S02 - ATT 4 - 581-22-700 - 100 Drawings Part-2 of 24.pdf
PDF 18 MB Posted
- Attached to
- EHRM Huntington VAMC 581-22-700 Construct Infrastructure Upgrades Federal contract opportunity
- Solicitation number
- 36C77626R0025
About this file
Document Summary
This is a comprehensive set of 100% Construction Documents (design and specification drawings) for the EHRM Infrastructure Upgrades project at the VA Medical Center in Huntington, West Virginia (Project Number 581-22-700). The documents were prepared by WSP USA Inc. (Architecture/Engineer of Record) and SPEES Design Build as the consultant, with an issue date of September 3, 2025. The project involves phased construction and renovation work across multiple buildings (01, 02, 12, 23, and 23R) on the Marshall Campus, with primary focus on a new Data Center facility (Building GC115-1) that will be constructed in three phases.
The construction documents include detailed structural steel design sheets (S-512, S-515), cold-formed steel framing details (S-525 through S-528), mechanical anchorage specifications (S-541 through S-544), comprehensive floor and roof plans across all building levels, building sections and details, and extensive ICRA (Infection Control Risk Assessment) barrier and phasing plans reflecting the sensitive healthcare environment. Key construction requirements address composite steel deck flooring with concrete topping, light-gauge steel framing systems rated for various load capacities, shear wall construction with specific fastening schedules, column connections, and detailed ICRA Class II, III, and IV infection control protocols for phased demolition and construction activities. The Data Center construction is sequenced across three phases (1B, 2A, and 2B) to maintain functionality of existing facilities, with extensive coordination requirements for mechanical, electrical, and plumbing systems. Fire-rated construction, seismic design criteria (SDS = 1.194g), and comprehensive material specifications including specific fastener types, welding requirements, and finishing standards are detailed throughout the drawings and specifications.
View the file
Other files for this federal contract opportunity
Show all 50
EHRM Huntington VAMC 581-22-700 Construct Infrastructure Upgrades has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WELDING AT ALL SUPPORTS
PARALLEL TO FLUTES
WELDING AT ALL SUPPORTS
PERPENDICULAR TO FLUTES
3/4
(4) WELDS
PER UNIT
3/4 6
DECK CONT @
INTERIOR
SUPPORTS
(NOTE 5)
3' - 0"
NOTES:
1. T= DECK + CONCRETE THICKNESS = 5-1/4".
2. MAXIMUM SUPERIMPOSED TOTAL LOAD (ASD) TO BE 239 PSF (MAX 9'-0" SPAN).
3. FASTEN DECK TO SUPPORTS TO PROVIDE MINIMUM DIAPHRAGM SHEAR OF 1940 PLF (ASD EQ) AND 2475 PLF (ASD WIND).
4. DECK SHALL BE CONTINUOUS FOR AT LEAST 2 SPANS.
5. 3/4"Ø ARC SPOT (PUDDLE) WELDS SHALL BE 1/2"Ø EFFECTIVE. WHERE APPLICABLE, PUDDLE WELDS MAY BE ELIMINATED AT HEADED
STUD LOCATIONS.
6. 2" MIN BEARING ON PERPENDICULAR SUPPORTS.
7. SIDE LAPS SHALL BE 1-1/2" LONG TOP SEAM WELDS. CLINCH JOINT PRIOR TO WELDING TO ENSURE CONTACT BETWEEN LIPS.
8. SEE FOR DECK EDGE CONDITIONS.
9. CONCRETE FILL TO BE REINFORCED WITH #3 @ 12"OC EW
10. REINFORCE DECK OPENINGS PER . DECK OPENINGS MAY NOT BE SHOWN ON PLAN. SEE ARCHITECTURAL AND MECHANICAL
DRAWINGS FOR ADDITIONAL INFORMATION.
11. SEE FOR CONSTRUCTION JOINTS.
FIN PER ARCH
7" 5"
GA
I
(IN /FT)
20 0.422
+S
(IN /FT)
0.323
-S
(IN /FT)
0.333
DECK
2" PLW2
SIDE LAP CONNECTION
3' - 0"
5"1' - 0"
T
/F1 S-512
/C1 S-512
PUNCHLOK II @ 24" OC
MARK
D1
#3 @ 12" OC EW
3/ 4"
C
LR
3/4"Ø HSA
BEAM PER PLAN
SINGLE ROW OF HSA
LOCATED WITHIN MIDDLE
OF 1/3 BEAM FLANGE
WIDTH
OR STUD
1'-0" MAX BTWN
ARC SPOT WELD NOTE 4
P
LA
N
P E
R
8" MIN
1'-0" MAX
END OF BEAM OR SLAB EDGE
NOTES:
1. THE MINIMUM NUMBER OF HSA REQUIRED IS SHOWN AS (X) ON FRAMING PLANS.
2. NO HSA ARE REQUIRED WHERE (0) APPEARS OR WHERE NO DESIGNATION IS GIVEN.
3. PROVIDE ADDITIONAL HSA AS REQUIRED TO MEET MINIMUM HSA REQUIREMENT.
4. PROVIDE HSA SPACING AT A MINIMUM OF EITHER 3’-0” OR 8 X SLAB THICKNESS
REINF.
SP
A
3" M
IN
BEAM BELOW
BEAM ELEVATION
BEAM SECTION
PLAN AT DOUBLE ROW OF HSA
T R
O U
G H
D E
C K
2"
2" M
IN
1/
2" M
IN
C O
V E
R
1/ 2"
M
IN
C O
N C
EA SIDE
1" MIN
CONC COVER
ARC SPOT
WELD, TYP
CL HSA
C
LR
1/
2"
SHEAR CONNECTOR
PER PLAN
GIRDER PER PLAN
COMP FLR PER
PLAN
(2) #3 CHAIR BARS
1' - 0" 1' - 6"
#3x6'-0" @ 18" OC
CTR @ BEAM
CL
METAL DECK WELDS ALL
AROUND HOLE
LOCATE W10 AT FIRST LOW FLUTE
NEAREST EDGE OF OPENING
SEE TYP DECK EDGE CONDITIONS SEE TYP DECK EDGE CONDITIONS
W10
C6
L
D E
C K
S
P A
N
W x1
C6x8.2
/4
2 3/4"
0" TO 1'-6", NO ADDED BEAM REQD.
ADD REINF AS SHOWN ABOVE
2'-1" TO 6'-0"
W x1
C6x8.2
2'-1" TO 6'-0"
W x1
C6x8.2
6" T
O L
6" TO 2'-0" 2'-0" TYP
2" CLR
6" T
O L
(1) #4 ALL SIDES.
BOT BARS PARALLEL TO DECK SHALL BE PLACED
1" CLR FROM BOT OF DECK, SEE NOTE 4
6 1/4"
0" TO 1'-6", NO ADDL BEAM REQD.
ADD REINF AS SHOWN
HOLES LESS THAN 6" DO NOT REQUIRE REINF.
SEE NOTE 4
NOTES:
1. BLOCK OUT OPENING BEFORE PLACING CONCRETE.
2. REMOVE BLOCKOUT AND CUT DECK AFTER CONCRETE HAS CURED.
3. CONTRACTOR SHALL COORDINATE OPENING SIZE AND LOCATION WITH
ARCHITECTURAL DRAWINGS.
4. THE OPENING NOTED REQUIRES A CLEAR SPACING FROM ADJACENT
OPENINGS OF THREE TIMES THE MAXIMUM OPENING DIMENSION. IF THE
REQUIRED LAYOUT CANNOT CONFORM TO THESE REQUIREMENTS,
REINFORCE THE GROUP AS A SINGLE COMBINED PENETRATION.
SECTION A SECTION B
PLAN
A
B
WEB PL
THICKNESS [IN]
(50 KSI)
FLANGE PL
THICKNESS [IN]
(50 KSI)
FLANGE BOLT
DIA [IN]
NON FRAME COLUMN SPLICE SCHEDULE
WEB BOLT DIA
[IN]
STORY HEIGHT 10'-0" TO 13'-11"
COLUMN
SIZE
W8x40 1/2 1/2 3/4 3/4
WEB PL EA SIDE W/ (8) A325-SC
BOLTS REF SCHED FOR PL & BOLTS
COL PER PLAN
1/
2"
3" 3"
3" 3"
1/
2"
CL COL
K+1/4" T-1/2" K+1/4"
1/
2"
3"
1/
2"
1/ 2"
3"
1/
2"
INSIDE FLANGE PL1/2x(bf/2-K)
SEE SCHED
I
4' -0
T
O P
O F
S T
L B
E A
M
OUTSIDE FLANGE
PL t x (bf) W/ (8) A325-
SC BOLTS,
SEE SCHED FOR PL
& BOLTS
SINGER FILLER PL AS
REQD EA SIDE OF COL
1 1/2"
MILL COL FOR FULL BRG
W12X35 1/2 1/2 3/4 3/4
CJP, TYP
(6) 3/4"Ø A325-SC BOLTS T&B
STIFF PL
AS A MINIMUM MATCH WIDTH & THICKNESS
OF BEAM FLANGE (50 KSI), TYP
TYPICAL SHEAR CONN PER
5/16
3 SIDES,
TYP 5/16
3 SIDES
CJP, TYP
TYPICAL SHEAR CONN PER
5/16
3 SIDES,
TYP
1 1/2" TYP
3"
5/16
3 SIDES
1 1/2" TYP
CL COLUMN
/D3 S-511
1 1/2" 3" 3"
1 1/2"
/D3 S-511
(6) 3/4"Ø A325-SC BOLTS T&B
STIFF PL
AS A MINIMUM MATCH WIDTH & THICKNESS
OF BEAM FLANGE (50 KSI), TYP
1 1/2" 3" 3"
1 1/2"
CL COLUMN
STRONG AXIS
WEAK AXIS
CONSTR JOINT
BEAM PER PLAN
TEMPORARY FORM
FIRST POUR
EQ
SECOND POUR
EQ
STL DECK PER PLAN
FLR DECK PER PLAN
EDGE FORM PER MTL DECK
INSTALLER. 18 GA MIN.
BEAM PER PLAN
CONT 97 GA L3x3 TRACK & CONC OVER
METAL DECK CONN PER
EXT NON-LOAD BEARING
NON-SHEAR WALL STUD
PER SCHED /C3 S-525
FINISH PER ARCH
/C3 S-525
CONC EDGE
3" MIN
3 3/4" MAX
TOC EL
PER PLAN
TOC EL
PER PLAN
2' -6
M
A X
NOTES:
ADDL INFORMATION PER /F4 S-528
1"
1"
1/4"Ø SCREW ANCHOR @
16" OC LINE UP WITH EACH
STUD
#10 SCREW EA STUD
HEADED ANCHOR OR
SCREW ANCHOR 3/8"Ø W/ 2
1/2" EMBED @ 32" OC MAX
1/8 1-16
@ EA STUD
CONT #4
CONT CONC
EDGE FORM
CONT #4
BEAM PER PLAN
STL DECK & CONC
TOPPING PER
TYP
#3 @ 15" OC
FOR DECK
WELDING SEE TYP
NOTE:
FOR NUMBER OF SHEAR STUDS, SEE PLAN,
FOR SIZE & WELDING, SEE
CL BEAM & HSA
2'-0" MIN
PER ARCH
EDGE FORM
BRG 2 3/4" MIN
DECK BR'G TYP
2 3/4" MIN STL
TYP
1 1/2" CLR
FOR 10GA
9" MAX
/B1 S-512
/B1 S-512
/B5 S-512
1/8 1 1/2-12
EDGE FORM TO
BEAM FLANGE TYP
7" MAX FOR 12GA
4" MAX FOR 16GA
2" MAX FOR 18GA
WSP USA Inc.
Suite 300
Federal Way, WA 98003-2600
TEL: (206) 431-2300
FAX: (206) 431-2250
33301 9th Avenue South
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
S-512
TYPICAL STRUCTURAL STEEL
DETAILSSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
581-22-700
09/03/2025 CH JKM
100% CONSTRUCTION
DOCUMENTS
1" = 1'-0" B1
COMPOSITE STEEL DECK - FLOOR
1" = 1'-0" B5
TYPICAL HSA CONNECTION DETAIL
1" = 1'-0" D7
COMP DECK PARALLEL TO GIRDER
1" = 1'-0" F1
COMPOSITE DECK OPENINGS
1" = 1'-0"
F5
OPTIONAL BOLTED COLUMN SPLICE
1" = 1'-0" F7
OPTIONAL LATERAL BEAM TO COL MOMENT CONN
1" = 1'-0" C1
CONSTRUCTION JOINT AT COMP FLR
1" = 1'-0" B8
TYPICAL PARAPET DETAIL AT ROOF
Revisions: Date:
1" = 1'-0" D5
STEEL DECK PARALLEL TO BEAM, TYP UNO
PLAN
WELDING AT ALL SUPPORTS
PARALLEL TO FLUTES
WELDING AT ALL SUPPORTS
PERPENDICULAR TO FLUTES
3' - 0"
3/4
(4) WELDS PER
UNIT
3/4 12
DECK CONT @ INTERIOR
SUPPORTS
(NOTE 4)
L
D E
C K
S
P A
N
L4 x4 x1 /4
L4x4x1/4
/4
2 3/4"
0" TO 6"
1'-4" TO 5'-6"
2'-0" TO 5'-6"
T O
L
6 1/4"
3x LARGEST HOLE SIZE OR
ADD REINF
HOLES LESS THAN 6" DO NOT REQUIRE REINF PROVIDED THEY DO NOT
CUT MORE THAN ONE WEB. SEE NOTE 3
NOTES:
1. INSTALL REINFORCEMENT BEFORE CUTTING HOLES.
2. CONTRACTOR SHALL COORDINATE OPENING SIZE AND LOCATION WITH
MECHANICAL AND ELECTRICAL CONTRACTORS.
3. THE OPENING NOTED REQUIRES A CLEAR SPACING FROM ADJACENT
OPENINGS OF THREE TIMES THE MAXIMUM OPENING DIMENSION. IF THE
REQUIRED LAYOUT CANNOT CONFORM TO THESE REQUIREMENTS,
REINFORCE THE GROUP AS A SINGLE COMBINED PENETRATION.
PLAN
T O
2"
6"
6" TO 2'-0"
TYP
1'-6"
A
S-515 B3
1/8 L3x3x3/16x WIDTH OF OPNG
L3x3x3/16 x WIDTH OF OPNG + 3'-0"
SECTION A
1' - 6"
NOTE:
WELD DECK PER DETAILS
& NOTES
OPNG
L4x4x1/4x0'-6", TYP
L4x4x1/4, TYP
B5
S-515
3/16
TYP
CL JOIST
CL JOIST
OWJ PER PLAN
NOTE:
ROOF DECK NOT SHOWN FOR CLARITY.
3/16
3/16
TYP
3/16
L3x3x1/4, TYP
SUPPORT ONLY REQD WHEN
UNSUPPORTED DECK AREA EXCEEDS 3"
COL PER PLAN
PLAN
D E
C K
S P
A N 3/16
TYP
L3x3x1/4
(2) 1/2"Øx6" HSA
#4 CONT
EDGE FORM BY MTL DECK
INSTALLER
FLATTEN DECK AS REQD
3/16
BENT PL TO
L3x3 & COL
3/16
3/16L3x3 TO COL
FLANGE, TYP
T Y
P
2" 3"
OFFSET>3"
CL
COL PER PLAN
D E
C K
S P
A N
OFFSET<3"
CL
T Y
P 1/
2" M
A X
PL3/8. ALIGN TOP OF PL W/
TOC
3/16
SECTION
SECTION
PLAN
PROVIDE 16GA MIN SHEEL
METAL AS REQD
L3x3x1/4, TYP
SUPPORT ONLY REQD WHEN
UNSUPPORTED DECK AREA EXCEEDS 3"
COL PER PLAN
CONDITION #1
DECK SPAN
3" M
A X
3" M
A X
3/16
TYP
CONDITION #2
PROVIDE 16GA MIN SHEEL
METAL TO FILL COL CAVITY AS
REQD
L3x3x1/4
3/16
3/16
TYP
DECK SPAN
L3x3x1/4
T Y
P
3" M
IN
3/16
3/16
TYP
PROVIDE 16GA MIN SHEEL
METAL TO FILL COL CAVITY AS
REQD
DECK SPAN
CONDITION #3
COL PER PLAN
COL PER PLAN
TYP
2 1/2" MAX
STIFF PL1/4
BEAM PER PLAN
ROOF DECK PER PLAN
TOS EL
PER PLAN
POST HSS3x3x1/4
ALIGN W/ MECH UNIT LEG
AS SHOWN BELOW
C12 PER PLAN @ EA POST
ROOFING PER ARCH
M A
X
6"
3/16
MECH UNIT PER
MANUFACTURER
TYP
1" MIN
TYP
1 1/2"
PLAN
POST BELOW
PL5/8
MECH UNIT LEG
M A
X
EXIST SILL PL
NOTES:
1. FOR INFO NOT SHOWN SEE
TOC EL
PER PLAN
JA
M
B
JA
M
B
HEADER
DOOR OPG WIDTH
S-525 E1
/F3 S-525
EXIST WOOD STUD,
TYP
EXIST DBL TOP PL
CFS TRACK W/ #8 WOOD
SCREWS @ 8" OC
(2 MIN), TYP
CFS TRACK W/ #8 WOOD
SCREWS @ 8" OC
WSP USA Inc.
Suite 300
Federal Way, WA 98003-2600
TEL: (206) 431-2300
FAX: (206) 431-2250
33301 9th Avenue South
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
S-515
TYPICAL STRUCTURAL STEEL
DETAILSSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
581-22-700
09/03/2025 CH JKM
100% CONSTRUCTION
DOCUMENTS
1" = 1'-0" B1
TYPICAL STEEL DECK TO STL BEAM CONN
1" = 1'-0" D8
ROOF DECK OPNG LESS THAN 5'-6"
1/2" = 1'-0" B3
ROOF DECK OPENINGS >12"
1" = 1'-0"
B5
SECTION AT OPENING
1" = 1'-0" F1
TYP DECK SUPPORT AT EXT COL
1" = 1'-0"
F3
TYP DECK SUPPORT AT INT COL
1" = 1'-0" F5
MECH UNIT SUPPORT
3/4" = 1'-0" D6
OPENING IN EXISTING WOOD FRAMED WALL
Revisions: Date: 041 OF 693
B
B
A
EXTERIOR LOAD BEARING WALL OPENING FRAMING SCHEDULE
MAX OPENING
WIDTH JAMB HEADER WINDOW SILL
4'-0"
(2) 600S200-54 + 600T125-54
(2) 600S162-54 STUD+(2) 600T200-54
TRACK
8'-0"
(2) 600S200-54 + 600T125-54
WALL TYPE
600S200-68
(UNO ON PLAN &
SHEAR WALL SCHED)
18'-0" 600T200-54/ 1/2"Ø x 4" CONC
SCREWS AT 4'-0" MAX ON
CENTER (SEE NOTE 1 FOR PAF
ALTERNATIVE)
600T200-54 600S200-68
TOP TRACK
(SEE NOTE 2)
TYPE MAX SPACING
STUDS
(3)600S162-54 STUD+
(2)600T200-54 TRACK
600S162-54 SILL
+ 600T200-54 TRACK
600S162-54 SILL
+ 600T200-54 TRACK
EXTERIOR LOAD BEARING WALL FRAMING SCHEDULE
BOTTOM SILL
TRACK/CONN'S
MAX. HEIGHT
#10 SCREW
EACH TRACK FLANGE
TRACK
CONNECTORS
16" OC, TYP
NOTES:
1. ANY LOW-VELOCITY HEADED POWDER ACTUTATED FASTENERS WITH MINIMUM SHANK DIAMETER = 0.145 INCH, 1 1/4" MINIMUM PENETRATION, AND MINIMUM ALLOWABLE SHEAR CAPACITY 200 LBS.
2. ANCHORS MUST BE INSTALLED TO THE TORQUE RECOMMENDATIONS BY THE ANCHOR MANUFACTURER TO OBTAIN MAXIMUM LOADING.
3. MAX HEIGHT REFERS TO MAXIMUM HEIGHT TO ROOF BEARING ELEVATION.
NOTES:
1. PREFABRICATED HEADER AND JAMB ASSEMBLIES MAY BE USED IN LIEU OF BUILT-UP SECTIONS SPECIFIED IF THEIR SECTION PROPERTIES
EXCEED THOSE SPECIFIED.
2. SEE TYPICAL DETAILS FOR TYPICAL WALL FRAMING ELEVATION AND CONNECTIONS BETWEEN BUILT-UP MEMBER COMPONENTS.
3. HEADERS REQUIRE WEB STIFFENERS.
WALL TYPE
600S200-68
(UNO ON SHEAR
WALL SCHED)
MAX. HEIGHT
18'-0"
BOTTOM SILL
TRACK/CONN'S
600T200-54 600S200-68 16" OC
TOP TRACK
(SEE NOTE 2)
TYPE
TRACK
CONNECTORS
STUDS
INTERIOR LOAD BEARING WALL OPENING FRAMING SCHEDULE
MAX OPENING
WIDTH
JAMB HEADER WINDOW SILL
4'-0"
600T200-54/ 1/2"Ø x 4" CONC
SCREWS AT 4'-0" MAX ON
CENTER (SEE NOTE 1 FOR PAF
ALTERNATIVE)
INTERIOR LOAD BEARING WALL FRAMING SCHEDULE
#10 SCREW
EACH TRACK FLANGE
MAX SPACING
(2) 600S162-54 + 6002T 125-54
600S162-54 SILL
+ 600T200-54 TRACK
NOTES:
1. ANY LOW-VELOCITY HEADED POWDER ACTUTATED FASTENERS WITH MINIMUM SHANK DIAMETER = 0.145 INCH, 1 1/4" MINIMUM PENETRATION, AND MINIMUM ALLOWABLE SHEAR CAPACITY 200 LBS.
2. ANCHORS MUST BE INSTALLED TO THE TORQUE RECOMMENDATIONS BY THE ANCHOR MANUFACTURER TO OBTAIN MAXIMUM LOADING.
NOTES:
1. PREFABRICATED HEADER AND JAMB ASSEMBLIES MAY BE USED IN LIEU OF BUILT-UP SECTIONS SPECIFIED IF THEIR SECTION PROPERTIES EXCEED
THOSE SPECIFIED.
2. SEE TYPICAL DETAILS FOR WALL FRAMING ELEVATION AND CONNECTIONS BETWEEN BUILT-UP MEMBER COMPONENTS.
3. HEADERS REQUIRE WEB STIFFENERS.
8'-0"
(2) 600S162-97 + 600T125-97
600S162-54 SILL
+ 600T200-54 TRACK
(2) 1200S162-97 STUD+(2)
600T200-97 TRACK
WALL TYPE
TOWER: 800S200-54 14'-0"
800T200-54/ 1/2"Ø x 4" CONC
SCREWS AT 2'-0" MAX ON
CENTER (SEE NOTE 1 FOR PAF
ALTERNATIVE)
800T200-54 800S200-54
TOP TRACK
(SEE NOTE 2)
TYPE MAX SPACING
STUDS
EXTERIOR NON-LOAD BEARING WALL FRAMING SCHEDULE
BOTTOM SILL
TRACK/CONN'S
MAX. HEIGHT
#10 SCREW
EACH TRACK FLANGE
TRACK
CONNECTORS
16" OC, TYP
NOTES:
1. ANY LOW-VELOCITY HEADED POWDER ACTUTATED FASTENERS WITH MINIMUM SHANK DIAMETER = 0.145 INCH, 1 1/4" MINIMUM PENETRATION, AND MINIMUM ALLOWABLE SHEAR CAPACITY 200 LBS.
2. ANCHORS MUST BE INSTALLED TO THE TORQUE RECOMMENDATIONS BY THE ANCHOR MANUFACTURER TO OBTAIN MAXIMUM LOADING.
3. MAX HEIGHT REFERS TO MAXIMUM HEIGHT TO ROOF BEARING ELEVATION.
DATA CENTER:
600S200-54 (UNO ON PLAN
& SHEAR WALL SCHED)
18'-0"
600T200-54/ 1/2"Ø x 4" CONC
SCREWS AT 2'-0" MAX ON
CENTER (SEE NOTE 1 FOR PAF
ALTERNATIVE)
600T200-54 600S200-54
#10 SCREW
EACH TRACK FLANGE16" OC, TYP
(2) 600S162-54 STUD+(2) 600T200-54
TRACK
SCHEDULE GENERAL NOTES:
1. ALL WALLS ON PERIMETER OF THE DATA CENTER BUILDING ARE CONSIDERED EXTERIOR WALLS
SCREW MAXIMUM MATERIAL
THICKNESS
NOTE
TYPICAL, UNLESS NOTED OTHERWISE
HEADERS, METAL DECK TO FRAMING
COLD-FORMED FASTENER SCHEDULE
#10
#12
68 MIL
1/8"
NOTES:
1. FASTENERS SHALL BE GALVANIZED SELF-DRILLING SCREWS.
2. SCREW LENGTH AND DRILL POINT SHALL BE SELECTED TO PROVIDE SUFFICIENT THREAD ENGAGEMENT.
PENETRATIONS THROUGH JOINED MATERIALS SHALL NOT BE LESS THAN THREE EXPOSED THREADS.
3. SCREWS SHALL BE INSTALLED WITH SCREW DRIVERS WITH CONTROLS FOR PROPER SPEED, TORQUE AND SETTING
DEPTH.
4. USE MINIMUM SCREW SIZE PER MANUFACTURER'S CATALOG AT HARDWARE (SIMPSON OR APPROVED EQUAL).
#8 54 MIL
FOR ATTACHMENT TO STEEL MEMBERS1/4"Ø 1/8"
1"1"
HEADER PER PLAN & SCHED
L1 1/2x1 1/2x54 MILx0'-4" W/
(3) #10 EA LEG,
TYP T&B OF HEADER
JAMB STUD PER PLAN & SCHED
PL97 MILx4x0'-9 1/2" W/ (9) #12 TO HEADER
& (9) #12 TO JAMB,
TYP EA FACE OF HEADER
OMIT @ SIM (NON-LOAD BEARING)
1" 1"
1" 1"
1"1"
HEADER PER PLAN & SCHED
L1 1/2x1 1/2x54 MILx0'-4" W/
(3) #10 EA LEG,
TYP T&B OF HEADER
JAMB STUD PER PLAN & SCHED
PL54 MILx4x0'-5" W/ (4) #10 TO HEADER &
(4) #10 TO JAMB,
TYP EA FACE OF HEADER
OMIT @ SIM (NON-LOAD BEARING)
TYPE 1 - 4'-0" OPENING
TYPE 2 - 8'-0" OPENING
3/ 4"
1" T
Y P
SILL PER SCHED
L1 1/2x1 1/2x54 MILx0'-4" W/ (3) #10 EA
LEG,
TYP T&B OF SILL
JAMB STUD PER PLAN &
SCHED
C TYPICAL SILL ASSEMBLY
TYPICAL JAMB ASSEMBLY
TYPICAL BOX HEADER ASSEMBLY
B
A
NOTE 1
1-12
1-12
NOTE 2
1-12
1-12
NOTES:
1. SILL MEMBERS PER SCHEDULE.
2. #10 SCREWS @ 12" OC AS SHOWN.
1-12
1-12
NOTE 2
NOTES:
1. JAMB MEMBERS PER SCHEDULE.
2. #10 SCREWS @ 12" OC AS SHOWN.
NOTE 1
NOTE 2 NOTE 2
NOTE 1 NOTE 1
NOTES:
1. HEADER MEMBERS PER SCHEDULE.
2. #10 SCREWS @ 12" OC AS SHOWN.
NOTE 2
NOTE 1
NOTE 2
NOTE 1
NOTE 2
NOTE 1NOTE 1
A A
TYP BRIDGING
PER
BOTTOM TRACK
SEE TYP DETAILS FOR
ATTACHMENT TO SLAB
NOTES:
1. PREFABRICATED LINTEL AND JAMB ASSEMBLIES MAY BE USED IN LIEU OF BUILT-UP SECTIONS
SPECIFIED IF THEIR SECTION PROPERTIES EXCEED THOSE SPECIFIED.
2. SEE DETAILS A THROUGH C FOR TYPICAL WALL FRAMING ELEVATION AND CONNECTIONS BETWEEN
BUILT-UP MEMBER COMPONENTS.
3. HEADERS REQUIRE WEB STIFFENERS.
4. USE #8 SMS FOR 20 GA AND 18 GA COMPONENTS, UNO.
5. USE #12 SMS FOR 16 GA. COMPONENTS UNO.
TOC EL
PER PLAN
JA
M
B
JA
M
B
HEADER
DOOR OPG WIDTH
TYP TOP TRACK SPLICE PER
JA
M
B
LOUVER OR DUCT
S-525 E1
/B3 S-526
W E
B D
E P
T H
FLANGE DEPTH
UN-PUNCHED STEEL TRACK
MINIMUM PROPERTIES
PUNCHED STEEL STUD
MINIMUM PROPERTIES
W E
B D
E P
T H
FLANGE DEPTH
NOTES:
1. STEEL STUDS & TRACKS 12, 14, AND 16 GA. SHALL BE GRADE 50.
2. STEEL STUDS & TRACKS 20 GA. & 18 GA. SHALL BE GRADE 33.
3. WHERE WEB HEIGHT-TO-THICKNESS RATIO EXCEEDS 200, PROVIDE WEB STIFFENERS AT ALL SUPPORT POINTS AND
CONCENTRATED LOADS.
4. BLOCK STUDS PER
5. ALL TRACKS SHALL BE PROVIDED WITH UN-PUNCHED HOLES TYPICAL.
6. MATERIALS, DIMENSIONS, AND PROPERTIES OF STEEL STUDS & TRACKS SHALL BE PER STEEL STUD
MANUFACTURERS ASSOCIATION (SSMA) AND LATEST ICC REPORT No. ESR-3064P, UNLESS ALTERNATE STEEL
STUDS/TRACKS HAVE BEEN APPROVED BY THE ENGINEER.
7. WHERE SIZE AND SPACING OF LIGHT GAGE STEEL STUDS FOR HORIZONTAL OR DIAGONAL BRACING IS NOT SPECIFIED IN THE STRUCTURAL AND ARCHITECTURAL DETAILS, PROVIDE AS A MINIMUM 400S137-33 AT 16" O.C. W/ (4)
#8 SHEET METAL SCREWS AT EACH END CONNECTION AND BLOCKING PER
/D9 S-527
/D9 S-527
WSP USA Inc.
Suite 300
Federal Way, WA 98003-2600
TEL: (206) 431-2300
FAX: (206) 431-2250
33301 9th Avenue South
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
S-525
TYPICAL COLD-FORMED STEEL
DETAILS - SHEET 1SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
581-22-700
09/03/2025 CH JKM
100% CONSTRUCTION
DOCUMENTS
12" = 1'-0" C3
FRAMING SCHEDULES - LOAD BEARING WALLS
12" = 1'-0" B1
COLD-FORMED STL FASTENER SCHED
3" = 1'-0" E1
LOAD BRG HEADER TO JAMB CONN
3" = 1'-0" F1
SILL TO JAMB CONN
3/4" = 1'-0"
F3
COLD-FORMED STEEL STUD BEARING WALL ELEVATION
6" = 1'-0" C8
COLD-FORMED STL FASTENER SCHED
Revisions: Date: 042 OF 693
FACE OF DOOR/ WINDOW/ LOUVER OPNG
BOTTOM TRACK
PER SCHED
ANCHORAGE
PER SCHED
DOOR /WINDOW JAMB PER SCHED
ANGLE 68 MILxSTUD DEPTH LLV W/
(4) #10 SCREWS TO JAMB
3"
2"
TYPICAL WALL STUD
DOOR / W
INDOW O
PNG
ISOMETRIC VIEW
FASTEN BRIDGE CLIP OR
ANGLE AS REQD PER AISI
D3.2.2
SECTION
STUD,
SEE ELEVATIONS
FOR SIZE & SPACING
BRIDGE CLIP OR ANGLE TO
MATCH OR EXCEED STUD GAGE
COLD-FORMED CONT
BRIDGING CHANNEL
4' -0
O
C M
A X
E D
G E
D
IS
T A
N C
E
M
IN
WALL STUD PER SCHED
SCREW AT EA STUD
FLANGE PER
ANCHORAGE PER SCHED
3" MIN FROM CONC EDGE
/B1 S-525
SCREW ATTACHMENT
CONT COLD
ROLLED CHANNEL
S E
E N
O T
E
M A
X
DEFLECTION GAP
d
CLIP ANGLE
NOTE:
AT DEEP LEG SLOTTED DEFLECTION TRACKS BRIDGING MUST BE INSTALLED
WITHIN 12" OF TOP OF STUD.
NOTE:
FLAT STRAP BRIDGING REQUIRED AT STUD DEPTH > 6" AND SHEATHING ONE SIDE ONLY.
TRACK BLOCK PIECE TO
MATCH WALL STUD GAGE.
CLIP FLANGE & BEND.
INSTALL MAX @ 10'-0" OC HORIZ
SCREW ATTACHMENT
M
IN2"
STUD PER PLAN
& SCHED
WALL SHEATHING
CONT TAUT FLAT STRIP
(MATCH STUD GAGE)
SCREW TO EA STUD
NOTES:
1. SHEATHING BOTH SIDES NOT SHOWN FOR CLARITY.
2. FLAT STRAP BRIDGING BOTH SIDES REQUIRED AT STUD DEPTH > 6" AND NO
SHEATHING.
TRACK BLOCK PIECE TO MATCH WALL
STUD GAGE.
CLIP FLANGE & BEND.
INSTALL AT PANEL EDGES
SCREW ATTACHMENT
M
IN2"
STUD PER PLAN & SCHED
CONT TAUT FLAT STRIP
(MATCH STUD GAGE)
SCREW TO EA STUD
SCREW ATTACHMENT
STUD PER
PLAN & SCHED
WALL FINISH
CLIP TRACK FLANGE
AT LAP JOINT
TOP TRACK PER SCHED
TOP TRACK
(2) #10 SCREWS EA SIDE OF
JOINT @ EA TRACK FLANGE.
(8) #10 SCREWS TOTAL
CL SPLICE
54 MIL STUD TO MATCH TRACK SIZE x 1'-0" LONG
1" 2" 1"
JOINT
(1) #10 SCREWS @ EA
FLANGE, TYP
WALL STUD PER SCHED, TYP
JAMB STUD PER SCHED
INFILL STUD PER SCHED
TRACK ABOVE HEADER TO
MATCH WALL TOP TRACK
HEADER MEMBERS
PER SCHED
DECK PER PLAN
WALL PARALLEL TO DECK FLUTES
3/4" GAP
CONT 14 GA DEEP TRACK W/ (2) #10
SCREWS TO EA PL
(DO NOT FASTEN TO STUDS OR TOP
TRACK)
TYP TOP TRACK W/ #10 WAFERHEAD SCREWS
THROUGH DEEP TRACK SLOTS TO STUDS
PL 16 GAx8" WIDE @ 2'-0" OC
ATTACH TO DECK W/ (2) #10 TEK SCREWS PER
FLUTE
DECK PER PLAN
WALL PERPENDICULAR TO DECK FLUTES
3/4" GAP
CONT 14 GA DEEP TRACK W/ (2) #10
SCREWS TO DECK
(DO NOT FASTEN TO STUDS OR TOP
TRACK)
TYP TOP TRACK W/ #10 WAFERHEAD SCREWS
THROUGH DEEP TRACK SLOTS TO STUDS
MTL CLIP 54MIL x 0'-5" LONG
W/ (3) #10 SCREWS EA LEG
4"
2"
(4) #10 SCREWS T&B
TYP ROOF JOIST SECTION
BLOCKING @ 4'-0" OC MAX.
ALL EXTERIOR BAYS MUST BE
BLOCKED
ROOF DECK PER PLAN
#10 SCREWS @ EA JOIST T&B
CONT FLAT STRAP 43MILx1 1/2" @ 4'-0" OC
ROOF JOIST PER PLAN, TYP
DECK PER PLAN
WALL PERPENDICULAR TO DECK FLUTES
CONT 14 GA DEEP TRACK W/
(2) #10 SCREWS TO EA PL
TYP TOP TRACK W/ #10
SCREWS TO STUDS
ATTACH TO DECK W/ (2) #10
TEK SCREWS PER FLUTE
SHEAR WALL PER PLAN
TOW DATA
CENTER
18' - 0"
WALL FRMG
HSS COL PER PLAN
CAP PL1/2
3/16
END PL1/2
3/8 PP
LEDGER PER /F1 S-527
(4) #12 SCREWS
NOTE:
FOR ADDITIONAL INFORMATION REFER TO /B9 S-511
L4x4x3/8 EA SIDE OF BEAM W/
(3) 5/8"Ø THROUGH BOLTS.
PROVIDE SHORT SLOTTED
HOLES IN BEAM, TYP
HSS COL PER PLAN
CF STUD S162 TO
MATCH SIZE & GAUGE
OF WALL STUDS, TYP
#12 SMS @ 12" OC, TYP
AT SHEAR WALL,
PROVIDE CONT
BLOCKING PER
CONTINUOUS TRACK
LEDGER, SPLICE
PER
LEDGER ATTACHMENT PER
TYP/F1 S-527
/B4 S-528
/D9 S-527
NOTE: ROOF FRAMING NOT SHOWN FOR CLARITY
3/4" = 1'-0" B1
TYP JAMB STUD BASE CONNECTION
3/4" = 1'-0"
B3
TYPICAL BRIDGING
3/4" = 1'-0" B5
WALL STUD BASE CONN
WSP USA Inc.
Suite 300
Federal Way, WA 98003-2600
TEL: (206) 431-2300
FAX: (206) 431-2250
33301 9th Avenue South
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
S-526
TYPICAL COLD-FORMED STEEL
DETAILS - SHEET 2SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
581-22-700
09/03/2025 CH JKM
100% CONSTRUCTION
DOCUMENTS
1" = 1'-0" B7
DEFLECTION TRACK
3/4" = 1'-0" D5
SINGLE FLAT STRAP BRIDGING
3/4" = 1'-0"
D3
DOUBLE FLAT STRAP BRIDGING
3/4" = 1'-0" B9
TRACK LAP CONN AT CORNER
3" = 1'-0" D1
TOP TRACK SPLICE-NON SHEAR WALL
3" = 1'-0"
D7
NON LOAD BRG EXT HEADER ATTACHMENT
3" = 1'-0" F1
DEFLECTION TRACK TO DECK
3" = 1'-0"
F5
TYPICAL JOIST BLOCKING
1 1/2" = 1'-0" F8
TRACK TO DECK
1 1/2" = 1'-0"
F9
BEAM TO COL CONN
1 1/2" = 1'-0" D9
STUD FASTENING TO HSS COL
Revisions: Date: 043 OF 693
PLAN
NOTES:
1. USE 15/32" STRUCTURAL 1 SHEATHING. SEE GENERAL NOTES FOR SHEAR WALL CONSTRUCTION.
2. FASTENERS TO BE #10-16 (#3 POINT) FLAT HEAD SCREWS.
3. BLOCK ALL PANEL EDGES.
4. EDGE FASTENER SPACING AT WALL BOUNDARIES AND PANEL EDGES.
5. FASTENER SPACING IN FIELD = 12" OC.
6. SILL PLATE ANCHORAGE TO CONCRETE TO BE 1/2" DIA. HILTI KH-EZ CONC SCREWS W/ 4-1/4" EMBED.
7. AVAILABLE STRENGTH REFERS TO LATERAL FORCES INCLUDING SEISMIC AND WIND.
TYPE
SHEAR WALL SCHEDULE
STUD TOP TRACK BOTTOM TRACK BOTTOM TRACK FASTENERS TO
CONCRETE
ΦVn AVAILABLE STRENGTH (lb/ft)
SW 1 6" OC 600S250-68 @ 16"OC 600T200-54 600T200-54 564CONC SCREWS @ 32" OC
PANEL EDGE
FASTENER SPACING
(NOTE 4)
SW 2 6" OC 600S250-97 @ 16"OC 600T200-97 600T200-54 564CONC SCREWS @ 32" OC
AT VERTICAL JOINTS:
WALL STUDS PER PLAN
AT HORIZONTAL JOINTS:
BLOCK TO MATCH WALL STUD GA &
THICKNESS
SHEATHING PER SHEAR WALL
SCHED
EDGE FASTENING PER
SHEAR WALL SCHED
MIN
3/8"
MIN
3/8"
SCREW
EDGE SPACING PER
SCHED
SCREW
FIELD SPACING
PER SCHED
PANEL EDGE
BLOCKING
ALL PANEL EDGES
FULLY BLOCKED
TOC
PER PLAN
D3
S-527
D3
S-527
S-527 B1
S-527 D5
S-527 D1
PLAN
TOP TRACK
TYP STUD
CL SPLICE
DBL STUD AT
SPLICE LOCATION
CL SPLICETYP
1"
TYP
1"
1"
1"
2"
1"
CL PL & TRACK
PL 54 MIL x 4" x 2'-4"
TOP TRACK PER SCHED
EQ EQ
(24) #12 SCREWS
(12) EA SIDE OF SPLICE
S
S
S
S
S
PANEL EDGE
S = SCREW EDGE SPACING PER
SHEAR WALL SCHEDULE
S = SCREW EDGE SPACING PER
SHEAR WALL SCHEDULE
(2) STUDS (3) STUDS (4) STUDS
SECTION ELEVATION
OMIT TRACK AT DOOR OR
WALL ENDTYP BOTTOM TRACK
(54 MIL MIN)
SHEAR WALL BOUNDARY
STUDS
OPNG PER PLAN/ELEVATION
CONC SCREW
ANCHORAGE PER SCHED
#10 SCREW EA FLANGE
EF, TYP
TYP STUDS
TOC
PER PLAN
M
IN
TO BOUNDARY
+/- 12"
SW SCHEDULE
SPACING PER
HOLDOWN PER PLAN & DETAIL /D7 S-527
SCREW AS REQD
STUD PER PLAN &
SCHED
SHEAR WALL
SHEATHING PER
SCHED
TRACK BLOCKING PIECE TO MATCH
WALL STUD GAGE UNO.
CLIP FLANGE AND BEND. INSTALL
AT HORIZ SHEATHING EGDES
TYP STUD SECTION
CLIP ANGLE 54 MIL
EA END OF BLOCKING
W/ (3) #10 SCREWS
EA LEG
WALL STUD
PER PLAN
PLAN
ISOMETRIC VIEW
ANCHOR BOLT PER
SCHED
GALVANIZE ANCHOR ON
EXT/PERIMETER WALLS
SOG PER PLAN
FDTN PER PLAN
HOLDOWN PER PLAN AND SCHED
INSTALL PER MFR
RECOMMENDATIONS
CL CFS STUD & TENSION TIE
EDGE OF (E) STRUCTURE. GC VERIFY
/B9 S-527
/B9 S-527
T125-54 TOP TRACK TO
MATCH STUD WIDTH
JOIST TO LEDGER W/ CLIP ANGLE 1 1/2"x1 1/2" x 97 MIL W/ (4) #12 SCREWS @ 1 1/2"
OC EA LEG, UNO. PROVIDE CLIP ANGLE
WITH MIN ALLOWABLE CAPACITY OF 3200#
STUD WALL PER PLAN
ROOF DECK PER PLAN
ROOF JOIST PER PLAN
NOTE:
SPLICE EA JOIST LEDGER PER WHERE REQUIRED./B4 S-528
EXPANSION JOINT AND
COVER PER PLAN
(E) STRUCTURE
GC VERIFY
ATTACH LEDGER TO BLOCKING
W/(4) #10 SCREWS EA BLOCKING
PANEL FASTENERS PER
SHEAR WALL SCHEDULE,
MINIMUM (4) #10 SCREWS
PER BLOCKING
1"
SHEAR WALL ATTACHMENT PER SCHEDULE
SHEAR WALL SHEATHING PER SCHEDULE
2"
CONT. BENT PL 16GA x 1 1/2" x 1 1/2"
SHEAR/BR'G WALL PER
PLAN. ALIGN JOISTS W/
STUD BELOW
MST12 STRAP @ 48" OC BELOW MTL
DECK W/ (4) #10 SCREWS EA LEG
M A
X
1"
CONT T200-97 LEDGER TO
MATCH JOIST DEPTH. ATTACH
TO JOIST W/ #10 SCREWS T&B.
ATTACH LEDGER TO EA STUD W/
(4) #12 SCREW TYP
T125-54 TOP TRACK TO
MATCH STUD WIDTH
CLIP ANGLE 1 1/2"x1 1/2" x
54 MIL W/ (4) #10 SCREWS
1 1/2" OC EA LEG, EA END
OF BLOCKING
CONT T200-68 LEDGER TO MATCH
JOIST DEPTH, ATTACH TO
BLOCKING W/ #10 SCREWS T&B
STUD WALL PER PLAN
ROOF DECK PER PLAN
STUD BLOCKING 43 MIL @ 4'-0" OC
ALIGN W/ DECK FLUTES
NOTE:
SPLICE EA JOIST LEDGER PER WHERE REQUIRED./B4 S-528
ROOF JOIST PER
PLAN
EXPANSION JOINT AND
COVER PER ARCH
(E) STRUCTURE. GC VERIFY
ATTACH LEDGER TO BLOCKING
W/(4) #10 SCREWS EA BLOCKING
1"
SHEAR WALL ATTACHMENT PER SCHEDULE CONT BLOCKING PER
AT JOINT BTWN BOT OF JOIST &
SHEATHINGSHEAR WALL SHEATHING PER SCHED.
CONT. BENT PL 16GA x 1 1/2" x 1 1/2"
/D9 S-527
MST12 STRAP @ 48" OC BELOW MTL
DECK W/ (4) #10 SCREWS EA LEG
CONT JOIST LEDGERS (2)
1200T150-68 BACK-TO-BACK.
SPLICE PER B4/S-528
JOIST PER PLAN. ALIGN
WITH STUDS BELOW
TYP TOP TRACK W/ #10
SCREWS TO STUDS
SHEAR/BR'G WALL PER
PLAN. ALIGN JOISTS W/
STUD BELOW
@ SHEAR WALL: (2) #10 @ 6" OC
@ BR'G WALL/HDR: (2) #10 @ 12" OC
DECK PER PLAN
1 1/2" MIN BR'G AT EA JOIST
CLIP ANGLE 1 1/2"x1 1/2" x 97 MIL
W/ (4) #12 SCREWS 1 1/2" OC EA
LEG, EA END OF JOIST. PROVIDE
CLIP ANGLE WITH MIN
ALLOWABLE CAPACITY OF 3200#
CONT JOIST LEDGERS (2)
1200T150-68 BACK-TO-BACK.
SPLICE PER B4/S-528
JOIST PER PLAN
TYP TOP TRACK W/ #10
SCREWS TO STUDS
SHEAR/BR'G WALL PER
PLAN. ALIGN JOISTS W/
STUD BELOW
@ SHEAR WALL: (2) #10 @ 6" OC
@ BR'G WALL/HDR: (2) #10 @ 12" OC
DECK PER
PLAN
JOIST PER PLAN
STUD BLOCKING 43 MIL @ 4'-0" OC
ALIGN W/ DECK FLUTES
CLIP ANGLE 1 1/2"x1 1/2" x
54 MIL W/ (4) #10 SCREWS
1 1/2" OC EA LEG, EA END
OF BLOCKING
1 1/2" MIN BR'G AT EA JOIST
SHEAR WALL ATTACHMENT
PER SCHEDULE
#10 SCREW @ 12" OC STAGGERED
CLIP ANGLE 1 1/2"x1 1/2" x 97 MIL W/
(4) #12 SCREWS 1 1/2" OC EA LEG.
PROVIDE CLIP ANGLE WITH MIN
ALLOWABLE CAPACITY OF 3200#
HOLDOWN SCHEDULE
MARK
STUD
FASTENERS
ANCHOR DIAMETER &
EMBEDMENT
WASHER PLATE
S/HDU4
S/HDU5
(6) #14
(12) #14
5/8" ø x 9" EMBED
5/8" ø x 12" EMBED
3/8"ø x 1 1/2" x 1 1/2"
3/8"ø x 1 1/2" x 1 1/2"
NOTES:
1. HOLDOWNS ARE MANUFACTURED BY SIMPSON STRONG
TIE PER UES ER-124.
2. SECURE HOLDOWNS TO 43 MIL MIN STEEL FRAMING
MEMBER BY FILLING PRE-PUNCHED HOLES WITH SELF-
DRILLING SCREWS NOTED ABOVE.
JOIST LEDGERS (2)
1200T150-68 BACK-TO-BACK
TYP TOP TRACK W/ #10
SCREWS TO STUDS
SHEAR/BR'G WALL PER
PLAN. ALIGN JOISTS W/
STUD BELOW
@ SHEAR WALL: (2) #10 @ 6" OC
@ BR'G WALL/HDR: (2) #10 @ 12" OC
DECK PER
PLAN
JOIST PER PLAN
STUD BLOCKING 43 MIL @ 4'-0" OC
ALIGN W/ DECK FLUTES
CLIP ANGLE 1 1/2"x1 1/2" x
54 MIL W/ (4) #10 SCREWS
1 1/2" OC EA LEG, EA END
OF BLOCKING
SHEAR WALL ATTACHMENT
PER SCHEDULE
(E) STRUCTURE.
DEMO IN PHASE
PER PLAN
3" = 1'-0" D3
SHEAR WALL EDGE FASTENING
3/4" = 1'-0" B3
TYP SHEAR WALL SCHEDULE AND ELEVATION (OSB SHEATHING)
WSP USA Inc.
Suite 300
Federal Way, WA 98003-2600
TEL: (206) 431-2300
FAX: (206) 431-2250
33301 9th Avenue South
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
S-527
TYPICAL COLD-FORMED STEEL
DETAILS - SHEET 3SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
581-22-700
09/03/2025 CH JKM
100% CONSTRUCTION
DOCUMENTS
1 1/2" = 1'-0" D5
SHEAR WALL TOP TRACK SPLICE
1/2" = 1'-0" B1
SHEARWALL EDGE FASTENING
1 1/2" = 1'-0" D1
SHEAR WALL BOT TRACK CONN
3/4" = 1'-0"
D9
SHEAR WALL BLOCKING DETAIL
1" = 1'-0" D7
TENSION TIE CONN TO FDTN
1 1/2" = 1'-0" F1
TYP PARAPET DETAIL WALL
PERPENDICULAR TO JOIST
1 1/2" = 1'-0" F3
TYP PARAPET DETAIL
WALL PARALLEL TO JOIST
1 1/2" = 1'-0" F5
TYPICAL INTERIOR BEARING WALL
1 1/2" = 1'-0"
F7
TYP INT BRG WALL W/ JOISTS BOTH DIRECTIONS
1 1/2" = 1'-0" B9
HOLDOWN SCHEDULE
1 1/2" = 1'-0" F9
INTERIOR WALL
Revisions: Date: 044 OF 693
#12 SCREWS
@ 12" OC
JOIST SUPPORT,
TYP
#10 SCREWS
@ 12" OC
SUPPORT PARALLEL TO DECK
EDGE INTERMEDIATE SIDE SEAM
SCREWS PER PATTERN BELOW
JOIST SUPPORT, TYP
SUPPORT PERPENDICULAR TO DECK
JOINT INTERMEDIATE EDGE
BRG TYP
1 5/8" MIN
36/4 FASTENER PATTERN AT ALL
SUPPORTS (#12 SCREWS) UNO
3' - 0" WIDE PANEL
TYP FASTENER PATTERN
MTL CLOSURE STRIP
AS REQD, TYP
#12 SCREWS
@ 12" OC
(24) #12 SCREWS EA SIDE OF JOIST (48 TOTAL)CONT TRACK LEDGER
OR COLLECTOR
STAGGER SPLICES 3'-0" MIN @ BTB
COLLECTOR LOCATIONS
T Y
P 1"
T Y
P
2"
TYP
1 1/2"
TYP
2"
1 1/2"
STUD TO MATCH SIZE & GAGE OF
TRACK LEDGER OR COLLECTOR
ROOF OPNG PER PLAN
3' '-0
M
A X
P E
R P
LA
N
ROOF JOIST PER PLAN, TYP
DBL ROOF JOIST, TYP
ROOF JOIST SECTION, TYP
CLIP ANGLE 1 1/2"x1 1/2" x 54 MIL W/ (4) #10
SCREWS EA LEG, UNO
1/16 1-2
1/16 1-2
4" WELDS @
EDNS, TYP4'-0" MAX
PER PLAN
TYP STUD
SCREWS @ 24" OC
FIN PER ARCH, TYP
NOTE:
FOR SCREW SIZES, SEE NOTES 4 & 5 ON DET /F3 S-525
TYP STUD
SCREWS @ 24" OC
FIN PER ARCH, TYP
NOTE:
FOR SCREW SIZES, SEE NOTES 4 & 5 ON DET /F3 S-525
TYP ROOF JOIST BTB
(4) #10 SCREWS T&B
ROOF JOIST PER PLAN, TYP
#10 SCREWS AT EA JOIST T&B
DBL MTL CLIP 54MIL x x 0'-5" LONG
W/ (4) #10 SCREWS EA LEG
2"
4"
CONT FLAT STRAP 43MIL x 1 1/2"
@ EA BLOCKING
OMIT AT CONT WALL BLOCKING
ROOF DECK PER PLAN
JOIST TO LEDGER W/ CLIP ANGLE 1 1/2"x1 1/2" x 68 MIL W/ (4) #10 SCREWS @ 1 1/2"
OC EA LEG, UNO
ROOF DECK PER PLAN
ROOF PURLIN PER PLAN
PURLIN HANGER PER
ROOF BEAM PER PLAN
/D1 S-528
CONNECTOR
TYPE
CFS PURLIN HANGER SCHEDULE
DIMENSIONS [IN]
TOP FLANGE
CONNECTOR
WIDTH HEIGHT
3 1/8 12
ALLOWABLE LOADS [LBS]
UPLIFT DOWN
1010 2220
BB JOIST PER PLAN
DECK PER
PLAN
#10 SCREW @ 12" OC STAGGERED
JOIST PER PLAN
400S162-54 WEB STIFFENER W/ (4) #10
SCREWS CENTER BELOW MECH UNIT
LEG. EA JOIST
DECK PER PLAN
PL1/4x12x1'-0"
ATTACH TO TEDK W/ (16)
#8 SCREWS AT EQ SPA
ARIOUND PERIMETER
LEG OF MECH UNIT PER MFR
T125-54 TOP TRACK TO
MATCH STUD WIDTH
ROOF DECK PER PLAN
ROOF JOIST PER PLAN.
BEAR ON TOP OF STUD WALL(FULL
WIDTH)
NOTE:
SPLICE EA JOIST LEDGER PER WHERE REQUIRED./B4 S-528
EXPANSION JOINT AND
COVER PER PLAN
(E) STRUCTURE
GC VERIFY
PANEL FASTENERS PER
SHEAR WALL SCHEDULE,
MINIMUM (4) #10 SCREWS
PER BLOCKING
SHEAR WALL ATTACHMENT PER SCHEDULE
SHEAR WALL SHEATHING PER SCHEDULE
CONT. BENT PL 16GA x 1 1/2" x 1 1/2" SHEAR/BR'G WALL PER
PLAN. ALIGN JOISTS W/
STUD BELOW
M A
X
1"
CONT T200-97 BLKG TO
MATCH JOIST DEPTH. ATTACH
TO JOIST PER
(3) #10 SCREWS T&B AT PARAPET
STUD TO JOIST CONNECTION
/F5 S-526
T125-54 TOP TRACK TO
MATCH STUD WIDTH
PARAPET STUD TO MATCH WALL
STUD BELOW. MATCH WALL STUD
SIZE TYP
DIAPHRAGM ATTACHMENT
FLR DECK PER PLAN
BEAM PER PLAN
TRACK & CONN PER
EXT NON-LOAD BEARING
NON-SHEAR WALL STUD
PER SCHED
KICKER PER PLAN,
CONN PER /E1 S-511
/C3 S-525
FINISH PER ARCH
/C3 S-525
14 GA HAT CHANNEL
@ 16" OC
CONC EDGE
3" MIN
3 3/4" MAX
NOTE 2
NOTES:
1. ATTACH HAT CHANNEL TO WF BEAM WITH (2) POWER
ACTUATED PIN OF 0.145" MIN SHANK DIAMETER WITH
PENETRATION PER ESR @ EACH FLANGE (TOTAL 4)
2. ATTACH TOP TRACK TO HAT CHANNEL W/ (3) #10 SCREWS.
NOTE 1
CONT 14 GA DEEP
SLOTTED TRACK
HEADED ANCHOR OR
SCREW ANCHOR 3/8"Ø W/ 2
1/2" EMBED @ 32" OC MAX
EDGE FORM 18 GA MIN
1 1/2"
1/
2"
TYP
3/4"
CFS WALL STUDS
FIN PER ARCH, TYP
CONT 14 GA DEEP SLOTTED TRACK
STL BEAM PER PLAN
(2) PAF, STAGGERED.
TYPE, SIZE, & SPACING PER
CL BEAM, TRACK, & WALL
FULL DEPTH STIFF
PL3/8 EA SIDE, TYP
KICKER L3 @ 1/3 SPANS OF BEAM OR
6'-0" OC MAX, WHICHEVER IS LESS,
CONN PER /E1 S-511
/C3 S-525
WSP USA Inc.
Suite 300
Federal Way, WA 98003-2600
TEL: (206) 431-2300
FAX: (206) 431-2250
33301 9th Avenue South
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
S-528
TYPICAL COLD-FORMED STEEL
DETAILS - SHEET 4SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
581-22-700
09/03/2025 CH JKM
100% CONSTRUCTION
DOCUMENTS
3" = 1'-0" C1
TYP ROOF DECK FASTENING TO COLD FORMED JOIST
3" = 1'-0" B4
TYP ROOF JOIST/LEDGER SPLICE
3/4" = 1'-0"
B6
TYP FRAMING AT ROOF OPENING
1 1/2" = 1'-0" B8
TYPICAL CORNER PLAN
1 1/2" = 1'-0" C4
TYPICAL INTERSECTION PLAN
1 1/2" = 1'-0"
C6
DBL JOIST CONN SUPPORT LEG
1 1/2" = 1'-0" C8
TYP CFS JOIST TO STEEL BEAM CONN
12" = 1'-0" D1
CFS PURLIN HANGER SCHEDULE
1 1/2" = 1'-0"
D4
TYP BB JOIST CONNECTION
1 1/2" = 1'-0" D6
TYP MECH UNIT LEG SUPPORT
1 1/2" = 1'-0" F1
JOIST BEARING ON WALL DETAIL
1" = 1'-0"
F4
TYPICAL EXTERIOR WALL DETAIL
1" = 1'-0" F8
TYP NON-BEARING INT STUDS TO BOT OF BEAM
Revisions: Date: 045 OF 693
M
IN
M A
X
C.G.
8"
MAX
M A
X
6"
MIN.
TYP.
1/2"∅ X 3 1/4" EMB.
STAINLESS STEEL HILTI
KWIK BOLT TZ2 PER
ICC-ES 4266, TYP. (2 PER
POST)
UNISTRUT OUTSIDE ANGLE
FITTING P2098 (HG) @ BOTTOM
& P2100 (HG) @ TOP WITH
3/8"∅ BOLTS & CHANNEL NUTS,
TYP. @ BRACES
UNISTRUT P1000T (HG) BRACE
UNISTRUT P1000T (HG) BASE
UNISTRUT P1026 (HG)
FITTING WITH 3/8"∅
BOLTS & CHANNEL
NUTS (1 EA. SIDE)
3"
UNISTRUT POSTS PER
ELEVATION, TYP.
ELECTRICAL
EQUIPMENT,
200 LB MAX
±2'-6"
3"
8" CONC PAD,
REINFORCING PER ELEV.
12"
MAX
OUTDOOR UNIT SUPPORT
UNISTRUT P2233 (HG) BRACKET
M
IN
ATTACH ELECTRICAL
EQUIPMENT TO UNISTRUT WITH
3/8"∅ A307 BOLTS, GALVANIZED,
(EA CORNER, 4 TOTAL)
C.G.
6"
MIN.
TYP.
1/2"∅ X 3 1/4" EMB.
STAINLESS STEEL HILTI
KWIK BOLT TZ2 PER
ICC-ES 4266, TYP. (2 PER
POST)
UNISTRUT P1000T (HG) BASE
UNISTRUT P1001T (HG)
POSTS W/ P1000T
BRACE
ELECTRICAL
EQUIPMENT,
200 LB MAX
±2'-0"
OUTDOOR UNIT SUPPORT
UNISTRUT P2233 (HG) BRACKET,
ALIGN W/ ℄ OF UNIT ANCHOR
POINTS, VERIFY PER MNFR
ATTACH ELECTRICAL
EQUIPMENT TO UNISTRUT WITH
3/8"∅ A307 BOLTS, GALVANIZED,
(EA CORNER, 4 TOTAL)
4" 1'-6"
MAXMIN
TYP.
M
IN
M A
X
S.O.G. W/ #4 @
12" O/C EA WAY
@ T&B OF SLAB
FINISHED GRADE
M
IN
T
Y P
M
IN
T
Y P
4"
MIN
(E) STUD WALL
(E) WALL FTG
8" CONC PAD
FINISHED GRADE
(E) VENEER NOTE: ALL EXPOSED
STEEL SHALL BE
GALVANIZED, UNO.
UNISTRUT P1000T
(HG) STRUT W/
P1359 (HG) 90°
FITTING @ FS OF EA
POST
.5
STRUT PER ELEV W/
UNISTRUT P1359 (HG) 90°
FITTING @ EA POST W/ 1/2"∅
BOLTS & CHANNEL NUTS (4
TOTAL)
2" TYP.
M A
X
M A
X
M A
X
℄BRACE, FS
P1000 BRACE W/ 1/2"∅
BOLTS INTO POSTS. DRILL
HOLE AS REQ'D THROUGH
WEB & EXTEND UNISTRUT
2" MIN EA SIDE BEYOND
HOLES
TOP VIEW
SCALE: N.T.S.
M
IN
M A
X
C.G.
8"
MAX
M A
X
ELECTRICAL
EQUIPMENT,
200 LB MAX
12"
MAX
OUTDOOR UNIT SUPPORT
UNISTRUT P2233 (HG) BRACKET
ATTACH ELECTRICAL
EQUIPMENT TO P1000 (HG)
UNISTRUT WITH 3/8"∅ A307
BOLTS, GALVANIZED, (EA
CORNER, 4 TOTAL)
(E) 8"
PARTIALLY
GROUTED CMU
WALL
(E) WALL FTG
4"
MIN
UNISTRUT P1000HS (HG)
GROUTED CELL: 1/2"∅ X
3 1/4" EMB. SS HILTI KWIK
BOLT TZ2 PER ICC-ES 4561
UNGROUTED CELL: 1/2"∅
SS THD ROD X 2" EMB.
INTO HILTI HIY 270 PER
ICC-ES 4143 TYP.
C.G.
8"
MAX
M A
X
12"
MAX
4"
MIN
(E) SOG
(E) GRADE
PER CIVIL
NOTE:
1. ANCHORS MUST BE INSTALLED A
MINIMUM OF 2'-0" FROM WALL ENDS
AND OPENINGS AND A MINIMUM OF 1'-0"
FROM CONTROL JOINTS TO AVOID
DAMAGING THE JAMB REINFORCEMENT.
2. DO NOT DAMAGE (E) REINFORCEMENT.
3. DO NOT INSTALL ANCHORS WITHIN 1
1/4" OF HEAD JOINTS OR BED JOINTS.
M
IN
T Y
P
OUTDOOR UNIT SUPPORT
UNISTRUT P2233 (HG) BRACKET
ATTACH ELECTRICAL
EQUIPMENT TO P1000 (HG)
UNISTRUT WITH 3/8"∅ A307
BOLTS, GALVANIZED, (EA
CORNER, 4 TOTAL) VERIFY
ANCHOR POINTS PER MNFR
UNISTRUT P1000HS (HG)
(E) 8"
PARTIALLY
GROUTED CMU
WALL
P1000 (HG) UNISTRUT OVER
P2233 (HG) BRACKET,
ATTACH W/ P1047 (HG) "U"
FITTING WITH 3/8"∅ BOLTS,
GALVANIZED, (4 EA FITTING)
NOTE: ALL EXPOSED
STEEL SHALL BE
GALVANIZED, UNO.
M A
X T
Y P
1/2"Ø
1/2"Ø
3/8"Ø
3/8"Ø
3/8"Ø
1/2"Ø
3/8"Ø
1/2"Ø
UNISTRUT P1001T (HG)
POSTS W/ P1001T BRACE
3/8"Ø
3/8"Ø
1/2"Ø
1/2"Ø
3/8"Ø
WSP USA Inc.
Suite 300
Federal Way, WA 98003-2600
TEL: (206) 431-2300
FAX: (206) 431-2250
33301 9th Avenue South
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
S-541
MECHANICAL ANCHORAGE
DETAILSSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
581-22-700
09/03/2025 CH Author
100% CONSTRUCTION
DOCUMENTS
f1
SMALL EQUIPMENT FRAME AT STUD WALL (WEIGHT = 200 LBS MAX)
f7
SMALL EQUIPMENT ANCHORAGE AT CMU WALL (WEIGHT = 200 LBS MAX)
Revisions: Date: 046 OF 693
T/ EXISTING FLOOR
EXISTING WALL STUD BEYOND
350S162-43 (50 ksi) MIN @ 16"
OC MAX VERIFY IN FIELD
EXISTING WALL SHEATHING
NOT SHOWN FOR CLARITY.
BOT OF EXISTING
STR FLOOR/ ROOF MEMBER
P1000H3
P1026 EA SIDE W/ 1/2" DIA.
THROUGH BOLT TO P9000 AND TO
P1000H3 W/ 1/2" DIA. BOLT W/
CHANNEL & NUT TYP
P9000, TYP
P1000H3 W/ SELF DRILLING HEX
HEAD 1/4" DIA. SHEET METAL
SCREWS W/ FLAT WASHER TO
EXISTING BOTTOM TRACK AT 3
LOCATIONS
EXIST WALL
BOT TRACK
MIN
3"
7" M
IN
M A
X
5/16"Ø BOLTS IN EACH
MOUNTING KEYHOLE
TO UNISTRUT W/
SPRING NUTS OR
EQUAL AND LOCK
WASHERS
(4 MIN, TOTAL NO PER
MFR), TYP
P1000H3 W/ P1026 EA
END T&B W/ 1/2"Ø BOLT
W/ CHANNEL & NUT
LOADED CABINET WEIGHT
= 450 LBS MAX
P1000H3
D4
S-542
F1
S-542
S-542 F4
S-542
F4 OPP
NOTES:
1. UNISTRUT TO BE UNPUNCHED UNLESS NOTED OTHERWISE ON THE DETAILS.
2. PROVIDE UNISTRUT ENDCAPS AND CHANNEL CAPPING STRIP FOR EXPOSED UNISTRUT.
3. THE CABINET SHALL BE PLACED ON INTERIOR WALLS ONLY.
4. SEISMIC DESIGN CRITERIA:
SDS = 1.194g MAXIMUM Ip = 1.5 MAXIMUM
5. SHEET METAL SCREWS SHALL BE ELCO DRIL-FLEX SELF DRILLING STRUCTURAL SCREW.
SELF DRILLING HEX HEAD 1/4" DIA.
SHEET METAL SCREWS (SCREWS TO
BE CENTER ON STUD) W/ FLAT
WASHER INTO 3 EXISTING STUD
P1026 EA SIDE W/ 1/2" DIA. THROUGH
BOLT TO P9000 AND TO P1000H3 W/
1/2" DIA. BOLT W/ CHANNEL & NUT TYP
EXISTING
TOP TRACK
'-0
M
A X
BOT OF EXISTING
STR FLOOR/ ROOF MEMBER
T/ EXISTING FLOOR
MAX
2' - 6"
P1000H3 W/ CONNECTION TO
EXISTING BOTTOM TRACK PER
ELEVATION
EXIST WALL
BOTTOM TRACK
AVOID CONFLICTS
W/ EXIST ANCHORS
CABINET PER ELEV
NO GAP BTWN P9000 AND
EXIST WALL FINISH
P9000 W/ CONNECTION TO T&B
PER ELEV
UNIT ANCHORAGE TO
UNISTRUT PER ELEV
EXISTING WALL STUD
PER ELEVATION
P1000 PER ELEV
P1000H3 W/ CONNECTION
TO EXISTING STUD AND
P9000 PER ELEVATION
P1000H3 MUST
BEAR ON FLOOR
M
IN
CABINET BELOW
PER ELEV
P1000H3 W/ CONNECTION TO
MINIMUM 3 EXISTING STUDS
PER ELEVATION
CABINET ANCHORAGE
TO UNISTRUT PER ELEV
EXISTING WALL STUD, TYP
P9000 W/ CONNECTION
TO T&B PER ELEV
EXISTING WALL FINISH
P1000H3
P3300HS WITH (2) 1/2"
DIA. THRU BOLT TO P9000
P9000
P1026 EA END T&B W/ 1/2"Ø
BOLT WITH CHANNEL & NUT
NOTES:
1. UNISTRUT TO BE UNPUNCHED UNLESS NOTED OTHERWISE ON THE DETAILS.
2. PROVIDE UNISTRUT ENDCAPS AND CHANNEL CAPPING STRIP FOR EXPOSED UNISTRUT.
3. THE CABINET SHALL BE PLACED ON INTERIOR WALLS ONLY.
4. SEISMIC DESIGN CRITERIA:
SDS= 1.194g MAXIMUM Ip = 1.5 MAXIMUM
5. NON-BEARING WALLS ARE NOT SUPPORTING THE FLOOR OR ROOF MEMBERS ABOVE. IF
CONDITION NOT KNOWN USE DETAILS FOR LOAD BEARING WALLS.
6. SHEET METAL SCREWS SHALL BE ELCO DRIL-FLEX SELF DRILLING STRUCTURAL SCREW.
T/ EXISTING FLOOR
EXIST WALL STUD BEYOND 350S162-54
(50 ksi) MIN @ 16" OC MAX, TYP
VERIFY IN FIELD
EXISTING WALL SHEATHING NOT SHOWN
FOR CLARITY.
BOT OF EXISTING
STR FLOOR/ ROOF MEMBER
P3000 W/ SELF DRILLING HEX
HEAD 1/4"Ø SHEET METAL
SCREWS W/ FLAT WASHER
INTO 3 EXISTING STUD, TYP
5/16"Ø BOLTS IN EACH MOUNTING
KEYHOLE TO UNISTRUT W/
SPRING NUTS OR EQUAL AND
LOCK WASHERS
(4 MIN, TOTAL NO PER MFR) TYP
EXIST WALL BOT TRACK
CABINET HINGE, TYP
LOADED CABINET WEIGHT
= 450 LBS MAX
D9
S-542
F6
S-542
EXISTING SLOTTED
DEFLECTION TRACK
LOCATE ANCHOR EQUAL
DISTANCE BETWEEN
EXISTING STUDS ON SIDE
WITH CABINET HINGE
EQ EQ
'-0
M
A X
BOT OF EXISTING
STR FLOOR/ ROOF MEMBER
T/ EXISTING FLOOR
MAX
2' - 6"
CABINET PER ELEV
CABINET ANCHORAGE TO
UNISTRUT PER ELEV
EXISTING WALL STUD
PER ELEVATION
P3300
CONN TO EXIST WALL
PER ELEV, TYP
EXIST SLOTTED
DEFLECTION TRACK
M
IN
CABINET BELOW PER ELEV
P3300 W/ CONNECTION TO
EXISTING WALL PER ELEV
CABINET ANCHORAGE
TO UNISTRUT PER ELEV
EXISTING WALL STUD, TYP
EXISTING WALL FINISH
WSP USA Inc.
Suite 300
Federal Way, WA 98003-2600
TEL: (206) 431-2300
FAX: (206) 431-2250
33301 9th Avenue South
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
S-542
TYPICAL DETAILS-CABINET TO
CFS FRAMED WALLSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
581-22-700
09/03/2025 CH JKM
100% CONSTRUCTION
DOCUMENTS
1 1/2" = 1'-0" D1
ELEVATION - LOAD BEARING CFS FRAMED WALL
1 1/2" = 1'-0"
D4
SECTION - LOAD BEARING CFS FRAMED WALL
1 1/2" = 1'-0" F1
PLAN - LOAD BEARING CFS FRAMED WALL
3" = 1'-0"
F4
DETAIL
1 1/2" = 1'-0" D6
ELEVATION - NON-LOAD BEARING CFS FRAMED WALL
1 1/2" = 1'-0"
D9
SECTION - NON-LOAD BEARING CFS FRAMED WALL
1 1/2" = 1'-0" F6
PLAN - NON-LOAD BEARING CFS FRAMED WALL
Revisions: Date: 047 OF 693
T/ EXISTING FLOOR
EXIST WALL STUD 2x4 MIN @
16" OC MAX BEYOND VERIFY
IN FIELD, TYP
EXIST WALL SHEATHING NOT
SHOWN FOR CLARITY
BOT OF EXISTING
STR FLOOR/ ROOF MEMBER
P1000H3
P1026 EA SIDE W/ 1/2" DIA.
THROUGH BOLT TO P9000 AND TO
P1000H3 W/ 1/2" DIA. BOLT W/
CHANNEL & NUT TYP
P9000, TYP
P1000H3 W/ 3/8"Ø LAG SCREWS
W/ 2" EMBED IN EXISTING SILL
PLATE W/ FLAT WASHER AT 3
LOCATIONS
EXIST WALL SILL PL
5/16"Ø BOLTS IN EACH
MOUNTING KEYHOLE TO
UNISTRUT W/ SPRING NUTS OR
EQUAL AND LOCK WASHERS
(4 MIN, TOTAL NO PER MFR), TYP
P1000H3 W/ P1026 EA END T&B W/
1/2"Ø BOLT W/ CHANNEL & NUT
LOADED CABINET WEIGHT
= 450 LBS MAX
P1000H3
D4
S-543
F1
S-543
S-543 F4
S-543
F4 OPP
NOTES:
1. UNISTRUT TO BE UNPUNCHED UNLESS NOTED OTHERWISE ON THE DETAILS.
2. PROVIDE UNISTRUT ENDCAPS AND CHANNEL CAPPING STRIP FOR EXPOSED UNISTRUT.
3. THE CABINET SHALL BE PLACED ON INTERIOR WALLS ONLY. CONTRACTOR TO VERIFY EXISTING
WALL STUD SIZE AND GRADE.
4. PROVIDE 3/16" DIA. PILOT HOLE FOR 3/8" DIA. LAG SCREWS.
5. SEISMIC DESIGN CRITERIA:
SDS= 1.194g MAXIMUM Ip = 1.5 MAXIMUM
M A
X
7" M
IN
3/8"Ø LAG SCREWS W/ 2" EMBED INTO
3 EXISTING STUDS W/ FLAT WASHER,
CTR SCREWS ON EA EXIST STUD
EXIST WALL TOP PL
3" MIN
P1026 EA SIDE W/ 1/2" DIA. THROUGH
BOLT TO P9000 AND TO P1000H3 W/
1/2" DIA. BOLT W/ CHANNEL & NUT TYP
9' -0
M
A X
BOT OF EXISTING
STR FLOOR/ ROOF MEMBER
T/ EXISTING FLOOR
MAX
2' - 6"
P1000H3 W/ CONNECTION TO
EXISTING BOTTOM PL PER
ELEVATION
EXIST WALL SILL PL
AVOID CONFLICTS W/
EXIST CONNECTORS
CABINET PER ELEV
NO GAP BTWN P9000 AND
EXIST WALL FINISH
P9000 W/ CONNECTION TO T&B
PER ELEV
CABINET ANCHORAGE TO
UNISTRUT PER ELEV
EXISTING WALL STUD
PER ELEVATION
P1000 PER ELEV
P1000H3 W/ CONN TO EXIST
STUD & P9000 PER ELEVATION
P1000H3 MUST
BEAR ON FLOOR
M
IN
CABINET BELOW PER ELEV
P1000H3 W/ CONN TO MINIMUM
3 EXISTING STUDS PER ELEV
CABINET ANCHORAGE
TO UNISTRUT PER ELEV
EXIST WALL STUD, TYP
P9000 W/ CONN TO
T&B PER ELEV
EXIST WALL FINISH
P1000H3
P3300HS WITH (2) 1/2" DIA.
THRU BOLT TO P9000
P9000
P1026 EA END T&B W/ 1/2"Ø
BOLT WITH CHANNEL & NUT
NOTES:
1. UNISTRUT TO BE UNPUNCHED UNLESS NOTED OTHERWISE ON THE DETAILS.
2. PROVIDE UNISTRUT ENDCAPS AND CHANNEL CAPPING STRIP FOR EXPOSED UNISTRUT.
3. THE CABINET SHALL BE PLACED ON INTERIOR WALLS ONLY. CONTRACTOR TO VERIFY EXISTING WALL STUD SIZE AND GRADE.
4. PROVIDE 3/16" DIA. PILOT HOLE FOR 3/8" DIA. LAG SCREWS.
5. SEISMIC DESIGN CRITERIA:
SDS= 1.194g MAXIMUM Ip = 1.5 MAXIMUM
6. NON-BEARING WALLS ARE NOT SUPPORTING THE FLOOR OR ROOF MEMBERS ABOVE. IF CONDITION NOT KNOWN USE DETAILS
FOR LOAD BEARING WALLS.
T/ EXISTING FLOOR
EXIST WALL STUD BEYOND
2x4 MIN @ 16" OC MAX, TYP
VERIFY IN FIELD
EXISTING WALL SHEATHING
NOT SHOWN FOR CLARITY
BOT
OF EXISTING
STR FLOOR/ ROOF MEMBER
P3000 W/ 3/8"Ø LAG SCREWS W/ 2"
EMBED INTO 3 EXISTING STUDS
W/ FLAT WASHER,
CTR ON EA EXIST STUD
5/16"Ø BOLTS IN EACH MOUNTING
KEYHOLE TO UNISTRUT W/
SPRING NUTS OR EQUAL AND
LOCK WASHERS
(4 MIN, TOTAL NO PER MFR), TYP
EXIST WALL SILL PL
CABINET HINGE, TYP
LOADED CABINET
WEIGHT = 450 LBS MAX
D9
S-543
F6
S-543
EQEQ
LOCATE ANCHOR EQUAL
DISTANCE BETWEEN
EXISTING STUDS ON SIDE
WITH CABINET HINGE
9' -0
M
A X
T/ EXISTING FLOOR
MAX
2' - 6"
CABINET PER ELEV
CABINET ANCHORAGE TO
UNISTRUT PER ELEV
EXISTING WALL STUD
PER ELEVATION
P3300
CONN TO EXIST WALL
PER ELEV, TYP
GAP OR VERT SLOT CONN
BOT OF EXISTING
STR FLOOR/ ROOF MEMBER
M
IN
CABINET BELOW PER ELEV
P3300 W/ CONN TO
MINIMUM 3 EXISTING
STUDS PER ELEV
CABINET ANCHORAGE
TO UNISTRUT PER ELEV
EXIST WALL STUD, TYP
EXIST WALL FINISH
WSP USA Inc.
Suite 300
Federal Way, WA 98003-2600
TEL: (206) 431-2300
FAX: (206) 431-2250
33301 9th Avenue South
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
S-543
TYPICAL DETAILS-CABINET TO
WOOD FRAMED WALLSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
581-22-700
09/03/2025 CH JKM
100% CONSTRUCTION
DOCUMENTS
1 1/2" = 1'-0" D1
ELEVATION - LOAD BEARING WOOD FRAMED WALL
1 1/2" = 1'-0"
D4
SECTION - LOAD BEARING WOOD FRAMED WALL
1 1/2" = 1'-0" F1
PLAN - LOAD BEARING WOOD FRAMED WALL
3" = 1'-0"
F4
ELEVATION
1 1/2" = 1'-0" D6
ELEVATION - NON-LOAD BEARING WOOD FRM WALL
1 1/2" = 1'-0"
D9
SECTION - NON-LOAD BEARING WOOD FRM WALL
1 1/2" = 1'-0" F6
PLAN - NON-LOAD BEARING WOOD FRAMED WALL
Revisions: Date: 048 OF 693
HILTI KWIK HUS-EZ SCREW
ANCHORS 3/8"Ø W/ 3 1/2" MIN
EMBEDMENT IN TO EXISTING
CONCRETE (MINIMUM F'c = 3000 psi)
IN EACH MOUNTING KEYHOLE,
(TOTAL 6)
2'
M A
X
LOADED CABINET
WEIGHT = 450 LBS MAX
EXIST CONC WALL,
6" THICK, MIN
NOTES:
1. ANCHORS INTO CONCRETE TO BE EITHER STAINLESS STEEL OR GALVANIZED.
2. DO NOT DRILL THROUGH EXISTING REINFORCEMENT
EDGE DISTANCE
8" MIN
EDGE OF EXIST
CONC WALL
WHERE OCCURS
HILTI KWIK HUS-EZ SCREW
ANCHORS 3/8"Ø W/ 3" MIN
EMBEDMENT IN GROUTED CMU
BLOCK (TOTAL 6)2'
M
A X
LOADED CABINET WEIGHT
= 450 LBS MAX
EXIST CMU WALL,
8" THICK, MIN
NOTES:
1. USE HOLLOW CMU WALL DETAIL IF NOT ALL ANCHORS INSTALLED IN GROUTED CELLS.
2. REFER TO ICC-ESR REPORT SPECIFIC TO THE ANCHOR FOR ACCEPTABLE INSTALLATION.
3. DO NOT DRILL THROUGH EXISTING REINFORCEMENT.
EDGE DISTANCE
8" MIN
2'
M A
X
LOADED CABINET WEIGHT
= 450 LBS MAX
EXIST CMU WALL,
8" THICK, MIN
NOTES:
1. THIS DETAIL IS USED WHEN AT LEAST ONE ANCHOR IS
INSTALLED IN A HOLLOW CELL.
2. REFER TO ICC-ESR REPORT SPECIFIC TO THE ANCHOR
FOR ACCEPTABLE INSTALLATION.
3. DO NOT DRILL THROUGH EXISTING REINFORCEMENT.
THREADED ROD (GR. 36) 3/8"Ø W/
4" MIN EMBEDMENT IN EXIST
HOLLOW CMU BLOCK W/ HILTI HIT-
HY 270 (ICC-ESR 4143) & SCREEN
TUBES OR EQUAL (TOTAL 8)
EDGE DISTANCE
8" MINP1000H3
5/16"Ø BOLTS IN EACH
MOUNTING KEYHOLE TO
UNISTRUT W/ SPRING NUTS OR
EQUAL AND LOCK WASHERS,
TYP (TOTAL 6)
F5
S-544
HILTI KWIK HUS-EZ SCREW
ANCHORS 3/8"Ø W/ 4" MIN
EMBEDMENT IN GROUTED
CELLS
T/ EXISTING FLOOR
MAX
2' - 6"
CABINET PER PLANCABINET ANCHORAGE TO
UNISTRUT PER F4/S-544, TYP
EXISTING CMU WALL PER PLAN
BOT OF EXISTING
STR FLOOR/ ROOF MEMBER
M
INP1000H3 W/ ANCHORS TO
CMU PER F4/S-544, TYP
8" M
IN
8" M
IN
WSP USA Inc.
Suite 300
Federal Way, WA 98003-2600
TEL: (206) 431-2300
FAX: (206) 431-2250
33301 9th Avenue South
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
S-544
TYPICAL DETAILS-CABINET TO
CONCRETE AND CMU WALLSPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
581-22-700
09/03/2025 CH JKM
100% CONSTRUCTION
DOCUMENTS
1 1/2" = 1'-0" F1
PLAN AT EXIST CONC WALL
1 1/2" = 1'-0"
F3
PLA AT GROUTED CELLS OF EXIST CMU WALL
1 1/2" = 1'-0" F4
PLAN AT HOLLOW CELLS OF EXIST CMU WALL
1 1/2" = 1'-0"
F5
SECTION AT HOLLOW CELLS OF EXIST CMU WALL
Revisions: Date: 049 OF 693
AB
ABA
AC(T)
ACM
ACW
ADA
ADJ
A/E
AF
AFF
AGG
ALT
ALUM
APPROX
ARCH
ASPH
A/V
BARR
BATH
BB
BLDG
BLK
BLKG
BLW
BM
BMTU
BO
BOC
BOS
BRC
BRKT
BRNG
BTM
BTWN
CAB
CC
CD
CJ
CLG
CLR
CMU
CO
COL
COMP
CONC
CONN
CONST
CONT
COORD
COR
CORR
CS
CT
CTR
CV
AND
ANGLE
AT
CENTERLINE
DEGREES
NUMBER
ANCHOR BOLT
ARCHITECTURAL BARRIERS ACT
ACOUSTICAL CEILING (TILE)
ASBESTOS CONTAINING MATERIAL
ACOUSTICAL WALL
AMERICANS W/ DISABILITIES ACT
ADJACENT
ARCHITECT/ENGINEER
ACCESS FLOOR
ABOVE FINISH FLOOR
AGGREGATE
ALTERNATE
ALUMINUM
APPROXIMATELY
ARCHITECT(URAL)
ASPHALT
AUDIO / VIDEO
BARRIER
BATHROOM
BACKER BOARD
BUILDING
BLOCK
BLOCKING
BELOW
BEAM
BONE MARROW TRANSPLANT UNIT
BOTTOM OF
BOTTOM OF CURB
BOTTOM OF SLAB
BRACE, BRACING
BRACKET
BEARING
BOTTOM
BETWEEN
CABINET
CONTRACTOR FURN, CONTRACTOR INST
CONSTRUCTION/CONTRACT DOCUMENTS
CONTROL JOINT
CEILING
CLEAR(ANCE)
CONCRETE MASONRY UNIT
CONTRACTING OFFICER
COLUMN
COMPOSITION
CONCRETE
CONNECTION
CONSTRUCTION
CONTINUOUS
COORDINATE
CONTRACTING OFFICER REPRESENTATIVE
CORRIDOR
CONCRETE SEALER
CERAMIC TILE
CENTER
CONTRACTOR FURNISHED, VA INSTALLED
HDR
HDWE
HM
HORZ
HPDL
HR
HT
HVAC
ICRA
ID
ILSM
INCL
INST
INSUL
INT
JT
KV
LAM
LAV
LCM
LT
MAT
MAX
MDF
MECH
MEP
MFR
MIN
MISC
MOD
MTL
N N/A
NEG
NO.
NOM
NTS
O.C.
OPNG
OPP
OPT
OVHD
P
PCONC
PCRA
PL
PLAM
PLY(WD)
PNL
PR
PRFB
PS
PT
PTN(S)
PVMT
QTY
HEADER
HARDWARE
HOLLOW METAL
HORIZONTAL
HIGH PRESSURE DECORATIVE LAM
HOUR
HEIGHT
HEATING, VENTILATION & AIR CONDITIONING
INFECTIOUS CONTROL RISK ASSESSMENT
INSIDE DIAMETER OR DIM
INTERIM LIFE SAFETY MEASURES
INCLUDE(D,ING)
INSTALL
INSULATION
INTERIOR
JOINT
KILOVOLT
LAMINATE(D)
LAVATORY
LEAD CONTAINING MATERIAL(S)
LIGHT
MATERIAL(S)
MAXIMUM
MEDIUM-DENSITY FIBREBOARD
MECHANIC(AL)
MECHANICAL, ELECTRICAL, PLUMBING
MANUFACTURE(R)
MINIMUM
MISCELLANEOUS
MODIFIED
METAL
NORTH
NOT APPLICABLE
NEGATIVE
NUMBER
NOMINAL
NOT TO SCALE
ON CENTER(S)
OPENING
OPPOSITE
OPTION(AL)
OVERHEAD
PAINT
PRECAST CONCRETE
PRE-CONSTRUCTION RISK ASSESSMENT
PLATE
PLASTIC LAMINATE
PLYWOOD
PANEL
PAIR
PREFABRICATED
PLASTIC
PRESSURE TREATED
PARTITION(S)
PAVEMENT
QUANTITY
RAD
RCP
REF
REINF
REP
REQ(s,(')D)
RESIL
REV
RF
RM
RMV
RO
S
SCHED
SD
SECT
SF
SFRM
SHG
SHT(G)
SIM
SM
SOW
SPEC
SQ
SS
ST
STDG
STL
STOR
STRUCT
SUSP
SV
SYS
TEMP
T&G
THK
THRESH
TOC
TOS
TPH
TRANS
TS
TYP
UON
VA
VAR
VB
VC
VERT
VIF
VV
W W/
WD
WDW
WGHT
W/O
WP
WR
RADIUS
REFLECTED CEILING PLAN
REFERENCE
REINFORCE(D,ING)
REPRESENTATIVE
REQUIRE(D,S,MENT(S))
RESILIENT
REVERSE
RADIO FREQUENCY / ROOF
ROOM
REMOVE
ROUGH OPENING
SOUTH
SCHEDULE
SCHEMATIC DESIGN
SECTION
SQUARE FEET
SPRAY APPLIED FIRE-RESISTIVE MATERIAL
SHINGLES
SHEET (SHEATHING)
SIMILAR
SEAM
SCOPE OF WORK
SPECIFICATION
SQUARE
STAINLESS STEEL
STAIN
STANDING
STEEL
STORAGE
STRUCTURAL