S02 - ATT 23 - 581-22-700 - 100 Drawings Part-21 of 24.pdf
PDF 19 MB Posted
- Solicitation number
- 36C77626R0025
About this file
This document is a comprehensive set of telecommunications infrastructure plans for the VA Huntington Healthcare Facility Upgrades project located at 1540 Spring Valley Drive, Huntington, WV 25704-9300. The plans detail telecommunications installations across multiple buildings (01S, 01W, 01, 02, 03, 04, 05, 06, 07, 08, 09, and 12) and multiple levels within each building, with drawings prepared by SPEES Design Build (23830 Pacific Highway S., Kent, WA 98032) as part of 100% Construction Documents dated September 3, 2025.
The telecommunications plans specify the installation of Category 6A (CAT6A) cabling throughout the facility to replace existing Category 6 and below infrastructure. Key elements include: telecommunications outlets with specified port quantities in various rooms and spaces; wireless access points (WAPs) to be re-fed with dual CAT6A cables; cable tray systems with fire-stop sleeves at penetrations; conduit runs of varying sizes (primarily 2-inch and 4-inch); pull boxes at required intervals per ANSI/TIA-569; and multiple telecommunications rooms (TRs) serving Tower 1, Tower 2, Tower 3, and Tower 4 locations. The plans incorporate fiber-optic backbone cabling with A-side and B-side diverse routing for redundancy. All cabling must meet a maximum outer diameter of 0.250 inches to support 40% conduit fill ratios. The general notes require contractor field verification of existing conditions, protection of existing work from damage, proper fire-rating sealing at penetrations, and comprehensive testing and certification of all installations. Outlet locations are marked as approximate with final placement to be coordinated with the VA and documented on as-built drawings.
View the file
Other files
Show 40 more
Latest 50 of 68 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
360°
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAPWAP
WAP
WAP
WAP
WAP
WAP
WAP
AREA SHOWN
J K L M N O P Q R S T U V W
X Y
01STN400Gb
01STN400Gb
01STN400Gb
01STN400Gb
01STN400Ga
B L D
G
S
B L D
G
S E
E S
H E
E T
T
N G
BLDG 12: SEE SHEET 12TN100G
B L D
G
S E
E S
H E
E T
T
N G
01STN400Ga
TYP.
GB160
PUBLIC ELEV.
P3
PUBLIC ELEV.
P2
PUBLIC ELEV.
P1
MEN
GB174
STAIR 1
LINEN
GB169
HAC
GB170
GB173
PUBLIC LOBBY
CG19
TELE.
GB171
ELEC.
GB172
SERVICE ELEV.
S1
SERVICE ELEV.
S2
SERVICE LOBBY
CG17
GB168g
BVA
GB168c
IRM
GB168a
EXAM
GB168k
FEE CLAIMS
GB168b
BOOTH
EXAMINER
GB168j
GB168l
GB168
GB168i
GB168h
MEDICAL
RECORDS
GB168d
GB168f
GB168e
STAIR 4
MECH RM
GB167
HEALTH TECH
GB149c
HEALTH TECH
GB149d
EXAM
GB149e
EXAM
GB149f
EXAM
GB149g
AUDIOLOGY
ROOM
GB149
RECEP
GB148
OFFICE
GB148a
OFFICE
GB148b
OFFICE
GB146
TLT
GB145
CERUMEN
MGMT
GB147b
TLT
GB144
GB143
HAC
GB142
GERI PACT
GB151
GERI PACT
GB152
GB140
GB141
STORAGE
GB141a
CLEAN SUPPLY
GB139
PALL CARE
GB138
PALL CARE
GB137
GERI PACT
GB153
GERI PACT
GB154
EXAM 8
GB136
PHARM
GB135
AMCARE ADMIN
GB150
AMCARE
GB150A
AMCARE ADMIN
GB168rr
GERI PACT
GB155HCORRIDOR
CG11
CORRIDOR
CG13
CORRIDOR
CG10
EXAM 7
GB134
EXAM 6
GB133
WALK IN CLINIC
GB156
EXAM 15
EXAM 4
GB132
LOUNGE
GB129
WALK IN CLINIC
GB158
GB127
GB130
EXAM 5
GB131
CORRIDOR
CG16
AMCARE ADMIN
GB155b
AMCARE
GB155G
EXAM 5
GB155F
VAPD
GB155c
VAPD
GB165
AMCARE ADMIN
CG24
VAPD
GB164
GB159
GB161
EXAMINER
GB149h
EXAMINER
GB149i
BOOTH
BOOTH
BOOTH
ELEC.
GB166b
TEL
GB166a
EXAMINER
GB149j
POSTIOGRAPHY
& LAB
GA121
CORRIDOR
CG14
CORRIDOR
CG15
STAIR 3
STAIR 2
MECH
GB166
DATA OUTLETS AND DEVICES IN THIS
AREA SHALL BE SERVED FROM
TELECOMMUNICATIONS ROOM T4-00G.
DATA OUTLETS AND DEVICES IN THIS
AREA SHALL BE SERVED FROM
TELECOMMUNICATIONS ROOM T1-00G.
WOMEN
GB175
BLDG 01A: SEE SHEET 01ATN100G
BLDG 01A: SEE SHEET 01ATN100G
TR TOWER 4
T4-00G
TR TOWER 1
T1-00G
01STN400Ga
01STN400Ga
TYP.
N2 N2
N2 N2 N2
N2
N2
N2 N2 N2 N2 N2 N2 N2 N2
N2
N2
N2N2N2
N2
N2
N2 N2
N2
N2
N2
N2 N2 N2
N2 N2 N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2N2
N2 N2
N2
N2
N2
N2
N2
N2
N2 N2
N2
N2
N2
N2 N2
N2
N2
N2
N2
N2
N2
N2
N2
N2 N2
N2
N2 N2
N2 N2 N2 N2
N2
N2
N2
DV1
DD2N2
N2
N2 N2
N2 N2
N2
N2
N2
N2 N2
N2
N2
N2
N2 N2
N2
N2 N2
DD3
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2 DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2 DV1
DD2
DV1
DD2 DV1
DD2
DV1
DD2
DV1
DD2 DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2 DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
N2
N2
N2
DV1
DD2
N2
DD2
N2
DD1
N2
DD1
N2
DD1
N2
N2
DD1
DD1
N2
DD1
N2 N2
DD1
DD1
DV1
DD2
N2
N2
DV1
DD2
N2
DV1
DD2
N2 N2
N2
N2
N2 N2
N2
N2
N2
N2
N2
BLDG 01S
N2
CABLE PATH FED
FROM T4-00G
CABLE PATH FED
TO 23R LVL 00G
TYP.
BLDG 01: SEE SHEET 01TN100G
BLDG 02: SEE SHEET 02TN100G
BLDG 01: SEE SHEET 01TN100G13
TYP.
TYP.
TN509
TYP.
TN509
BLDG 01
BLDG 02
BLDG 01W
BLDG 01SBLDG 23R
BLDG 23
BLDG 01A
BLDG 12
A SIDE FIBER WORK
B SIDE FIBER WORK
FIBER-OPTIC BACKBONE CABLING
REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC
CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS
DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER
PATHWAY DETAILS.
SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.
LEGEND:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/0
/2
:4
:2 a m
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /E
E
B L D
G
G R
O U
N D
F L
O O
R .r v t
01STN100G
BLDG 01S - LEVEL 00G -
TELECOMMUNICATIONS PLAN
01S
KG RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
PROJECT
NORTH
- 3/32" = 1'-0"
1 BLDG 01S - LEVEL 00G - TELECOMMUNICATIONS PLAN 8'0 16' 24'
PROJECT
NORTH
Revisions: Date:
PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO
REPLACE EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT
SHALL REMAIN AND BE UTILIZED TO FEED NEW CABLING; REFERENCE DETAIL "1" ON
SHEET TN501 AND THE GENERAL NOTES ON THIS SHEET FOR ADDITIONAL
INFORMATION. COORDINATE WITH VA FOR EXACT OUTLET PLACEMENT.
EXISTING WIRELESS ACCESS POINT SHALL BE RE-FED WITH (2) CAT6A CABLES.
PROVIDE CABLE TRAY AS INDICATED. REFERENCE DETAIL "6" ON SHEET TN501 AND
TELECOMMUNICATIONS WAO AND CABLE TRAY SCHEDULE ON SHEET TN701.
WHERE WALL EXTENDS TO CEILING, CABLE TRAY SHALL STOP AND TRANSITION TO
HORIZONTAL FIRE STOP SLEEVES [(2) 4", MINIMUM]. WHERE EXISTING CABLE TRAY
IS PRESENT, IT SHALL BE DEMOLISHED AND REPLACED AS INDICATED. EXISTING
SLEEVES MAY BE UTILIZED IF SUITABLE FOR REUSE, BUT NOT IN PLACE OF FIRE
STOP SLEEVES AS MENTIONED ABOVE. WHERE CLEARANCES OR OBSTRUCTIONS
DO NOT PERMIT INSTALLATION OF CABLE TRAY, PROVIDE J-HOOKS AS REQUIRED
FOR CABLE DISTRIBUTION.
PROVIDE (2) 4" HORIZONTAL SLEEVES.
LOCKING TDU (TUBE DISTRIBUTION UNIT) ENCLOSURE TUBE.
PROVIDE (6) TWO-INCH CONDUITS.
PROVIDE (8) TWO-INCH CONDUITS.
PROVIDE (2) TWO-INCH CONDUITS FROM ROOM T1-01 ON FLOOR ABOVE.
PROVIDE (6) TWO-INCH CONDUITS TO ROOM T1-01 ON FLOOR ABOVE.
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS
REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO
BE DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS
OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS
TO EXTEND TO ASSOCIATED TR AS REQUIRED.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED
TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL
LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED
FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF
A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
7. WHEN PROVIDING A WAO IN LOCATIONS WHERE AN EXISTING WAO CURRENTLY
DOES NOT EXIST, PROVIDE (1) 4-INCHSQUARE BACKBOX WITH SINGLE-GANG
REDUCING MUD RING AND (1) 1-1/4" CONDUIT EXTENDING FROM BACKBOX TO
ACCESSIBLE CEILING SPACE. ONCE IN ACCESSIBLE CEILING SPACE, CABLING SHALL
EXTEND TO ITS ASSOCIATED TR VIA CABLE TRAY; UTILIZE J-HOOKS EVERY 48” WHEN
TRANSITIONING TO OR FROM CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT,
EXTEND HORIZONTAL CABLING FROM WAO TO TR VIA J-HOOKS ONLY.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO
SEAL IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS
FOR PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES ON AS-BUILT DRAWINGS.
11. GREYED OUT WAO'S SHALL BE DEMOLISHED BACK TO THE SOURCE AND NOT
REPLACED. PLACE A BLANK FACEPLATE OVER THE OUTLET BOX.
12. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND
ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION
13. THE CONTRACTOR SHALL BID AND INSTALL CAT6A CABLE WITH AN OD NOT
GREATER THAN 0.250" (6.35mm) (4) CAT6A CABLES WITH AN 0.250" (6.35mm) OD OR
SMALLER CAN BE INSTALLED IN A 3/4” CONDUIT SUPPORTING A 40% FILL RATIO.
GENERAL NOTES
KEY NOTES
KEY PLAN
INTERNAL FIBER ROUTE. PROVIDE (2) TWO-INCH CONDUITS.
PROVIDE (2) TWO-INCH CONDUITS TO ROOM BB112 ON FLOOR BELOW.
PROVIDE (2) TWO-INCH CONDUITS TO ROOM 1B130 ON FLOOR ABOVE.
PROVIDE (2) TWO-INCH CONDUITS TO ROOM 1B120a ON FLOOR ABOVE.
PROVIDE (2) TWO-INCH CONDUITS TO ROOM T4-01 ON FLOOR ABOVE.
KEY NOTES
WAP WAP
WAP
WAP
WAP WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP WAP
WAP
WAP
WAP
WAP
WAP
W
W
W
WAP
AREA SHOWN
J K L M N O P Q R S T U V W X Y
ELEV
S-2
B L D
G
R
S
E E
S H
E E
T
R
T N
B L D
G
S
B L D
G
S
B L D
G
S E
E S
H E
E T
T
N
01STN401a
PT TREATMENT /
CT EXERCISE
1B125K
P.T.
1B125I
POLYTRAUMA
1B124E
ORTHOTICS
SPLINT
1B124C
1B123C
1B123B
CONFERENCE
1B122H
SEC'Y
ASSOC.
DIRECTOR
1B122F
DIRECTOR
1B122E
PASS
1B122M
COS
1B122D
KITCHEN
1B122C
STOR
1B122B
WAIT
1B122L
AA / COS
1B122A
CONN.
CORRIDOR TO
BUILDING
1S
STR 3
CORRIDOR
C1-9
TRAINING
DIRECTOR
ROOM
1B121
CORRIDOR
C1-4
ELEC
1B120a
MICROBIOLOGY
1B116
WOMEN
1B119
HSC
1B118
MEN
1B117
BIO-LAB
1B116A
CORR.
C1-7
COLD
1B116B
STERIL
1B115
DI WATER
1B113
ROOM
1B114AF. TLT
1B14B
M. TLT
SPECIAL
CHEMISTRY
1B105F
BREAK RM
1B114
STAIRS
GENERAL LAB
1B105
SPECIMEN
ACCESSION
1B105H
BLOOD SPEC'L
1B107
TLT
1B106
CORRIDOR
C1-6
CORRIDOR
C1-11
PROSTHETICS
INVENT/DISTR.
1B109
HISTO REVIEW
1B109A
CYTOLOGY
1B108C
GROSS RM
1B108B
HAC
1B111
FLOUR. MICRO
1B112
CHIEF
1B110G
RESID.
1B110F
LAB SERVICE
1B110
SEC'Y
HISTOLOGY
1B108
STAFF
1B110C
STAFF
1B110B
STAFF
1B110A
CORRIDOR
C1-10
CORRIDOR
C1-11
EXAM D
1B124G
EXAM E
1B124F
ELEC
1B1241
1B124A
1B123E
1B124B
PR / QA
1B122
1B123
CORRIDOR
C1-8
PASS
1B1221
1B123A
AAD
1B122I
1B123D
SPEECH
1B124D
STAIR
1B125N
1B125O
1B125M
WC TOILET
1B1251
TOILET
1B125J
1B125F
1B125E
IT
1B125P
ELEC
1B125Q
EXAM
1B125H
CORRIDOR
C1-12
WAITING
1B126
RECEP
1B126C
RECEP
1B125A
EXAM PROC
1B125C
BREAK
1B126E
PLSTR
1B126D
CORRIDOR
1B126A
FITTING
1B1261
FITTING
1B126J
ORTHO
1B126B
1B126L
STORAGE
1B126K
SERVICE LOBBY
C1-14
CORRIDOR
C1-15
PROSTHETICS
OFFICE
1B127
PROSTHETICS
OFFICE
1B127A
TRASH CH
1B128
LINEN CH
1B129
STAIR
MALE TOILET
1B132
FEMALE TOILET
1B133
PUBLIC LOBBY
C1-17
ELEC
1B 131
TELE
1B130
CHILLER PLANT
BUILDING #1S
TYP.
B L D
G
S E
E S
H E
E T
T
N
B L D
G
A
S
E E
S H
E E
T
A
T N
SECURE STOR.
1B105C
RECEIV.
1B104
FLAMM/TOXIC
1B105D
COLD RM
1B105E
BLOOD BANK
1B105A
CHIEF TECH
1B105G
SLIDE & BLOCK
1B108A
HISA PROG
1B126H
LAB FUME
1B126G
CPO
1B126F
PHYS
1B125D
LIN
1B125G
ADP FILES
1B122K
BULK STORAGE
1B105B
CORRIDOR
C1-5
CORRIDOR
C1-13
ELEV
1B120b
01STN401d
01STN401c
01STN401b
DATA OUTLETS AND
DEVICES IN THIS AREA
SHALL BE SERVED FROM
TELECOMMUNICATIONS
ROOM T1-01
DATA OUTLETS AND DEVICES
IN THIS AREA SHALL BE
SERVED FROM
TELECOMMUNICATIONS
ROOM T4-01
DATA OUTLETS
AND DEVICES IN
THIS AREA SHALL
BE SERVED FROM
TELECOMMUNICAT
IONS ROOM T4-01.
DATA OUTLETS
AND DEVICES IN
THIS AREA SHALL
BE SERVED
FROM
TELECOMMUNICA
TIONS ROOM
T1-01.
01STN401a
TR TOWER 4
T4-01
TR TOWER 1
T1-01
01STN401a
01STN401a
01STN401d
01STN401d 3
01STN401b
01STN401b
01STN401c
01STN401c
01STN401b
TYP.
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2 DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2 DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2 DV1
DD2
DV1
DD2
DV1
DD2 DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2 DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2N2
N2
N2
N2
N2N2
N2
N2
N2 N2
N2
N2
N2
N2
DV1
DD2
N2
N2
N2
N2 N2
N2
N2
N2 N2
N2
N2
N2 N2
N2 N2
N2
N2
N2 N2
N2
N2
N2
N2
N2 N2
N2
N2
N2
N2 N2
N2
N2
N2 N2
N2
N2 N2
N2
N2
N2
N2
N2 N2 N2
N2 N2
N2
N2
N2
N2
N2
N2 N2
N2
N2 N2
N2
N2 N2 N2
N2
N2
N2
N2
N2
N2 N2
N2
N2 N2
N2
N2
N2 N2
N2
N2
N2 N2
N2
N2 N2
N2
N2 N2
N2
N2
N2
N2
2 2
2 2
DV6 DV4
DV4
N2 N2
DD4
DV4
DV4
N2
N2
DD2
DD4
N2
N2
DD4
N2
DV1
DV1
DD3
DV1
DD4
DD2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2 N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2 N2
N2
N2
N2
N2
N2
N2
N2
CABLE PATH TO
BLDG 12
CABLE PATH TO
BLDG 23R LVL 01
N2
N2
B L D
G
A
S
E E
S H
E E
T
A
T N
B L D
G
S E
E S
H E
E T
T
N
BLDG 02: SEE SHEET 02TN101
BLDG 01: SEE SHEET 01TN101
N2
N2
16 18
TYP.
TYP.
TN509
BLDG 01SBLDG 23R
BLDG 23
BLDG 01A
BLDG 01W
BLDG 02
BLDG 01
BLDG 12
A SIDE FIBER WORK
B SIDE FIBER WORK
FIBER-OPTIC BACKBONE CABLING
REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC
CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS
DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER
PATHWAY DETAILS.
SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.
LEGEND:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/0
/2
:4
:4 a m
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /E
E
B L D
G
L E
V E
L
.r v t
01STN101
BLDG 01S - LEVEL 01 - TELECOMMUNICATIONS
PLAN
01S
KG RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
- 3/32" = 1'-0"
1 BLDG 01S - LEVEL 01 - TELECOMMUNICATIONS PLAN
PROJECT
NORTH
8'0 16' 24'
TRUE
NORTH
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS
REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO
BE DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS
OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS
TO EXTEND TO ASSOCIATED TR AS REQUIRED.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED
TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL
LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED
FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF
A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
7. WHEN PROVIDING A WAO IN LOCATIONS WHERE AN EXISTING WAO CURRENTLY
DOES NOT EXIST, PROVIDE (1) 4-INCHSQUARE BACKBOX WITH SINGLE-GANG
REDUCING MUD RING AND (1) 1-1/4" CONDUIT EXTENDING FROM BACKBOX TO
ACCESSIBLE CEILING SPACE. ONCE IN ACCESSIBLE CEILING SPACE, CABLING SHALL
EXTEND TO ITS ASSOCIATED TR VIA CABLE TRAY; UTILIZE J-HOOKS EVERY 48” WHEN
TRANSITIONING TO OR FROM CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT,
EXTEND HORIZONTAL CABLING FROM WAO TO TR VIA J-HOOKS ONLY.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO
SEAL IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS
FOR PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES ON AS-BUILT DRAWINGS.
11. GREYED OUT WAO'S SHALL BE DEMOLISHED BACK TO THE SOURCE AND NOT
REPLACED. PLACE A BLANK FACEPLATE OVER THE OUTLET BOX.
12. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND
ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.
13. THE CONTRACTOR SHALL BID AND INSTALL CAT6A CABLE WITH AN OD NOT
GREATER THAN 0.250" (6.35mm) (4) CAT6A CABLES WITH AN 0.250" (6.35mm) OD OR
SMALLER CAN BE INSTALLED IN A 3/4” CONDUIT SUPPORTING A 40% FILL RATIO.
Revisions: Date:
GENERAL NOTES
KEY PLAN
KEY NOTES
PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO REPLACE
EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT SHALL REMAIN
AND BE UTILIZED TO FEED NEW CABLING; REFERENCE DETAIL '1' ON SHEET TN501 AND
GENERAL NOTES ON THIS SHEET FOR ADDITIONAL INFORMATION. COORDINATE WITH
VA FOR EXACT OUTLET PLACEMENT.
EXISTING WIRELESS ACCESS POINT SHALL BE RE-FED WITH (2) CAT6A CABLES.
PROVIDE CABLE TRAY AS INDICATED. REFERENCE DETAIL "6" ON SHEET TN501 AND
TELECOMMUNICATIONS WAO AND CABLE TRAY SCHEDULE ON SHEET TN701. WHERE
WALL EXTENDS TO CEILING, CABLE TRAY SHALL STOP AND TRANSITION TO
HORIZONTAL FIRE STOP SLEEVES [(2) 4", MINIMUM]. WHERE EXISTING CABLE TRAY IS
PRESENT, IT SHALL BE DEMOLISHED AND REPLACED AS INDICATED. EXISTING
SLEEVES MAY BE UTILIZED IF SUITABLE FOR REUSE, BUT NOT IN PLACE OF FIRE STOP
SLEEVES AS MENTIONED ABOVE. WHERE CLEARANCES OR OBSTRUCTIONS DO NOT
PERMIT INSTALLATION OF CABLE TRAY, PROVIDE J-HOOKS AS REQUIRED FOR CABLE
DISTRIBUTION.
PROVIDE (2) 4" HORIZONTAL SLEEVES.
LOCKING TDU (TUBE DISTRIBUTION UNIT) ENCLOSURE TUBE.
PROVIDE (8) TWO-INCH CONDUITS.
PROVIDE (2) TWO-INCH CONDUITS.
PROVIDE (6) TWO-INCH CONDUITS.
PROVIDE (8) TWO-INCH CONDUITS FROM ROOM GB171 ON FLOOR BELOW.
PROVIDE (2) TWO-INCH CONDUITS TO ROOM T1-00G ON FLOOR BELOW.
PROVIDE (2) TWO-INCH CONDUITS TO ROOM T1-02 ON FLOOR ABOVE.
KEY NOTES
PROVIDE (8) TWO-INCH CONDUITS TO ROOM T1-00G ON FLOOR BELOW.
PROVIDE (2) TWO-INCH CONDUITS TO ROOM 2B191 ON FLOOR ABOVE.
PROVIDE (4) TWO-INCH CONDUITS FROM ROOM GB-171 ON FLOOR BELOW.
PROVIDE (2) TWO-INCH CONDUITS FROM ROOM GB-171 ON FLOOR BELOW.15
KEY NOTES
PROVIDE (2) TWO-INCH CONDUITS TO ROOM T4-02 ON FLOOR ABOVE.
PROVIDE (4) TWO-INCH CONDUITS FROM ROOM T4-00G ON FLOOR BELOW .
PROVIDE (2) TWO-INCH CONDUITS FROM ROOM T4-00G ON FLOOR BELOW.
PROVIDE (2) TWO-INCH CONDUITS FROM ROOM GB166b ON FLOOR BELOW.19
PROVIDE (2) TWO-INCH CONDUITS FROM ROOM GB166b ON FLOOR BELOW.
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAPWAP
WAP
WAP WAP
WAP WAP WAP WAP
WAP
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS
REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE
DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE
NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES BE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO
REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,
MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE
INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY
FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
7. WHEN PROVIDING A WAO IN LOCATIONS WHERE AN EXISTING WAO CURRENTLY
DOES NOT EXIST, PROVIDE (1) 4-INCHSQUARE BACKBOX WITH SINGLE-GANG
REDUCING MUD RING AND (1) 1-1/4" CONDUIT EXTENDING FROM BACKBOX TO
ACCESSIBLE CEILING SPACE. ONCE IN ACCESSIBLE CEILING SPACE, CABLING SHALL
EXTEND TO ITS ASSOCIATED TR VIA CABLE TRAY; UTILIZE J-HOOKS EVERY 48” WHEN
TRANSITIONING TO OR FROM CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND
HORIZONTAL CABLING FROM WAO TO TR VIA J-HOOKS ONLY.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL
IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR
PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.
11. GREYED OUT WAO'S SHALL BE DEMOLISHED BACK TO THE SOURCE AND NOT
REPLACED. PLACE A BLANK FACEPLATE OVER THE OUTLET BOX.
12. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND
ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.
13. THE CONTRACTOR SHALL BID AND INSTALL CAT6A CABLE WITH AN OD NOT GREATER
THAN 0.250" (6.35mm) (4) CAT6A CABLES WITH AN 0.250" (6.35mm) OD OR SMALLER
CAN BE INSTALLED IN A 3/4” CONDUIT SUPPORTING A 40% FILL RATIO.
AREA SHOWN
M N O P Q R S T U V W
X Y
DRESS
2B127
DRS
2B128
DRS
2B129
DRS
2B126
DRS
2B125
WC TLT
2B122a
WC STRET
2B130a
RADIO FLOUR.
2B122
RADIO FLOUR
2B120
WC TLT
2B120a
CORRIDOR
C2-6
DED. CHEST
2B131
2B132a
FILM
2B132
EQUIP
2B136
UPS
CLEAN
2B135
SOIL UTIL.
2B137
G.P. ROOM
2B153
G.P. ROOM
2B152
AUTOMATED
2B148
VIEW
2B144
HAC
2B138
DRS
2B140
DRS
2B142
RECEP. NUC. MED.
2B167a
DARK RM
2B184
PT. TLT
2B 183
NUCLEAR MEDICINE
2B186
WAITING
2B167
ELEC
2B168
TELE
2B 169
HAC
2B170
MEN
2B171a
LOUNGE
2B171
WC TOIL
2B171b
CORRIDOR
C2-42
DR. OFFICE
2B180
VIEW/CONF.
2B172
STOR
2B173
SECY\
2B179
STOR.
2B178
ULTRASOUND
2B180a
ULTRA SOUND
2B181
SCAN THYROID
2B182
SCAN STATIONARY
2B185
HIGH LEVEL IN-VITRO
2B187
WAITING RM
2B188
CORRIDOR
C2-15
SERVICE LOBBY
C2-16
I/R SUITE
2B118
BARIUM PREP
2B133
CORRIDOR
C2-8
CORRIDOR
C2-7
2B171c
CORRIDOR
C2-13
STR 4
ISOTOPIC STOR GL WASH
& STER PREP RM
2B177
LOUNGE
2B176
2B175
2B174
FILE STORAGE
2B166f
ELEC CLOSET
2B166e
CLERK TYP.
2B165
SEC'Y
2B164
COMMON VIEW
2B163
CHIEF
2B162
MRI EQUIP SCAN RM
2B166b
DRESS
2B166c
MRI WAITING
2B161a
CORRIDOR
C2-14
COMPUTER
2B145a
READING
2B145HAC
2B151
TLT
2B154
ELECT. CLO.
2B155a
TELE. CLO.
2B155b
MECH
2B155
CORRIDOR
C2-41
IMAGING LOUNGE
2B160
IRM
2B159
IRM
2B158
COMPUTER TRAINING
2B156
STAIR
CONTROL ROOM
STAIR
CORRIDOR
C2-11
INPT BEDS
2B161
CT BRIGHTSCR
2B146
32 SLICE CT
2B149
CONTROL RM
2B147
MRI CONTROL
2B166d
MRI SCAN ROOM
2B166a
CORRIDOR
C2-12
CORRIDOR
C2-10
ELEV
P - 3
ELEV
P - 2
ELEV
P - 1
PUBLIC LOBBY
C2-18
MEN
2B195
WOMEN
2B196
STAIR
EMS
2B189
HAC
2B190
TRASH CH
2B193
LINEN CH
2B194
TELE
2B191
ELEC
2B192
ELEV
S - 1
ELEV
S - 2
CORRIDOR
C2-19
WAITING
2B130
CORRIDOR
C2-5
CORRIDOR
C2-9
TYP.
BLDG 01S
BLDG 12: SEE SHEET 12TN102
B L D
G
S
B L D
G
S E
E S
H E
E T
T
N
01STN402b
01STN402b
01STN402b
DATA OUTLETS AND
DEVICES IN THIS AREA
SHALL BE SERVED FROM
TELECOMMUNICATIONS
ROOM T4-02
DATA OUTLETS AND
DEVICES IN THIS AREA
SHALL BE SERVED FROM
TELECOMMUNICATIONS
ROOM T1-02
DATA OUTLETS AND
DEVICES IN THIS AREA
SHALL BE SERVED FROM
TELECOMMUNICATIONS
ROOM T4-02
DATA OUTLETS AND
DEVICES IN THIS AREA
SHALL BE SERVED FROM
TELECOMMUNICATIONS
ROOM T1-02
B L D
G
S
B L D
G
S E
E S
H E
E T
T
N
TR TOWER 4
T4-02
TR TOWER 1
T1-02
01STN402b
01STN402a
01STN402a
TYP.
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DD2
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DV1
DD2
DV1
DD2
DD3
DV1
DD2
DD4
DD3
DV1
DD2
DV1
DD2
DV1
DD2 DV1
DD2 DD2
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DD2 DD3
DD3
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DD2DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DD2
DV1
DD2
DV1
DD2DD2
DV1
DD2
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DD4DD4
DD2
DD2 DD2
DV1
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2 DV1
DD2
DV1
DD2
DD3
DD3
DD3
DV1
DD2
DV1
DD2 DD3
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DD4
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD1
DV1
DD1
DV1
DD1
DV1
DD1
DV1
DD1
N2
N2
N2
N2
N2
N2
N2
N2
N2 N2
N2 N2 N2
N2
N2
N2 N2
N2
N2
N2
N2 N2
N2
N2
N2 N2
N2
N2 N2
N2 N2 N2
N2 N2
N2
N2
N2
N2
N2
N2 N2
N2
N2
N2
N2
N2
N2
N2 N2
N2
N2 N2
N2
N2
N2
N2
N2
N2 N2N2
N2
N2
N2
N2
N2
N2N2
N2
N2
N2 N2
N2
N2N2N2
N2
N2 N2
N2 N2N2
N2
N2 N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2 N2 N2
N2
N2 N2
N2
N2
N2
N2
N2
N2 N2
N2
N2
N2
N2
N2
DD3 DD3
N2N2
DV1
N2
N2
DV1
DV1
N2
3 3
3 3
N2
DV1
DD2
N2
N2
N2
N2
N2
N2N2 N2
N2
N2
N2
N2
N2
N2
N2
N2
CABLE PATH TO
BLDG 12
N2
01STN402a
01STN402a
BLDG 02: SEE SHEET 02TN102
BLDG 01: SEE SHEET 01TN102
B L D
G
B L D
G
A
N2
N2CHIEF
TECH.
2B117
M.TLT.
2B121
F.TLT.
2B123
ULTRA -
SOUND
2B124
LOUNGE
2B119
PASSAGE
2B198
RESID. LAB
2B197
RESID.
FELL/STUD
2B199
CORR
TYP.
TYP.
TN509
TN509
BLDG 01S
BLDG 01A BLDG 01
BLDG 01W
BLDG 02
BLDG 23R
BLDG 23
BLDG 12
A SIDE FIBER WORK
B SIDE FIBER WORK
FIBER-OPTIC BACKBONE CABLING
REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC
CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS
DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER
PATHWAY DETAILS.
SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.
LEGEND:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/0
/2
:2
:5 a m
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /E
E
B L D
G
L E
V E
L
.r v t
01STN102
BLDG 01S - LEVEL 02 - TELECOMMUNICATIONS
PLAN
01S
KG RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
GENERAL NOTES
KEY PLAN
- 3/32" = 1'-0"
1 BLDG 01S - LEVEL 02 - TELECOMMUNICATIONS PLAN
PROJECT
NORTH
8'0 16' 24'
PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO REPLACE
EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT SHALL REMAIN
AND BE UTILIZED TO FEED NEW CABLING; REFERENCE DETAIL '1' ON SHEET TN501
AND GENERAL NOTES ON THIS SHEET FOR ADDITIONAL INFORMATION. COORDINATE
WITH VA FOR EXACT OUTLET PLACEMENT.
PROVIDE CABLE TRAY AS INDICATED. REFERENCE DETAIL "6" ON SHEET TN501 AND
TELECOMMUNICATIONS WAO AND CABLE TRAY SCHEDULE ON SHEET TN701. WHERE
WALL EXTENDS TO CEILING, CABLE TRAY SHALL STOP AND TRANSITION TO
HORIZONTAL FIRE STOP SLEEVES [(2) 4", MINIMUM]. WHERE EXISTING CABLE TRAY IS
PRESENT, IT SHALL BE DEMOLISHED AND REPLACED AS INDICATED. EXISTING
SLEEVES MAY BE UTILIZED IF SUITABLE FOR REUSE, BUT NOT IN PLACE OF FIRE
STOP SLEEVES AS MENTIONED ABOVE. WHERE CLEARANCES OR OBSTRUCTIONS
DO NOT PERMIT INSTALLATION OF CABLE TRAY, PROVIDE J-HOOKS AS REQUIRED
FOR CABLE DISTRIBUTION.
EXISTING WIRELESS ACCESS POINT SHALL BE RE-FED WITH (2) CAT6A CABLES.
PROVIDE (2) 4" HORIZONTAL SLEEVES.
LOCKING TDU (TUBE DISTRIBUTION UNIT) ENCLOSURE TUBE.
PROVIDE (2) TWO-INCH CONDUITS TO ROOM T1-03 ON FLOOR ABOVE.
PROVIDE (2) TWO-INCH CONDUITS FROM ROOM T1-01 ON FLOOR BELOW.
PROVIDE (2) TWO-INCH CONDUITS TO ROOM 3B-176 ON FLOOR ABOVE.
PROVIDE (2) TWO-INCH CONDUITS FROM ROOM 1B130 ON FLOOR BELOW.
PROVIDE (2) TWO-INCH CONDUITS TO ROOM T4-03 ON FLOOR ABOVE.
PROVIDE (2) TWO-INCH CONDUITS FROM ROOM T4-01 ON FLOOR BELOW.
PROJECT
NORTH
Revisions: Date:
B L D
G
A
S
E E
S H
E E
T
A
T N
B L D
G
S E
E S
H E
E T
T
N
KEY NOTES
WAPWAP
WAP
WAP
WAP
WAP
WAP
WAPWAP
WAP
WAP
WAP
WAP WAP
WAP
WAP
WAP
WAP
WAP
WAP
W
W
AREA SHOWN
K L M N O P Q R S T U V W X Y
6 BLDG 01S
BLDG 01A: SEE SHEET 01ATN103
TYP.
01STN403a
01STN403a
EXAM
3C-108C
EXAM
3C-108D
EXAM
3C-108E
EXAM
3C-108F
PROCEDURE
ROOM
3B-116
DICTATION
3B118DECON
3B-124A
PREP CLEAN
3B-124B
TOILET
3B-116B
PRE-OP
3B183
TOILET
3B184
PRE-OP
3B185
PRE-OP
3B186
STORAGE
3B187
ANTE-ROOM
3B-188
ISOLATION
3B-189
PRE-OP
3B-190
PRE-OP
3B-191
PRE-OP
3B-192
PRE-OP
3B193
TOILET
3B194
PRE-OP
3B195
PRE-OP
3B196
TOILET
3B-189A
NURSE STATION
3B-197A
NURSE STATION
3B-197B
STERILE
SUPPLIES
3B198
STRETCHER
STORAGE
3B-199
LOUNGE
3B-200
TOILET
3B-201
CRASH/CART
C3-7.2
BLANKET
WARMER
C3-7.4
NOURISH
C3-7.3
LOCKERS
C3-7.1
SOILED
3B-182
CLEAN
3B-211
TOILET
3B-210
H.A.C.
3B-209
CORRIDOR
CORRIDOR
C3-17
ELEV. LOBBY
C3-18
EQUIPMENT
3B-169
F. TLT.
3B-181
M. TLT
3B-180
STAIR
BIO-HAZARD
3B-179
TOILET
3B-175A
PAPER
RECYCLE
3B-178
FAMILY
WAITING
3B-175
CLERK
3B-171
ELEC
3B-177
IT
3B-176
CORRIDOR
C3-16
IMPLANT
COORDINATOR
3B-146
TOILET
3B-172A
H.A.C.
3B-173
PT DRESS
3B-172
PAIN/BRONCH
PROCEDURE
ROOM
3B-147
P-1
P-2
PATIENT BAYS
C3-15
NURSE STATION
3B-151
PATIENT BAYS
C3-14
LINEN CLOSET
3B-164
FROZEN
SECTION
3B-150
ELEC
3B-163
IT
3B-162
PACU
3B-160
PACU
3B-159
CORRIDOR
C3-13
CORRIDOR
3B-161
SOILED
3B-152
CLEAN
3B-153
PACU
3B-158
PACU
3B-157
ISOLATION
PACU
3B-156
ANTE-ROOM
3B-155
3B-168
TOILET
3B-169A
SOILED
HOLDING
3B-148
BREAK
3B-165
ANESTHESIA
WORKROOM
3B-149
EXIST STAIR
STAIR-4
OR 4
3B-141
STERILE
SUPPLIES
3B-141A
OR SUPPLIES
3B-139A
OR 3
3B-139
CORRIDOR
C3-10A
SEMI
RESTRICTED
CORRIDOR
C3-10
CYSTO OR 2
3B-137
OR 1
3B-135
CYSTO
SUPPLIES
3B-174A
OR SUPPLIES
3B-135A
IMPLANT
STORAGE
3B-133
EQUIPMENT
STORAGE
3B-134
ORTHO OR 6
3B-136
CONTROL
3B-154
CLEAN
DUMBWAITER
3B-138A
LOW VOLTAGE
3B-132
CORRIDOR
C3-8
CLEAN CORE
3B-138
STORAGE
3B-167
OR NURSE
MANAGER
3B205
CORRIDOR
C3-7
GAS BOTTLE
STORAGE
3B204
SURGERY H.A.C.
3B202
SOILED
DUMBWAITER
3B203A
SOILED
3B203
INFECTIOUS
FLUID MGT.
3B208
PRE-OP
PRE-OP
3B-207
EXIST STAIR
STAIR-3
ANESTHESIA
3B127
CHIEF
ANESTHESIA
3B128
SHOWER
3B129A
FEMALE
LOCKER ROOM
3B129
MALE LOCKER
ROOM
3B130
SHOWER
3B130A
VESTIBULE
3B131A
LOUNGE
3B-131
IT
3B-126B
ELEC
3B-126A
MECHANICAL
3B-126
STAIR
CORRIDOR
C3-9
B L D
G
S
TR TOWER 4
T4-03
01STN403a
01STN403b
01STN403b
01STN403b
01STN403b
01STN403a
01STN403b
01STN403b
TYP.
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD1
DV1
DD1
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DV1
DD2
DD6
DD1 DD1DD1
DD3
DD3
DD3 DD3
DD3
DD3
DD3
DD1
DD1
DD1 DD1
DD1
DD1
DD1
DV1
DD2
N2
N2
N2N2
N2
N2N2
N2
N2 N2
N2
N2
N2
N2
N2
N2
N2N2
N2
N2
N2 N2
N2
N2 N2 N2 N2
N2N2
N2
N2
N2
N2N2
N2
N2 N2
N2N2N2N2 N2
N2
N2
N2
N2 N2
N2
N2 N2 N2
N2
N2 N2
N2 N2N2
N2 N2
N2
N2
N2
N2
N2 N2 N2
N2
N2
N2
N2 N2
N2N2
N2
N2
N2
N2
N2
N2 N2
N2
N2
N2
N2
2 2 2
PRODUCER
ROOM 3
3B123
2 TR TOWER 1
T1-03
N2
N2
N2
N2
N2
N2
N2
N2 N2
N2N2
N2 N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
DV1
DD2
DV1
DD2
N2
DATA OULETS AND DEVICES IN
THIS AREA SHALL BE SERVED
FROM TELECOMMUNICATIONS
ROOM T4-03
DATA OUTLETS AND DEVICES IN
THIS AREA SHALL BE SERVED
FROM TELECOMMUNICATIONS
ROOM T1-03
B L D
G
S E
E S
H E
E T
T
N
BLDG 01: SEE SHEET 01TN103BLDG 01A: SEE SHEET 01ATN103
DATA OULETS AND DEVICES IN
THIS AREA SHALL BE SERVED
FROM TELECOMMUNICATIONS
ROOM T4-03
DATA OUTLETS AND DEVICES IN
THIS AREA SHALL BE SERVED
FROM TELECOMMUNICATIONS
ROOM T1-03
TYP.
BLDG 01
BLDG 01W
BLDG 02
BLDG 01A
BLDG 01S
BLDG 23R
BLDG 23
BLDG 12
A SIDE FIBER WORK
B SIDE FIBER WORK
FIBER-OPTIC BACKBONE CABLING
REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC
CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS
DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER
PATHWAY DETAILS.
SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.
LEGEND:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/3
/2
:4
:2
A M
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /E
E
B L D
G
L E
V E
L
.r v t
01STN103
BLDG 01S - LEVEL 03 - TELECOMMUNICATIONS
PLAN
01S
KG RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
GENERAL NOTES
KEY NOTES
PROJECT
NORTH
- 3/32" = 1'-0"
1 BLDG 01S - LEVEL 03 - TELECOMMUNICATIONS PLAN
PROJECT
NORTH
4'0 8' 12'
1 PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO
REPLACE EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT
SHALL REMAIN AND BE UTILIZED TO FEED NEW CABLING; REFERENCE DETAIL
'1' ON SHEET TN501 AND GENERAL NOTES ON THIS SHEET FOR ADDITIONAL
INFORMATION. COORDINATE WITH VA FOR EXACT OUTLET PLACEMENT.
EXISTING WIRELESS ACCESS POINT SHALL BE RE-FED WITH (2) CAT6A CABLES.
PROVIDE CABLE TRAY AS INDICATED. REFERENCE DETAIL "6" ON SHEET TN501 AND
TELECOMMUNICATIONS WAO AND CABLE TRAY SCHEDULE ON SHEET TN701. WHERE
WALL EXTENDS TO CEILING, CABLE TRAY SHALL STOP AND TRANSITION TO
HORIZONTAL FIRE STOP SLEEVES [(2) 4", MINIMUM]. WHERE EXISTING CABLE TRAY IS
PRESENT, IT SHALL BE DEMaOLISHED AND REPLACED AS INDICATED. EXISTING
SLEEVES MAY BE UTILIZED IF SUITABLE FOR REUSE, BUT NOT IN PLACE OF FIRE
STOP SLEEVES AS MENTIONED ABOVE. WHERE CLEARANCES OR OBSTRUCTIONS
DO NOT PERMIT INSTALLATION OF CABLE TRAY, PROVIDE J-HOOKS AS REQUIRED
FOR CABLE DISTRIBUTION.
PROVIDE (2) 4" HORIZONTAL SLEEVES.
LOCKING TDU (TUBE DISTRIBUTION UNIT) ENCLOSURE TUBE.
PROVIDE (2) TWO-INCH CONDUITS TO ROOM T1-04 ON FLOOR ABOVE.
PROVIDE (2) TWO-INCH CONDUITS FROM ROOM T1-02 ON FLOOR BELOW.
PROVIDE (2) TWO-INCH CONDUITS TO ROOM 4B149 ON FLOOR ABOVE.
PROVIDE (2) TWO-INCH CONDUITS FROM ROOM 2B191 ON FLOOR BELOW.
PROVIDE (2) TWO-INCH CONDUITS TO ROOM T4-04 ON FLOOR ABOVE.
PROVIDE (2) TWO-INCH CONDUITS FROM ROOM T4-02 ON FLOOR BELOW.
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS
REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO
BE DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS
OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS
TO EXTEND TO ASSOCIATED TR AS REQUIRED.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED
TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL
LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED
FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF
A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
7. WHEN PROVIDING A WAO IN LOCATIONS WHERE AN EXISTING WAO CURRENTLY
DOES NOT EXIST, PROVIDE (1) 4-INCHSQUARE BACKBOX WITH SINGLE-GANG
REDUCING MUD RING AND (1) 1-1/4" CONDUIT EXTENDING FROM BACKBOX TO
ACCESSIBLE CEILING SPACE. ONCE IN ACCESSIBLE CEILING SPACE, CABLING SHALL
EXTEND TO ITS ASSOCIATED TR VIA CABLE TRAY; UTILIZE J-HOOKS EVERY 48” WHEN
TRANSITIONING TO OR FROM CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT,
EXTEND HORIZONTAL CABLING FROM WAO TO TR VIA J-HOOKS ONLY.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO
SEAL IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS
FOR PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES ON AS-BUILT DRAWINGS.
11. GREYED OUT WAO'S SHALL BE DEMOLISHED BACK TO THE SOURCE AND NOT
REPLACED. PLACE A BLANK FACEPLATE OVER THE OUTLET BOX.
12. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND
ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.
13. THE CONTRACTOR SHALL BID AND INSTALL CAT6A CABLE WITH AN OD NOT
GREATER THAN 0.250" (6.35mm) (4) CAT6A CABLES WITH AN 0.250" (6.35mm) OD OR
SMALLER CAN BE INSTALLED IN A 3/4” CONDUIT SUPPORTING A 40% FILL RATIO.
Revisions: Date:
KEY PLAN
WAP
WAP
WAP WAP
WAP
WAP
WAP
WAP WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP WAP
WAP
WAP
WAP
WAP WAP
AREA SHOWN
J K L M N O P Q R S T U
V W X Y
01STN404a
01STN404a
TYP.
DATA OUTLETS AND DEVICES
IN THIS AREA SHALL BE SERVED
FROM TELECOMMUNICATIONS
ROOM T4-04.
DATA OUTLETS AND DEVICES
IN THIS AREA SHALL BE SERVED
FROM TELECOMMUNICATIONS
ROOM T1-04.
DATA OUTLETS AND DEVICES
IN THIS AREA SHALL BE SERVED
FROM TELECOMMUNICATIONS
ROOM T4-04.
DATA OUTLETS AND DEVICES
IN THIS AREA SHALL BE SERVED
FROM TELECOMMUNICATIONS
ROOM T1-04.
01STN404a
01STN404b
01STN404b
TELE
4B-111a
ELEC
4B-110
HOSPITALIST
4B-111
2 BED RM
4B-112
BATH
4B114A
BATH
4B112A
TLT
4B113
2 BED RM
4B114
MEDIC. N4 - BM
NURSE
NURSING
4B-115A
2 BED RM
4B-116
BATH
4B-117A
BATH
4B-116A
2 BED RM
4B117
BATH
4B-119a
ANTE RM
4B-118
1 BED RM
ISOLATION
4B-119
NUTRI.
4B-120
SOILED UTILITY
4B-121
OXYGEN/CLEAN
UTILITY
4B-122
BATH
4B-123a
1 BED RM
4B123
BATH
4B124a
2 BED RM
4B124
CYLINDER
STORAGE
4B125
BATH
4B126a
2 BED RM
4B126
BATH
4B127a
1 BED RM
4B127
BATH
4B128c
1 BED RM
4B128
BATH
4B129a
2 BED RM
4B129
BATH
4B131a
1 BED RM
4B131
FAMILY CENTER
4B130C
BATH
4B133a
1 BED RM
4B133
2 BED RM
4B136
BATH
4B136a
BATH
4B137A
2 BED RM
4B137
2 BED RM
4B141
BATH
4B141A
BATH
4B143A
2 BED RM
4B143
1 BED RM
4B147
BATH
4B147a
1 BED RM
4B148
BATH
4B148a
SOILED FOOD
4B151C
MEN
4B153
CART
4B152
WOMEN
4B154
VISITOR
LOUNGE
C4-1
FAMILY WAITING
4B-100
4B-101a
4B-100a
EQUIPMENT
STORAGE
4B101b
4B-101f
ISOLATION C
4B-101g
D
E
F
G
ISOLATION H
4B-101j
4B-101k
I
J
RESIDENT
4B101m
HN MICU
4B104
HAC
4B106
RESIDENT
4B101m
CORRIDOR
C4-3
4B-101
MICU NURSES
STATION
CLEAN UTIL.
4B101l
SOIL. UTIL.
4B101n
ON-CALL
4B102
BATH
4B102a
4B101cB
FEMALE
LOCKER
4B101ca
STAFF LOUNGE
4B-101c
4B-101cd
MALE LOCKER
4B-101cC
CLEAN LINEN
4B101D
HAC
4B101e
NUTRI
4B101h
MED
4B101i
CORRIDOR
C4-5
CORRIDOR
C4-5
CORRIDOR
C4-6
SERVICE LOBBY
C4-16
PHARMACIST
4B103 BLDG. MGMT.
STORAGE
4B103A LINEN
4B145
NSO
4B144
CLEAN UTIL.
4B105
SOCIAL
WORKER
4B107
NURSE MGR
4B109
CM CRC
4B140
OFFICE
4B146
B
A
PUBLIC LOBBY
C4-2
P3
4B104
P2
P1
4B106
STAIR 1
4B155
TELE
4B149
ELEC.
4B150
S1
4B158
S2
4B159
CORRIDOR
C4-15
CART
4B161
STAIR 3
CORRIDOR
C4-7
N4 - B
4B115
CORRIDOR
C4-11
TELEMETRY
MED. RM
4B109A
WARD CLERKS
4B142A
STORAGE
4B139
CORRIDOR
C4-14
NURSE C
4B-130
CORRIDOR
C4-9
MEDIC
4B-130A
STAFF LOUNGE
4B132
NURSE D
4B-130B
TLT
4B132a
STORAGE
4B134
STAIR 4
4B164
SOILED LNEN
4B135
ELEC
4B138A TELE
4B138B
WARD
4-SOUTH
CORRIDOR
C4-8
C4 -12A
4B142B
NURSE E
C4-12B
TR TOWER 1
T1-04
TR TOWER 4
T4-04
TYP.
DV1
DD2
N2
2 2
2 2
2 2
2 2
DV1
DD2
N2
DV1
DD3
N2
DV1
DD3
N2
DV1
DD3
N2
DV1
DD3
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DD1
N2
DD3
N2
DV1
DD2
N2
DD6
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DD6
N2
DD1
N2
DD6
N2
DD1
N2
DD1
N2
DD1
N2
DD1
N2
DD4
N2
DD1
N2
DD6
N2
DD6
N2
DD6
N2
DD1
N2
DD1
N2
DD1
N2
B
DD1
N2
DD1
N2
DD1
N2
DD1
N2
DV1
DD1
N2
DV1
DD1
N2
DV1
DD1
N2
DV1
DD1
N2
DV1
DD1
N2
DV1
DD3
N2
DV1
DD3
N2
DV1
DD3
N2
DV1
DD3
N2
DV1
DD3
N2
DV1
DD3
N2 DV1
DD3
N2
DV1
DD3
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2 DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2 N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2 N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2
N2 N2 N2
N2
N2
N2
N2
N2
N2
N2
N2
DD3 DD3
DD3
N2
DD3
N2
DV1
DD1
N2
DV1
DD1
B L D
G
A
S
E E
S H
E E
T
A
T N
B L D
G
S E
E S
H E
E T
T
N
BLDG 01S
BLDG 01A: SEE SHEET 01ATN104
TN509
TYP.
TN509
TYP.
TYP.
BLDG 01S
BLDG 01
BLDG 01W
BLDG 02
BLDG 23R
BLDG 23
BLDG 01A
BLDG 12
A SIDE FIBER WORK
B SIDE FIBER WORK
FIBER-OPTIC BACKBONE CABLING
REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC
CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS
DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER
PATHWAY DETAILS.
SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.
LEGEND:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/0
/2
:1
:4 a m
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /E
E
B L D
G
L E
V E
L
.r v t
01STN104
BLDG 01S - LEVEL 04 - TELECOMMUNICATIONS
PLAN
01S
KG RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
GENERAL NOTES
PROJECT
NORTH
- 3/32" = 1'-0"
1 BLDG 01S - LEVEL 04 - TELECOMMUNICATIONS PLAN 8'0 16' 24'
PROJECT
NORTH
KEY NOTES
PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO
REPLACE EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT
SHALL REMAIN AND BE UTILIZED TO FEED NEW CABLING; REFERENCE DETAIL '1' ON
SHEET TN501 AND GENERAL NOTES ON THIS SHEET FOR ADDITIONAL INFORMATION.
COORDINATE WITH VA FOR EXACT OUTLET PLACEMENT.
EXISTING WIRELESS ACCESS POINT SHALL BE RE-FED WITH (2) CAT6A CABLES.
PROVIDE CABLE TRAY AS INDICATED. REFERENCE DETAIL "6" ON SHEET TN501 AND
TELECOMMUNICATIONS WAO AND CABLE TRAY SCHEDULE ON SHEET TN701. WHERE
WALL EXTENDS TO CEILING, CABLE TRAY SHALL STOP AND TRANSITION TO
HORIZONTAL FIRE STOP SLEEVES [(2) 4", MINIMUM]. WHERE EXISTING CABLE TRAY IS
PRESENT, IT SHALL BE DEMOLISHED AND REPLACED AS INDICATED. EXISTING
SLEEVES MAY BE UTILIZED IF SUITABLE FOR REUSE, BUT NOT IN PLACE OF FIRE
STOP SLEEVES AS MENTIONED ABOVE. WHERE CLEARANCES OR OBSTRUCTIONS
DO NOT PERMIT INSTALLATION OF CABLE TRAY, PROVIDE J-HOOKS AS REQUIRED
FOR CABLE DISTRIBUTION.
LOCKING TDU (TUBE DISTRIBUTION UNIT) ENCLOSURE TUBE.
PROVIDE (2) TWO-INCH CONDUITS TO ROOM T1-05 ON FLOOR ABOVE.
PROVIDE (2) TWO-INCH CONDUITS FROM ROOM T1-03 ON FLOOR BELOW.
PROVIDE (2) TWO-INCH CONDUITS TO ROOM 5B151 ON FLOOR ABOVE.
PROVIDE (2) TWO-INCH CONDUITS FROM ROOM 3B-176 ON FLOOR BELOW.
PROVIDE (2) TWO-INCH CONDUITS TO ROOM T4-05 ON FLOOR ABOVE.
PROVIDE (2) TWO-INCH CONDUITS FROM ROOM T4-03 ON FLOOR BELOW.
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS
REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO
BE DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS
OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED
AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS
NOTED OTHERWISE.
5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED
BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS
TO EXTEND TO ASSOCIATED TR AS REQUIRED.
6. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED
TO REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL
LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED
FOR THE INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF
A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.
7. WHEN PROVIDING A WAO IN LOCATIONS WHERE AN EXISTING WAO CURRENTLY
DOES NOT EXIST, PROVIDE (1) 4-INCHSQUARE BACKBOX WITH SINGLE-GANG
REDUCING MUD RING AND (1) 1-1/4" CONDUIT EXTENDING FROM BACKBOX TO
ACCESSIBLE CEILING SPACE. ONCE IN ACCESSIBLE CEILING SPACE, CABLING SHALL
EXTEND TO ITS ASSOCIATED TR VIA CABLE TRAY; UTILIZE J-HOOKS EVERY 48” WHEN
TRANSITIONING TO OR FROM CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT,
EXTEND HORIZONTAL CABLING FROM WAO TO TR VIA J-HOOKS ONLY.
8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT
CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180
DEGREES.
9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION
OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO
SEAL IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS
FOR PARTITION TYPES AND WALL HEIGHTS.
10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;
DOCUMENT VARIANCES ON AS-BUILT DRAWINGS.
11. GREYED OUT WAO'S SHALL BE DEMOLISHED BACK TO THE SOURCE AND NOT
REPLACED. PLACE A BLANK FACEPLATE OVER THE OUTLET BOX.
12. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE
DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,
ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND
ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.
13. THE CONTRACTOR SHALL BID AND INSTALL CAT6A CABLE WITH AN OD NOT
GREATER THAN 0.250" (6.35mm) (4) CAT6A CABLES WITH AN 0.250" (6.35mm) OD OR
SMALLER CAN BE INSTALLED IN A 3/4” CONDUIT SUPPORTING A 40% FILL RATIO.
KEY PLAN
Revisions: Date:
WAP WAP WAP
WAP
WAP WAP WAP
WAP
WAP
WAP
WAP
WAP
WAP WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
M N O P Q R S T U V W X Y
01STN405b
01STN405a
TYP.
DATA
OUTLETS AND
DEVICES IN
THIS AREA
SHALL BE
SERVED FROM
TELECOMMUNI
CATIONS
ROOM T4-05.
DATA OUTLETS AND
DEVICES IN THIS AREA
SHALL BE SERVED FROM
TELECOMMUNICATIONS
ROOM T4-05.
DATA OUTLETS AND
DEVICES IN THIS AREA
SHALL BE SERVED FROM
TELECOMMUNICATIONS
ROOM T1-05.
DATA
OUTLETS AND
DEVICES IN
THIS AREA
SHALL BE
SERVED FROM
TELECOMMUNI
CATIONS
ROOM T1-05.
PALATIVE 2
CARE BED
5B112
PALATIVE 2
CARE BED
5B113
TELE
5B112B
ELEC
5B111
BATH
5B112A
BATH
5B115A
PALATIVE 2
CARE BED
5B115
BATH
5B113A
STAFF
5B114
BREAK RM
5B116A
MEDIC. N5-B.M.
NURSE B
5B116N5-B
2 BED
5B117
BATH
5B118A
2 BED
5B118
BATH
5B117A
CORRIDOR
C5-4
1 BED
5B120
BATH
5B120A
NUTRI
5B121
BATH
5B119
SOILED UTILITY
5B122
CLEAN UTILITY
5B123
BATH
5B124A
1 BED
5B124
WC BATH
5B125A
2 BED RM
5B125
HAC
5B127
BATH
5B128A
2 BED RM
5B128
BATH
5B129A
1 BED
5B129
WC BATH
5B130A
1 BED
5B130
WC BATH
5B131A 2 BED RM
5B131
WC BATH
5B133A
FAMILY
CENTER
5B132
1 BED RM
5B133
WC BATH
5B135A
1 BED RM
5B135
NURSE D
N5-D
5B126B
NURSE C
N5-C
5B136
STERILE SUP.
N5-C/B
5B126A
CORRIDOR
C5-6
STAFF LOUNGE
5B134
TOILET
5B134A
STORAGE
TELE
5B138
ELEC
5B139
2 BED RM
5B37
2 PAT BATH
5B142A
2 PAT BATH
5B137A
2 BED RM
5B142
2 BED RM
5B143
BATH
5B143ABATH
5B145A
2 BED RM
5B145
1 BED
5B149
BATH
5B149A
1 BED
5B150
TRASH
5B152
LINEN
5B154
BATH
5B150A
STAIR
MEN
5B155
WOMEN
5B156
ELEV
P1
ELEV
P2
ELEV
P3
VISITOR
LOUNGE
CORRIDOR
C5-7
CORRIDOR
C5-5
STAIR
M.E.D. RM
5B109A
STORAGE
5B138A
WARD
CLERKS
5B139A
CASE CLIN MRG
CRD.
5B140
UTILITY
CHARGING
5B141B
NURSE MGR
5B109
CORRIDOR
C5-10
CORRIDOR
C5-8
CORRIDOR
C5-3A
N5-A/E
C5-3B
NURSE E N5-E
5B141
NURSE A N5-A
5B141A
WOUND
CARE
5B146
CLEAN
LINEN
5B107
BLDG MGNT
STOR.
5B106A
STRETCHER
STORAGE
5B106
SOILDED
LINEN
5B147
SOC WORK
5B-141H
TELE CLO
5B151
ELEC
5B153
ELEV
S1
SERVICE LOBBY
C5-12
ELEV
S2
NURSE
CONFERENCE
5B-101
MED PHYSICAL
& REHAB
5B-100
MED TEAM #2
5B-102
2 BED RM
5B-103
BATH
5B105A
BATH
5B103A
2 BED RM
5B105
CORRIDOR
C5-3
PUBLIC LOBBY
C5-2
CORRIDOR
C5-11
2 BED RM
5B108
2 PAT BATH
5B110A
2 PAT BATH
5B108A
2 BED RM
5B110
STAIR
TR TOWER 4
T4-05
TR TOWER 1
T1-05
01STN405a
01STN405a
01STN405b
01STN405a
TYP.
DV1
DD5
N2
DV1
DD5
N2
DV1
DD5
N2
DV1
DD1
N2
DV1
DD2
N2
DV1
DD5
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD5
N2
DV1
DD2
N2
DV1
DD5
N2
DV1
DD2
N2
DV1
DD5
N2
DV1
DD2
N2
DV1
DD2
N2
DD1
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD5
N2
DV1
DD5
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD5
N2
DD1
N2
DV1
DD2
N2
DV1
DD5
N2
DV1
DD5
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD1
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD2
N2
DV1
DD5
N2
DV1
DD5
N2
DV1
DD5
N2
DV1
DD3
N2
DD1
N2
DV1
DD5
N2
DV1
DD2
N2
DV1
DD5
N2
DV1
DD5
N2
DV1
DD5
N2
DD1
N2
N2
N2
N2
N2 N2
N2 N2 N2
N2
N2
N2 N2
N2 N2
N2
N2
N2
N2
N2
J K L
TYP.
TN509
TYP.
TN509
TYP.
AREA SHOWN
BLDG 01S
BLDG 23R
BLDG 23
BLDG 01A
BLDG 01W
BLDG 02
BLDG 01
BLDG 12
A SIDE FIBER WORK
B SIDE FIBER WORK
FIBER-OPTIC BACKBONE CABLING
REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC
CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS
DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER
PATHWAY DETAILS.
SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.
LEGEND:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/0
/2
:4
:0 a m
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /E
E
B L D
G
L E
V E
L
.r v t
01STN105
BLDG 01S - LEVEL 05 - TELECOMMUNICATIONS
PLAN
01S
KG RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
GENERAL NOTES
- 1" = 10'-0"
1 BLDG 01S - LEVEL 05 - TELECOMMUNICATIONS PLAN
0 10' 20'
PROJECT
NORTH
1 PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO
REPLACE EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT
SHALL REMAIN AND BE UTILIZED TO FEED NEW CABLING; REFERENCE DETAIL
'1' ON SHEET TN501 AND GENERAL NOTES ON THIS SHEET FOR ADDITIONAL
INFORMATION. COORDINATE WITH VA FOR EXACT OUTLET PLACEMENT.
EXISTING WIRELESS ACCESS POINT SHALL BE RE-FED WITH (2) CAT6A CABLES.
PROVIDE CABLE TRAY AS INDICATED. REFERENCE DETAIL "6" ON SHEET TN501 AND
TELECOMMUNICATIONS WAO AND CABLE TRAY SCHEDULE ON SHEET TN701. WHERE
WALL EXTENDS TO CEILING, CABLE TRAY SHALL STOP AND TRANSITION TO
HORIZONTAL FIRE STOP SLEEVES [(2) 4", MINIMUM]. WHERE EXISTING CABLE TRAY IS
PRESENT, IT SHALL BE DEMOLISHED AND REPLACED AS INDICATED. EXISTING
SLEEVES MAY BE UTILIZED IF SUITABLE FOR REUSE, BUT NOT IN PLACE OF FIRE
STOP SLEEVES AS MENTIONED ABOVE. WHERE CLEARANCES OR OBSTRUCTIONS
DO NOT PERMIT INSTALLATION OF CABLE TRAY, PROVIDE J-HOOKS AS REQUIRED
FOR CABLE DISTRIBUTION.
PROVIDE (2) 4" HORIZONTAL SLEEVES.
PROVIDE (1) 4" HORIZONTAL SLEEVES.
LOCKING TDU (TUBE DISTRIBUTION UNIT) ENCLOSURE TUBE.
PROVIDE (2) TWO-INCH CONDUITS FROM ROOM T1-04 ON FLOOR BELOW.
PROVIDE (2) TWO-INCH CONDUITS TO ROOM 6B106 ON FLOOR ABOVE.
PROVIDE (2) TWO-INCH CONDUITS FROM ROOM 4B149 ON FLOOR BELOW.
PROVIDE (2) TWO-INCH CONDUITS FROM ROOM T4-04 ON FLOOR BELOW.
TRUE
NORTH
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS
REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO
BE DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS
OTHERWISE NOTED.
2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL
DRAWINGS AS REQUIRED.
4. ALL…
This is the start of the file's text. The full file is on GovTribe.