND FLOOR
100' - 0"
SLOPE
6 1/2"
ALUMINUM FRAME
AND GLAZING
PRE-FINISHED METAL
FLASHING W/END DAMS
CONT. BACKER ROD &
SEALANT , BOTH SIDES
EDGE OF
CONCRETE SLAB
1 5/8"
1/2" EXPANSION
MATERIAL
16" GA - 6" CFMF
CHANNEL
5/8" GWB
6" CFMF BOX
BEAM HEADER
1/2" HORIZONTAL
RESILIENT
CHANNEL AT 24"
OC VERTICALLY
ALUMINUM FRAMED
STOREFRONT
PREFIN METAL WALL
PANEL TRIM
FWP1 2" INSULATED
METAL WALL PANEL
3" 16 GA HORIZ
FURRING CHANNEL AT
48" OC VERTICALLY
FLUID APPLIED
MEMBRANE AIR
BARRIER
1/2" EXT GYPSUM
SHEATHING
INSULATED
LAMINATED GLASS
UNIT
SELF-ADHERED
UNDERLAYMENT
FLASHING
2"
MINIMAL EXPANDING
FOAM INFILL
SEALANT AND
BACKER ROD
2" 3"
1/2" 6" 1/2" 5/8" 7 1/4"
VISUAL PLANE
OF AIR BARRIER
3 7/8" 1 5/8" 6"
9 1/2"
NOM 4" SPRAY FOAM
AIR BARRIER
5801 Broadway Extension, Suite 500 Oklahoma City, OK 73118-7436
405.840.2931 | fsb-ae.com
Frankfurt-Short-Bruza Associates,P.C.
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
C
B
A
D
C
B
A
54321
20190310
NDM
Jo int
B as e S an
A nto nio
JB
SA
Ke lly
A nn ex , T ex as
Te xa s A ir
Na tio na l G ua rd
9t h
FW
F-1
6 M iss ion Tr ain ing
C en ter (M
TC
3" 9"6"0
3" = 1'-0"
C :\U sers\keisner\D ocum ents\90310_Arch_keisnerU
7YM
G .rvt
9/16/2024 10:29:08 AM
15 AUGUST 2024
ROOM FINISH SCHEDULE &
GLAZING TYPES AND MISC.
DETAILS
AE601
MJT
BKG
GMD
ROOM FINISH SCHEDULE
ROOM
NUMBER ROOM NAME Area FLOOR FINISH
BASE
FINISH
WALL FINISHES CEILING
FINISH NOTESNORTH SOUTH EAST WEST
101 VEST 38 SF WOC1 RB1 - - PT1 PT1 GWB, PT3
102 BREAK ROOM 262 SF VCT1 RB1 PT1 PT1 PT1 PT1 ACP1
103 GUEST
WORKSTATIONS
162 SF VCT1 RB1 PT1 PT1 PT1 PT1 ACP1
104 MX / WS 170 SF VCT1 RB1 PT1 PT1 PT1 PT1 ACP1
105 CORRIDOR 456 SF VCT1 RB1 PT1 PT1 PT1 PT1 ACP1
106 MECH 399 SF CONC1 RB1 PT1 PT1 PT1 PT1 EXP, PT3 1
107 STORAGE 110 SF VCT1 RB1 PT1 PT1 PT1 PT1 EXP, PT3 1
108 MEN 290 SF CONC1 (OLI #5 -
PRC1)
RB1
(OLI #4 -
PRCB1)
PT4 (OLI #4 - PT4 /
PRC1 / PRC2)
PT4 (OLI #4 - PT4 /
PRC1 / PRC2)
PT4 (OLI #4 - PRC1
/ PRC2)
PT4 (OLI #4 - PT4 /
PRC1 / PRC2)
GWB, PT3 2
109 MAN TRAP 134 SF VCT1 RB1 PT1 PT1 PT1 PT1 ACP1 / PT6 5
110 WAITING 120 SF VCT1 RB1 PT1 PT1 PT1 - ACP1
111 JAN 23 SF CONC1 RB1 PT1 PT1 / FRP1 PT1 / FRP1 PT1 EXP, PT3 1, 2, 4
112 WOMEN 140 SF CONC1 (OLI #5 -
PRC1)
RB1
(OLI #4 -
PRCB1)
PT4 (OLI #4 - PT4 /
PRC1 / PRC2)
PT4 (OLI #4 - PT4 /
PRC1 / PRC2)
PT4 (OLI #4 - PT4 /
PRC1 / PRC2)
PT4 (OLI #4 - PT4 /
PRC1 / PRC2)
GWB, PT3 2
113 ELEC 112 SF CONC1 RB1 PT1 PT1 PT1 PT1 EXP, PT3 1
114 CLASSROOM 731 SF CPT2 / RAF1/
CONC1
RB1 PT1 PT1 PT1 PT1 ACP1 / PT6 5, 6
115 AP PM OFFICE 183 SF CPT1 RB1 PT1 PT1 PT1 PT1 ACP1 / PT6 5
116 AP PM 389 SF CPT1 RB1 PT1 PT1 PT1 PT1 ACP1 / PT6 5
117 COMM 96 SF CONC2 RB1 PT1 PT1 PT1 PT1 EXP, PT3 1
118 AREA 1 COMM 180 SF RAF2/ CONC1 RB1 PT1 PT1 PT1 PT1 EXP, PT3 1, 5, 6
119 FIRE RISER 60 SF CONC1 RB1 PT1 PT1 PT1 PT1 EXP, PT3 1
120 STUDENT STUDY 516 SF RAF1/ CONC1 RB1 PT1 PT1 PT1 PT1 ACP1 / PT6 5, 6
121 MOC 713 SF CPT2 / RAF1/
CONC1
RB1 PT1 PT1 PT1 PT1 ACP1 / PT6 5, 6
122 SIM 1 1242 SF CONC2 (OLI #3 -
ERF1)
RB1
(OLI #3 -
ERB1)
PT1 PT1 PT1 PT1 ACP1 / PT6 5
123 SIM 2 1243 SF CONC2 (OLI #3 -
ERF1)
RB1
(OLI #3 -
ERB1)
PT1 PT1 PT1 PT1 ACP1 / PT6 5
124 AREA 1 ELEC. 194 SF RAF2/ CONC1 RB1 PT1 PT1 PT1 PT1 EXP, PT3 1, 5, 6
125 NETWORK SERVER 144 SF RAF2/ CONC1 RB1 PT1 PT1 PT1 PT1 ACP1 / PT6 5, 6
126 BDS 6 271 SF RAF1/ CONC1 RB1 PT1 PT1 PT1 PT1 ACP1 / PT6 5, 6
127 CORR 628 SF RAF1/ CONC1 RB1 PT1 PT1 PT1 PT1 ACP1 / PT6 5, 6
128 BDS 5 273 SF RAF1/ CONC1 RB1 PT1 PT1 PT1 PT1 ACP1 / PT6 5, 6
129 MX AREA / SPARES 351 SF RAF2/ CONC1 RB1 PT1 PT1 PT1 PT1 ACP1 / PT6 5, 6
130 BDS 1 356 SF RAF1/ CONC1 RB1 PT1 PT1 PT1 PT1 ACP1 / PT6 5, 6
131 BDS 2 349 SF RAF1/ CONC1 RB1 PT1 PT1 PT1 PT1 ACP1 / PT6 5, 6
132 BDS 3 346 SF RAF1/ CONC1 RB1 PT1 PT1 PT1 PT1 ACP1 / PT6 5, 6
133 BDS 4 359 SF RAF1/ CONC1 RB1 PT1 PT1 PT1 PT1 ACP1 / PT6 5, 6
134 SIM 3 1240 SF CONC2 (OLI #3 -
ERF1)
RB1
(OLI #3 -
ERB1)
PT1 PT1 PT1 PT1 ACP1 / PT6 5
135 SIM 4 1240 SF CONC2 (OLI #3 -
ERF1)
RB1
(OLI #3 -
ERB1)
PT1 PT1 PT1 PT1 ACP1 / PT6 5
GENERAL NOTES
A. FINISHES LISTED IN ROOM FINISH SCHEDULE ARE
BASE BID UNLESS NOTED OTHERWISE.
B. REFER TO SPECIFICATION SECTION 090600
"SCHEDULES FOR FINISHES" FOR FINISH CODE
LEGEND AND FINISHES, MATERIALS, PATTERNS,
AND COLORS.
C. MANUFACTURER NAME AND DESCRIPTION
INDICATED ARE EXAMPLES INTENDED TO INDICATE
COLOR, PATTERN, DESIGN INTENT, AND QUALITY
OF MATERIALS. THEY ARE NOT INTENDED TO LIMIT
CHOICE OF MANUFACTURER'S FOR EQUAL
PRODUCTS. THE MANUFACTURERS LISTED ARE A
BASIS OF DESIGN. FINAL COLOR AND PATTERN
SELECTIONS ARE BY CONTRACTING OFFICER
FROM MANUFACTURERS FULL CATALOG OF COLOR
AND FINISH OPTIONS AVAILABLE.
a. THE "FINISH" MANUFACTURERS LISTED IN THE
FINISH SCHEDULE LEGEND ARE FOR COLOR
REPRESENTATION AND BASIS OF DESIGN ONLY
AND ARE NOT TO BE CONSIDERED AS SOLE
SOURCE PRODUCTS. THE CONTRACTOR MAY
PRESENT ALTERNATE 'OR EQUAL'
MANUFACTURERS WITH SUPPORTING BACK-UP
DATA ALONG WITH COLOR CHARTS FROM ALL
STANDARD FINISHES AND COLORS CURRENTLY
AVAILABLE FOR FINAL SELECTION BY THE
CONTRACTING OFFICER.
D. LISTED PRODUCTS ARE INCLUDED TO ILLUSTRATE
MINIMUM QUALITY AND PERFORMANCE
REQUIREMENTS ONLY. ANY PRODUCT MAY BE
USED THAT INCLUDES THE SAME SALIENT
QUALITIES AS THOSE INDICATED.
E. REFER TO SHEET AE102 FOR REFLECTED CEILING
PLAN.
F. REFER TO SHEETS AE402 FOR INTERIOR
ELEVATIONS.
G. REFER TO SHEET AE403 FOR FINISH DETAILS AND
FLOORING TRANSITIONS.
H. ALL INTERIOR MTL DOORS SHALL BE PAINTED
(PT5), UNO.
I. ALL INTERIOR WOOD DOORS SHALL RECEIVE
WOOD STAIN (WD1), UNO.
J. ALL INTERIOR MTL DOOR FRAMES SHALL BE
PAINTED (PT5), UNO.
K. ALL EXTERIOR STEEL DOORS AND FRAMES SHALL
BE PAINTED PT6 ON THE EXTERIOR SIDE AND PT5
ON THE INTERIOR SIDE. THE TRANSITION LINE
BETWEEN THE TWO PAINTS SHALL OCCUR AT AN
INSIDE CORNER AT THE MIDPOINT OF THE DOOR
FRAME.
L. ALL GROUT AT TILED SURFACES IS TO BE (GR1),
U.N.O.
M. ALL BASE & WALL CABINETRY IS TO BE PLASTIC
LAMINATE (PLAM1), U.N.O.
N. ALL COUNTERTOPS & WINDOW SILLS ARE TO BE
SOLID SURFACE (SSM1), U.N.O.
O. ALL EXPOSED VERTICAL STEEL FRAMING
(INCLUDING COLUMNS, BRACE FRAMING, ETC.)
SHALL RECEIVE SEMIGLOSS PAINT TO MATCH
ADJACENT WALL, UNO.
P. WHERE EXPOSED STRUCTURE CEILINGS ARE
SCHEDULED TO RECEIVE PAINT, THE EXPOSED
CEILING AND ALL STRUCTURAL ELEMENTS SHALL
BE PAINTED WITH SCHEDULED PAINT COLOR.
Q. PAINTED GYP BD WALLS IN WET AREAS
(INCLUDING RESTROOMS, JANITOR CLOSETS, ETC.)
SHALL RECEIVE EPOXY PAINT IN COLOR TO MATCH
SCHEDULED PAINT.
R. ALL EXTERIOR WINDOWS SHALL RECEIVE ROLLER
SHADES (RS1).
S. REFER TO SHEET AE503 FOR ACCESS FLOORING
DETAILS.
T. FLOOR FINISHES SHOWN ON ACCESS FLOORING
ARE FACTORY INSTALLED ON ACCESS FLOOR
PANELS.
U. ALL SCHEDULED FLOOR, WALL, AND BASE
FINISHES ARE BASE BID, UNO. REFER TO INTERIOR
ELEVATION SHEET AE402 AND FINISH PLANS SHEET
IN102 FOR EXTENT OF BID ALTERNATE FINISHES.
FINISH SCHEDULE NOTES
1. ALL EXPOSED STRUCTURE CEILINGS SHALL BE
PAINTED, PT3 - UNO.
2. ALL EXPOSED GWB IN ROOMS INDICATED SHALL BE
PAINTED WITH EPOXY PAINT COLOR TO MATCH
SCHEDULED PAINT.
3. NOT USED.
4. INSTALL FIBER REINFORCED PANEL (FRP1) ON
WALLS INDICATED, REFER TO ELEVATIONS FOR
EXTENTS.
5. FOR VISUAL INTRUSION DETECTION INSPECTION
PURPOSES IN ALL AREA 1 PERIMETER WALL AREAS
INDICATED ON FLOOR PLAN SHEET AE101: 1) ROOMS
WITH NO CEILINGS - FINISH ALL PARTITIONS AS
SCHEDULED FROM TRUE FLOOR TO TRUE CEILING
(ROOF DECK). 2) ROOMS WITH CEILINGS - FINISH ALL
PARTITIONS AS SCHEDULED FROM TRUE FLOOR TO
THE CEILING GRID & TILES AND PAINT THE
REMAINDER OF THE PARTITIONS (PT6) FLAT BLACK
ABOVE THE CEILING GRID & TILES UP TO THE TRUE
CEILING (ROOF DECK) INCLUDING A 6" FULL SPRAY
OVERLAP ONTO THE STEEL ROOF DECK
STRUCTURE. (NO PAINT IS REQUIRED ON THE
REMAINDER OF THE STEEL STRUCTURE AND STEEL
ROOF DECK) REFER TO DETAIL C1/AE403
6. PROVIDE TREATED CONCRETE UNDER RAF TO KEEP
DUST DOWN.
FINISH LEGEND
ACP ACOUSTICAL CEILING PANEL
CONC CONCRETE
CPT CARPET TILE
ERF EPOXY RESINOUS FLOORING
ERB EPOXY RESINOUS INTEGRAL BASE
EXP EXPOSED TO STRUCTURE
GR GROUT
GWB GYPSUM BOARD
PLAM PLASTIC LAMINATE
PT PAINT
PRC PORCELAIN TILE
PRCB PORCELAIN TILE BASE
RAF RAISED ACCESS FLOORING
RB RUBBER BASE
SSM SOLID SURFACE MATERIAL
VCT VINYL COMPOSITE TILE
WOC WALK-OFF CARPET
GLAZING GENERAL NOTES
A. ALL FRAME DIMENSIONS ARE NOMINAL ROUGH
OPENING AND CONTRACTOR SHALL COORDINATE
ACTUAL OPENING SIZES WITH RESPECT TO
REQUIRED SHIM SPACE AND ADJACENT MATERIALS.
B. ALL EXTERIOR ALUMINUM FRAMES SHALL RECEIVE
1/8" CLEAR ANODIZED BRAKE METAL SILL FLASHING
PANS BENEATH ANCHORS AND SHIMS WITH A 1/4"
VERTICAL BRAKE NEAR THE INSIDE FACE OF FRAME
EXTENDING OUT TO DRAIN AND DOWN 1/4" OVER
BRICK ROWLOCK SILL COURSE SET IN BUTYL
SEALANT INCLUDING CLEANED SEALING BEADS AT
EACH JAMB.
C. PROVIDE MINIMAL EXPANDING FOAM TO FILL THE
ENTIRE PERIMETER SHIM CAVITY AROUND EACH
EXTERIOR ALUMINUM STOREFRONT FRAME TO
PROVIDE ENHANCED THERMAL PERFORMANCE AND
TO BLOCK AIR AND MOISTURE INFILTRATION.
D. NO EXPOSED FASTENERS SHALL BE ALLOWED IN
THE ALUMINUM STOREFRONT FRAMES.
SCALE: 3" = 1'-0"
SILL DETAILB1
SCALE: 3" = 1'-0"
HEAD DETAILD1
GLAZING TYPE NOTES
1. 2 1/2" X 6 1/2" BLAST RESISTANT ALUM FRAMING
WITH STEEL INSERTS AS SPECIFIED AND REQUIRED
BY FINAL, SUBMITTED AND APPROVED BLAST
DESIGN.
2. INSULATED BLAST RESISTANT LAMINATED VISION
GLAZING AS SPECIFIED AND REQUIRED BY FINAL,
SUBMITTED AND APPROVED BLAST DESIGN.
3. INTERIOR SILL TO RECEIVE SOLID SURFACE (SSM1).
4. TEMPERED SAFETY GLAZING AT ENTIRE INTERIOR
ALUM STOREFRONT FRAME "EX1" IN VESTIBULE 101.
LEGEND GRAPHIC VISUAL PLANE OF CONT AIR
BARRIER WHERE SHOWN ALL SHEETS
SCALE: 3/8" = 1'-0"
GLAZING ELEVATIONS
2' 6'4'0
3/8" = 1'-0"
SCALE: 3" = 1'-0"
SILL DETAILA1
SCALE: 3" = 1'-0"
JAMB DETAILC1
NOTE: REFERENCE SPECIFICATION SECTIONS
07 05 23 AND 07 27 10.00 10 FOR DESCRIPTION
OF AIR BARRIER SYSTEM
1 Addendum 02 09/16/2024