S02 - ATT 16 - 581-22-700 - 100 Drawings Part-14 of 24.pdf
PDF 16 MB Posted
- Solicitation number
- 36C77626R0025
About this file
This document is a comprehensive set of electrical one-line diagrams and schedules for the EHRM Infrastructure Upgrades project at the Huntington VA Medical Center in Huntington, West Virginia. The drawings, dated September 3, 2025, cover electrical distribution systems across multiple buildings (Buildings 4, 5, 6, 7, 8, 9, 15, 20, 23R, 25, 28, 34, 52, and trailer facilities TR1, TR2, TR3/4/5) at the 1540 Spring Valley Drive facility.
The scope includes detailed one-line diagrams showing transformer specifications, circuit breaker ratings and types (primarily Square D and Powerpact models), panelboard configurations with load calculations in amperes at various voltages (480V, 208V, 240V, and 120V), feeder cable sizes and lengths, motor connections with horsepower ratings, and automatic transfer switch (ATS) details. Key electrical equipment specifications include transformers ranging from 8kVA to 500kVA with impedance percentages between 3.7% and 6.4%, circuit breakers from 15A to 1600A, and short circuit current amperage (SCA) and short circuit amperage rating (SCAR) values for each panelboard. The documents also include generator capacity information, metering and load data points, and notes referencing associated panel schedules and electrical specifications. Construction documents indicate this is at 100% completion level, with general notes requiring contractor field verification of existing conditions, submission of shutdown and phasing plans 30 days prior to implementation, compliance with AIC ratings per panelboard schedules, and integration of digital power meters with the facility BMS system.
View the file
Other files
Show 40 more
Latest 50 of 68 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
F: 4_EPA-1-A
(1) #4 THWN; 5 ft
CB: 4_EPA-1-A Main
SQUARE D (EG)
100 A
PNL: 4_EPA-1-A
480.0V, 100A
0.9k SCA
35k SCAR
CB: 4_Roadway lts
SQUARE D (EG)
30 A
F: 4_Pnl LA-D-E-1-B
(1) #1 THWN; 10 ft
F: 4_XF Elev
(1) #12 THWN; 60 ft
S
P XF: 4_Elev 45kVA; 5.60%Z
Pri: 480V
Sec: 240V
F: 4_Elev
(1) #10 THWN; 15 ft
S
P
F: 4_XF ELA-B-A
(1) #4/0 THWN; 10 ft
XF: 4_ELA-B-A
225kVA; 6.00%Z
Pri: 480V
Sec: 208V
F: 4_Pnl ELA-B-A
(2) #3/0 THWN; 30 ft
FU: 4_Elev
0 A
MTR: 4_Elev
5.0 hp
Load Factor 1.00
X"d 0.17 pu
CB: 4_ELA-B-A Main
SQUARE D (LA)
400 A
PNL: 4_ELA-B-A
208.0V, 400A
5.6k SCA
65k SCAR
CB: 4_Booster fryer
SQUARE D (QO)
40 A
CB: 4_EX fan
SQUARE D (QO-VH)
20 A
CB: 4_Griddle
SQUARE D (QO)
30 A
CB: 4_Deep fryer
SQUARE D (QO)
50 A
CB: 4_Coffee maker
SQUARE D (QO)
30 A
CB: 4_Oven
SQUARE D (QO)
70 A
CB: 4_XF Elev
SQUARE D (FA)
30 A
CB: 4_EPA-1-B Main
SQUARE D (LA)
400 A
PNL: 4_EPA-1-B
480.0V, 400A, 5.9k SCA
22k SCAR
CB: 4_XF ELA-B-A
SQUARE D (Q2H)
225 A
PNL: 4_LA-D-E-1-B
208.0V, 225A
1.2k SCA
65k SCAR
CB: 4_LA-D-E-1-B Main
SQUARE D (Q2H)
150 A
TAP: 4_pnl EPA-1-A_xf LA-D-E-1 480.0V, 0.9k SCA
F: 4_XF LA-D-E-1-B Disc
(1) #4 THWN; 5 ft
FU: 4_XF LA-D-E-1-B
BUSSMANN (FRS-R)
60 A
F: 4_XF LA-D-E-1-B
(1) #4 THWN; 5 ft
S
P
XF: 4_LA-D-E-1-B
45kVA; 5.80%Z
Pri: 480V
Sec: 208V
70A 3P
04-P-02C
PANEL
'04-4001A'
225AF/100AT
208/120V
3PH, 4W
F: 1_Pnl 4-EPA-1-B
(2) #3/0 THWN; 580 ft
F: 1_Pnl 4-EPA-1-A Tap
(1) #6 THWN; 560 ft
TRANSFORMER 'TX-TRA-4001'
PRI: 480V
SEC: 120/208V
30KVA
K-13 RATED
FROM "1-EDPA-G-ESA"
SEE SHEET 01EP612
FROM "1-EDPA-G-ESA"
SEE SHEET 01EP612
SPD
ENCLOSED CIRCUIT BREAKER
"ECB-TX-TRA-4001"
100A/3P
100A 3P
SPARE
50A 3P
SPARE
200A 3P
SPARE
04-P-02A
(X5)
04-P-02B
SPARE (X4)
@ TRANSFORMER
WEST OF BLDG. 4
XF: Sub 11
S
P
500kVA; 5.96%Z
Pri: 4160V
Sec: 480V
F: 4_XF Sub 11
(2) #350 THWN; 3 ft
TAP: 4_XF Sub 11
480.0V, 8.7k SCA
CB: 4_DPA-G-A
SQUARE D (LA)
400 A
F: 4_TR T1_T2
(1) #250 THWN; 5 ft
CB: 4_TR T1_T2
SQUARE D (JD)
175 A
F: 4_Pnl DPA-G-A
(1) #350 THWN; 50 ft
CB: 4_DPA-G-A Main
SQUARE D (LH)
400 A
PNL: 4_DPA-G-A
480.0V, 400A
8.0k SCA
35k SCAR
CB: XF DLA-G-A
SQUARE D (KA)
225 A
F: XF DLA-G-A
(1) #4/0 THWN; 20 ft
S
P
XF: 4_DLA-G-A
150kVA; 4.30%Z
Pri: 480V
Sec: 208V
F: 4_Pnl DLA-G-A
(2) #3/0 THWN; 30 ft
ELEC. RM. - ACCESS FROM MECH. RM.
BEHIND KITCHEN GROUND FLOOR
CB: 4_Supply Fan
SQUARE D (EH)
15 A
CB: 4_SF-4
SQUARE D (EH)
15 A
F: 4_SF-4
(1) #12 THWN; 20 ft CB: 4_DLA-G-A Main
SQUARE D (LA)
400 A
PNL: 4_DLA-G-A
208.0V, 400A
5.9k SCA
65k SCAR
CB: 4_Pnl LA-G-E
SQUARE D (Q2)
200 A
F: 4_Pnl LA-G-E
(1) #3/0 THWN; 15 ft
CB: 4_LA-G-E Main
SQUARE D (Q2M)
225 A
PNL: 4_LA-G-E
208.0V, 225A
5.6k SCA
65k SCAR
CB: 4_Pnl LA-G-A1
SQUARE D (QO-VH)
50 A
F: 4_Pnl LA-G-A1
(1) #6 THWN; 15 ft
PNL: 4_LA-G-A1
208.0V, 100A
4.6k SCA
65k SCAR
CB: 4_Exh fan
SQUARE D (QO-VH)
15 A
CB: 4_Deli oven
SQUARE D (QO-VH)
50 A
CB: 4_AC units 2
SQUARE D (QO)
20 A
CB: 4_Pnl LA-G-A
SQUARE D (Q2H)
200 A
F: 4_Pnl LA-G-A
(1) #3/0 THWN; 10 ft
CB: 4_Pnl LA-1-A
SQUARE D (FA)
100 A
F: 4_Pnl LA-1-A
(1) #2 THWN; 40 ft
CB: 4_LA-1-A Main
SQUARE D (Q2H)
100 A
PNL: 4_LA-1-A
208.0V, 225A
4.6k SCA
65k SCAR
PNL: 4_LA-G-A
208.0V, 225A
5.7k SCA
65k SCAR
CB: 4_AC units 1
SQUARE D (QO)
20 A
CB: 4_HV Pump P-8
SQUARE D (EG)
30 A
MTR: 4_HV Pump P-8
7.5 hp
Load Factor 1.00
X"d 0.17 pu
MECH. RM. BEHIND KITCHEN
GROUND FLOOR
CB: 4_AHU 1
SQUARE D (EG)
60 A
MTR: 4_AHU 1
5.0 hp
Load Factor 1.00
X"d 0.17 pu
CB: 4_DPA-G-B Main
SQUARE D (KA)
200 A
PNL: 4_DPA-G-B
480.0V, 200A
7.8k SCA
65k SCAR
CB: 4_HV Pump P-9
SQUARE D (EG)
30 A
MTR: 4_HV Pump P-9
7.5 hp
Load Factor 1.00
X"d 0.17 pu
CB: 4_Disposal
SQUARE D (QO-VH)
20 A
GROUND FLOOR HALLWAY
BEHIND KITCHEN
CB: 4_steamer
SQUARE D (QO)
60 A
CB: 4_Vulcan Oven
SQUARE D (QO)
60 A
MCP: 4_SF-4
SQUARE D (FAL)
1ST FLOOR MECH. RM. - ACCESS DOOR TO
STEPS FROM OUTSIDE
MTR: 4_SF-4
5.0 hp
Load Factor 1.00
X"d 0.17 pu
F: 4_Pnl LA-G-D
(2) #3/0 THWN; 35 ft
GROUND FLOOR
TUNNEL ENT.
CB: 4_LA-G-D Main
SQUARE D (LA)
400 A
F: 4_Pnl LA-G-B
(1) #1/0 THWN; 25 ft
F: 4_Pnl LA-2-A
(1) #1/0 THWN; 90 ft
2ND FLOOR ACCESS
FROM RM 2A1042
CB: 4_LA-G-B Main
SQUARE D (Q2H)
150 A
PNL: 4_LA-G-B
208.0V, 225A
5.6k SCA
65k SCAR
CB: 4_LA-2-A Main
SQUARE D (Q2H)
150 A
PNL: 4_LA-2-A
208.0V, 225A
4.2k SCA
65k SCAR
CB: 4_LA-G-C Main
SQUARE D (Q2H)
150 A
PNL: 4_LA-G-C
208.0V, 225A
5.5k SCA
65k SCAR
PNL: 4_LA-G-D
208.0V, 400A
5.9k SCA
65k SCAR
CB: 4_Grill
SQUARE D (QO)
60 A
GND FLOOR
TUNNEL ENT.
F: 4_Pnl LA-G-C
(1) #1/0 THWN; 30 ft
CB: 4_Pnl LA-G-D
SQUARE D (LA)
400 A
CB: 4_Pnl LA-G-B
SQUARE D (Q2H)
150 A
CB: 4_Pnl LA-2-A
SQUARE D (Q2H)
150 A
CB: 4_EF-1
SQUARE D (EH)
15 A
CB: 4_Pnl DPA-G-B
SQUARE D (KA)
200 A
F: 4_Pnl DPA-G-B
(1) #3/0 THWN; 15 ft
CB: 4_Pnl PA-1-A
SQUARE D (FA)
100 A
F: 4_Pnl PA-1-A
(1) #2 THWN; 60 ft
SPARE
F: 4_Pnl DPA-1-B
(1) #3/0 THWN; 10 ft
CB: 4_DPA-1-B Main
SQUARE D (KA)
200 A
PNL: 4_DPA-1-B
480.0V, 200A
7.7k SCA
65k SCAR
PNL: 4_PA-1-A
480.0V, 125A
6.5k SCA
14k SCAR
CB: 4_CW PUMP
SQUARE D (EH)
45 A
MTR: 4_CW PUMP
10.0 hp
Load Factor 1.00
X"d 0.17 pu
CB: 4_DLA-1-A Main
SQUARE D (MA)
600 A
S
P
F: 4_XF DLA-1-A
(1) #350 THWN; 15 ft
XF: 4_DLA-1-A
225kVA; 6.00%Z
Pri: 480V
Sec: 208V
F: 4_Pnl DLA-1-A
(2) #350 THWN; 20 ft
PNL: 4_DLA-1-A
208.0V, 600A
6.3k SCA
42k SCAR
43, 45, 47
CB: 4_Pnl LA-G-C
SQUARE D (Q2H)
150 A
30A 3P
PANEL
'04-4001B'
225AF/100AT
208/120V
3PH, 4W
TRANSFORMER 'TX-TRB-4001'
PRI: 480V
SEC: 120/208V
15KVA
K-13 RATED
04-P-01C
TO "T1-2-T1-2"
SEE SHEET TR12EP601
FROM " SUB 11 4KV-1"
SPD
CB: 4_Pnl DPA-1-B
SQUARE D (KA)
200 A
ENCLOSED CIRCUIT BREAKER
"ECB-TX-TRB-4001"
100A/3P
04-P-01A
3P SPACE (X10)SPARE SPARE
200A
3P
100A
3P
CB: 4_XF DLA-1-A
SQUARE D (LA)
300 A
PNL: 4_DPA-1-A
480.0V, 400A
7.8k SCA
30k SCAR
CB: 4_DPA-1-A Main
SQUARE D (MA)
400 A
F: 4_Pnl DPA-1-A
(1) #350 THWN; 60 ft
CB: 4_DPA-1-A
SQUARE D (LA)
400 A
04-P-01B
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/3
/2
:2
:2
A M
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /V
A H
U N
T
IN
G T
O N
L e g e n d
G e n e ra l N o te s D ia g ra m s a n d
D e ta ils
.r v t
04EP601
BLDG 04 - ONE-LINE DIAGRAM
DCW/NVP RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
GENERAL NOTES
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES
FOUND SHALL BE REPORTED TO THE ENGINEER.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY POWER PLANS,
AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW 30 DAYS PRIOR
TO IMPLEMENTATION.
3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.
4. NOT ALL ONE-LINE DIAGRAM DRAWING SHEETS MAY HAVE WORK SHOWN; ALL ONE-
LINE DRAWINGS HAVE BEEN INCLUDED IN THIS DRAWING SET FOR REFERENCE
PURPOSES.
5. REFERENCE SHEET 04EP611 FOR REVISED ONE-LINE DIAGRAM.
6. ALL PROVIDED DIGITAL POWER METERS (DPM) SHALL BE INTEGRATED INTO THE
EXISTING FACILITY BMS SYSTEM; PROVIDE ALL REQUIRED RACEWAYS, CABLING, AND
INTEGRATION TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL SYSTEM.
7. CONTRACTOR SHALL PROVIDE CIRCUIT BREAKERS WITH AIC RATING EQUAL TO OR
GREATER THAN HIGHEST FAULT CURRENT RATING INDICATED ON ASSOCIATED
PANELBOARD SCHEDULE AND ONE-LINE DIAGRAM.
8. CIRCUIT BREAKERS SERVING TRANSFORMERS SHALL BE LOCKABLE.
- NTS
1 BLDG 04 - ONE-LINE DIAGRAM
REFERENCE ASSOCIATED PANEL SCHEDULE ON BUILDING '04' SCHEDULE SHEETS
FOR ADDITIONAL INFORMATION.
UTILIZE EXISTING SPACE(S) TO PROVIDE CIRCUIT BREAKER AS SHOWN.
Revisions: Date:
SUBSTATION 12
LOCATED ACROSS
STREET FROM
BUILDING 5.
FROM "EDP-15"
SEE SHEET 15EP601
TO "T3-5"
FROM "EDP-15"
SEE SHEET 15EP601
TO "XF 28-LA-D-G-AA"
SEE SHEET 28EP611
TO "ATS-6"
SEE SHEET 06EP611
F: Sub 12 MDP 500 kcmil (760.0 A) QtyPerPhase 2
Length 10.0 ft
CB: F: Sub 12 MDP MAIN Type Powerpact P-Frame, 6.0A/P/H
Sensor/Trip 800.0 A
CB: F: Sub 12 MDP MAIN-GF Type Powerpact P-Frame, 6.0A/P/H Sensor/Trip 800.0 A
SUB-12 - MDP
SWBD: Sub 12 MDP 11823. 14 Amps 3P
12160. 77 Amps SLG
480.0 Volts RMS
SUB 12 MDP CB ATS2-RRTP
Type LC
Sensor/Trip 600.0 A
SUB 12 MDP CB 5_ATS-5LS
Type Powerpact HJ
Sensor/Trip 60.0 A
SUB 12 MDP CB BLDG 5 - ATS 5
Type LX/LXI Series 3, Micrologic
Sensor/Trip 400.0 A
SUB 12 MDP CB ENG. TRLRS.
Type LX/LXI Series 3, Micrologic
Sensor/Tri p 250.0 A
SUB 12 MDP CB BLDG 28
Type LX/LXI Series 3, Micrologic
Sensor/Trip 250.0 A
SUB 12 MDP CB NO LABEL
Type LX/LXI Series 3, Micrologic
Sensor/Tri p 250.0 A
SUB 12 MDP_BLDG 6 - ATS-6
Type LX/LXI Series 3, Micrologic
Sensor/Tri p 250.0 A
SUB 12 MDP_TVSS
Type HJ, Powerpact Sensor/Tri p 60.0 A
F; 5_ATS 5LS - E
4 AWG (95.0 A)
Qt yPerPhase 1 Length 230. 0 ft
F: ATS 5LS - N
6 AWG (75.0 A)
Qt yPerPhase 1 Length 50. 0 ft
5_ATS 5LS
480V
3PH
60A
5_ATS 5LS BUS
6879.86 Amps 3P
4960.94 Amps SLG
480.0 Volts RMS
CBL: 5 FSS DSC
2 AWG (130.0 A)
Qt yPerPhase 1 Length 10. 0 ft
5_FSS DSC
6566.80 Amps 3P
4671.74 Amps SLG
480.0 Volts RMS
CBL-5_XF T-LG
8 AWG (55.0 A)
Qt yPerPhase 1 Length 10. 0 ft
5_XF T-LG - SEC
5639.11 Amps 3P
3831.78 Amps SLG
480.0 Volts RMS
5_XF T-LG
Nominal kVA 30 kVA Z% 4. 0000 % 480/208 V
5_XF T-LG SEC
1835.93 Amps 3P
1912.55 Amps SLG
208.0 Volts RMS
F: 5_Pnl LS -G
4/0 AWG (230. 0 A)
Qt yPerPhase 1 Length 20. 0 ft
5_CB: LS -G MAIN
Type MA Sensor/Tri p 400.0 A
5_PNL: LS -G
1796.28 Amps 3P
1846.49 Amps SLG
208.0 Volts RMS
5_PNL LS-G CB PNL G
Type QO, 3-Pol e Sensor/Tri p 60.0 A
F: 5_Pnl G
6 AWG (65.0 A)
Qt yPerPhase 1 Length 50. 0 ft
5_PNL: G
1434.05 Amps 3P
1255.21 Amps SLG
208.0 Volts RMS
5_PNL G CB
Type QO, 1-Pole Sensor/Trip 20.0 A
BLDG 5 - Elec . Rm. 5043
CB: 5_MDP Main Type MG w/ ET 1.0, 2-8x Inst .
Sensor/Tri p 600.0 A
PNL: 5_MDP
9920.83 Amps 3P
9139.00 Amps SLG
480.0 Volts RMS
600ASTART OF SINGLE PHASE
CB: 5 TVSS
Type FH Sensor/Tri p 60.0 A
CB: 5_XF T-LG
Type HG Sensor/Trip 150.0 A
F: 5_XF T-LG
1/0 AWG (150. 0 A)
Qt yPerPhase 1 Length 15. 0 ft
XF: 5_T-LG - PRI
9463.80 Amps 3P
8484.49 Amps SLG
480.0 Volts RMS
XF: 5_T-LG
Nominal kVA 112 kVA Z% 5.1000 % 480/208 V
XF: 5_T-LG - SEC
4766.45 Amps 3P
5140.13 Amps SLG
208.0 Volts RMS
F: 5_Pnl LG 600 kcmi l (420.0 A) Qt yPerPhase 1 Length 15. 0 ft
CB: 5_LG Main Type LA Sensor/Tri p 400.0 A
PNL: 5_LG
4623.78 Amps 3P
4892.48 Amps SLG
208.0 Volts RMS
400A
CB: 5_Pnl LGA Type QO-VH, 6-Pole Sensor/Tri p 100.0 A
F: 5_Pnl LGA
2 AWG (115.0 A)
QtyPerPhase 1 Length 15.0 ft
PNL: 5_LGA
4313.79 Amps 3P
4328.74 Amps SLG
208.0 Volts RMS
CB: 5_Pnl L1 Type QO-VH, 6-Pole Sensor/Trip 150.0 A
F: 5_Pnl L1
1/0 AWG (150. 0 A)
Qt yPerPhase 1 Length 100. 0 ft
PNL: 5_L1
3288.32 Amps 3P
2790.20 Amps SLG
208.0 Volts RMS
CB: 5_Pnl L2 Type QO-VH, 3-Pole Sensor/Tri p 150.0 A
F: 5_Pnl L2
1/0 AWG (150.0 A)
QtyPerPhase 1 Length 80.0 ft
PNL: 5_L2
3509.35 Amps 3P
3085.49 Amps SLG
208.0 Volts RMS
MTR: 5_Chiller Comps Rated HP 20 hp
FU: 5_Pnl CHiller Type FLSRID, 600V Class RK5 Sensor/Tri p 80.0 A
TAP: 5_Pnl Chiller
8591.21 Amps 3P
7157.46 Amps SLG
480.0 Volts RMS
MTR: 5_Chiller fans
Rated HP 2 hp
F: 5_Pnl Chiller
3 AWG (100.0 A)
Qt yPerPhase 1 Length 30. 0 ft
CB: 5_Pnl Chiller
Type FH Sensor/T ri p 80.0 A
CB: 5_XF T-5-DLGA (OFF)
Type J-Frame, Powerpact Sensor/Tri p 200.0 A
F: 5_XF T-5-DLGA
4/0 AWG (230. 0 A)
Qt yPerPhase 1 Length 20. 0 ft
XF : 5_T 5-DLGA - PRI
9472.63 Amps 3P
8531.13 Amps SLG
480.0 Volts RMS
XF : 5_T-5-DLGA
Nominal kVA 75 kVA Z% 6. 4000 % 480/208 V
XF : 5_T-5-DLGA - SEC
2831.48 Amps 3P
2959.24 Amps SLG
208.0 Volts RMS
F: 5_Pnl DLGA
2/0 AWG (175. 0 A)
Qt yPerPhase 1 Length 1.0 ft
CB: 5_Pnl DLGA Main Type LA Sensor/Tri p 400.0 A
PNL: 5_DLGA
2826.03 Amps 3P
2949.88 Amps SLG
208.0 Volts RMS
CB: 5_Bldg 8 Type Q2 Sensor/Tri p 200.0 A
CB: 5_XF BLDG 28
Type FH Sensor/Trip 100.0 A
CB: 5_At ic heat 1
Type EG Sensor/Tri p 20.0 A
CB: 5_At ic heat 2
Type EG Sensor/Tri p 20.0 A
CB: 5_Attic heat 3
Type EG Sensor/Trip 20.0 A
CB: 5_ERU Exh
Type EG Sensor/Tri p 20.0 A
F: 5_ERU Exh
12 AWG (20.0 A)
Qt yPerPhase 1 Length 30.0 ft
FU: 5_ERU Exh
Type AJT, 600V Class J Sensor/Trip 30.0 A
MTR: 5_ERU Exh
Rated HP 5 hp
CB: 5_ERU supply Type EG Sensor/Trip 20.0 A
F: 5_ERU supply
12 AWG (20.0 A)
Qt yPerPhase 1 Length 30. 0 ft
FU: 5_ERU supply Type AJT, 600V Class J Sensor/T ri p 30.0 A
MTR: 5_ERU supply Rated HP 7.5 hp
CB: 5_Pump 1 Type EG Sensor/Tri p 20.0 A
F: 5_Pump 1
12 AWG (20.0 A)
Qt yPerPhase 1 Length 20. 0 ft
FU: 5_Pump 1 Type FLSRID, 600V Class RK5 Sensor/Tri p 15.0 A
MTR: 5_Pump 1 Rated HP 1.5 hp
CB: 5_Pump 2 Type EG Sensor/Tri p 20.0 A
F: 5_Pump 2
12 AWG (20.0 A)
QtyPerPhase 1 Length 20.0 ft
FU: 5_Pump 2 Type FLSRID, 600V Class RK5 Sensor/Trip 15.0 A
MTR: 5_Pump 2 Rated HP 1.5 hp
CB: 5_Pump 3 Type EG Sensor/Trip 20.0 A
F: 5_Pump 3
12 AWG (20.0 A)
Qt yPerPhase 1 Length 20. 0 ft
FU: 5_Pump 3 Type FLSRID, 600V Class RK5 Sensor/Tri p 15.0 A
MTR: 5_Pump 3 Rated HP 5 hp
CB: 5_Pump 4 Type EG Sensor/Tri p 20.0 A
F: 5_Pump 4
12 AWG (20.0 A)
QtyPerPhase 1 Length 20.0 ft
FU: 5_Pump 4 Type FLSRID, 600V Class RK5 Sensor/Trip 15.0 A
MTR: 5_Pump 4 Rated HP 5 hp
CB: 5_Cond Pump Type EG Sensor/Trip 20.0 A
PNL: 5_HMG
6968.45 Amps 3P
5210.68 Amps SLG
480.0 Volts RMS
CB: 5_Water heater
Type EG Sensor/Tri p 20.0 A
F: 5_Pnl HGM
3 AWG (100.0 A)
Qt yPerPhase 1 Length 70. 0 ft
CB: 5_Pnl HGM Type FH Sensor/Trip 100.0 A
CB: 5_Pnl HG
Type FH Sensor/Tri p 100.0 A
F: 5_Pnl HG
3 AWG (100.0 A)
Qt yPerPhase 1 Length 20. 0 ft
PNL: 5_HG
8992.73 Amps 3P
7757.53 Amps SLG
480.0 Volts RMS
CB: 5_Pnl Elevator-1
Type FH Sensor/Tri p 70.0 A
F: 5_Pnl Elevator 1
4 AWG (85.0 A)
QtyPerPhase 1 Length 40.0 ft
CB: 5_Pnl Elevator_1 Type FA Sensor/Tri p 70.0 A
MTR: 5_Elevator 1
Rated HP 30 hp
CB:
Type FH Sensor/Trip 70.0 A
F: 5_Pnl MDP 350 kcmil (620.0 A) QtyPerPhase 2 Length 90.0 ft
F: 5_ATS-5 - E
500 kcmi l (380.0 A) Qty Per Phase 1 Length 175. 0 ft
E N
F: 5_ATS-5 - N
500 kcmil (380.0 A) QtyPerPhase 1 Length 50.0 ft
5_ATS 5
400A 4P
S
P
S
P
E N
S
P
100A/3P
05-P-02
PANEL
'05-5044A'
225AF/100AT
208/120V
3PH, 4W
05-P-01B
60A/3P
TRANSFORMER '5-TRA-5044'
PRI: 480V
SEC: 120/208V
30KVA
K-13 RATED
S
P
05-P-01A
TO "9-ATS-2"
SEE SHEET 09EP601
FROM "SUB 12"
SPD
PANEL
'05-5044B'
225AF/100AT
208/120V
3PH, 4W
SPD
UNKNOWN LOAD
SPARETVSS
20A/3P
SPARE 3P SPACE 1P SPACE
(X3)
(X10)
CB: 5_Pnl LS-G Type QO-VH, 6-Pole Sensor/Trip 150.0 A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/3
/2
:3
:0
A M
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /V
A H
U N
T
IN
G T
O N
L e g e n d
G e n e ra l N o te s D ia g ra m s a n d
D e ta ils
.r v t
05EP601
BLDG 05 - ONE-LINE DIAGRAM
DCW/NVP RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
GENERAL NOTES
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES
FOUND SHALL BE REPORTED TO THE ENGINEER.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY POWER PLANS,
AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW 30 DAYS PRIOR
TO IMPLEMENTATION.
3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.
4. NOT ALL ONE-LINE DIAGRAM DRAWING SHEETS MAY HAVE WORK SHOWN; ALL ONE-
LINE DRAWINGS HAVE BEEN INCLUDED IN THIS DRAWING SET FOR REFERENCE
PURPOSES.
5. ALL PROVIDED DIGITAL POWER METERS (DPM) SHALL BE INTEGRATED INTO THE
EXISTING FACILITY BMS SYSTEM; PROVIDE ALL REQUIRED RACEWAYS, CABLING, AND
INTEGRATION TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL SYSTEM.
6. CONTRACTOR SHALL PROVIDE CIRCUIT BREAKERS WITH AIC RATING EQUAL TO OR
GREATER THAN HIGHEST FAULT CURRENT RATING INDICATED ON ASSOCIATED
PANELBOARD SCHEDULE AND ONE-LINE DIAGRAM.
7. CIRCUIT BREAKERS SERVING TRANSFORMERS SHALL BE LOCKABLE.
1 REFERENCE ASSOCIATED PANEL SCHEDULE ON BUILDING '05' SCHEDULE SHEETS
FOR ADDITIONAL INFORMATION.
UTILIZE EXISTING SPACE TO PROVIDE CIRCUIT BREAKER AS SHOWN.
ADDITIONAL LOAD HAS BEEN ADDED TO FEEDER. REFERENCE CONTINUED ONE-LINE
DIAGRAM AS INDICATED ON DRAWING AND ASSOCIATED PANEL SCHEDULE FOR
ADDITIONAL LOADING INFORMATION.
- 1/4" = 1'-0"
1 BLDG 05 - ONE-LINE DIAGRAM
LOAD DATA POINT NOTES
LOAD DATA POINT: EXISTING SWITCHBOARD 'SUB 12 MDP'. REFERENCE "METERING
AND LOAD INFORMATION SCHEDULE" ON SHEET 05EP701 FOR ADDITIONAL
INFORMATION.
LOAD DATA POINT: EXISTING PANELBOARD '5-MDP' MAIN. REFERENCE "METERING
AND LOAD INFORMATION SCHEDULE" ON SHEET 05EP701 FOR ADDITIONAL
INFORMATION.
F: 6_CB MDP6
(1) #250 THWN; 100 ft
CB: 6_Pnl L1 and L2
SQUARE D (QO)
100 A
F: 6_Pnl L1 and L2
(1) #3 THWN; 40 ft
PNL: 6_L1
208.0V, 100A 2.4k SCA 65k SCAR F: 6_Pnl L2
(1) #3 THWN; 30 ft
6-6105
PNL: 6_L2
208.0V, 100A 2.1k SCA 65k SCAR
6-6208A
PNL: 6_LB1
208.0V, 100A 2.6k SCA 65k SCAR
PNL: 6_LA
208.0V, 100A 2.2k SCA 65k SCAR
CB: 6_Pnl LB1
SQUARE D (QO)
100 A
F: 6_Pnl LB1
(1) #3 THWN; 20 ft
CB: 6_Pnl LA
SQUARE D (QO)
100 A
F: 6_Pnl LA
(1) #3 THWN; 60 ft
CB: 6_LB Main
SQUARE D (QD)
225 A
S
P
CB: 6_XF T-LG
SQUARE D (ED)
125 A
F: 6_XF T-LG
(1) #1 THWN; 15 ft
XF: 6_T-LG
75kVA; 5.50%Z Pri: 480V Sec: 208V
F: 6_Pnl LB
(1) #4/0 THWN; 15 ft MTR: 6_Elevator
30.0 hp Load Factor 1.00 X"d 0.17 pu
6-AH1C
PNL: 6_LB
208.0V, 225A 2.7k SCA 65k SCAR
CB: 6_Pnl Kiln
SQUARE D (QO)
60 A
CB: 6_HW P-2
SQUARE D (ED)
15 A
MTR: 6_HW P-2
0.5 hp Load Factor 1.00 X"d 0.17 pu
CB: 6_HW P-1
SQUARE D (ED)
15 A
MTR: 6_HW P-1
0.5 hp Load Factor 1.00 X"d 0.17 pu
CB: 6_Elevator-2
SQUARE D (HJ)
70 A
CB: 6_MDP6 Main
SQUARE D (JD)
225 A
F: 6_Pnl MDP6
(1) #4/0 THWN; 50 ft
PNL: 6_MDP6
480.0V, 225A, 4.8k SCA 65k SCAR
CB: 6_Elevator-1
SQUARE D (ED)
80 A
F: 6_Elevator
(1) #4 THWN; 25 ft
FROM "EDP-15"
SEE SHEET 15EP601
E N
ATS-6
225A
FROM "SUB 12"
SEE SHEET 05EP601
F: 6_ATS-6 - N.2
4/0 AWG (230. 0 A)
QtyPerPhase 1 Length 8.0 ft
F: 6_ATS-6 - E
4/0 AWG (230. 0 A)
QtyPerPhase 1 Length 225. 0 ft
F: 6_ATS-6-N
4/0 AWG (230.0A)
QTY Per Phase 1 Length 85.0 ft
CB: BLDG 6 ATS_ECB W/ TVSS
Type UNKNOWN Sensor/Trip 225.0A
20A/1P
SPARE (X7)
50A/2P
SPARE (X1)
30A/3P
SPARE (X1)
PANEL
'Kiln' 208V 60A
3PH, 4W
125 A 3P
SPARE (X22)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/3
/2
:3
:5
A M
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /V
A H
U N
T
IN
G T
O N
L e g e n d
G e n e ra l N o te s D ia g ra m s a n d
D e ta ils
.r v t
06EP601
BLDG 06 - ONE-LINE DIAGRAM - EXISTING
DCW/NVP RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
GENERAL NOTES
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES
FOUND SHALL BE REPORTED TO THE ENGINEER.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY POWER PLANS,
AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW 30 DAYS PRIOR
TO IMPLEMENTATION.
3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.
4. NOT ALL ONE-LINE DIAGRAM DRAWING SHEETS MAY HAVE WORK SHOWN; ALL ONE-
LINE DRAWINGS HAVE BEEN INCLUDED IN THIS DRAWING SET FOR REFERENCE
PURPOSES.
5. ALL PROVIDED DIGITAL POWER METERS (DPM) SHALL BE INTEGRATED INTO THE
EXISTING FACILITY BMS SYSTEM; PROVIDE ALL REQUIRED RACEWAYS, CABLING, AND
INTEGRATION TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL SYSTEM.
6. CONTRACTOR SHALL PROVIDE CIRCUIT BREAKERS WITH AIC RATING EQUAL TO
OR GREATER THAN HIGHEST FAULT CURRENT RATING INDICATED ON ASSOCIATED
PANELBOARD SCHEDULE AND ONE-LINE DIAGRAM.
- NTS
1 BLDG 06 - ONE-LINE DIAGRAM - EXISTING
1 (3) EXISTING 20A, 1P CIRCUIT BREAKERS SHALL BE SALVAGED TO VA. REFERENCE
REVISED ONE-LINE DIAGRAMS AND ASSOCIATED PANEL SCHEDULES FOR
ADDITIONAL INFORMATION.
F: 6_CB MDP6
(1) #250 THWN; 100 ft
20A/3P
MTR: 6_Elevator
30.0 hp Load Factor 1.00 X"d 0.17 pu
6-AH1C
CB: 6_HW P-2
SQUARE D (ED)
15 A
MTR: 6_HW P-2
0.5 hp Load Factor 1.00 X"d 0.17 pu
CB: 6_HW P-1
SQUARE D (ED)
15 A
MTR: 6_HW P-1
0.5 hp Load Factor 1.00 X"d 0.17 pu
CB: 6_Elevator-2
SQUARE D (HJ)
70 A
CB: 6_MDP6 Main
SQUARE D (JD)
225 A
F: 6_Pnl MDP6
(1) #4/0 THWN; 50 ft
PNL: 6_MDP6
480.0V, 225A, 4.8k SCA 65k SCAR
CB: 6_Elevator-1
SQUARE D (ED)
80 A
F: 6_Elevator
(1) #4 THWN; 25 ft
FROM "EDP-15"
SEE SHEET 15EP601
PANELBOARD
'06-6113A'
100AF/60AT
208/120V
3PH, 4W
E N
ATS-6
225A
TRANSFORMER
'XF-06-6113AB'
PRI: 480V
SEC: 120/208V
15KVA
K-13 RATED
PANELBOARD
'06-6113B'
100AF/60AT
208/120V
3PH, 4W
FROM "SUB 12"
SEE SHEET 05EP601
F: 6_ATS-6 - N.2
4/0 AWG (230. 0 A)
QtyPerPhase 1 Length 8.0 ft
F: 6_ATS-6 - E
4/0 AWG (230. 0 A)
QtyPerPhase 1 Length 225. 0 ft
SPD SPD
1 1
F: 6_ATS-6-N
4/0 AWG (230.0A)
QTY Per Phase 1 Length 85.0 ft
CB: BLDG 6 ATS_ECB W/ TVSS
Type UNKNOWN Sensor/Trip 225.0A
06-P-02 06-P-03
06-P-01C
06-P-01A
CB: 6_Pnl L1 and L2
SQUARE D (QO)
100 A
F: 6_Pnl L1 and L2
(1) #3 THWN; 40 ft
PNL: 6_L1
208.0V, 100A 2.4k SCA 65k SCAR F: 6_Pnl L2
(1) #3 THWN; 30 ft
6-6105
PNL: 6_L2
208.0V, 100A 2.1k SCA 65k SCAR
6-6208A
PNL: 6_LB1
208.0V, 100A 2.6k SCA 65k SCAR
PNL: 6_LA
208.0V, 100A 2.2k SCA 65k SCAR
CB: 6_Pnl LB1
SQUARE D (QO)
100 A
F: 6_Pnl LB1
(1) #3 THWN; 20 ft
CB: 6_Pnl LA
SQUARE D (QO)
100 A
F: 6_Pnl LA
(1) #3 THWN; 60 ft
CB: 6_LB Main
SQUARE D (QD)
225 A
S
P
CB: 6_XF T-LG
SQUARE D (ED)
125 A
F: 6_XF T-LG
(1) #1 THWN; 15 ft
XF: 6_T-LG
75kVA; 5.50%Z Pri: 480V Sec: 208V
F: 6_Pnl LB
(1) #4/0 THWN; 15 ft
PNL: 6_LB
208.0V, 225A 2.7k SCA 65k SCAR
CB: 6_Pnl Kiln
SQUARE D (QO)
60 A
20A/1P
SPARE (X7)
50A/2P
SPARE (X1)
30A/3P
SPARE (X1)
PANEL
'Kiln' 208V 60A
3PH, 4W
ENCLOSED CIRCUIT BREAKER
"ECB-06-6113AB"
60A/3P
20A/3P
SPARE ( )X19
06-P-01B
ENCLOSED CIRCUIT BREAKER
"ECB-XF-06-6113AB"
60A/3P
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/3
/2
:2
:1
A M
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /V
A H
U N
T
IN
G T
O N
L e g e n d
G e n e ra l N o te s D ia g ra m s a n d
D e ta ils
.r v t
06EP611
BLDG 06 - ONE-LINE DIAGRAM - REVISED
DCW/NVP RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
GENERAL NOTES
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES
FOUND SHALL BE REPORTED TO THE ENGINEER.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY POWER PLANS,
AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW 30 DAYS PRIOR
TO IMPLEMENTATION.
3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.
4. NOT ALL ONE-LINE DIAGRAM DRAWING SHEETS MAY HAVE WORK SHOWN; ALL ONE-
LINE DRAWINGS HAVE BEEN INCLUDED IN THIS DRAWING SET FOR REFERENCE
PURPOSES.
5. ALL PROVIDED DIGITAL POWER METERS (DPM) SHALL BE INTEGRATED INTO THE
EXISTING FACILITY BMS SYSTEM; PROVIDE ALL REQUIRED RACEWAYS, CABLING, AND
INTEGRATION TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL SYSTEM.
6. CONTRACTOR SHALL PROVIDE CIRCUIT BREAKERS WITH AIC RATING EQUAL TO
OR GREATER THAN HIGHEST FAULT CURRENT RATING INDICATED ON ASSOCIATED
PANELBOARD SCHEDULE AND ONE-LINE DIAGRAM.
7. CIRCUIT BREAKERS SERVING TRANSFORMERS SHALL BE LOCKABLE.
- NTS
1 BLDG 06 - ONE-LINE DIAGRAM - REVISED
1 REFERENCE ASSOCIATED PANEL SCHEDULE ON BUILDING '06' SCHEDULE SHEETS
FOR ADDITIONAL INFORMATION.
UTILIZE SPACE FROM SALVAGED SPARES TO PROVIDE CIRCUIT BREAKER(S) AS
INDICATED. REFERENCE EXISTING ONE-LINE DIAGRAM AND ASSOCIATED REVISED
PANEL SCHEDULES FOR CIRCUITING INFORMATION.
F: 7_ATS-7 - E
300 kcmil (285.0 A) QtyPerPhase 1 Length 435.0 ft
F: 7_ATS-7 - N
300 kcmil (285.0 A) QtyPerPhase 1 Length 435.0 ft
DISC - ATS-7 - E DISC - ATS-7 - N
ATS-7 - E
3764.31 Amps 3P
433.31 Amps SLG
480.0 Volts RMS
E N
ATS-7
225A
BUS-ATS-7
3955.62 Amps 3P
3270.65 Amps SLG
480.0 Volts RMS
F: H-P7-G
4/0 AWG (230.0 A)
QtyPerPhase 1 Length 10.0 ft
H-P7-G/ MCB
Type J-Frame, Powerpact Sensor/Trip 225.0 A
F: H-P7-A
4/0 AWG (230.0 A)
QtyPerPhase 1 Length 40.0 ft
CB: XF T-8
Type LH
Sensor/Trip 150.0 A
PNL H-P7-A
3759.76 Amps 3P
3051.95 Amps SLG
480.0 Volts RMS
H-P7-A/ TYP
Type EDB Sensor/Trip 60.0 A
CB: XF T-7B
Type EDB Sensor/Trip 50.0 A
F: XF T-7B
6 AWG (65.0 A)
QtyPerPhase 1 Length 8.0 ft
XF: T-7B - PRI
3640.09 Amps 3P
2902.10 Amps SLG
480.0 Volts RMS
S
P
XF: T-7B
Nominal kVA 30 kVA Z% 3.9100 %
480/208 V
XF: T-7B - SEC
1702.78 Amps 3P
1824.92 Amps SLG
208.0 Volts RMS
F: L-P7-AA
2 AWG (115.0 A)
QtyPerPhase 1 Length 8.0 ft
L-P7-AA/ MCB
Type ED Sensor/Trip 100.0 A
PNL: L-P7-AA
1677.72 Amps 3P
1778.81 Amps SLG
208.0 Volts RMS
L-P7-AA/ TYP
Type GD, 1-Pole Sensor/Trip 20.0 A
CB: L-P7-GB
Type QO, 3-Pole
Sensor/Trip 100.0 A
F: L-P7-GB
3/0 AWG (200.0 A)
QtyPerPhase 1 Length 6.0 ft
PNL: L-P7-GB
3253.94 Amps 3P
3554.88 Amps SLG
208.0 Volts RMS
L-P7-GB/ TYP
Type QO, 1-Pole Sensor/Trip 20.0 A
S
P
PNL: H-P7-G
3915.03 Amps 3P
3224.68 Amps SLG
480.0 Volts RMS
225A
CB: XF T-7
Type EDB Sensor/Trip 100.0 A
F: XF T-7
2 AWG (115.0 A)
QtyPerPhase 1 Length 8.0 ft
XF: T-7 - PRI
3852.96 Amps 3P
3148.34 Amps SLG
480.0 Volts RMS
XF: T-7
Nominal kVA 75 kVA Z% 3.7000 % 480/208 V
XF: T-7 - SEC
3457.02 Amps 3P
3968.32 Amps SLG
208.0 Volts RMS
F: L-P7-GA
2 AWG (115.0 A)
QtyPerPhase 1 Length 8.0 ft
DISC: PNL L-P7-GA FS
DISC: LP7-GA
3355.93 Amps 3P
3756.58 Amps SLG
208.0 Volts RMS
F: L-P7-GA.2
3/0 AWG (200.0 A)
QtyPerPhase 1 Length 8.0 ft
PNL: L-P7-GA
3297.04 Amps 3P
3639.27 Amps SLG
208.0 Volts RMS
L-P7-GA/ TYP
Type QO, 1-Pole
Sensor/Trip 20.0 A
ATS-7 - N
3955.62 Amps 3P
3270.65 Amps SLG
480.0 Volts RMS
FROM "SUB 12 BLDGS 7&8"
FROM "15-EDP"
SEE SHEET 15EP601
50A/3P50A/3P
PANELBOARD
"07-7004A"
225AF/100AT
208/120V
3PH, 4W
SPD
PANELBOARD
"07-7004B"
225AF/100AT
208/120V
3PH, 4W
SPD
NEMA L5-30
30A, 120V
LOCKING
TRANSFORMER '7-TRB-7004'
PRI: 480V
SEC: 120/208V
15KVA
K-13 RATED
TRANSFORMER '7-TRA-7004'
PRI: 480V
SEC: 120/208V
30KVA
K-13 RATED
07-P-01C
07-P-03 07-P-04
07-P-01A 07-P-02A
07-P-02C
TE 7300
SIDE B
NEMA L5-30
30A, 120V
LOCKING
TE 7300
SIDE A
1 1
2 2
ENCLOSED CIRCUIT
BREAKER
"ECB-7-TRB-7004"
60A/3P
07-P-01B
ENCLOSED CIRCUIT
BREAKER
"ECB-7-TRA-7004"
100A/3P
07-P-02B
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/3
/2
:2
:2
A M
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /V
A H
U N
T
IN
G T
O N
L e g e n d
G e n e ra l N o te s D ia g ra m s a n d
D e ta ils
.r v t
07EP601
BLDG 07 - ONE-LINE DIAGRAM
DCW/NVP RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
GENERAL NOTES
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES
FOUND SHALL BE REPORTED TO THE ENGINEER.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY POWER PLANS,
AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW 30 DAYS PRIOR
TO IMPLEMENTATION.
3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.
4. NOT ALL ONE-LINE DIAGRAM DRAWING SHEETS MAY HAVE WORK SHOWN; ALL ONE-
LINE DRAWINGS HAVE BEEN INCLUDED IN THIS DRAWING SET FOR REFERENCE
PURPOSES.
5. REFERENCE SHEET 07EP611 FOR REVISED ONE-LINE DIAGRAM.
6. ALL PROVIDED DIGITAL POWER METERS (DPM) SHALL BE INTEGRATED INTO THE
EXISTING FACILITY BMS SYSTEM; PROVIDE ALL REQUIRED RACEWAYS, CABLING, AND
INTEGRATION TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL SYSTEM.
7. CONTRACTOR SHALL PROVIDE CIRCUIT BREAKERS WITH AIC RATING EQUAL TO
OR GREATER THAN HIGHEST FAULT CURRENT RATING INDICATED ON ASSOCIATED
PANELBOARD SCHEDULE AND ONE-LINE DIAGRAM.
8. CIRCUIT BREAKERS SERVING TRANSFORMERS SHALL BE LOCKABLE.
- NTS
1 BLDG 07 - ONE-LINE DIAGRAM
1 REFERENCE ASSOCIATED PANEL SCHEDULE ON BUILDING '07' SCHEDULE SHEETS
FOR ADDITIONAL INFORMATION.
UTILIZE EXISTING SPACE TO PROVIDE CIRCUIT BREAKER AS SHOWN.2
PANEL
"L-P8-G-EM"
100A 208/120V
3PH
4W
PANEL
"8-EM-LP"
125A 208/120V
3PH
4W
S
P
FROM "5-LG"
SEE SHEET 05EP601
FROM "SUB 12 BLDGS 7&8"
F: BLDG 8/ H-P8-G
4/0 AWG (230.0 A)
QtyPerPhase 1 Length 144.0 ft
H-P8-G/ MCB
Type UNKNOWN Sensor/Trip 225.0 A
F: P.B. H-P8-A 2/0 AWG (350.0 A) QtyPerPhase Length 50.0 ft
PNL: H-P8-G
5273.10 Amps 3P
4864.70 Amps SLG
480.0 Volts RMS
225A
F: XFMR T-8A
2 AWG (230.0 A) QtyPerPhase 2 Length 8.0 ft
XF: T-8A - PRI
5221.39 Amps 3P
4785.29 Amps SLG
480.0 Volts RMS
XF: T-8A
Nominal kVA 75 kVA Z% 5.0000 % 480/208 V
PNL: H-P8-A
5059.99 Amps 3P
4559.35 Amps SLG 480.0 Volts
RMS
H-P8-A/ MCB
Type UNKNOWN Sensor/Trip 150.0 A
H-P8-A/ TYP
Type EDB Sensor/Trip 30.0 A
XF: T-8A - SEC
3096.45 Amps 3P
3385.86 Amps SLG 208.0 Volts RMS
F: L-P8-GA
3/0 AWG (400.0 A) QtyPerPhase 2 Length 40.0 ft
CB: L-P8-GA/ MCB
Type UNKNOWN Sensor/Trip 225.0 A
PNL: L-P8-GA
2979.71 Amps 3P
3171.18 Amps SLG
208.0 Volts RMS
225A
CB: L-P8-GB
Type Q2 Sensor/Trip 100.0 A
F: L-P8-GB
3/0 AWG (400.0 A) QtyPerPhase 2 Length 4.0 ft
PNL: L-P8-GB
2968.38 Amps 3P
3150.69 Amps SLG
208.0 Volts RMS
L-P8-GB/ TYP
Type QO, 1-Pole Sensor/Trip 20.0 A
J
20A 1P
SPARE (X8)
20A 1P
SPARE (X9)
15A 1P
SPARE (X3)
30A 2P
SPARE (X2)1P SPACE (X3)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/3
/2
:2
:0
A M
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /V
A H
U N
T
IN
G T
O N
L e g e n d
G e n e ra l N o te s D ia g ra m s a n d
D e ta ils
.r v t
08EP601
BLDG 08 - ONE-LINE DIAGRAM - EXISTING
DCW/NVP RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
GENERAL NOTES
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES
FOUND SHALL BE REPORTED TO THE ENGINEER.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY POWER PLANS,
AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW 30 DAYS PRIOR
TO IMPLEMENTATION.
3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.
4. NOT ALL ONE-LINE DIAGRAM DRAWING SHEETS MAY HAVE WORK SHOWN; ALL ONE-
LINE DRAWINGS HAVE BEEN INCLUDED IN THIS DRAWING SET FOR REFERENCE
PURPOSES.
5. REFERENCE SHEET 08EP611 FOR REVISED ONE-LINE DIAGRAM.
6. ALL PROVIDED DIGITAL POWER METERS (DPM) SHALL BE INTEGRATED INTO THE
EXISTING FACILITY BMS SYSTEM; PROVIDE ALL REQUIRED RACEWAYS, CABLING, AND
INTEGRATION TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL SYSTEM.
7. CONTRACTOR SHALL PROVIDE CIRCUIT BREAKERS WITH AIC RATING EQUAL TO
OR GREATER THAN HIGHEST FAULT CURRENT RATING INDICATED ON ASSOCIATED
PANELBOARD SCHEDULE AND ONE-LINE DIAGRAM.
1 (4) EXISTING 20A, 1P CIRCUIT BREAKERS SHALL BE SALVAGED TO VA. REFERENCE
REVISED ONE-LINE DIAGRAMS AND ASSOCIATED PANEL SCHEDULES FOR ADDITIONAL
INFORMATION.
- NTS
1 BLDG 08 - ONE-LINE DIAGRAM - EXISTING
S
P
F: BLDG 8/ H-P8-G
4/0 AWG (230.0 A)
QtyPerPhase 1 Length 144.0 ft
H-P8-G/ MCB
Type UNKNOWN Sensor/Trip 225.0 A
20A 1P
F: P.B. H-P8-A 2/0 AWG (350.0 A) QtyPerPhase Length 50.0 ft
PNL: H-P8-G
5273.10 Amps 3P
4864.70 Amps SLG
480.0 Volts RMS
225A
F: XFMR T-8A
2 AWG (230.0 A) QtyPerPhase 2 Length 8.0 ft
XF: T-8A - PRI
5221.39 Amps 3P
4785.29 Amps SLG
480.0 Volts RMS
XF: T-8A
Nominal kVA 75 kVA Z% 5.0000 % 480/208 V
K-13 RATED
PNL: H-P8-A
5059.99 Amps 3P
4559.35 Amps SLG 480.0 Volts
RMS
H-P8-A/ MCB
Type UNKNOWN Sensor/Trip 150.0 A
H-P8-A/ TYP
Type EDB Sensor/Trip 30.0 A
XF: T-8A - SEC
3096.45 Amps 3P
3385.86 Amps SLG 208.0 Volts RMS
F: L-P8-GA
3/0 AWG (400.0 A) QtyPerPhase 2 Length 40.0 ft
CB: L-P8-GA/ MCB
Type UNKNOWN Sensor/Trip 225.0 A
PNL: L-P8-GA
2979.71 Amps 3P
3171.18 Amps SLG
208.0 Volts RMS
225A
PANELBOARD
"08-8009B"
225AF/100AT
208/120V
3PH, 4W
PANELBOARD
"08-8009A"
225AF/100AT
208/120V
3PH, 4W
08-P-04
08-P-01
NEMA L5-30
30A, 120V
LOCKING
TE 8301
SIDE B
NEMA L5-30
30A, 120V
LOCKING
TE 8301
SIDE A 1 2
SPARE (X8)
CB: L-P8-GB
Type Q2 Sensor/Trip 100.0 A
F: L-P8-GB
3/0 AWG (400.0 A) QtyPerPhase 2 Length 4.0 ft
PNL: L-P8-GB
2968.38 Amps 3P
3150.69 Amps SLG
208.0 Volts RMS
L-P8-GB/ TYP
Type QO, 1-Pole Sensor/Trip 20.0 A
20A 1P
SPARE
15A 1P
SPARE (X3)
30A 2P
SPARE (X2)
100A 3P
100A 3P
30A 1P
(X2)
08-P-02 08-P-03
PANEL
"L-P8-G-EM"
100A 208/120V
3PH
4W
PANEL
"8-EM-LP"
125A 208/120V
3PH
4W
FROM "5-LG"
SEE SHEET 05EP601
J
3 2
SPD SPD
FROM "SUB 12 BLDGS 7&8"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/3
/2
:2
:2
A M
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /V
A H
U N
T
IN
G T
O N
L e g e n d
G e n e ra l N o te s D ia g ra m s a n d
D e ta ils
.r v t
08EP611
BLDG 08 - ONE-LINE DIAGRAM - REVISED
DCW/NVP RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
GENERAL NOTES
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES
FOUND SHALL BE REPORTED TO THE ENGINEER.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY POWER PLANS,
AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW 30 DAYS PRIOR
TO IMPLEMENTATION.
3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.
4. NOT ALL ONE-LINE DIAGRAM DRAWING SHEETS MAY HAVE WORK SHOWN; ALL ONE-
LINE DRAWINGS HAVE BEEN INCLUDED IN THIS DRAWING SET FOR REFERENCE
PURPOSES.
5. ALL PROVIDED DIGITAL POWER METERS (DPM) SHALL BE INTEGRATED INTO THE
EXISTING FACILITY BMS SYSTEM; PROVIDE ALL REQUIRED RACEWAYS, CABLING, AND
INTEGRATION TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL SYSTEM.
6. CONTRACTOR SHALL PROVIDE CIRCUIT BREAKERS WITH AIC RATING EQUAL TO
OR GREATER THAN HIGHEST FAULT CURRENT RATING INDICATED ON ASSOCIATED
PANELBOARD SCHEDULE AND ONE-LINE DIAGRAM
7. CIRCUIT BREAKERS SERVING TRANSFORMERS SHALL BE LOCKABLE.
- NTS
1 BLDG 08 - ONE-LINE DIAGRAM - REVISED
1 REFERENCE ASSOCIATED PANEL SCHEDULE ON BUILDING '08' SCHEDULE SHEETS
FOR ADDITIONAL INFORMATION.
UTILIZE EXISTING SPACE TO PROVIDE CIRCUIT BREAKER AS INDICATED. REFERENCE
ASSOCIATED REVISED PANEL SCHEDULES FOR CIRCUITING INFORMATION.
UTILIZE SPACE FROM SALVAGED SPARES TO PROVIDE CIRCUIT BREAKER(S) AS
INDICATED. REFERENCE EXISTING ONE-LINE DIAGRAM AND ASSOCIATED REVISED
PANEL SCHEDULES FOR CIRCUITING INFORMATION.
100A/3P
FROM "SUB 12"
SEE SHEET 05EP601
FROM "EDP-15"
SEE SHEET 15EP611
PANELBOARD
'09-9202B'
225AF/100AT
208/120V
3PH 4W
DISC: MOBILE GEN-SET
E N 009 - ATS-2
480V 600A
S
P
DISC: 009 - DE
E N
009-ATS-1
F: ATS-2-RRTP (BLDG 9)
350 kcmil (620.0 A) QtyPerPhase 2 Length 358.0 ft
F: 009 - ATS-2 - E 350 kcmil (620.0 A) QtyPerPhase 2 Length 55.0 ft
BUS: 009_ATS-2
8198.86 Amps 3P
7105.00 Amps SLG
480.0 Volts RMS
F: 009-MDPH 350
kcmil (620.0 A) QtyPerPhase 2 Length 12.0 ft
009-MDPH/ MCB
Type SGLA, Spectra RMS Sensor/Trip 600.0 A
009-MDPH - SG-1
Type SELA, Spectra RMS Sensor/Trip 50.0 A
009-MDPH - AHU-1 RFI
Type SELA, Spectra RMS Sensor/Trip 40.0 A
009-MDPH - CU AHU
Type SFLA, Spectra RMS Sensor/Trip 200.0 A
F: CU-AHU
3/0 AWG (200.0 A)
QtyPerPhase 1 Length 40.0 ft
BUS: CU-AHU
7429.77 Amps 3P
6175.57 Amps SLG
480.0 Volts RMS
009-MDPH - AHU-1 HEAT COIL
Type SFLA, Spectra RMS Sensor/Trip 200.0 A
F: AHU-1 HEAT COIL
3/0 AWG (200.0 A)
QtyPerPhase 1 Length 40.0 ft
BUS: AHU-1 HEAT COIL
7429.77 Amps 3P
6175.57 Amps SLG
480.0 Volts RMS
009-MDPH - XF-TN_ATS-1
Type SELA, Spectra RMS Sensor/Trip 70.0 A
009-MDPH - NO LABEL
Type SELA, Spectra RMS Sensor/Trip 25.0 A
009-MDPH - AHU-1 SFI
Type SELA, Spectra RMS Sensor/Trip 25.0 A
50A 3P
009-MDPH - XFMR TMDPL
Type SELA, Spectra RMS Sensor/Trip 150.0 A
F: XF TMDPL
1/0 AWG (150.0 A)
QtyPerPhase 1 Length 12.0 ft
XF: TMDPL - PRI
7845.68 Amps 3P
6659.60 Amps SLG
480.0 Volts RMS
XF: TMDPL
Nominal kVA 112.5 kVA Z% 5.0000 % 480/208 V
XF: TMDPL - SEC
4648.60 Amps 3P
5082.06 Amps SLG
208.0 Volts RMS
F: MDPL
500 kcmil (380.0 A) QtyPerPhase 1 Length 12.0 ft
MDPL/ MCB
Type SGLA, Spectra RMS Sensor/Trip 400.0 A
PNL: 009_MDPL
4536.00 Amps 3P
4880.14 Amps SLG
208.0 Volts RMS
400A
PNL; 1N & 2N
Type UNKNOWN Sensor/Trip 225.0 A
F: 1N & 2N
4/0 AWG (230.0 A)
QtyPerPhase 1 Length 25.0 ft
1N/ MCB
Type THQD Sensor/Trip 225.0 A
009 - MDPH
8113.58 Amps 3P
7004.02 Amps SLG
480.0 Volts RMS
600 A
009-MDPH - ELEVATOR
Type SELA, Spectra RMS Sensor/Trip 150.0 A
F: ELEVATOR
1/0 AWG (150.0 A)
QtyPerPhase 1 Length 40.0 ft
BUS: AHU-1 H.C.0
7256.84 Amps 3P
5934.60 Amps SLG
480.0 Volts RMS
PNL: 1N
4261.52 Amps 3P
4398.69 Amps SLG
208.0 Volts RMS
1N/ TYP
Type THHQB-LM, 1 pole Sensor/Trip 20.0 A
F: 2N
4/0 AWG (230.0 A)
QtyPerPhase 1 Length 15.0 ft
2N/ MCB
Type THQD Sensor/Trip 225.0 A
PNL: 2N
4109.45 Amps 3P
4144.05 Amps SLG
208.0 Volts RMS
2N/ TYP
Type THHQB-LM, 1 pole Sensor/Trip 20.0 A
F: DE - RRTP (BLDG 9)
2/0 AWG (175.0 A)
QtyPerPhase 1 Length 460.0 ft
F: 009 - ATS-1 - N1
4 AWG (85.0 A)
QtyPerPhase 1 Length 10.0 ft
F: 009 - ATS-1 - N
4 AWG (85.0 A)
QtyPerPhase 1 Length 10.0 ft
BUS-ATS-1
7701.93 Amps 3P
6441.88 Amps SLG
480.0 Volts RMS
F: XF-TN
4 AWG (85.0 A)
QtyPerPhase 1 Length 10.0 ft
XF: TN - PRI
7292.53 Amps 3P
5910.57 Amps SLG
480.0 Volts RMS
XF: TN
Nominal kVA 45 kVA Z% 3.3666 % 480/208 V
XF: TN - SEC
3083.85 Amps 3P
3269.82 Amps SLG
208.0 Volts RMS
F: PNL 1E
1 AWG (130.0 A)
QtyPerPhase 1 Length 15.0 ft
1E/ MCB
Type THQD Sensor/Trip 125.0 A
PNL: 009_1E
2905.30 Amps 3P
2946.14 Amps SLG
208.0 Volts RMS
1E/ TYP
Type THQD Sensor/Trip 125.0 A
F: PNL 2E
1 AWG (130.0 A)
QtyPerPhase 1 Length 15.0 ft
2E/ MCB
Type THQD Sensor/Trip 125.0 A
PNL: 2E
2745.19 Amps 3P
2677.68 Amps SLG
208.0 Volts RMS
2E/ TYP
Type THQD Sensor/Trip 125.0 A
S
P
09-P-02C
PANELBOARD
'09-9202A'
225AF/100AT
208/120V
3PH 4W
SPD
09-P-01
SPD
TRANSFORMER ''XFMR-09-9202A''
PRI:480V
SEC: 120/208V
30kVA
K-13 RATED
09-P-02B
2 2
009-MDPH - NO LABEL
Type SELA, Spectra RMS Sensor/Trip 90 A
ENCLOSED CIRCUIT BREAKER
"ECB-XFMR-09-9202A"
100A/3P
09-P-02A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/3
/2
:2
:1
A M
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /V
A H
U N
T
IN
G T
O N
L e g e n d
G e n e ra l N o te s D ia g ra m s a n d
D e ta ils
.r v t
09EP601
BLDG 09 - ONE-LINE DIAGRAM
DCW/NVP RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
GENERAL NOTES
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES
FOUND SHALL BE REPORTED TO THE ENGINEER.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY POWER PLANS,
AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW 30 DAYS PRIOR
TO IMPLEMENTATION.
3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.
4. NOT ALL ONE-LINE DIAGRAM DRAWING SHEETS MAY HAVE WORK SHOWN; ALL ONE-
LINE DRAWINGS HAVE BEEN INCLUDED IN THIS DRAWING SET FOR REFERENCE
PURPOSES.
5. REFERENCE SHEET 09EP611 FOR REVISED ONE-LINE DIAGRAM.
6. ALL PROVIDED DIGITAL POWER METERS (DPM) SHALL BE INTEGRATED INTO THE
EXISTING FACILITY BMS SYSTEM; PROVIDE ALL REQUIRED RACEWAYS, CABLING, AND
INTEGRATION TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL SYSTEM.
7. CONTRACTOR SHALL PROVIDE CIRCUIT BREAKERS WITH AIC RATING EQUAL TO
OR GREATER THAN HIGHEST FAULT CURRENT RATING INDICATED ON ASSOCIATED
PANELBOARD SCHEDULE AND ONE-LINE DIAGRAM.
8. CIRCUIT BREAKERS SERVING TRANSFORMERS SHALL BE LOCKABLE.
LOAD DATA POINT NOTES
- NTS
1 BLDG 09 -ONE-LINE DIAGRAM
LOAD DATA POINT: EXISTING PANELBOARD "9-MDPH" MAIN. REFERENCE "METERING
AND LOAD INFORMATION SCHEDULE" ON SHEET 09EP701 FOR ADDITIONAL
INFORMATION.
1 REFERENCE ASSOCIATED PANEL SCHEDULE ON BUILDING '09' SCHEDULE SHEETS
FOR ADDITIONAL INFORMATION.
SALVAGE EXISTING 90A, 3P SPARE CIRCUIT BREAKER TO THE VA AND PROVIDE
OVERCURRENT PROTECTIVE DEVICE TO SUPPLY LOAD AS SHOWN.
UTILIZE EXISTING SPACE TO PROVIDE CIRCUIT BREAKER AS SHOWN.
GEN-BLDG 015
Rated Size 350kW Rated PF 0.900 Lag Rated Voltage 480V
CB: EDP-15
Type UNKNOWN Sensor/Trip 500.0A
F: EDP-15
350kcmil (700.0A) QtyPerPhase 2 Length 25.0ft
Bldg. 5 - ATS-5LS Type HJ, Powerpact Sensor/Trip 60.0A
TO 'ATS-5LS'
SEE SHEETS 05EP601
AND 05EP611
TVSS
Type HJ, Powerpact Sensor/Trip 60.0A
TO "7-ATS-7"
SEE SHEET 07EP611
TO "5-ATS-5"
SEE SHEETS 05EP601
AND 05EP611
TO "ATS-28"
SEE SHEETS 28EP601
AND 28EP611
TO "ATS-6"
SEE SHEETS 06EP601
AND 06EP611
TO "09-ATS-1"
SEE SHEET 09EP611
Bldg. 7 - ATS-7 Type J-Frame, Powerpact Sensor/Trip 250.0A
Bldg. 5 - ATS-5 Type J-Frame, Powerpact Sensor/Trip 250.0A
Bldg. 28 - ATS-28 Type HJ, Powerpact Sensor/Trip 60.0A
Bldg. 6 - ATS-6 Type J-Frame, Powerpact Sensor/Trip 250.0A
DE - RRTP (BLDG 9)
Type HJ, Powerpact Sensor/Trip 150.0A
PNL: EDP-15
5711.80 Amps 3P
461.22 Amps S LG
480.0 Volts RMS
BLDG015 - 350 KW GENERATOR
TVSS
3P SPACE (X3)
2 2 2 2 2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/3
/2
:2
:0
A M
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /V
A H
U N
T
IN
G T
O N
L e g e n d
G e n e ra l N o te s D ia g ra m s a n d
D e ta ils
.r v t
15EP601
BLDG 15 - ONE-LINE DIAGRAM
DCW/NVP RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
GENERAL NOTES
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES
FOUND SHALL BE REPORTED TO THE ENGINEER.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY POWER PLANS,
AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW 30 DAYS PRIOR
TO IMPLEMENTATION.
3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.
4. NOT ALL ONE-LINE DIAGRAM DRAWING SHEETS MAY HAVE WORK SHOWN; ALL ONE-
LINE DRAWINGS HAVE BEEN INCLUDED IN THIS DRAWING SET FOR REFERENCE
PURPOSES.
5. ALL PROVIDED DIGITAL POWER METERS (DPM) SHALL BE INTEGRATED INTO THE
EXISTING FACILITY BMS SYSTEM; PROVIDE ALL REQUIRED RACEWAYS, CABLING, AND
INTEGRATION TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL SYSTEM.
6. CONTRACTOR SHALL PROVIDE CIRCUIT BREAKERS WITH AIC RATING EQUAL TO
OR GREATER THAN HIGHEST FAULT CURRENT RATING INDICATED ON ASSOCIATED
PANELBOARD SCHEDULE AND ONE-LINE DIAGRAM.
- NTS
1 BLDG 15 - ONE-LINE DIAGRAM
1 REFERENCE ASSOCIATED GENERATOR CAPACITY AND LOAD INFORMATION
SCHEDULE ON ELECTRICAL SCHEDULE SHEETS FOR ADDITIONAL INFORMATION.
ADDITIONAL LOAD HAS BEEN ADDED TO FEEDER. REFERENCE CONTINUED ONE-LINE
DIAGRAM AS INDICATED ON DRAWING AND ASSOCIATED PANEL SCHEDULES FOR
ADDITIONAL LOADING INFORMATION.
M
551 ENCLOSURE
UTIL METER
#587973873
CT ENC
G
400A 3P
60A 3P
100A 3P
100A 3P
MSB, 1000A, 120/208V, 3P, 4W, NEMA 1
ATS-02
ATS-SB
400 A 208V
PANEL
"LSW"
100A
208/120V
3PH
4W
PANEL
"SBE1"
150A
208/120V
3PH
4W
PANEL
"SWBD2"
150A 208/120V
3PH
4W
PANEL
"MECH"
400A 208/120V
3PH
4W
SWBD1, 400A, 120/208V,
3P, 4W, NEMA 1
400A 3P
150A 3P
150A 3P
PADMOUNT W/ ENCLOSURE
150KW GENERATOR
120/208V
400A 3P
100A 3P
100A/3P
100A/3P 100A/3P
PANELBOARD
'20-20211AB'
225AF/100AT
208/120V
3PH, 4W
PANELBOARD
'20-20211AA'
225AF/100AT
208/120V
3PH, 4W
100A/3P
PANELBOARD
'20-20121A'
225AF/100AT
208/120V
3PH, 4W
PANELBOARD
'20-20121B'
225AF/100AT
208/120V
3PH, 4W
20-P-04
20-P-03
20-P-0220-P-01
E N
E N
SPD
SPD
SPD
SPD
3 3
3P SPACE
400A 3P
400A 3P
SPARESPARESPARE (X12)
20A 1P
SPARE (8X)
1000A/3P
LSI
TO UTILITY
BLDG 20
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/3
/2
:2
:0
A M
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /V
A H
U N
T
IN
G T
O N
L e g e n d
G e n e ra l N o te s D ia g ra m s a n d
D e ta ils
.r v t
20EP601
BLDG 20 - ONE-LINE DIAGRAM
DCW/NVP RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
- NTS
1 BLDG 20 - ONE-LINE DIAGRAM
1 REFERENCE ASSOCIATED PANEL SCHEDULE ON BUILDING '20' SCHEDULE SHEETS
FOR ADDITIONAL INFORMATION.
REFERENCE ASSOCIATED GENERATOR CAPACITY AND LOAD INFORMATION
SCHEDULE ON ELECTRICAL SCHEDULE SHEETS FOR ADDITIONAL INFORMATION.
UTILIZE EXISTING SPACE TO PROVIDE CIRCUIT BREAKER AS SHOWN.
GENERAL NOTES
KEY NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY DISCREPANCIES
FOUND SHALL BE REPORTED TO THE ENGINEER.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY POWER PLANS,
AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW 30 DAYS PRIOR
TO IMPLEMENTATION.
3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.
4. NOT ALL ONE-LINE DIAGRAM DRAWING SHEETS MAY HAVE WORK SHOWN; ALL ONE-
LINE DRAWINGS HAVE BEEN INCLUDED IN THIS DRAWING SET FOR REFERENCE
PURPOSES.
5. ALL PROVIDED DIGITAL POWER METERS (DPM) SHALL BE INTEGRATED INTO THE
EXISTING FACILITY BMS SYSTEM; PROVIDE ALL REQUIRED RACEWAYS, CABLING, AND
INTEGRATION TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL SYSTEM.
6. CONTRACTOR SHALL PROVIDE CIRCUIT BREAKERS WITH AIC RATING EQUAL TO
OR GREATER THAN HIGHEST FAULT CURRENT RATING INDICATED ON ASSOCIATED
PANELBOARD SCHEDULE AND ONE-LINE DIAGRAM.
7. CIRCUIT BREAKERS SERVING TRANSFORMERS SHALL BE LOCKABLE.
F: 23R_SWBD
(4) #600 THWN; 150 ft
CB: 23R_SWBD Main
SQUARE D (PX)
1600 A
CB: 23R_1000A Xfer Sw
SQUARE D (NA)
1000 A
F: 23R_1000A Xfer Sw
(3) #400 THWN; 15 ft
CB: 23R_ACRCU-B
SQUARE D (LC)
600 A
F: 23R_ACRCU-B
TAP: 23R_Disc ACRCU-B 480.0V, 21.1k SCA 600A
F: 23R_Disc ACRCU-B
(2) #350 THWN; 10 ft
Open
CB: 23R_IPU-3
SQUARE D (FC)
20 A
Start of single phase
F: 23R_IPU-3
(1) #12 THWN; 70 ft
Open
CB: 23R_IPU-4
SQUARE D (FC)
20 A
Start of single phase
F: 23R_IPU-4
(1) #12 THWN; 70 ft
F: 23R_Elevator
(1) #1 THWN; 70 ft
BLDG 23R
ELEC RM G01
CONTROLLER
CB:23R_IPU-3 Main
SQUARE D (FA)
20 A
PNL: 23R_IPU-3
208.0V, CB:23R_IPU-4 Main
SQUARE D (FA)
20 A
PNL: 23R_IPU-4
120.0V, CB: 23R_Encl CB Elevator
SQUARE D (KA)
125 A
MTR: 23R_Elevator
60.0 hp
Load Factor 1.00
X"d 0.17 pu
BLDG 23R ROOF
E N
ATS: 23R_ATS
1000A
MTR: 23R_ACRCU-B Comp-1
206.0 hp
F: 23R_Pnl EDP
(3) #400 THWN; 25 ft
CB: 23R_EDP Main
SQUARE D (NX)
1200 A
PNL: 23R_EDP
480.0V, 1000A
23.9k SCA
35k SCAR
CB: 23R_EMCC
SQUARE D (LC)
400 A
F: 23R_EMCC
(1) #500 THWN; 15 ft
CB: 23R_ELP
SQUARE D (FC)
60 A
F: 23R_ELP
(1) #6 THWN; 10 ft
PNL: 23R_ELP
480.0V, 100A
19.7k SCA
50k SCAR
CB: 23R_ACRCU-1
SQUARE D (LC)
500 A
F: 23R_ACRCU-1
(1) #500 THWN; 100 ft
TAP: 23R_ACRCU-1
480.0V, 20.9k SCA
F: 23R_ACRCU-B-3
(2) #350 THWN; 10 ft
Open CB: 23R_XF Water Tower Pnl
SQUARE D (FC)
50 A
F: 23R_XF Water Tower Pnl
(1) #6 THWN; 350 ft
TAP: 23R_Disc Wtr Twr Pnl 480.0V, 60A S
P
T2
CB: 23R_XF ERDP
SQUARE D (KC)
125 A
F: 23R_XF ERDP
(1) #2 THWN; 5 ft
T2
XF: 23R_ERDP
75kVA; 5.50%Z
Pri: 480V
Sec: 208V
F: 23R_Disc Water Tower Pnl
(1) #6 THWN; 10 ft
Start of single phase
S
P XF: Water Tower Pnl 15kVA; 3.70%Z
Pri: 480V
Sec: 240V
F: 23R_Water Tower Pnl
(1) #6 THWN; 5 ft
CB: 23R_Water Tower Pnl Main
SQUARE D (QO-VH)
100 A
PNL: 23R_Water Tower Pnl 240.0V, @ WATER TOWER BASE
PNL: 23R_ERPG
208.0V, 100A
3.3k SCA
10k SCAR
BLDG 23R ROOF
MTR: 23R_ACRCU-1 Comp-1
117.5 hp
Load Factor 1.00
X"d 0.17 pu
MTR: 23R_ACRCU-1 Fan-1
3.0 hp
Load Factor 1.00
X"d 0.17 pu
MTR: 23R_ACRCU-1 Comp-2
117.5 hp
Load Factor 1.00
X"d 0.02 pu
BUS: 23R_ACRCU-1
480.0V, 20.8k SCA
PNL: 23R_ERP2
208.0V, 225A
3.0k SCA
100k SCAR
CB: 23R_Pnl ERP2A
SQUARE D (QO-VH)
100 A
MTR: 23R_ACRCU-1 Fan-2
3.0 hp
Load Factor 1.00
X"d 0.17 pu
F: 23R_Pnl ERP2A
(1) #2 THWN; 5 ft
CB: 23R_GBP Main
SQUARE D (QO-VH)
100 A
PNL: 23R_GBP
208.0V, 100A
2.9k SCA
10k SCAR
CB: 23R_Unit Heater
SQUARE D (QO-VH)
30 A
PNL: 23R_ERP2A
208.0V, 100A
3.0k SCA
10k SCAR
CB: 23R_CtrlTemp 207 EvapCoil2
SQUARE D (QO-VH)
20 A
BLDG 23R ELECT RM 220
MCC: 23R_EMCC_1
480.0V, 600A
22.4k SCA
42k SCAR
CB: 23R_EF-15
SQUARE D (FA)
15 A
CB: 23R_EF-18
SQUARE D (FA)
15 A
CB: 23R_EF-19
SQUARE D (FA)
15 A
CB: 23R_EF-20
SQUARE D (FA)
15 A
CB: 23R_HWRP
SQUARE D (FA)
15 A
CB: 23R_EF-2
SQUARE D (FA)
15 A
CB: 23R_EF-3
SQUARE D (FA)
15 A
CB: 23R_EF-4
SQUARE D (FA)
15 A
CB: 23R_EF-21
SQUARE D (FA)
15 A
CB: 23R_EF-22
SQUARE D (FA)
15 A
CB: 23R_Med Air Comp
SQUARE D (FH)
40 A
CB: 23R_Dom Wtr Booster
SQUARE D (FH)
30 A
CB: 23R_Comp 1
SQUARE D (FH)
20 A
CB: 23R_Med Vac Pump
SQUARE D (FH)
20 A
CB: 23R_CP-1
SQUARE D (FH)
15 A
CB: 23R_CP-2
SQUARE D (FH)
15 A BUS: 23R_EMCC
(1) #600 Class B; 1 ft
CB: 23R_Ctrl Temp 207 EvapCoil
SQUARE D (QO-VH)
20 A
CB: 23R_Refrig B23 Evap Coil
SQUARE D (QO-VH)
20 A
BLDG 23R ELECT RM B-22
BLDG 23R
ELECT RM 117
PNL: 23R_ERP1
208.0V, 100A
2.8k SCA
10k SCAR
PNL: 23R_ERPB
208.0V, 225A
3.0k SCA
200k SCAR
CB: 23R_Refrig B05 Evap Coil
SQUARE D (QO-VH)
20 A
CB: 23R_Pnl ERPG
SQUARE D (FA)
60 A
F: 23R_Pnl ERPG
(1) #6 THWN; 10 ft
CB: 23R_Pnl ERP2
SQUARE D (FA)
100 A
F: 23R_Pnl ERP2
(1) #2 THWN; 40 ft
CB: 23R_Generator GBP
SQUARE D (FA)
100 A
F: 23R_Generator GPB
(1) #2 THWN; 50 ft
CB: 23R_Pnl ERPB
SQUARE D (FA)
60 A
F: 23R_Pnl ERPB
(1) #6 THWN; 20 ft
CB: 23R_ERDP Main
SQUARE D (KA)
150 A
F: 23R_Pnl ERDP
(1) #4/0 THWN; 5 ft
Load Factor 1.00
X"d 0.17 pu
MTR: 23R_ACRCU-B Fan-1
3.0 hp
Load Factor 1.00
X"d 0.02 pu
MTR: 23R_ACRCU-B Comp-2
170.0 hp
Load Factor 1.00
X"d 0.17 pu
MTR: 23R_ACRCU-B Fan-2
3.0 hp
Load Factor 1.00
X"d 0.02 pu
CB: 23R_Pnl RP2B
SQUARE D (KA)
225 A
F: 23R_Pnl RP2B
(1) #4/0 THWN; 35 ft
PNL: 23R_RP2B
208.0V, 225A
6.2k SCA
100k SCAR
CB: 23R_Glassware Wshr Rm 204
SQUARE D (QO-VH)
20 A
BLDG 23R RM 220
MCC: 23R_MCC
480.0V, 600A
20.8k SCA
42k SCAR
CB: 23R_AH-1
SQUARE D (FA)
100 A
MTR: 23R_AH-1
30.0 hp
Load Factor 1.00
X"d 0.17 pu
CB: 23R_AH-2
SQUARE D (FA)
70 A
MTR: 23R_AH-2
25.0 hp
Load Factor 1.00
X"d 0.17 pu
PNL: 23R_ERDP
208.0V, 150A 3.5k SCA 200k SCAR
CB: 23R_Pnl ERP1
SQUARE D (FA)
60 A
F:…