S02 - ATT 24 - 581-22-700 - 100 Drawings Part-22 of 24.pdf

PDF 19 MB Posted

Attached to
EHRM Huntington VAMC 581-22-700 Construct Infrastructure Upgrades
Solicitation number
36C77626R0025
Issued by

About this file

These are telecommunications infrastructure design drawings for the VA Huntington facility EHRM (Electronic Health Record Management) Infrastructure Upgrades project. The documents include Level 01, Level 02, Level 00B, and Level 00G telecommunications plans for multiple buildings (12, 20, 23R, 25, 28, 34, TR1-TR5), supplemented by enlarged plans for specific telecommunications rooms and data center phases.

The project involves comprehensive category 6A cabling upgrades replacing existing category 6 and below infrastructure. Key scope includes: removal and replacement of telecommunications outlets with specified port quantities; installation of cable tray systems with fire-stop sleeves at wall penetrations; routing of horizontal and backbone fiber-optic cabling with A-side and B-side diversity; provision of pull boxes at 100-foot intervals per ANSI/TIA-569; and sealing of all interior wall and ceiling penetrations to match existing fire ratings. Telecommunications rooms referenced include T4-01 and T4-02 in Building 01S, room 20121 in Building 20, room B09 in Building 23R, room PG103-25 in Building 25, and TR1-103A serving trailers. The contractor must field-verify all existing equipment, provide labor for installation, termination, testing, labeling, and certification of outlets, and coordinate routing with architectural features, mechanical systems, and existing obstructions. Demolition includes removal of existing category 6 and below cabling back to source and disposal of associated equipment, with some equipment designated for salvage to VA. Data center phasing is depicted across multiple phases (1B, 2A, 2B) showing equipment relocation and progressive infrastructure modifications.

View the file

Other files

File Type Posted
S06 - 36C77626R0025 0008.pdf PDF
S06 - Amendment 0008 - ATT 7 - 02EP100B - ELECTRICAL 20260413.pdf PDF
S06 - Amendment 0008 - ATT 11 - Burn Permit.pdf PDF
S06 - Amendment 0008 - ATT 10 - 260508 - Sheet AD103-1B Data Center Phase 1B Demo Roof update.pdf PDF
S06 - Amendment 0008 - ATT 9 - 260508 - Sheet AD101-1B Data Center Phase 1B Demo Floor Plan update.pdf PDF
S06 - Amendment 0008 - ATT 1 - TechQuestionsVAresponses Final Set - Huntington EHRM IU.pdf PDF
S06 - Amendment 0008 - ATT 14 - Energized Electrical Work Permit.pdf PDF
S06 - Amendment 0008 - ATT 5 - ELECTRICAL 2026.04.13.pdf PDF
S06 - Amendment 0008 - ATT 6 - 01WEP100G - ELECTRICAL 20260413.pdf PDF
S06 - Amendment 0008 - ATT 3 - Civil OSP Redesign-signed.pdf PDF
S06 - Amendment 0008 - ATT 12 - Environmental Report Huntington WV.pdf PDF
S06 - Amendment 0008 - ATT 8 - 260508 - Sheet 01S-AE452 TR Tower 4 Wall sections update.pdf PDF
S06 - Amendment 0008 - ATT 13 - Hot Tapping Permit.pdf PDF
S06 - Amendment 0008 - ATT 2 - UPDATED SHEETS.pdf PDF
S06 - Amendment 0008 - ATT 4 - Structural Set 04-21-2026.pdf PDF
S06 - 36C77626R0025 0007.pdf PDF
S06 - Amendment 0007 - ATT 1 - TechQuestionsVAresponses Partial 4 - Huntington EHRM IU.pdf PDF
S06 - Amendment 0007 - ATT 3 - Lift Planning.pdf PDF
S06 - Amendment 0007 - ATT 2 - Geotechnical Report.pdf PDF
S06 - Amendment 0007 - ATT 5 - Appendix A - PFC FPT.pdf PDF
S06 - Amendment 0007 - ATT 4 - 01 00 00 - GENERAL REQUIREMENTS_A1.pdf PDF
S06 - Amendment 0007 - ATT 6 - Crane lift Info.pdf PDF
S06 - 36C77626R0025 0006.pdf PDF
S06 - Amendment 0006 - ATT 1 - TechQuestionsVAresponses Partial 3 - Huntington EHRM IU.pdf PDF
S06 - 36C77626R0025 0005.pdf PDF
S06 - Amendment 0004 - ATT 2 - FAR 52.222-90 ADDRESSING DEI DISCRIMINATION BY FEDERAL CONTRACTORS - APR 2026.pdf PDF
S06 - Amendment 0004 - ATT 1 - TechQuestionsVAresponses Partial 2 - Huntington EHRM IU.pdf PDF
S06 - 36C77626R0025 0004.pdf PDF
S06 - Amendment 0003 - ATT 2 - TechQuestionsVAresponses Partial - Huntington EHRM IU.pdf PDF
S06 - 36C77626R0025 0003.pdf PDF
S06 - 36C77626R0025 0002.pdf PDF
S06 - Amendment 0001 - ATT 1 - Site Visit In-Sheet - Huntington EHRM IU.pdf PDF
S06 - 36C77626R0025 0001.pdf PDF
S02 - ATT 28 - 581-22-700 - FLS Compliance Letter.pdf PDF
S02 - ATT 3 - 581-22-700 - 100 Drawings Part-1 of 24.pdf PDF
S02 - ATT 15 - 581-22-700 - 100 Drawings Part-13 of 24.pdf PDF
S02 - ATT 30 - 581-22-700 - 100 Commissioning Plan.pdf PDF
S02 - ATT 20 - 581-22-700 - 100 Drawings Part-18 of 24.pdf PDF
S02 - ATT 1 - 581-22-700 - 100 Specifications Part-1 of 2.pdf PDF
S02 - ATT 10 - 581-22-700 - 100 Drawings Part-8 of 24.pdf PDF
S02 - ATT 12 - 581-22-700 - 100 Drawings Part-10 of 24.pdf PDF
S02 - ATT 23 - 581-22-700 - 100 Drawings Part-21 of 24.pdf PDF
S02 - ATT 31 - 581-22-700 - Topographic Survey TR Tower 3.pdf PDF
S02 - ATT 25 - 581-22-700 - 100 Drawings Part-23 of 24.pdf PDF
S02 - ATT 16 - 581-22-700 - 100 Drawings Part-14 of 24.pdf PDF
S02 - ATT 21 - 581-22-700 - 100 Drawings Part-19 of 24.pdf PDF
S02 - ATT 34 - HEFP SEP Design Alerts 1-9 and 11-16.pdf PDF
S02 - ATT 29 - 581-22-700 - Geotechnical Report - W24044 - VA Duct Bank 11.21.24.pdf PDF
S02 - ATT 14 - 581-22-700 - 100 Drawings Part-12 of 24.pdf PDF
S02 - ATT 27 - 581-22-700 - Asbestos locations.xlsx XLSX spreadsheet
Show 40 more

Latest 50 of 68 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

WAP

WAP WAP WAP

WAP

WAP

WAP

WAP

WAP

W

W

AREA SHOWN

H I J K L M N O P Q R S T

B L D

G

B L D

G

B L D

G

B L D

G

A

S

E E

S H

E E

T

A

T N

TYP.

E.M.S. CHIEF

1A116

INT. DESIGN

1A116A

E.M.S. SECT.

1A117

E.M.S.

1A117B

E.M.S. SUPERS

1A117A

HR

1A119

HR

1A120

HR

1A120A

ELEV

P7

STAIRS

BUS OFFICE PC

1A114

BUS DATA

OFFICE

1A113A

CHIEF STAFF

CREDENTIAL

PRIVILEGE

1A113

QM INFECTION

CONTROL

1A112B

QM

1A112A

HR

1A112

IRM

1A111

ELEC

1A110

F. TLT

1A109A

M. TLT

1A109

QM

1A108

QM

1A107

QM

1A106QM

1A105

QM

1A104

QM

1A103

HR

1A102

PIV

1A101

PIV

1A101A

LOBBY

STAIRS

HAC

1A121

HR

1A122

HRM

1A123

HR

1A124

HRM

1A125

HR

1A129

HR

1A128

HR ASST. CHIEF

1A127

HR SECT.

1A126

CHIEF HRM

1A126A

CORRIDOR

C1-4

134A

DATA OUTLETS AND DEVICES IN THIS AREA SHALL BE SERVED FROM

TELECOMMUNICATIONS ROOM T4-01 AT BLDG. 01S, TR TOWER 4 LEVEL 01.

TYP.

2 2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2 DV1

DD2DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

N2

N2 N2

N2

N2 N2

N2

N2

N2 N2

N2 N2

N2N2

N2 N2

N2N2N2

N2

N2

N2

N2 N2

N2

N2

N2 N2

N2

N2

N2

N2

N2

N2

N2

N2 N2

N2

N2

N2

N2

N2

N2 N2

N2

N2

N2

N2

N2

N2

N2

N2

N2

N2

DD1

DD1

DV1

DD2

N2

12TN401

12TN401

N2

N2

N2

N2

N2

N2

N2

N2

CABLE PATH FROM

T4-01 IN BLDG 01STN101

N2

N2

HR

1A122A

BLDG 01S: SEE SHEET 01STN101

BLDG 01A: SEE SHEET 01ATN101

BLDG 23R: SEE SHEET 23RTN101

BLDG 23

B L D

G

R

S

E E

S H

E E

T

R

T N

BLDG 01S: SEE SHEET 01STN101

BLDG 12

BLDG 01SBLDG 23R

BLDG 23

BLDG 01A

BLDG 01W

BLDG 02

BLDG 01

BLDG 12

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:4

:2 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

L E

V E

L

.r v t

12TN101

BLDG 12 - LEVEL 01 -TELECOMMUNICATIONS

PLAN

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

- 3/32" = 1'-0"

1 BLDG 12 - LEVEL 01 -TELECOMMUNICATIONS PLAN

PROJECT

NORTH

8'0 16' 24'

TRUE

NORTH

GENERAL NOTES

KEY PLAN

KEY NOTES

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO

BE DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS

OTHERWISE NOTED.

2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS

TO EXTEND TO ASSOCIATED TR AS REQUIRED.

6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED

TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL

LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED

FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF

A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

7. WHEN PROVIDING A WAO IN LOCATIONS WHERE AN EXISTING WAO CURRENTLY

DOES NOT EXIST, PROVIDE (1) 4-INCHSQUARE BACKBOX WITH SINGLE-GANG

REDUCING MUD RING AND (1) 1-1/4" CONDUIT EXTENDING FROM BACKBOX TO

ACCESSIBLE CEILING SPACE. ONCE IN ACCESSIBLE CEILING SPACE, CABLING SHALL

EXTEND TO ITS ASSOCIATED TR VIA CABLE TRAY; UTILIZE J-HOOKS EVERY 48” WHEN

TRANSITIONING TO OR FROM CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT,

EXTEND HORIZONTAL CABLING FROM WAO TO TR VIA J-HOOKS ONLY.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO

SEAL IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS

FOR PARTITION TYPES AND WALL HEIGHTS.

10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES ON AS-BUILT DRAWINGS.

11. GREYED OUT WAO'S SHALL BE DEMOLISHED BACK TO THE SOURCE AND NOT

REPLACED. PLACE A BLANK FACEPLATE OVER THE OUTLET BOX.

12. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE

DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,

ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND

ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.

13. THE CONTRACTOR SHALL BID AND INSTALL CAT6A CABLE WITH AN OD NOT

GREATER THAN 0.250" (6.35mm) (4) CAT6A CABLES WITH AN 0.250" (6.35mm) OD OR

SMALLER CAN BE INSTALLED IN A 3/4” CONDUIT SUPPORTING A 40% FILL RATIO.

Revisions: Date:

PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO REPLACE

EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT SHALL REMAIN

AND BE UTILIZED TO FEED NEW CABLING; REFERENCE DETAIL '1' ON SHEET TN501 AND

GENERAL NOTES ON THIS SHEET FOR ADDITIONAL INFORMATION. COORDINATE WITH

VA FOR EXACT OUTLET PLACEMENT.

EXISTING WIRELESS ACCESS POINT SHALL BE RE-FED WITH (2) CAT6A CABLES.

PROVIDE CABLE TRAY AS INDICATED. REFERENCE DETAIL "6" ON SHEET TN501 AND

TELECOMMUNICATIONS WAO AND CABLE TRAY SCHEDULE ON SHEET TN701. WHERE

WALL EXTENDS TO CEILING, CABLE TRAY SHALL STOP AND TRANSITION TO

HORIZONTAL FIRE STOP SLEEVES [(2) 4", MINIMUM]. WHERE EXISTING CABLE TRAY IS

PRESENT, IT SHALL BE DEMOLISHED AND REPLACED AS INDICATED. EXISTING

SLEEVES MAY BE UTILIZED IF SUITABLE FOR REUSE, BUT NOT IN PLACE OF FIRE STOP

SLEEVES AS MENTIONED ABOVE. WHERE CLEARANCES OR OBSTRUCTIONS DO NOT

PERMIT INSTALLATION OF CABLE TRAY, PROVIDE J-HOOKS AS REQUIRED FOR CABLE

DISTRIBUTION.

PROVIDE (2) 4" HORIZONTAL SLEEVES.

WAP

WAP

WAP

WAP

WAP

WAP

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.

6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO

REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,

MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE

INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY

FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

7. WHEN PROVIDING A WAO IN LOCATIONS WHERE AN EXISTING WAO CURRENTLY

DOES NOT EXIST, PROVIDE (1) 4-INCHSQUARE BACKBOX WITH SINGLE-GANG

REDUCING MUD RING AND (1) 1-1/4" CONDUIT EXTENDING FROM BACKBOX TO

ACCESSIBLE CEILING SPACE. ONCE IN ACCESSIBLE CEILING SPACE, CABLING SHALL

EXTEND TO ITS ASSOCIATED TR VIA CABLE TRAY; UTILIZE J-HOOKS EVERY 48” WHEN

TRANSITIONING TO OR FROM CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND

HORIZONTAL CABLING FROM WAO TO TR VIA J-HOOKS ONLY.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

11. GREYED OUT WAO'S SHALL BE DEMOLISHED BACK TO THE SOURCE AND NOT

REPLACED. PLACE A BLANK FACEPLATE OVER THE OUTLET BOX.

12. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE

DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,

ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND

ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.

13. THE CONTRACTOR SHALL BID AND INSTALL CAT6A CABLE WITH AN OD NOT GREATER

THAN 0.250" (6.35mm) (4) CAT6A CABLES WITH AN 0.250" (6.35mm) OD OR SMALLER

CAN BE INSTALLED IN A 3/4” CONDUIT SUPPORTING A 40% FILL RATIO.

AREA SHOWN

H I J K L M N O P Q R

S T

2A130A

2A130

2A129

2A128

F. TLT

2A126

SUP

2A127

2A125

ELEV

P7

OFFICE

2A124

CHF. S.W.

2A123

OFFICE

2A122C

VEST.

2A122

OFFICE

2A122B

2A122A

2A121

2A117

2A116

2A115

2A120

2A119

STAIR

2A114

2A113A

2A113

KITCHEN

2A112

HAC

2A111

ELEC

2A110

SUP

2A108

MEN

2A107

LIBRARY

CORRIDOR

WALSH

CONFERENCE

2A100

2A101a

STAIRS

LRC EQUIP

2A135

EDUC

ASST

2A134

VISUAL

INFO.

SPEC.

2A133

2A101b

2A101

CLOSET

2B111b

MED.

MEDIA

PRODUCTION

2A132

TYP.

B L D

G

B L D

G

B L D

G

B L D

G

A

S

E E

S H

E E

T

A

T N

BLDG 23R: SEE SHEET 23RTN102

BLDG 23

BLDG 01S: SEE SHEET 01STN102

BLDG 12

12TN402

12TN402

12TN402

TYP.

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2 DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2 DV1

DD2

N2

N2

N2

N2

N2

N2

N2

N2

N2

N2 N2 N2

N2 N2

N2 N2

N2N2

N2

N2N2

N2

N2

N2 N2

N2 N2

N2

N2

N2

N2

N2

N2

N2 N2

N2

N2

N2 N2

N2

N2

N2

N2

DD3

DD2

N2

N2

N2

N2

N2

N2

N2

N2

N2

N2

N2

N2

N2

N2

N2

CABLE PATH FROM T4-02 IN BLDG 01STN102

N2

B L D

G

R

S

E E

S H

E E

T

R

T N

BLDG 01S: SEE SHEET 01STN102

BLDG 01A: SEE SHEET 01ATN102

BLDG 01A BLDG 01

BLDG 01W

BLDG 02BLDG 01S

BLDG 23R

BLDG 23

BLDG 12

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:2

:5 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

L E

V E

L

.r v t

12TN102

BLDG 12 - LEVEL 02 - TELECOMMUNICATIONS

PLAN

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

GENERAL NOTES

KEY PLAN

- 1" = 10'-0"

1 BLDG 12 - LEVEL 02 - TELECOMMUNICATIONS PLAN 0 10' 20'

PROJECT

NORTH

1 PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO REPLACE

EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT SHALL REMAIN

AND BE UTILIZED TO FEED NEW CABLING; REFERENCE DETAIL '1' ON SHEET TN501

AND GENERAL NOTES ON THIS SHEET FOR ADDITIONAL INFORMATION. COORDINATE

WITH VA FOR EXACT OUTLET PLACEMENT.

PROVIDE CABLE TRAY AS INDICATED. REFERENCE DETAIL "6" ON SHEET TN501 AND

TELECOMMUNICATIONS WAO AND CABLE TRAY SCHEDULE ON SHEET TN701. WHERE

WALL EXTENDS TO CEILING, CABLE TRAY SHALL STOP AND TRANSITION TO

HORIZONTAL FIRE STOP SLEEVES [(2) 4", MINIMUM]. WHERE EXISTING CABLE TRAY IS

PRESENT, IT SHALL BE DEMOLISHED AND REPLACED AS INDICATED. EXISTING

SLEEVES MAY BE UTILIZED IF SUITABLE FOR REUSE, BUT NOT IN PLACE OF FIRE

STOP SLEEVES AS MENTIONED ABOVE. WHERE CLEARANCES OR OBSTRUCTIONS

DO NOT PERMIT INSTALLATION OF CABLE TRAY, PROVIDE J-HOOKS AS REQUIRED

FOR CABLE DISTRIBUTION.

EXISTING WIRELESS ACCESS POINT SHALL BE RE-FED WITH (2) CAT6A CABLES.

PROVIDE (2) 4" HORIZONTAL SLEEVES.

PROJECT

NORTH

Revisions: Date:

DATA OUTLET AND DEVICES IN THIS AREA SHALL BE SERVED FROM

TELECOMMUNICATIONS ROOM T4-02 AT BLDG 01S,TR TOWER 4, LEVEL 02.

KEY NOTES

WAP

WAP

WAP

WAP

20TN401a

MRT

CODER

20112

MRT

CODER

20111

IT CLOSET

20120

TR

20121

DINING/

BREAK

ROOM

20102

MECH

20117

MFH

COORDINATOR

20118A

REC

THERAPIST

20118B

REGISTERED

NURSE /

NURSE

PRACTITIONER

20118

PSYCHOLOGIST

20118C

DIETITIAN

20118D

STAIRS

20184

BREAK

20123

MAJOR

ROBERT L.

BIAS

CONFERENCE

ROOM

20122

TOILET

ROOM

20104

TOILET

ROOM

20105

MRT

CODER

20113

MRT

CODER

20114

MRT

CODER

20106

MRT

CODER

20107

MRT

CODER

20109

MRT

CODER

20110

ENTRY

VESTIBULE

20100

LOBBY

20101

CORRIDOR

20140

CORRIDOR

20138

CORRIDOR

20141

RADIOLOGY

FILE

STORAGE

20129

SPRINKLER

ROOM

20138EXT

FILE

STORAGE

ROOM

(MAS &

HIMS)

20124

MR

STORAGE

20125

20136

20135

20134

VOLUNTARY

SERVICE

DAV

SUPPORT

20133

VESTIBULE

20144

TOILET

20132

HAC

20131

ELECTRICAL

20130

BIO

HAZARD

SOILED

20128

CLEAN

STORAGE

20127

STORAGE

20126

WORKERS

COMP FILE

STORAGE

20137

20TN401b

PSA MFH

20115

HBPC

COORD

20116

ELECTRICAL

20139EXT

TYP.

DATA OUTLETS AND DEVICES IN THIS AREA SHALL BE

SERVED FROM TELECOMMUNICATIONS ROOM 20121.

A

B C D

E F G H

I

20TN401b

20TN401a

TYP.

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

N2 N2 N2N2

N2

N2 N2 N2 N2

N2

N2

N2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

20TN401a

20TN401a

20TN401b

20TN401b

N2

N2

N2 N2

N2

TN508

TN508

TN509

TN509

AREA SHOWN

BLDG 20

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:0

:5 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

.r v t

20TN101

BLDG 20 - LEVEL 01 - TELECOMMUNICATIONS

PLAN

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

GENERAL NOTES

- 1/8" = 1'-0"

1 BLDG 20 - LEVEL 01 - TELECOMMUNICATIONS PLAN 4'0 8' 16'

TRUE

NORTH

PROJECT

NORTH

1 PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO

REPLACE EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT

SHALL REMAIN AND BE UTILIZED TO FEED NEW CABLING; REFERENCE DETAIL

'1' ON SHEET TN501 AND GENERAL NOTES ON THIS SHEET FOR ADDITIONAL

INFORMATION. COORDINATE WITH VA FOR EXACT OUTLET PLACEMENT.

EXISTING WIRELESS ACCESS POINT SHALL BE RE-FED WITH (2) CAT6A CABLES.

PROVIDE CABLE TRAY AS INDICATED. REFERENCE DETAIL "6" ON SHEET TN501 AND

TELECOMMUNICATIONS WAO AND CABLE TRAY SCHEDULE ON SHEET TN701. WHERE

WALL EXTENDS TO CEILING, CABLE TRAY SHALL STOP AND TRANSITION TO

HORIZONTAL FIRE STOP SLEEVES [(2) 4", MINIMUM]. WHERE EXISTING CABLE TRAY IS

PRESENT, IT SHALL BE DEMOLISHED AND REPLACED AS INDICATED. EXISTING

SLEEVES MAY BE UTILIZED IF SUITABLE FOR REUSE, BUT NOT IN PLACE OF FIRE

STOP SLEEVES AS MENTIONED ABOVE. WHERE CLEARANCES OR OBSTRUCTIONS

DO NOT PERMIT INSTALLATION OF CABLE TRAY, PROVIDE J-HOOKS AS REQUIRED

FOR CABLE DISTRIBUTION.

LOCKING TDU (TUBE DISTRIBUTION UNIT) ENCLOSURE TUBE.

PROVIDE (2) 4" HORIZONTAL SLEEVES.

PROVIDE (2) TWO-INCH CONDUITS.

PROVIDE (2) TWO-INCH CONDUITS TO TR 20211A ON FLOOR ABOVE.

PROVIDE (2) TWO-INCH CONDUIT TO ROOM 20228 ON FLOOR ABOVE.

OSP INFRASTRUCTURE. REFER TO CIVIL DRAWING CS100 FOR CONTINUATION.

KEY PLAN

KEY NOTES

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO

BE DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS

OTHERWISE NOTED.

2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS

TO EXTEND TO ASSOCIATED TR AS REQUIRED.

6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED

TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL

LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED

FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF

A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET

CURRENTLY DOES NOT EXIST, PROVIDE (1) 1" CONDUIT FROM NEW BACKBOX TO

ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO

TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM

OUTLET TO TR AS REQUIRED.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO

SEAL IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS

FOR PARTITION TYPES AND WALL HEIGHTS.

10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES ON AS-BUILT DRAWINGS.

11. GREYED OUT WAO'S SHALL BE DEMOLISHED BACK TO THE SOURCE AND NOT

REPLACED. PLACE A BLANK FACEPLATE OVER THE OUTLET BOX.

12. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE

DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,

ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND

ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION

13. THE CONTRACTOR SHALL BID AND INSTALL CAT6A CABLE WITH AN OD NOT

GREATER THAN 0.250" (6.35mm) (4) CAT6A CABLES WITH AN 0.250" (6.35mm) OD OR

SMALLER CAN BE INSTALLED IN A 3/4” CONDUIT SUPPORTING A 40% FILL RATIO.

Revisions: Date:

T D

U

T D

U T

D U

TDU

20TN402a

TR

20211A

SERVER

ROOM

SECURE

20211

20212

20213

20214

20216

20215

20218-

20217

20225

20224

20223

20222

20226

20227

20220

20221

20230-

20231

20229

20228

STAIRWAY

20232

20203

20202

20234

IT GROUP

20204

COMP

TECH

20205

20206

ASSISTANT

CHIEF OF

SERVICE

20207

LEAD

COM TECH

20208

COMP

TECH

20209

COMP

TECH

20210

STAIRWAY

20194

20236

TYP.

DATA OUTLETS AND DEVICES IN THIS AREA SHALL BE

SERVED FROM TELECOMMUNICATIONS ROOM 20211A.

20TN402a

A

B C D

E F G H

I

20219

TYP.

20TN402a

20TN402a

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2 N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2 N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

N2

DV1

DD2

20TN402b

20TN402b

TN509

AREA SHOWN

BLDG 20

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0 /2

:1

:5 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

.r v t

20TN102

BLDG 20 - LEVEL 02 - TELECOMMUNICATIONS

PLAN

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

GENERAL NOTES

- 1/8" = 1'-0"

1 BLDG 20 - LEVEL 02 - TELECOMMUNICATIONS PLAN 4'0 8' 16'

TRUE

NORTH

PROJECT

NORTH

1 PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO

REPLACE EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT

SHALL REMAIN AND BE UTILIZED TO FEED NEW CABLING; REFERENCE DETAIL

'1' ON SHEET TN501 AND GENERAL NOTES ON THIS SHEET FOR ADDITIONAL

INFORMATION. COORDINATE WITH VA FOR EXACT OUTLET PLACEMENT.

PROVIDE CABLE TRAY AS INDICATED. REFERENCE DETAIL "6" ON SHEET TN501 AND

TELECOMMUNICATIONS WAO AND CABLE TRAY SCHEDULE ON SHEET TN701. WHERE

WALL EXTENDS TO CEILING, CABLE TRAY SHALL STOP AND TRANSITION TO

HORIZONTAL FIRE STOP SLEEVES [(2) 4", MINIMUM]. WHERE EXISTING CABLE TRAY IS

PRESENT, IT SHALL BE DEMOLISHED AND REPLACED AS INDICATED. EXISTING

SLEEVES MAY BE UTILIZED IF SUITABLE FOR REUSE, BUT NOT IN PLACE OF FIRE

STOP SLEEVES AS MENTIONED ABOVE. WHERE CLEARANCES OR OBSTRUCTIONS

DO NOT PERMIT INSTALLATION OF CABLE TRAY, PROVIDE J-HOOKS AS REQUIRED

FOR CABLE DISTRIBUTION.

LOCKING TDU (TUBE DISTRIBUTION UNIT) ENCLOSURE TUBE.

PROVIDE (2) TWO-INCH CONDUIT FROM ELEC 20139EXT ON FLOOR BELOW.

PROVIDE (2) TWO-INCH CONDUIT FROM BREAK 20123 ON FLOOR BELOW.

PROVIDE (2) TWO-INCH CONDUIT.

KEY PLAN

KEY NOTES

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO

BE DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS

OTHERWISE NOTED.

2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS

TO EXTEND TO ASSOCIATED TR AS REQUIRED.

6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED

TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL

LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED

FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF

A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

7. WHERE NEW DATA OUTLETS ARE BEING PROVIDED AND EXISTING DATA OUTLET

CURRENTLY DOES NOT EXIST, PROVIDE (1) 1" CONDUIT FROM NEW BACKBOX TO

ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO

TR VIA CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM

OUTLET TO TR AS REQUIRED.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO

SEAL IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS

FOR PARTITION TYPES AND WALL HEIGHTS.

10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES ON AS-BUILT DRAWINGS.

11. GREYED OUT WAO'S SHALL BE DEMOLISHED BACK TO THE SOURCE AND NOT

REPLACED. PLACE A BLANK FACEPLATE OVER THE OUTLET BOX.

12. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE

DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,

ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND

ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION

13. THE CONTRACTOR SHALL BID AND INSTALL CAT6A CABLE WITH AN OD NOT

GREATER THAN 0.250" (6.35mm) (4) CAT6A CABLES WITH AN 0.250" (6.35mm) OD OR

SMALLER CAN BE INSTALLED IN A 3/4” CONDUIT SUPPORTING A 40% FILL RATIO.

Revisions: Date:

T D

U T

D U

WAP

WAP

WAP

WAP

WAP

WAP

360°

AREA SHOWN

A B D E F H I JGC

23RTN400B

B L D

G

R

S

T N

B

DATA OUTLETS AND DEVICES IN THIS AREA SHALL BE

SERVED FROM TELECOMMUNICATIONS ROOM B09.

BLDG 23R

BLDG 23

TYP.

BLDG 01S

BLDG 12

BLDG 23R

BLDG 23

B L D

G

23RTN400B

23RTN400B

TYP.

DD2

N2

DD2

N2

DV1

DD2

N2

DIAGNOST

TREATMENT

B20

FEED/

BEDDING

B21

ELEC.

B22

REFRIG

B23

QUARNTN

ROOM

B01

SIG./PH.

B27

T. SURG.

B19A

PRO LAB

B19

S. SURG.

B18A

ELEVATOR

SE-1

CORRIDOR

CB-6

CORRIDOR

CB-5

WORK/SUPP

B18

POST OP

B17

PREP/ SCRUB

B16

ANIMAL

B15

ANIMAL

B14

ANIMAL

B24

ANIMAL

B25

ANIMAL

B26

ANIMAL

B13

CLN CAGE

WASH

B08

SOILED CAGE

WASH

B10

CAGE STO.

B08A

RECEIVING

B02

MEN

B03

WOMEN

B04

COLD RM

B05

H.A.C.

B06

NECROPSY

B07

TRASH

B32

MU FLAM

B31

VA FLAM

B28

VA GAS

B29

MU GAS

B30

VET OFF

B12

PRO LAB

B11

SUP. OFF

B12A TR

B09

CORRIDOR

CB-2

CORRIDOR

CB-1

STAIR

S-1

CORRIDOR

CORRIDOR

147-

DD3

N2

DD3

N2

DD3

N2 DD3

N2

DD3

N2

DD3

N2

TN509

TN509

BLDG 23R

BLDG 02

BLDG 01S

BLDG 23

BLDG 01

BLDG 12

BLDG 01W

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:4

:3 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

B A

S E

M E

N T

.r v t

23RTN100B

BLDG 23R - LEVEL 00B -

TELECOMMUNICATIONS PLAN

23R

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

PROJECT

NORTH

- 1/8" = 1'-0"

1 BLDG 23R - LEVEL 00B - TELECOMMUNICATIONS PLAN 4'0 8' 16'

PROJECT

NORTH

Revisions: Date:

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO

BE DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS

OTHERWISE NOTED.

2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS

TO EXTEND TO ASSOCIATED TR AS REQUIRED.

6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED

TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL

LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED

FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF

A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

7. WHEN PROVIDING A WAO IN LOCATIONS WHERE AN EXISTING WAO CURRENTLY

DOES NOT EXIST, PROVIDE (1) 4-INCHSQUARE BACKBOX WITH SINGLE-GANG

REDUCING MUD RING AND (1) 1-1/4" CONDUIT EXTENDING FROM BACKBOX TO

ACCESSIBLE CEILING SPACE. ONCE IN ACCESSIBLE CEILING SPACE, CABLING SHALL

EXTEND TO ITS ASSOCIATED TR VIA CABLE TRAY; UTILIZE J-HOOKS EVERY 48” WHEN

TRANSITIONING TO OR FROM CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT,

EXTEND HORIZONTAL CABLING FROM WAO TO TR VIA J-HOOKS ONLY.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO

SEAL IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS

FOR PARTITION TYPES AND WALL HEIGHTS.

10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES ON AS-BUILT DRAWINGS.

11. GREYED OUT WAO'S SHALL BE DEMOLISHED BACK TO THE SOURCE AND NOT

REPLACED. PLACE A BLANK FACEPLATE OVER THE OUTLET BOX.

12. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE

DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,

ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND

ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION

13. THE CONTRACTOR SHALL BID AND INSTALL CAT6A CABLE WITH AN OD NOT

GREATER THAN 0.250" (6.35mm) (4) CAT6A CABLES WITH AN 0.250" (6.35mm) OD OR

SMALLER CAN BE INSTALLED IN A 3/4” CONDUIT SUPPORTING A 40% FILL RATIO.

PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO

REPLACE EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT

SHALL REMAIN AND BE UTILIZED TO FEED NEW CABLING; REFERENCE DETAIL "1" ON

SHEET TN501 AND THE GENERAL NOTES ON THIS SHEET FOR ADDITIONAL

INFORMATION. COORDINATE WITH VA FOR EXACT OUTLET PLACEMENT.

EXISTING WIRELESS ACCESS POINT SHALL BE RE-FED WITH (2) CAT6A CABLES.

PROVIDE CABLE TRAY AS INDICATED. REFERENCE DETAIL "6" ON SHEET TN501 AND

TELECOMMUNICATIONS WAO AND CABLE TRAY SCHEDULE ON SHEET TN701.

WHERE WALL EXTENDS TO CEILING, CABLE TRAY SHALL STOP AND TRANSITION TO

HORIZONTAL FIRE STOP SLEEVES [(2) 4", MINIMUM]. WHERE EXISTING CABLE TRAY

IS PRESENT, IT SHALL BE DEMOLISHED AND REPLACED AS INDICATED. EXISTING

SLEEVES MAY BE UTILIZED IF SUITABLE FOR REUSE, BUT NOT IN PLACE OF FIRE

STOP SLEEVES AS MENTIONED ABOVE. WHERE CLEARANCES OR OBSTRUCTIONS

DO NOT PERMIT INSTALLATION OF CABLE TRAY, PROVIDE J-HOOKS AS REQUIRED

FOR CABLE DISTRIBUTION.

LOCKING TDU (TUBE DISTRIBUTION UNIT) ENCLOSURE TUBE.

PROVIDE (2) FOUR-INCH HORIZONTAL SLEEVES.

PROVIDE (2) TWO-INCH CONDUITS TO ELEC G03 ON FLOOR ABOVE.

PROVIDE (2) TWO-INCH CONDUITS.

GENERAL NOTES

KEY NOTES

KEY PLAN

TDU

AREA SHOWN

A B D E F H I J KGC

B L D

G

R

B L D

G

S

S

E E

S H

E E

T

S

T N

G

B L D

G

B L D

G

S E

E S

H E

E T

T

N G

BLDG 23R

BLDG 23

DATA OUTLETS AND DEVICES IN THIS AREA SHALL BE SERVED FROM

TELECOMMUNICATIONS ROOM B09 ON LEVEL 00B.

TYP.

ELEVATOR

P-2

STAIR

S-2

OPEN MECHANICAL SPACE

GO7

MECH.

G02

CORRIDOR

G07

LIFT EQUIP.

G06

ELEVATOR EQUIP.

G01

ELEVATOR

SE-1

STAIR

S-1

LOBBY

G05

SIGNAL/PH

SE-2

ELEC.

G03

CORRIDOR

C-G1

N2

N2

N2

N2

TYP.

7 6

BLDG 01

BLDG 02

BLDG 01W

BLDG 01SBLDG 23R

BLDG 23

BLDG 01A

BLDG 12

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:5

:5 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

G R

O U

N D

F L

O O

R .r v t

23RTN100G

BLDG 23R - LEVEL 00G -

TELECOMMUNICATIONS PLAN

23R

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

PROJECT

NORTH

- 1/8" = 1'-0"

1 BLDG 23R - LEVEL 00G - TELECOMMUNICATIONS PLAN 4'0 8' 16'

PROJECT

NORTH

Revisions: Date:

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO

BE DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS

OTHERWISE NOTED.

2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.

6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED

TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL

LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED

FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF

A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

7. WHEN PROVIDING A WAO IN LOCATIONS WHERE AN EXISTING WAO CURRENTLY

DOES NOT EXIST, PROVIDE (1) 4-INCHSQUARE BACKBOX WITH SINGLE-GANG

REDUCING MUD RING AND (1) 1-1/4" CONDUIT EXTENDING FROM BACKBOX TO

ACCESSIBLE CEILING SPACE. ONCE IN ACCESSIBLE CEILING SPACE, CABLING SHALL

EXTEND TO ITS ASSOCIATED TR VIA CABLE TRAY; UTILIZE J-HOOKS EVERY 48” WHEN

TRANSITIONING TO OR FROM CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT,

EXTEND HORIZONTAL CABLING FROM WAO TO TR VIA J-HOOKS ONLY.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO

SEAL IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS

FOR PARTITION TYPES AND WALL HEIGHTS.

10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

11. GREYED OUT WAO'S SHALL BE DEMOLISHED BACK TO THE SOURCE AND NOT

REPLACED. PLACE A BLANK FACEPLATE OVER THE OUTLET BOX.

12. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE

DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,

ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND

ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.

13. THE CONTRACTOR SHALL BID AND INSTALL CAT6A CABLE WITH AN OD NOT

GREATER THAN 0.250" (6.35mm) (4) CAT6A CABLES WITH AN 0.250" (6.35mm) OD OR

SMALLER CAN BE INSTALLED IN A 3/4” CONDUIT SUPPORTING A 40% FILL RATIO.

GENERAL NOTES

KEY PLAN

PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO

REPLACE EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT

SHALL REMAIN AND BE UTILIZED TO FEED NEW CABLING; REFERENCE DETAIL "1" ON

SHEET TN501 AND THE GENERAL NOTES ON THIS SHEET FOR ADDITIONAL

INFORMATION. COORDINATE WITH VA FOR EXACT OUTLET PLACEMENT.

PROVIDE CONDUIT (4", MINIMUM) WITH APPROPRIATE FIRE-PROOFING AND

CAULKING AS REQUIRED TO EXTEND FROM LEVEL 00B ACCESSIBLE CEILING TO

LEVEL 00G ACCESSIBLE CEILING. CONDUIT PROVIDED TO SERVE HORIZONTAL

CABLING SERVING WAOs FROM TR AS INDICATED ON PLANS.

PROVIDE CONDUIT (4", MINIMUM) WITH APPROPRIATE FIRE-PROOFING AND

CAULKING AS REQUIRED TO EXTEND FROM LEVEL 00G ACCESSIBLE CEILING TO

LEVEL 01 ACCESSIBLE CEILING. CONDUIT PROVIDED TO SERVE HORIZONTAL

CABLING SERVING WAOs FROM TR AS INDICATED ON PLANS.

PROVIDE CABLE TRAY AS INDICATED. REFERENCE DETAIL "6" ON SHEET TN501 AND

TELECOMMUNICATIONS WAO AND CABLE TRAY SCHEDULE ON SHEET TN701.

WHERE WALL EXTENDS TO CEILING, CABLE TRAY SHALL STOP AND TRANSITION TO

HORIZONTAL FIRE STOP SLEEVES [(2) 4", MINIMUM]. WHERE EXISTING CABLE TRAY

IS PRESENT, IT SHALL BE DEMOLISHED AND REPLACED AS INDICATED. EXISTING

SLEEVES MAY BE UTILIZED IF SUITABLE FOR REUSE, BUT NOT IN PLACE OF FIRE

STOP SLEEVES AS MENTIONED ABOVE. WHERE CLEARANCES OR OBSTRUCTIONS

DO NOT PERMIT INSTALLATION OF CABLE TRAY, PROVIDE J-HOOKS AS REQUIRED

FOR CABLE DISTRIBUTION.

PROVIDE (2) TWO-INCH CONDUITS TO ROOM 117 ON FLOOR ABOVE.

PROVIDE (2) TWO-INCH CONDUITS TO ROOM B22 ON FLOOR BELOW.

PROVIDE (2) TWO-INCH CONDUITS TO ROOM B21 ON FLOOR BELOW.

KEY NOTES

WAP

WAP

AREA SHOWN

A B D E F H I JGC

TYP.

CONF.

INSTR. STOR.

WOMEN

115 MEN

ELEC

SIG/PH

STAIRS

S-1

LAB

101STORAGE

H.A.C.

LAB

LAB

LOUNGE

BSL

107B

LAB

SEC'Y CLERICAL

WP/

COMPUTER

COPY

LAB

105A

LAB

105B

LAB

105C

ADM. OFFICE

110B

ASSOC. CHIEF

STAFF

110A

GEN. LAB.

ANTE

107A

TLT

107C

ELEVATOR

SE - 1

MECH

SHAFT

SE-2

SAFETY

ALCOVE

SE-3

LAB

SAFETY

ALCOVE

SE - 4

S-2

P-2

B L D

G

R

B L D

G

S

S

E E

S H

E E

T

S

T N

BLDG 23R

BLDG 23

23RTN401

23RTN401

DATA OUTLETS AND DEVICES IN THIS AREA SHALL BE SERVED FROM

TELECOMMUNICATIONS ROOM B09 AT BLDG 23R, LEVEL 00B.

TYP.

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

DV1

DD2

N2

N2

N2

N2

N2

N2

N2

N2

N2

N2

DV1

DD3

DV2

DD2

N2

N2

N2

N2 N2

N2

N2

N2

N2

BLDG 01SBLDG 23R

BLDG 23

BLDG 01A

BLDG 01W

BLDG 02

BLDG 01

BLDG 12

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:4

:3 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

L E

V E

L

.r v t

23RTN101

BLDG 23R - LEVEL 01 -

TELECOMMUNICATIONS PLAN

23R

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

- 1/8" = 1'-0"

1 BLDG 23R - LEVEL 01 - TELECOMMUNICATIONS PLAN 4'0 8' 16'

PROJECT

NORTH

TRUE

NORTH

GENERAL NOTES

KEY PLAN

KEY NOTES

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO

BE DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS

OTHERWISE NOTED.

2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS

TO EXTEND TO ASSOCIATED TR AS REQUIRED.

6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED

TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL

LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED

FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF

A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

7. WHEN PROVIDING A WAO IN LOCATIONS WHERE AN EXISTING WAO CURRENTLY

DOES NOT EXIST, PROVIDE (1) 4-INCHSQUARE BACKBOX WITH SINGLE-GANG

REDUCING MUD RING AND (1) 1-1/4" CONDUIT EXTENDING FROM BACKBOX TO

ACCESSIBLE CEILING SPACE. ONCE IN ACCESSIBLE CEILING SPACE, CABLING SHALL

EXTEND TO ITS ASSOCIATED TR VIA CABLE TRAY; UTILIZE J-HOOKS EVERY 48” WHEN

TRANSITIONING TO OR FROM CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT,

EXTEND HORIZONTAL CABLING FROM WAO TO TR VIA J-HOOKS ONLY.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO

SEAL IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS

FOR PARTITION TYPES AND WALL HEIGHTS.

10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES ON AS-BUILT DRAWINGS.

11. GREYED OUT WAO'S SHALL BE DEMOLISHED BACK TO THE SOURCE AND NOT

REPLACED. PLACE A BLANK FACEPLATE OVER THE OUTLET BOX.

12. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE

DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,

ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND

ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.

13. THE CONTRACTOR SHALL BID AND INSTALL CAT6A CABLE WITH AN OD NOT

GREATER THAN 0.250" (6.35mm) (4) CAT6A CABLES WITH AN 0.250" (6.35mm) OD OR

SMALLER CAN BE INSTALLED IN A 3/4” CONDUIT SUPPORTING A 40% FILL RATIO.

Revisions: Date:

PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO REPLACE

EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT SHALL REMAIN

AND BE UTILIZED TO FEED NEW CABLING; REFERENCE DETAIL '1' ON SHEET TN501 AND

GENERAL NOTES ON THIS SHEET FOR ADDITIONAL INFORMATION. COORDINATE WITH

VA FOR EXACT OUTLET PLACEMENT.

EXISTING WIRELESS ACCESS POINT SHALL BE RE-FED WITH (2) CAT6A CABLES.

PROVIDE CABLE TRAY AS INDICATED. REFERENCE DETAIL "6" ON SHEET TN501 AND

TELECOMMUNICATIONS WAO AND CABLE TRAY SCHEDULE ON SHEET TN701. WHERE

WALL EXTENDS TO CEILING, CABLE TRAY SHALL STOP AND TRANSITION TO

HORIZONTAL FIRE STOP SLEEVES [(2) 4", MINIMUM]. WHERE EXISTING CABLE TRAY IS

PRESENT, IT SHALL BE DEMOLISHED AND REPLACED AS INDICATED. EXISTING

SLEEVES MAY BE UTILIZED IF SUITABLE FOR REUSE, BUT NOT IN PLACE OF FIRE STOP

SLEEVES AS MENTIONED ABOVE. WHERE CLEARANCES OR OBSTRUCTIONS DO NOT

PERMIT INSTALLATION OF CABLE TRAY, PROVIDE J-HOOKS AS REQUIRED FOR CABLE

DISTRIBUTION.

PROVIDE CONDUIT (4", MINIMUM) WITH APPROPRIATE FIRE-PROOFING AND

CAULKING AS REQUIRED TO EXTEND FROM LEVEL 00G ACCESSIBLE CEILING TO LEVEL

01 ACCESSIBLE CEILING. CONDUIT PROVIDED TO SERVE HORIZONTAL CABLING

SERVING WAOs FROM TR AS INDICATED ON PLANS.

PROVIDE CONDUIT (4", MINIMUM) WITH APPROPRIATE FIRE-PROOFING AND

CAULKING AS REQUIRED TO EXTEND FROM LEVEL 01 ACCESSIBLE CEILING TO LEVEL

02 ACCESSIBLE CEILING. CONDUIT PROVIDED TO SERVE HORIZONTAL CABLING

SERVING WAOs FROM TR AS INDICATED ON PLANS.

PROVIDE (2) TWO-INCH CONDUITS TO ROOM T4-01 ON FLOOR ABOVE.

PROVIDE (2) TWO-INCH CONDUITS TO ROOM G03 ON FLOOR BELOW.

WAP

WAP

WAP

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.

6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO

REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,

MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE

INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY

FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

7. WHEN PROVIDING A WAO IN LOCATIONS WHERE AN EXISTING WAO CURRENTLY

DOES NOT EXIST, PROVIDE (1) 4-INCHSQUARE BACKBOX WITH SINGLE-GANG

REDUCING MUD RING AND (1) 1-1/4" CONDUIT EXTENDING FROM BACKBOX TO

ACCESSIBLE CEILING SPACE. ONCE IN ACCESSIBLE CEILING SPACE, CABLING SHALL

EXTEND TO ITS ASSOCIATED TR VIA CABLE TRAY; UTILIZE J-HOOKS EVERY 48” WHEN

TRANSITIONING TO OR FROM CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND

HORIZONTAL CABLING FROM WAO TO TR VIA J-HOOKS ONLY.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

11. GREYED OUT WAO'S SHALL BE DEMOLISHED BACK TO THE SOURCE AND NOT

REPLACED. PLACE A BLANK FACEPLATE OVER THE OUTLET BOX.

12. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE

DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,

ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND

ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.

13. THE CONTRACTOR SHALL BID AND INSTALL CAT6A CABLE WITH AN OD NOT GREATER

THAN 0.250" (6.35mm) (4) CAT6A CABLES WITH AN 0.250" (6.35mm) OD OR SMALLER

CAN BE INSTALLED IN A 3/4” CONDUIT SUPPORTING A 40% FILL RATIO.

AREA SHOWN

A B D E F H IGC

LAB

CONTROL

TEMP.

CONTROL

TEMP.

INVEST.

OFFICE

STORAGE

FLAM STO.

210INVEST.

OFFICE

GLASS

WASH

LAB

LAB

STORAGE

MECH.

SHAFT

MEN

WOMENS

ELEVATOR

SE-1

SIG./PH

ELEC.

INSTR.

STORAGE

H.S. R&D

OFFICE

216A

H.S. R & D

SEC'Y

LAB

LAB

SAFETY

ALCOVE

SAFETY

ALCOVE

H.A.C

STAIR

FACULTY

LAB

LAB

WOMEN'S

TOILET

ELEC.

ROOM

E-123

STUDENT

OFFICE

FACULTY

LAB

FACULTY

OFFICE

FACULTY

OFFICE

224A

FACULTY

LAB

LEARNING

RESOURCES

S-2

P-2

C2-3

TYP.

BLDG 23R

BLDG 23

B L D

G

R

B L D

G

S

S

E E

S H

E E

T

S

T N

TYP.

DV1

DD2 DV1

DD2N2

N2

N2

N2

N2

N2

N2

N2

N2

N2

N2

DD3

N2

BLDG 01A BLDG 01

BLDG 01W

BLDG 02BLDG 01S

BLDG 23R

BLDG 23

BLDG 12

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:2

:1 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

L E

V E

L

.r v t

23RTN102

BLDG 23R - LEVEL 02 - TELECOMMUNICATIONS

PLAN

23R

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

GENERAL NOTES

KEY PLAN

KEY NOTES

- 1/8" = 1'-0"

1 BLDG 23R - LEVEL 02 - TELECOMMUNICATIONS PLAN 4'0 8' 16'

PROJECT

NORTH

1 PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO REPLACE

EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT SHALL REMAIN

AND BE UTILIZED TO FEED NEW CABLING; REFERENCE DETAIL '1' ON SHEET TN501

AND GENERAL NOTES ON THIS SHEET FOR ADDITIONAL INFORMATION. COORDINATE

WITH A FOR EXACT OUTLET PLACEMENT.

PROVIDE CABLE TRAY AS INDICATED. REFERENCE DETAIL "6" ON SHEET TN501 AND

TELECOMMUNICATIONS WAO AND CABLE TRAY SCHEDULE ON SHEET TN701. WHERE

WALL EXTENDS TO CEILING, CABLE TRAY SHALL STOP AND TRANSITION TO

HORIZONTAL FIRE STOP SLEEVES [(2) 4", MINIMUM]. WHERE EXISTING CABLE TRAY IS

PRESENT, IT SHALL BE DEMOLISHED AND REPLACED AS INDICATED. EXISTING

SLEEVES MAY BE UTILIZED IF SUITABLE FOR REUSE, BUT NOT IN PLACE OF FIRE

STOP SLEEVES AS MENTIONED ABOVE. WHERE CLEARANCES OR OBSTRUCTIONS

DO NOT PERMIT INSTALLATION OF CABLE TRAY, PROVIDE J-HOOKS AS REQUIRED

FOR CABLE DISTRIBUTION.

EXISTING WIRELESS ACCESS POINT SHALL BE RE-FED WITH (2) CAT6A CABLES.

PROVIDE CONDUIT (4", MINIMUM) WITH APPROPRIATE FIRE-PROOFING AND

CAULKING AS REQUIRED TO EXTEND FROM LEVEL 01 ACCESSIBLE CEILING TO LEVEL

02 ACCESSIBLE CEILING. CONDUIT PROVIDED TO SERVE HORIZONTAL CABLING

SERVING WAOs FROM TR AS INDICATED ON PLANS.

PROJECT

NORTH

Revisions: Date:

DATA OUTLET AND DEVICES IN THIS AREA…