S02 - ATT 25 - 581-22-700 - 100 Drawings Part-23 of 24.pdf

PDF 19 MB Posted

Attached to
EHRM Huntington VAMC 581-22-700 Construct Infrastructure Upgrades
Solicitation number
36C77626R0025
Issued by

About this file

This document is a set of construction drawings for telecommunications infrastructure upgrades at the VA Medical Center in Huntington, West Virginia. The project, identified as EHRM Infrastructure 581-22-700, involves enlarging telecommunications plans across multiple buildings and floor levels at 1540 Spring Valley Drive, Huntington, WV 25704-9300. The drawings are prepared by SPEES Design Build and are issued at 100% Construction Documents phase as of September 3, 2025.

The telecommunications work encompasses multiple buildings (01A, 01S, 01W, 02, 03, 04, and 05) across various levels, including ground floors, basements, and upper levels. Key work includes removing and replacing Category 6 and below cabling with CAT6A ports and cables; demolishing and reinstalling telecommunications outlets with specified port quantities; routing fiber-optic backbone cabling with diverse A-side and B-side pathways; installing telecommunications rooms with fire-rated plywood backboards; providing pull boxes at 100-foot intervals per ANSI/TIA-569; segregating data cabling from security, fire alarm, and nurse call systems using appropriate raceways and cable trays with tray dividers; and providing access control panels and related connections for physical access control systems. The drawings specify equipment salvage requirements, field verification of existing devices, fire-rating coordination with architectural drawings, and conduit sizing per code. Multiple telecommunications rooms (TRs) and telecommunications closets are shown with data racks, terminal boards, fire alarm panels, and fiber optic panels requiring installation and configuration.

View the file

Other files

File Type Posted
S06 - 36C77626R0025 0008.pdf PDF
S06 - Amendment 0008 - ATT 7 - 02EP100B - ELECTRICAL 20260413.pdf PDF
S06 - Amendment 0008 - ATT 11 - Burn Permit.pdf PDF
S06 - Amendment 0008 - ATT 10 - 260508 - Sheet AD103-1B Data Center Phase 1B Demo Roof update.pdf PDF
S06 - Amendment 0008 - ATT 9 - 260508 - Sheet AD101-1B Data Center Phase 1B Demo Floor Plan update.pdf PDF
S06 - Amendment 0008 - ATT 1 - TechQuestionsVAresponses Final Set - Huntington EHRM IU.pdf PDF
S06 - Amendment 0008 - ATT 14 - Energized Electrical Work Permit.pdf PDF
S06 - Amendment 0008 - ATT 5 - ELECTRICAL 2026.04.13.pdf PDF
S06 - Amendment 0008 - ATT 6 - 01WEP100G - ELECTRICAL 20260413.pdf PDF
S06 - Amendment 0008 - ATT 3 - Civil OSP Redesign-signed.pdf PDF
S06 - Amendment 0008 - ATT 12 - Environmental Report Huntington WV.pdf PDF
S06 - Amendment 0008 - ATT 8 - 260508 - Sheet 01S-AE452 TR Tower 4 Wall sections update.pdf PDF
S06 - Amendment 0008 - ATT 13 - Hot Tapping Permit.pdf PDF
S06 - Amendment 0008 - ATT 2 - UPDATED SHEETS.pdf PDF
S06 - Amendment 0008 - ATT 4 - Structural Set 04-21-2026.pdf PDF
S06 - 36C77626R0025 0007.pdf PDF
S06 - Amendment 0007 - ATT 1 - TechQuestionsVAresponses Partial 4 - Huntington EHRM IU.pdf PDF
S06 - Amendment 0007 - ATT 3 - Lift Planning.pdf PDF
S06 - Amendment 0007 - ATT 2 - Geotechnical Report.pdf PDF
S06 - Amendment 0007 - ATT 5 - Appendix A - PFC FPT.pdf PDF
S06 - Amendment 0007 - ATT 4 - 01 00 00 - GENERAL REQUIREMENTS_A1.pdf PDF
S06 - Amendment 0007 - ATT 6 - Crane lift Info.pdf PDF
S06 - 36C77626R0025 0006.pdf PDF
S06 - Amendment 0006 - ATT 1 - TechQuestionsVAresponses Partial 3 - Huntington EHRM IU.pdf PDF
S06 - 36C77626R0025 0005.pdf PDF
S06 - Amendment 0004 - ATT 2 - FAR 52.222-90 ADDRESSING DEI DISCRIMINATION BY FEDERAL CONTRACTORS - APR 2026.pdf PDF
S06 - Amendment 0004 - ATT 1 - TechQuestionsVAresponses Partial 2 - Huntington EHRM IU.pdf PDF
S06 - 36C77626R0025 0004.pdf PDF
S06 - Amendment 0003 - ATT 2 - TechQuestionsVAresponses Partial - Huntington EHRM IU.pdf PDF
S06 - 36C77626R0025 0003.pdf PDF
S06 - 36C77626R0025 0002.pdf PDF
S06 - Amendment 0001 - ATT 1 - Site Visit In-Sheet - Huntington EHRM IU.pdf PDF
S06 - 36C77626R0025 0001.pdf PDF
S02 - ATT 28 - 581-22-700 - FLS Compliance Letter.pdf PDF
S02 - ATT 3 - 581-22-700 - 100 Drawings Part-1 of 24.pdf PDF
S02 - ATT 15 - 581-22-700 - 100 Drawings Part-13 of 24.pdf PDF
S02 - ATT 30 - 581-22-700 - 100 Commissioning Plan.pdf PDF
S02 - ATT 20 - 581-22-700 - 100 Drawings Part-18 of 24.pdf PDF
S02 - ATT 24 - 581-22-700 - 100 Drawings Part-22 of 24.pdf PDF
S02 - ATT 1 - 581-22-700 - 100 Specifications Part-1 of 2.pdf PDF
S02 - ATT 10 - 581-22-700 - 100 Drawings Part-8 of 24.pdf PDF
S02 - ATT 12 - 581-22-700 - 100 Drawings Part-10 of 24.pdf PDF
S02 - ATT 23 - 581-22-700 - 100 Drawings Part-21 of 24.pdf PDF
S02 - ATT 31 - 581-22-700 - Topographic Survey TR Tower 3.pdf PDF
S02 - ATT 16 - 581-22-700 - 100 Drawings Part-14 of 24.pdf PDF
S02 - ATT 21 - 581-22-700 - 100 Drawings Part-19 of 24.pdf PDF
S02 - ATT 34 - HEFP SEP Design Alerts 1-9 and 11-16.pdf PDF
S02 - ATT 29 - 581-22-700 - Geotechnical Report - W24044 - VA Duct Bank 11.21.24.pdf PDF
S02 - ATT 14 - 581-22-700 - 100 Drawings Part-12 of 24.pdf PDF
S02 - ATT 27 - 581-22-700 - Asbestos locations.xlsx XLSX spreadsheet
Show 40 more

Latest 50 of 68 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AREA SHOWN

S T

ACCESS POWER

CONTROLLER

PANEL

TELEPHONE

TERMINAL

BOARDS

FIRE ALARM

PANEL

FIRE ALARM

SUB PANEL

DATA RACK 1

ANTE

T3-00X

105 SF

S T

ACCESS POWER

CONTROLLER

PANEL

FIRE ALARM

PANEL

FIRE ALARM

SUB PANEL

TELEPHONE

TERMINAL

BOARDS

ANTE

T3-00X

105 SF

GB123

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:4

:2 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

G R

O U

N D

F L

O O

R .r v t

01ATN400G

BLDG 01A - LEVEL 00G - ENLARGED

TELECOMMUNICATIONS PLANS

01A

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

KEY PLAN

GENERAL NOTES

PROJECT

NORTH

1/2" = 1'-0"01ATN100G

1 RM GB123 - DEMOLITION FLOOR PLAN

1/2" = 1'-0"01ATN100G

2 RM GB123 - TELECOMMUNICATIONS PLAN1'0 2' 4'

PROJECT

NORTH

2'0 4' 8'

PROJECT

NORTH

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE RACEWAYS TO EXTEND TO

ASSOCIATED TR AS REQUIRED.

5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO

REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,

MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE

INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY

FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

6. WHERE DATA OUTLETS ARE PROVIDED AND EXISTING DATA OUTLET CURRENTLY

DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW BACKBOX TO ACCESSIBLE

CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO TR VIA CABLE

TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM OUTLET TO TR AS

REQUIRED.

7. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

8. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

9. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

10. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL SYSTEMS

CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS; ADDITIONALLY,

CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS REQUIRED TO

SEGREGATE SYSTEMS FROM ONE ANOTHER.

11. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD

BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS

REQUIRED.

KEY NOTES

EXISTING EQUIPMENT SHALL BE SALVAGED TO VA. ASSOCIATED RACEWAYS AND

CABLING SHALL BE DEMOLISHED BACK TO SOURCE.

Revisions: Date: 627 OF 693

2B115

UNLABELED PANEL

TELEPHONE TERMINAL

BOARD

DATA RACK

TELE

2B115

28 SF

TELE

2B115

28 SF

UNLABELED PANEL

TELEPHONE TERMINAL

BOARD

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:2

:4 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

L E

V E

L

.r v t

01ATN402

BLDG 01A - LEVEL 02 - ENLARGED

TELECOMMUNICATIONS PLANS

01A

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

KEY NOTES

KEY PLAN

GENERAL NOTES

PROJECT

NORTH

1/2" = 1'-0"01ATN102

1 RM 2B115 - DEMOLITION FLOOR PLAN

1/2" = 1'-0"01ATN102

2 RM 2B115 - TELECOMMUNICATIONS PLAN1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.

5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO

REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,

MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE

INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY

FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

6. WHERE DATA OUTLETS ARE PROVIDED AND EXISTING DATA OUTLET CURRENTLY

DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW BACKBOX TO ACCESSIBLE

CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO TR VIA CABLE

TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM OUTLET TO TR AS

REQUIRED.

7. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

8. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

9. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

10. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL SYSTEMS

CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS; ADDITIONALLY,

CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS REQUIRED TO

SEGREGATE SYSTEMS FROM ONE ANOTHER.

11. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD

BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS

REQUIRED.

Revisions: Date:

1 EXISTING EQUIPMENT SHALL BE SALVAGED TO VA. ASSOCIATED RACEWAYS AND

CABLING SHALL BE DEMOLISHED TO SOURCE.

U

TELEPHONE TERMINAL

BOARDS

DATA RACK,

TYP.

TEL-COMM.

3B120

26 SF

U

TELEPHONE TERMINAL

BOARDS

TEL-COMM.

3B120

26 SF

3B120

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/3

/2

:4

:1

A M

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

L E

V E

L

.r v t

01ATN403

BLDG 01A - LEVEL 03 - ENLARGED

TELECOMMUNICATIONS PLANS

01A

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

KEY PLAN

GENERAL NOTES

PROJECT

NORTH

1/2" = 1'-0"01ATN103

1 RM 3B120 - DEMOLITION FLOOR PLAN

1/2" = 1'-0"01ATN103

2 RM 3B120 - TELECOMMUNICATIONS PLAN

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS

TO EXTEND TO ASSOCIATED TR AS REQUIRED.

5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO

REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,

MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE

INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY

FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

6. WHERE DATA OUTLETS ARE PROVIDED AND EXISTING DATA OUTLET CURRENTLY

DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW BACKBOX TO ACCESSIBLE

CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO TR VIA CABLE

TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM OUTLET TO TR AS

REQUIRED.

7. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

8. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

9. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

10. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL

SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;

ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS

REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.

11. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD

BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS

REQUIRED.

KEY NOTES

1 EXISTING EQUIPMENT SHALL BE SALVAGED TO VA. ASSOCIATED RACEWAYS AND

CABLING SHALL BE DEMOLISHED BACK TO SOURCE.

Revisions: Date:

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

W

360°

C

X

W

S

X

AREA SHOWN

V

TYP.

V

V

TYP.

TN501

DATA

RACK

TYP.

TN501

TR

BB100B-1S

106 SF

V

TN502

C

DATA

RACK

01S-BB100B-1SB

01S-BB100B-1SA

TN503

ACCESS CONTROL PANEL

"01S-ACP-BB100B"

TR

BB100B-1S

106 SF

SECONDARY

BONDING BUSBAR

BB100B-1S

IRM STORAGE

BB100A-1S

475 SF

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:4

:4 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

B A

S E

M E

N T

.r v t

01STN400Ba

BLDG 01S - LEVEL 00B - ENLARGED

TELECOMMUNICATIONS PLANS

01S

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

KEY PLAN

GENERAL NOTES

PROJECT

NORTH

1/2" = 1'-0"01STN100B

1 RM BB100A-1S - DEMOLITION FLOOR PLAN

1/2" = 1'-0"01STN100B

4 RM BB100B-1S - OVERHEAD PLAN

1/2" = 1'-0"01STN100B

2 RM BB100B-1S - TELECOMMUNICATIONS PLAN1'0 2' 4'

PROJECT

NORTH

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS

TO EXTEND TO ASSOCIATED TR AS REQUIRED.

5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO

REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,

MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE

INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY

FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

6. WHERE DATA OUTLETS ARE PROVIDED AND EXISTING DATA OUTLET CURRENTLY

DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW BACKBOX TO ACCESSIBLE

CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO TR VIA CABLE

TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM OUTLET TO TR AS

REQUIRED.

7. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

8. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

9. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

10. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL

SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;

ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS

REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.

11. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD

BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS

REQUIRED.

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

KEY NOTES

EXISTING EQUIPMENT SHALL BE DEMOLISHED. ASSOCIATED RACEWAYS AND

CABLING SHALL BE DEMOLISHED BACK TO SOURCE.

PROVIDE FIRE STOP SLEEVES AS REQUIRED. SIDE 'A' AND SIDE 'B' SLEEVES SHALL BE

SEPARATED BY AT LEAST 10-FT.

WIRE BASKET CABLE TRAY.

PROVIDE (1) CAT6A CABLE FOR ADDED SECURITY CAMERA.

PROVIDE (2)-CARD ACCESS CONTROL PANEL TO SERVE ALL PACS DOOR SECURITY

EQUIPMENT FOR THIS TR ROOM. PROVIDE ALL REQUIRED CONNECTIONS,

PROGRAMMING, POWER SUPPLIES, AND COMPONENTS TO PROVIDE A COMPLETE

AND FULLY FUNCTIONAL SYSTEM. REFERENCE SPECIFICATION "28 13 00 - PHYSICAL

ACCESS CONTROL SYSTEM" FOR ADDITIONAL INFORMATION.

RACK NOT IN CONTRACT.

Revisions: Date: 630 OF 693

X

TELEPHONE

TERMINAL

BOARDS

SIGNAL BOOSTER

DATA RACK 1

FIRE ALARM

SUB PANEL

FACP MODULES

TELE

BB112

30 SF

ELEC

BB110D

64 SF

TELECOMMUNICATIONS

ENCLOSURE

X

FIRE ALARM

SUB PANEL

FACP MODULES

TELEPHONE

TERMINAL

BOARDS

SIGNAL BOOSTER TELE

BB112

30 SF

ELEC

BB110D

64 SF

TELECOMMUNICATIONS

ENCLOSURE

BB112

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:4

:5 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

B A

S E

M E

N T

.r v t

01STN400Bb

BLDG 01S - LEVEL 00B - ENLARGED

TELECOMMUNICATIONS PLANS

01S

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

KEY PLAN

GENERAL NOTES

PROJECT

NORTH

1/2" = 1'-0"01STN100B

1 RM BB112 & BB110D - DEMOLITION FLOOR PLAN

1/2" = 1'-0"01STN100B

2 RM BB112 & BB110D - TELECOMMUNICATIONS PLAN1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS

TO EXTEND TO ASSOCIATED TR AS REQUIRED.

5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO

REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,

MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE

INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY

FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

6. WHERE DATA OUTLETS ARE PROVIDED AND EXISTING DATA OUTLET CURRENTLY

DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW BACKBOX TO ACCESSIBLE

CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO TR VIA CABLE

TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM OUTLET TO TR AS

REQUIRED.

7. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

8. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

9. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

10. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL

SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;

ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS

REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.

11. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD

BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS

REQUIRED.

EXISTING EQUIPMENT SHALL BE SALVAGED TO VA. ASSOCIATED RACEWAYS AND

CABLING SHALL BE DEMOLISHED BACK TO SOURCE.

KEY NOTES

Revisions: Date: 631 OF 693

W

360°

C

W

X X

S

W

X

S

C

W

X

360°

AREA SHOWN

T4-00G

T1-00G

P

TYP.

TN501

TYP.

TN501

TR TOWER 4

T4-00G

166 SF

DATA RACK, TYP

BUS DUCT

"01S-BD-TWR4B"

BUS DUCT

"01S-BD-TWR4A"

01S-BDCB-TWR4A

01S-BDCB-TWR4B

P

C

TN502

01S-T4-00GA

01S-T4-00GB

TR TOWER 4

T4-00G

166 SF

SECONDARY

BONDING BUSBAR

TN503

ACCESS CONTROL

PANEL "01S-ACP-T400G"

DATA RACK, TYP

BUS DUCT

"01S-BD-TWR4B"

BUS DUCT

"01S-BD-TWR4A"

CABLE TAP BOX

BUS DUCT CIRCUIT BREAKER

01S-BDCB-TWR4B

01S-BDCB-TWR4A

BUS DUCT CIRCUIT BREAKER

CABLE TAP BOX

X

TYP.

TN501

TYP.

TN501

DATA RACK,

TYP.

TR TOWER 1

T1-00G

169 SF

BUSDUCT

"01S-BD-TWR1B"

BUSDUCT

"01S-BD-TWR1A"

BUS DUCT CIRCUIT BREAKER

01S-BDCB-TWR1B

01S-T1-00GB

01S-BDCB-TWR1A

01S-T1-00GA

BUS DUCT CIRCUIT BREAKER

X

TN502

C

01S-T1-00GB

01S-T1-00GA

SECONDARY

BONDING BUSBAR

TN503

ACCESS CONTROL

PANEL "01S-ACP-T100G"

DATA RACK,

TYP.

TR TOWER 1

T1-00G

169 SF

BUSDUCT

"01S-BD-TWR1B"

BUSDUCT

"01S-BD-TWR1A"

01S-BDCB-TWR1A

BUS DUCT CIRCUIT BREAKER

CABLE TAP BOX

CABLE TAP BOX

BUS DUCT CIRCUIT BREAKER

01S-BDCB-TWR1B

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:4

:4 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

G R

O U

N D

F L

O O

R .r v t

01STN400Ga

BLDG 01S - LEVEL 00G - ENLARGED

TELECOMMUNICATIONS PLANS

01S

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

KEY PLAN

GENERAL NOTES

PROJECT

NORTH

1/2" = 1'-0"01STN100G

4 RM T4-00G - OVERHEAD PLAN

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1/2" = 1'-0"01STN100G

2 RM T4-00G - TELECOMMUNNICATIONS PLAN

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE RACEWAYS TO EXTEND TO

ASSOCIATED TR AS REQUIRED.

5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO

REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,

MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE

INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY

FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

6. WHERE DATA OUTLETS ARE PROVIDED AND EXISTING DATA OUTLET CURRENTLY

DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW BACKBOX TO ACCESSIBLE

CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO TR VIA CABLE

TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM OUTLET TO TR AS

REQUIRED.

7. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

8. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

9. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

10. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL SYSTEMS

CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS; ADDITIONALLY,

CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS REQUIRED TO

SEGREGATE SYSTEMS FROM ONE ANOTHER.

11. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD

BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS

REQUIRED.

KEY NOTES

PROVIDE FIRE STOP SLEEVES AS REQUIRED. SIDE 'A' AND SIDE 'B' SLEEVES SHALL BE

SEPARATED BY AT LEAST 10-FT.

WIRE BASKET CABLE TRAY.

PROVIDE (1) CAT6A CABLE FOR ADDED SECURITY CAMERA.

PROVIDE (2)-CARD ACCESS CONTROL PANEL TO SERVE ALL PACS DOOR SECURITY

EQUIPMENT FOR THIS TR ROOM. PROVIDE ALL REQUIRED CONNECTIONS,

PROGRAMMING, POWER SUPPLIES, AND COMPONENTS TO PROVIDE A COMPLETE

AND FULLY FUNCTIONAL SYSTEM. REFERENCE SPECIFICATION "28 13 00 - PHYSICAL

ACCESS CONTROL SYSTEM" FOR ADDITIONAL INFORMATION.

Revisions: Date:

1/2" = 1'-0"01STN100G

3 RM T1-00G - OVERHEAD PLAN

1/2" = 1'-0"01STN100G

1 RM T1-00G - TELECOMMUNICATIONS PLAN

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

DATA RACK

FIRE ALARM

SUB PANEL

FIBER OPTIC

PANEL

SIGNAL BOOSTERS

TELEPHONE

TERMINAL

BOARDS

TELE.

GB171

33 SF

X

FIRE ALARM

SUB PANEL

FIBER OPTIC

PANEL

SIGNAL BOOSTERS

TELEPHONE

TERMINAL

BOARDS

TELE.

GB171

33 SF

Q

TELEPHONE

TERMINAL

BOARDS

DATA RACK

FIRE ALARM

SUB PANEL

FIBER OPTIC

PANEL

TEL

GB166a

35 SF

TELECOMMUNICATIONS ENCLOSURE

Q

FIRE ALARM

SUB PANEL

FIBER OPTIC

PANEL

TELEPHONE

TERMINAL

BOARDS

TEL

GB166a

35 SF

TELECOMMUNICATIONS ENCLOSURE

AREA SHOWN

GB166a GB171

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:4

:5 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

G R

O U

N D

F L

O O

R .r v t

01STN400Gb

BLDG 01S - LEVEL 00G - ENLARGED

TELECOMMUNICATIONS PLANS

01S

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

1/2" = 1'-0"01STN100G

1 RM GB171 - DEMOLITION FLOOR PLAN

1/2" = 1'-0"01STN100G

2 RM GB171 - TELECOMMUNICATIONS PLAN

1/2" = 1'-0"01STN100G

3 RM GB166a - DEMOLITION FLOOR PLAN

1/2" = 1'-0"01STN100G

4 RM GB166a - TELECOMMUNICATIONS PLAN

KEY PLAN

GENERAL NOTES

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE RACEWAYS TO EXTEND TO

ASSOCIATED TR AS REQUIRED.

5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO

REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,

MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE

INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY

FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

6. WHERE DATA OUTLETS ARE PROVIDED AND EXISTING DATA OUTLET CURRENTLY

DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW BACKBOX TO ACCESSIBLE

CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO TR VIA CABLE

TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM OUTLET TO TR AS

REQUIRED.

7. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

8. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

9. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

10. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL SYSTEMS

CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS; ADDITIONALLY,

CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS REQUIRED TO

SEGREGATE SYSTEMS FROM ONE ANOTHER.

11. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD

BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS

REQUIRED.

KEY NOTES

EXISTING EQUIPMENT SHALL BE SALVAGED TO VA. ASSOCIATED RACEWAYS AND

CABLING SHALL BE DEMOLISHED BACK TO SOURCE.

Revisions: Date: 633 OF 693

C

360°

W

X X

S

C

W

360°

S

X

W

X

AREA SHOWN

P

TN503

SECONDARY

BONDING

BUSBAR

TN503

C

01S-T4-01B

01S-T4-01A

DATA

RACK,TYP.

TR TOWER 4

T4-01

160 SF

ACCESS

CONTROL

PANEL

"01S-ACP-T401"

BUS DUCT

"01S-BD-TWR4B"

BUS DUCT

"01S-BD-TWR4A"

BUS DUCT CIRCUIT BREAKER

BUS DUCT CIRCUIT BREAKER

P

TYP.

TN501 TYP.

TN501

TR TOWER 4

T4-01

160 SF

DATA

RACK,TYP.

BUS DUCT

"01S-BD-TWR4B"

BUS DUCT

"01S-BD-TWR4A"

BUS DUCT CIRCUIT BREAKER

BUS DUCT CIRCUIT BREAKER

T4-01

T1-01

X

01S-T1-01A

01S-T1-01B

DATA RACK,

TYP.

TN502

SECONDARY BONDING

BUSBAR

TN503

C

TR TOWER 1

T1-01

166 SFACCESS

CONTROL

PANEL

"01S-ACP-T101"

BUS DUCT

"01S-BD-TWR1B"

BUS DUCT

"01S-BD-TWR1A"

BUS DUCT CIRCUIT BREAKER

BUS DUCT CIRCUIT BREAKER

X

TYP.

TN501

TYP.

TN501

DATA RACK,

TYP.

TR TOWER 1

T1-01

166 SF

BUS DUCT

"01S-BD-TWR1B"

BUS DUCT

"01S-BD-TWR1A"

BUS DUCT CIRCUIT BREAKER

BUS DUCT CIRCUIT BREAKER

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:4

:0 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

L E

V E

L

.r v t

01STN401a

BLDG 01S - LEVEL 01 - ENLARGED

TELECOMMUNICATIONS PLANS

01S

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

GENERAL NOTES

KEY PLAN

KEY NOTES

1/2" = 1'-0"01STN101

2 RM T4-01 - TELECOMMUNICATIONS PLAN

1/2" = 1'-0"01STN101

4 RM T4-01 - OVERHEAD PLAN

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE RACEWAYS TO EXTEND TO

ASSOCIATED TR AS REQUIRED.

5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO

REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,

MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE

INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY

FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

6. WHERE DATA OUTLETS ARE PROVIDED AND EXISTING DATA OUTLET CURRENTLY

DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW BACKBOX TO ACCESSIBLE

CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO TR VIA CABLE

TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM OUTLET TO TR AS

REQUIRED.

7. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

8. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

9. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

10. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL SYSTEMS

CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS; ADDITIONALLY,

CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS REQUIRED TO

SEGREGATE SYSTEMS FROM ONE ANOTHER.

11. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD

BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS

REQUIRED.

Revisions: Date:

1/2" = 1'-0"01STN101

1 RM T1-01 - TELECOMMUNICATIONS PLAN

1/2" = 1'-0"01STN101

3 RM T1-01 - OVERHEAD PLAN 1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

PROVIDE FIRE STOP SLEEVES AS REQUIRED. SIDE 'A' AND SIDE 'B' SLEEVES SHALL BE

SEPARATED BY AT LEAST 10-FT.

WIRE BASKET CABLE TRAY.

PROVIDE (1) CAT6A CABLE FOR ADDED SECURITY CAMERA.

PROVIDE (2)-CARD ACCESS CONTROL PANEL TO SERVE ALL PACS DOOR SECURITY

EQUIPMENT FOR THIS TR ROOM. PROVIDE ALL REQUIRED CONNECTIONS,

PROGRAMMING, POWER SUPPLIES, AND COMPONENTS TO PROVIDE A COMPLETE AND

FULLY FUNCTIONAL SYSTEM. REFERENCE SPECIFICATION "28 13 00 - PHYSICAL ACCESS

CONTROL SYSTEM" FOR ADDITIONAL INFORMATION.

PROJECT

TELE

1B130

32 SF

FIRE ALARM PANELS

TELECOM

TERMINAL BOARDS

SIGNAL BOOSTERS

INTERCOM SYSTEM

PANEL

DATA RACK

X

TELE

1B130

32 SF

FIRE ALARM PANELS

TELECOM

TERMINAL BOARDS

SIGNAL BOOSTERS

INTERCOM SYSTEM

PANEL

1B130

X

TELE

1B130

32 SF

X

TELE

1B130

32 SF

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:4

:4 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

L E

V E

L

.r v t

01STN401b

BLDG 01S - LEVEL 01 - ENLARGED

TELECOMMUNICATIONS PLANS

01S

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

GENERAL NOTES

KEY PLAN

KEY NOTES

1/2" = 1'-0"01STN101

1 RM 1B130 - DEMOLITION FLOOR PLAN

1/2" = 1'-0"01STN101

2 RM 1B130 - TELECOMMUNICATIONS PLAN

1'0 2' 4'

PROJECT

NORTH

1/2" = 1'-0"01STN101

3 RM 1B130 - DEMOLITION OVERHEAD PLAN

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1/2" = 1'-0"01STN101

4 RM 1B130 - OVERHEAD PLAN 1'0 2' 4'

PROJECT

NORTH

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE RACEWAYS TO EXTEND TO

ASSOCIATED TR AS REQUIRED.

5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO

REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,

MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE

INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY

FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

6. WHERE DATA OUTLETS ARE PROVIDED AND EXISTING DATA OUTLET CURRENTLY

DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW BACKBOX TO ACCESSIBLE

CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO TR VIA CABLE

TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM OUTLET TO TR AS

REQUIRED.

7. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

8. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

9. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

10. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL SYSTEMS

CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS; ADDITIONALLY,

CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS REQUIRED TO

SEGREGATE SYSTEMS FROM ONE ANOTHER.

11. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD

BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS

REQUIRED.

Revisions: Date:

EXISTING EQUIPMENT SHALL BE SALVAGED TO VA. ASSOCIATED RACEWAYS AND

CABLING SHALL BE DEMOLISHED BACK TO SOURCE.

EXISTING VERTICAL CABLING SLEEVES SHALL BE PRESERVED. EXISTING CABLING

SHALL BE DEMOLISHED AND REMOVED.

EXISTING HORIZONTAL CABLING SLEEVES SHALL BE PRESERVED. EXISTING CABLING

SHALL BE DEMOLISHED AND REMOVED.

EXISTING CABLE TRAY SHALL BE DEMOLISHED.

PROJECT

IT

1B125P

32 SF

FIRE ALARM PANELS

FUSE BOXES TELECOM

TERMINAL

BOARDS

DATA RACK

X

IT

1B125P

32 SF

FIRE ALARM PANELS

FUSE BOXES TELECOM

TERMINAL

BOARDS

AREA SHOWN

1B125P

X

IT

1B125P

32 SF

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:5

:4 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

L E

V E

L

.r v t

01STN401c

BLDG 01S - LEVEL 01 - ENLARGED

TELECOMMUNICATIONS PLANS

01S

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

1/2" = 1'-0"01STN101

1 RM 1B125P - DEMOLITION FLOOR PLAN

1/2" = 1'-0"01STN101

2 RM 1B125P - TELECOMMUNICATIONS PLAN

GENERAL NOTES

KEY PLAN

KEY NOTES

EXISTING EQUIPMENT SHALL BE SALVAGED TO VA. ASSOCIATED RACEWAYS AND

CABLING SHALL BE DEMOLISHED BACK TO SOURCE.

EXISTING VERTICAL CABLING SLEEVES SHALL BE PRESERVED. EXISTING CABLING

SHALL BE DEMOLISHED AND REMOVED.

1/2" = 1'-0"01STN101

3 RM 1B125P - DEMOLITION OVERHEAD PLAN 1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE RACEWAYS TO EXTEND TO

ASSOCIATED TR AS REQUIRED.

5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO

REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,

MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE

INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY

FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

6. WHERE DATA OUTLETS ARE PROVIDED AND EXISTING DATA OUTLET CURRENTLY

DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW BACKBOX TO ACCESSIBLE

CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO TR VIA CABLE

TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM OUTLET TO TR AS

REQUIRED.

7. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

8. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

9. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

10. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL SYSTEMS

CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS; ADDITIONALLY,

CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS REQUIRED TO

SEGREGATE SYSTEMS FROM ONE ANOTHER.

11. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD

BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS

REQUIRED.

Revisions: Date:

PROJECT

Q R

1B120b

33 SF

DATA RACK

FIRE ALARM

PANEL

TELEPHONE

TERMINAL BOARDS

TELECOMMUNICATIONS

ENCLOSURE

Q R

1B120b

33 SF

FIRE ALARM

PANEL

TELEPHONE

TERMINAL BOARDS

TELECOMMUNICATIONS

ENCLOSURE

Q R

1B120b

33 SF

1B120b

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:5

:1 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

L E

V E

L

.r v t

01STN401d

BLDG 01S - LEVEL 01 - ENLARGED

TELECOMMUNICATIONS PLANS

01S

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

GENERAL NOTES

KEY PLAN

1/2" = 1'-0"01STN101

1 RM 1B120b - DEMOLITION FLOOR PLAN

1/2" = 1'-0"01STN101

2 RM 1B120b - TELECOMMUNICATIONS PLAN

1/2" = 1'-0"01STN101

3 RM 1B120b - DEMOLITION OVERHEAD PLAN

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

KEY NOTES

EXISTING EQUIPMENT SHALL BE SALVAGED TO VA. ASSOCIATED RACEWAYS AND

CABLING SHALL BE DEMOLISHED BACK TO SOURCE.

EXISTING VERTICAL CABLING SLEEVES SHALL BE PRESERVED. EXISTING CABLING

SHALL BE DEMOLISHED AND REMOVED.

EXISTING HORIZONTAL CABLING SLEEVES SHALL BE PRESERVED. EXISTING CABLING

SHALL BE DEMOLISHED AND REMOVED.

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE RACEWAYS TO EXTEND TO

ASSOCIATED TR AS REQUIRED.

5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO

REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,

MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE

INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY

FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

6. WHERE DATA OUTLETS ARE PROVIDED AND EXISTING DATA OUTLET CURRENTLY

DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW BACKBOX TO ACCESSIBLE

CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO TR VIA CABLE

TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM OUTLET TO TR AS

REQUIRED.

7. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

8. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

9. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

10. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL SYSTEMS

CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS; ADDITIONALLY,

CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS REQUIRED TO

SEGREGATE SYSTEMS FROM ONE ANOTHER.

11. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD

BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS

REQUIRED.

Revisions: Date:

PROJECT

C

X

SW

X

W

360°C

W

X X

S

AREA SHOWN

P

C

DATA

RACK,

TYP.

01S-T4-02A

01S-T4-02B

SECONDARY

BONDING

BUSBAR

ACCESS CONTROL

PANEL "01S-ACP-T4-02"

TR TOWER 4

T4-02

160 SF

TN502

TN503

BUS DUCT

"01S-BD-TWR4B"

BUS DUCT

"01S-BD-TWR4A"

BUS DUCT

CIRCUIT BREAKER

BUS DUCT

CIRCUIT BREAKER

P

DATA

RACK,

TYP.

TR TOWER 4

T4-02

160 SF

TYP.

TN501

TYP.

TN501

BUS DUCT

"01S-BD-TWR4B"

BUS DUCT

"01S-BD-TWR4A"

01S-T4-02A

01S-T4-02B

BUS DUCT CIRCUIT BREAKER

BUS DUCT

CIRCUIT BREAKER

T4-02 T1-02

X

C

01S-T1-02A

01S-T1-02B

ACCESS CONTROL

PANEL…