M-501 DETAILS.pdf
PDF 279 KB Posted
- Attached to
- Construct Mission Training Center (MTC) Facility Federal contract opportunity
- Solicitation number
- W50S78-24-B-0001
- Issued by
- Department of the Army National Guard
About this file
This document appears to be a set of technical details for the design and installation of various mechanical components for the Mission Training Center (MTC) facility project. It includes specifications for rigid and flexible ductwork, diffusers, air handlers, piping, and other HVAC-related elements. The document provides detailed drawings and installation requirements for these components, as well as guidance on penetrations through walls and other building elements.
The related federal contract opportunity is for the construction of the 15,200 square foot MTC facility at Joint Base San Antonio Lackland Air Force Base in Texas. The project is a 100% small business set-aside with a NAICS code of 236220 and a construction value between $10-25 million. The contract duration is 540 calendar days. The solicitation includes a base bid for the overall facility construction along with several options for additional items such as landscaping, floor finishes, and signage. The solicitation also identifies several brand name items that will be required for compatibility with existing systems.
View the file
Other files for this federal contract opportunity
Show all 50
Construct Mission Training Center (MTC) Facility has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BRANCH SUPPLY
DUCT W/ DUCTWRAP
RIGID DUCTWORK, WITH
EXTERNAL INSULATION
DIFFUSER SUSPENDED CEILING SYSTEMSURFACE MOUNT
PROVIDE BLANKET INSULATION
ON BACK OF DIFFUSER
INSULATED FLEXIBLE
DUCT. MAX. LENGTH
TO BE 5 FEET
RIGID ELBOW, WITH
EXTERNAL INSULATION
RUN-OUT DUCT TO BE SAME
DIAMETER AS DIFFUSER NECK
MANUAL
BALANCING
DAMPER
MANUAL DAMPER
45 DEGREE BRANCH
ENTRY CONNECTION
LAY-INSURFACE MOUNT
FLEXIBLE DUCT TO BE SAME
SIZE CONNECTED DUCTWORK.
EXHAUST REGISTER
OR GRILLE
FLEX. CONNECTION
ANGLE SUPPORT
HANGER ROD
VIBRATION ISOLATOR
HANG FROM ABOVE
CONNECTED RIGID DUCT TO BE
SAME SIZE AS FAN CONNECTION
(MIN. 2 DUCT DIAMETERS)
EXHAUST FAN
TRANSITION TO DUCT
SIZE AS REQUIRED
TRANSITION AS
REQUIRED TO DUCT
SIZE DOWNSTREAM OF
TERMINAL UNIT
HOT WATER HEATING COIL
TERMINAL
UNIT
INTERNAL DUCT
LINER
TERMINAL UNIT
BRANCH TAKE-OFF
DUCT SIZE AS
INDICATED ON
PLANS
AIR VALVE
ACTUATOR
CONTROL ENCLOSURE
LEAVE MIN. 12" CLEAR FROM ALL
OBSTRUCTIONS TO PERMIT
SEVICE
INSULATED ACCESS PANEL
TO PERMIT INSPECTION OF
AIR FLOW SENSOR
AIR FLOW
SENSOR
CONNECTED RIGID DUCT TO BE SAME
SIZE AS TERMINAL INLET SIZE (MIN. 6
DUCT DIAMETERS)
NOTE: REFER TO C4/M-502
FOR APPLICABLE COIL PIPING DETAIL.
6" FLEXIBLE
CONNECTION
DUCT
CMU WALL
GROUT
INSULATION
1" CLEARANCE BETWEEN
2" x 2" x 1/4"
TACKWELDED OR
RIVETED TO SLEEVE
20 GAGE GALVANIZED
STEEL COLLAR
(EXPOSED ONLY).
SECURE TO WALL ON 6
INCH CENTERS
(MINIMUM 4
FASTENERS PER SIDE).
20 GAGE
GALVANIZED
STEEL SLEEVE
FINISHED ESCUTCHEON
PIPING EXPOSED TO VIEWCONCEALED PIPING
PIPE AND INSULATION
PER SPECIFICATIONS
SEAL OR CAULK
SLEEVES
TERMINATE SLEEVE FLUSH
WITH FINISHED WALL
NON-LOAD BEARING WALLS:
MIN. 20 GA GALV. SHEET METAL SLEEVE
LOAD BEARING WALLS:
SCH 30 CARBON STEEL PIPE SLEEVE
FINISHED WALL
SURFACE
SEALING AND
ANCHORING
SEAL SLEEVE WITH TIGHTLY
PACKED CAULKING
COAT EXTERIOR SURFACES
STANDARD WEIGHT STEEL
CENTER PIPE
IN SLEEVE
BREAKAWAY SLIP JOINT
(TYP.)
TYP.
6" FLEXIBLE CONNECTION
SECURE RETAINING ANGLE TO
WALL SLEEVE WITH 1/2" LONG
WELDS @ 8" O.C.
10 GAUGE STEEL WALL
SLEEVE
1-1/2" x 1-1/2" x 1/8"
PERIMETER RETAINING
ANGLE. SECURE ANGLES
@ 3" O.C. ANGLES MUST
LAP STRUCTURAL
OPENING 1" MINIMUM
1/2" DIA. HARDENED
STEEL BARS AT 6" O.C.
EACH WAY. WELD AT ALL
INTERSECTIONS
HINGED ACCESS
DOOR WITH LOCK
HASP
SECURE AREA NON-SECURE AREA
NOTE: DUCT BARS ONLY REQUIRED FOR
DUCTS EXCEEDING 96 SQUARE INCHES
IN CROSS-SECTIONAL AREA.
HONEYCOMB
WAVE GUIDE
SHEILDING PANEL
SEE RF SHIELDING DETALS
SHEET AE520
FINISHED
ESCUTCHEON
PIPING EXPOSED TO VIEWCONCEALED PIPING
PIPE AND INSULATION
PER SPECIFICATIONS
SEAL OR CAULK
SLEEVES
TERMINATE SLEEVE FLUSH
WITH FINISHED WALL
LOAD BEARING WALLS:
SCH 30 CARBON STEEL PIPE SLEEVE
FINISHED WALL
SURFACE
NON-LOAD BEARING WALLS:
MIN. 20 GA GALV. SHEET METAL SLEEVE
SECURE AREA NON-SECURE AREA
GROUND PIPE WITHIN 6 INCH
OF THE SECURE PERIMETER
PENETRATION USING NO. 4
COPPER WIRE TO THE
BUILDING GROUND
WIRE CONTINUED
GROUND/BOND TO METALLIC
STRUCTURE ABOVE
SEE RF SHIELDING
DETAILS SHEET AE520
EXTERIOR WALL
SEE PLAN
FOR CONTINUATION.
SLEEVE CAULKING AND
SEALANT (LINKBELT SEAL
OPTIONAL)
SIZE SLEEVE TO
PROVIDE A MIN.
OF 2" CLEARANCE ALL
AROUND.
FLOORGRADE
ASMR GAS METER
ASSEMBLY 1200 CFH
TOTAL LOAD
GAS LINE SLEEVE, SEE
SITE PLAN FOR CONT.
AS SIZED BY
UTILITY COMPANY
GAS LINE
SLEEVE
VENT
STANDARD FLAT-
HEAD GAS COCK
WITH BRASS PLUG
AND WASHER.
GAS PRESSURE REGULATOR
10 IN.W.C.
UNION (TYP).
G
PLUG VALVE
REF PLANS FOR
SIZE AND CONT.
EQUIPMENT
UNION (TYP.)
DIRT LEG (LINE SIZE)
MINIMUM 3" DEEP
P
PRESSURE TEST
PORT (TYP.)
STRAINER
PEA EA
VIBRATION ISOLATOR, SPRING HANGER
MIN. 1" STATIC DEFLECTION
MIN. ONE EQUIVALENT DUCT
DIAMETER STRAIGHT DUCTWORK
MIN. THREE EQUIVALENT DUCT
DIAMETERS STRAIGHT DUCTWORK
FAN PROPELLER
DIRECT DRIVE MOTOR
FLEXIBLE CONNECTOR (TYP.)
5801 Broadway Extension, Suite 500 Oklahoma City, OK 73118-7436
405.840.2931 | fsb-ae.com
Frankfurt-Short-Bruza Associates,P.C.
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
C
B
A
D
C
B
A
54321
20190310
NDM
Jo in t B as e S an A nt on io
JB
SA
Ke lly A nn ex , T ex as
Te xa s Ai r N at io na l G ua rd 9t h
FW
F- M iss io n Tr ain in g Ce nt er (M
TC
C :\U sers\njd\O neD rive - FSB Architects +
Engineers\D ocum ents\90310_M ech_23_N
D oolittle8ZBW
T.rvt
9/16/2024 12:46:54 PM
15 AUGUST 2024
DETAILS
M-501
RRS
DLC
EAO
SCALE: NTS
TYPICAL DIFFUSER INSTALLATIOND1 SCALE: NTS
TYPICAL EXHAUST/RETURN GRILLE INSTALLATION DETAILD2 SCALE: NTS
CENTRIFUGAL IN-LINE FAN INSTALLATION DETAILD4
SCALE: NTS
TYPICAL SINGLE-DUCT VAV TERMINAL UNIT INSTALLATION DETAILC1 SCALE: NTS
DUCT PENETRATION THROUGH NON-FIRE RATED WALLSC3
SCALE: NTS
TYPICAL INTERIOR WALL PIPE PENETRATION DETAILB1
SCALE: NTS
PIPE PENETRATION THROUGH EXTERIOR WALLC4
SCALE: NTS
TYPICAL SECURE AREA DUCT PENETRATION DETAILA4SCALE: NTS
TYPICAL SECURE AREA PIPE PENETRATION DETAILA2SCALE: NTS
TYPICAL GAS METER / REGULATOR / ENTRY DETAILA1
SCALE: NTS
TYPICAL GAS CONNECTION DETAILB4
SCALE: NTS
HORIZONTAL MOUNTED AXIAL
INLINE FAN INSTALLATION DETAILB2
1 Addendum 02 09/16/2024