S02 - ATT 13 - 581-22-700 - 100 Drawings Part-11 of 24.pdf
PDF 4 MB Posted
- Solicitation number
- 36C77626R0025
About this file
This document is a set of enlarged electrical plans for the EHRM Infrastructure Upgrades project at VA Huntington, located at 1540 Spring Valley Drive, Huntington, WV 25704-9300. The plans were prepared by SPEES Design Build (23830 Pacific Highway S., Suite 300, Kent, WA 98032) and issued as 100% Construction Documents dated September 3, 2025.
The electrical plans cover multiple buildings and rooms, detailing demolition and new electrical installations across various facility levels. Key work includes demolition of existing electrical equipment with conduit and wire removed back to source; installation of new panelboards, transformers, and circuit breakers with dual-sided power sourcing (A and B side power feeds); furnishing and installing boxed power supplies for electrified door hardware; provision of secondary and primary bonding busbars per telecommunications requirements; and installation of mechanical units, receptacles, switches, and lighting systems. Standard requirements across all plans mandate contractor coordination with VA for essential electrical system shutdowns; provision of backup emergency power; sealing of penetrations to match fire ratings; updated circuit panel directories; pull boxes for feeder runs exceeding 250 feet or 270 degrees of bend; and panel and circuit labeling on all wiring devices. The plans reference corresponding one-line diagrams and telecommunications bonding riser diagrams for additional information, with all work conforming to VA standards and the National Electrical Code.
View the file
Other files
Show 40 more
Latest 50 of 68 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
J
A A
A
A
B
B
B
B
BBBB
Mo
A A
B B
A A
B B
E F
TYP.
FAN COIL UNIT
E F
TR
71 SF
09-9202A
09-9202B
7 09-AC-01-9202
FROM SHEET
09EP101
ACCESS CONTROL
PANEL "09-ACP-9202"
09-9202A-25
EP504
CC
P-TR-1A
P-TR-1B
EP502
09-9202A-25
09-P-02B
09-P-03
09-P-01
TO SHEET 09EP101
FROM SHEET 09EP101
E F
TYP.
E F
09-9202A
09-9202B
TR
71 SF
TYP.
EP508
EP508
09-9202A-4
2 2
L4
L4
AREA SHOWN
71 SF
IT
71 SF
IT
A SIDE POWER, CONCEALED WHERE POSSIBLE
B SIDE POWER, CONCEALED WHERE POSSIBLE
A SIDE POWER, UNDERGROUND / UNDERFLOOR
B SIDE POWER, UNDERGROUND / UNDERFLOOR
PROVIDED TO INDICATE 'A' AND 'B' SIDE SOURCED POWER FEEDERS.
REFERENCE GENERAL SYMBOL LEGEND FOR ADDITIONAL
INFORMATION.
LEGEND
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/0
/2
:5
:2 a m
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /E
E
B L D
G
.r v t
09EP402
BLDG 09 - LEVEL 02 - ENLARGED ELECTRICAL
PLANS
DCW/NVP RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
KEY NOTES
KEY PLAN
GENERAL NOTES
PROJECT
NORTH
- 1/2" = 1'-0"
1 RM 9202 - DEMOLITION ELECTRICAL PLAN
- 1/2" = 1'-0"
2 RM 9202 - ELECTRICAL PLAN
- 1/2" = 1'-0"
3 RM 9202 - DEMOLITION LIGHTING PLAN
- 1/2" = 1'-0"
4 RM 9202 - LIGHTING AND RECEPTACLE PLAN
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
EXISTING EQUIPMENT SHALL BE DEMOLISHED. ASSOCIATED CONDUIT AND WIRE
SHALL BE DEMOLISHED BACK TO SOURCE.
SOURCE A POWER PANELBOARD "09-9202A".
SOURCE B POWER PANELBOARD "09-9202B".
PROVIDE SECONDARY BONDING BUSBAR. REFERENCE TELECOMMUNICATIONS
BONDING RISER DIAGRAM ON SHEET EG603 FOR ADDITIONAL INFORMATION.
OVERHEAD TR RACK SOURCE A AND SOURCE B POWER RECEPTACLE.
FURNISH AND INSTALL BOXED POWER SUPPLIES AS INDICATED ABOVE ACCESSIBLE
CEILINGS. VERIFY LOCATIONS WITH ARCHITECT. PROVIDE (1) POWER SUPPLY FOR
EACH DOOR OPENING. PROVIDE 120V POWER TO ADEQUATELY SERVE DOORS WITH
ELECTRIFIED DOOR HARDWARE AND MAKE CONNECTIONS AS REQUIRED. SEE
REQUIREMENTS IN "08 71 00 - DOOR HARDWARE". COORDINATE WITH ARCHITECT AND
DOOR INSTALLER.
INTERIOR MECHANICAL UNIT POWERED FROM ASSOCIATED EXTERIOR UNIT. PROVIDE
CONDUIT AND WIRE PER MANUFACTURER'S REQUIREMENTS. REFERENCE
MECHANICAL DRAWINGS AND COORDINATE WITH MECHANICAL CONTRACTOR AS
REQUIRED.
CONDUIT ROUTED VERTICALLY FROM FLOOR BELOW. REFERENCE SHEET 09EP101
FOR ADDITIONAL INFORMATION.
CONDUIT ROUTED VERTICALLY TO FLOOR BELOW. REFERENCE SHEETS 09EP101 AND
09EP100 FOR ADDITIONAL INFORMATION.
PROVIDE TBB AS INDICATED; WHERE CONDUCTOR IS SUBJECT TO PHYSICAL
DAMAGE, CONDUCTOR SHALL BE ROUTED THROUGH RMC. REFERENCE
TELECOMMUNICATIONS BONDING RISER DIAGRAM ON SHEET EG603 FOR ADDITIONAL
INFORMATION.
PROVIDE SBC AS INDICATED; WHERE CONDUCTOR IS SUBJECT TO PHYSICAL
DAMAGE, CONDUCTOR SHALL BE ROUTED THROUGH RMC. REFERENCE
TELECOMMUNICATIONS BONDING RISER DIAGRAM ON SHEET EG603 FOR ADDITIONAL
INFORMATION.
Revisions: Date:
1. DEMOLITION PLANS/NOTES ARE BASED ON SITE INVESTIGATIONS AND RECORD
DRAWINGS. IF DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK, PROMPTLY
NOTIFY VA AND ENGINEER OF SAID DISCREPANCY.
2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER, LIGHTING AND ASSOCIATED CIRCUITRY AS REQUIRED.
ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE
DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS
OTHERWISE NOTED.
3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS AND
RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED, AND IN ALL LOCATIONS
WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION,
UNLESS OTHERWISE NOTED.
4. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM
SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED
EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER
AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO
ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL
REMAIN ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL
CONFORM WITH VA STANDARDS.
5. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING; PROVIDE CORE DRILLING AS REQUIRED.
COORDINATE WITH ARCHITECTURAL AND STRUCTURAL DRAWINGS AS REQUIRED.
6. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL
PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.
8. CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL FEEDERS WHERE FEEDER
RUNS EXCEED 250FT OR HAVE MORE THAN 270 DEGREES OF TOTAL BEND. PULL
BOX PLACEMENTS AND SIZING BY CONTRACTOR. COORDINATE PULL BOX
LOCATIONS WITH ALL OBSTRUCTIONS, TRADES, AND VA AS REQUIRED.
9. ALL RECEPTACLES AND SWITCHES SHALL BE PROVIDED WITH PANEL AND CIRCUIT
LABELING LOCATED DIRECTLY ON THE WALL PLATE; IE:"P4-1", PANEL "4", CIRCUIT
"1". REFERENCE WIRING DEVICE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
A A A A A A A A A
B B B B B B B B B
A A A A A A A A A
A A
A
A
A
A
A
B B
B
B
B
EP502
Mo
A A
B B
A A
B B
AREA SHOWN
TYP.
C
DUCTLESS AC UNIT
TR
20121
98 SF
EP504
20-VRF-01-20121
C
20-20121B
20-20121A
20-VRF-02-20121
ACCESS CONTROL
PANEL "20-ACP-20121"
20-20121A-25
P-TR-2B
P-TR-2A
20-20121A-25
20-20121A-11,13
20-20121A-7,9
D
D
FROM SHEET
20EP101
FROM SHEET
20EP101
20-P-02
20-P-04
20-P-05
TYP.
C
TR
20121
98 SF
C
20-20121A
20-20121B
L1L1
L1 L1
20-20121A-4
TYP.
EP508
EP508
2 2
20121
98 SF
20121
98 SF
20121
A SIDE POWER, CONCEALED WHERE POSSIBLE
B SIDE POWER, CONCEALED WHERE POSSIBLE
A SIDE POWER, UNDERGROUND / UNDERFLOOR
B SIDE POWER, UNDERGROUND / UNDERFLOOR
PROVIDED TO INDICATE 'A' AND 'B' SIDE SOURCED POWER FEEDERS.
REFERENCE GENERAL SYMBOL LEGEND FOR ADDITIONAL
INFORMATION.
LEGEND
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/0
/2
:0
:1 a m
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /E
E
B L D
G
.r v t
20EP401
BLDG 20 - LEVEL 01 - ENLARGED ELECTRICAL
PLANS
DCW/NVP RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
KEY NOTES
KEY PLAN
GENERAL NOTES
EXISTING EQUIPMENT SHALL BE DEMOLISHED. ASSOCIATED CONDUIT AND WIRE
SHALL BE DEMOLISHED BACK TO SOURCE.
SOURCE POWER PANELBOARD "20-20121A".
SOURCE POWER PANELBOARD "20-20121B".
PROVIDE SECONDARY BONDING BUSBAR. REFERENCE TELECOMMUNICATIONS
BONDING RISER DIAGRAM(S) FOR ADDITIONAL INFORMATION.
OVERHEAD TR RACK SOURCE A AND SOURCE B POWER RECEPTACLE.
FURNISH AND INSTALL BOXED POWER SUPPLIES AS INDICATED ABOVE
ACCESSIBLE CEILINGS. VERIFY LOCATIONS WITH ARCHITECT. PROVIDE (1) POWER
SUPPLY FOR EACH DOOR OPENING. PROVIDE 120V POWER TO ADEQUATE SERVE
DOORS WITH ELECTRIFIED DOOR HARDWARE AND MAKE CONNECTIONS AS
REQUIRED. SEE REQUIREMENTS IN 08 71 00 - DOOR HARDWARE. COORDINATE WITH
ARCHITECT AND DOOR INSTALLER.
PROVIDE RACEWAYS AND CONDUCTORS PER MANUFACTURER'S REQUIREMENTS.
REFERENCE MECHANICAL DRAWINGS AND COORDINATE WITH MECHANICAL
CONTRACTOR AS REQUIRED.
PROVIDE SBC AS INDICATED; WHERE CONDUCTOR IS SUBJECT TO PHYSICAL
DAMAGE, CONDUCTOR SHALL BE ROUTED THROUGH RMC. REFERENCE
TELECOMMUNICATIONS BONDING RISER DIAGRAM ON SHEET EG603 FOR ADDITIONAL
INFORMATION.
PROJECT
NORTH
1/2" = 1'-0"20EP101
1 RM 20121 - DEMOLITION ELECTRICAL PLAN
1/2" = 1'-0"20EP101
2 RM 20121 - ELECTRICAL PLAN
1/2" = 1'-0"20EP101
3 RM 20121 - DEMOLITION LIGHTING PLAN
1/2" = 1'-0"20EP101
4 RM 20121 - LIGHTING AND RECETACLE PLAN
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1. DEMOLITION PLANS/NOTES ARE BASED ON SITE INVESTIGATIONS AND RECORD
DRAWINGS. IF DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK, PROMPTLY
NOTIFY VA AND ENGINEER OF SAID DISCREPANCY.
2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER, LIGHTING AND ASSOCIATED CIRCUITRY AS REQUIRED.
ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE
DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS
OTHERWISE NOTED.
3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS AND
RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED, AND IN ALL LOCATIONS
WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION,
UNLESS OTHERWISE NOTED.
4. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM
SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED
EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER
AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO
ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL
REMAIN ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL
CONFORM WITH VA STANDARDS.
5. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING; PROVIDE CORE DRILLING AS REQUIRED.
COORDINATE WITH ARCHITECTURAL AND STRUCTURAL DRAWINGS AS REQUIRED.
6. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL
PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.
8. CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL FEEDERS WHERE FEEDER
RUNS EXCEED 250FT OR HAVE MORE THAN 270 DEGREES OF TOTAL BEND. PULL
BOX PLACEMENTS AND SIZING BY CONTRACTOR. COORDINATE PULL BOX
LOCATIONS WITH ALL OBSTRUCTIONS, TRADES, AND VA AS REQUIRED.
9. ALL RECEPTACLES AND SWITCHES SHALL BE PROVIDED WITH PANEL AND CIRCUIT
LABELING LOCATED DIRECTLY ON THE WALL PLATE; IE:"P4-1", PANEL "4", CIRCUIT
"1". REFERENCE WIRING DEVICE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
Revisions: Date:
J
J
AAA
AAAAAAABBBBBBB
BB
EP502
AAAAAAABBBBBBB
B
B
B
B B AA
AA
A
A
A
A
A
A
AA
A
A
A
AA
A
A
A
Mo
A A
B B
A A
B B
AREA SHOWN
20211A
TYP.
A
DUCTLESS AC UNIT 8
TR
20211A
113 SF
EP504
20-VRF-03-20211A
A
20-20211AA
20-20211AB
20-VRF-04-20211A
ACCESS CONTROL
PANEL "20-ACP-20211A"
20-20211A-25
DUCTLESS AC UNIT
20-20211A-25
P-TR-1A
P-TR-1B
20-20211AA-7,9
20-20211AA-11,13
20-P-03
20-P-01
CC
C C
P-TR-1B
P-TR-1A
TYP.
SERVER ROOM
SECURE
20211
84 SF
20-P-06
20-P-0512
TYP.
A
TR
20211A
113 SF
A
20-20211AB L5
L5
L5
20-20211AA
20-20211AA-4
TYP.
EP508
EP508
SERVER ROOM
SECURE
20211
84 SF
200 SF
20211
200 SF
20211
A SIDE POWER, CONCEALED WHERE POSSIBLE
B SIDE POWER, CONCEALED WHERE POSSIBLE
A SIDE POWER, UNDERGROUND / UNDERFLOOR
B SIDE POWER, UNDERGROUND / UNDERFLOOR
PROVIDED TO INDICATE 'A' AND 'B' SIDE SOURCED POWER FEEDERS.
REFERENCE GENERAL SYMBOL LEGEND FOR ADDITIONAL
INFORMATION.
LEGEND
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/0
/2
:0
:2 a m
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /E
E
B L D
G
.r v t
20EP402
BLDG 20 - LEVEL 02 - ENLARGED ELECTRICAL
PLANS
DCW/NVP RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
KEY NOTES
KEY PLAN
GENERAL NOTES
PROJECT
NORTH
- 1/4" = 1'-0"
1 RM 20211 - DEMOLITION ELECTRICAL PLAN
- 1/4" = 1'-0"
2 RM 20211A - ELECTRICAL PLAN
- 1/4" = 1'-0"
3 RM 20211 - DEMOLITION LIGHTING PLAN
- 1/4" = 1'-0"
4 RM 20211A - LIGHTING AND RECEPTACLE PLAN
2'0 4' 8'
PROJECT
NORTH
2'0 4' 8'
PROJECT
NORTH
2'0 4' 8'
PROJECT
NORTH
2'0 4' 8'
PROJECT
NORTH
EXISTING EQUIPMENT SHALL BE DEMOLISHED. ASSOCIATED CONDUIT AND WIRE
SHALL BE DEMOLISHED BACK TO SOURCE.
SOURCE POWER PANELBOARD "20-20211AA".
SOURCE POWER PANELBOARD "20-20211AB".
PROVIDE SECONDARY BONDING BUSBAR. REFERENCE TELECOMMUNICATIONS
BONDING RISER DIAGRAM(S) FOR ADDITIONAL INFORMATION.
OVERHEAD TR RACK SOURCE A AND SOURCE B POWER RECEPTACLE.
FURNISH AND INSTALL BOXED POWER SUPPLIES AS INDICATED ABOVE ACCESSIBLE
CEILINGS. VERIFY LOCATIONS WITH ARCHITECT. PROVIDE (1) POWER SUPPLY FOR
EACH DOOR OPENING. PROVIDE 120V POWER TO ADEQUATELY SERVE DOORS WITH
ELECTRIFIED DOOR HARDWARE AND MAKE CONNECTIONS AS REQUIRED. SEE
REQUIREMENTS IN "08 71 00 - DOOR HARDWARE". COORDINATE WITH ARCHITECT
AND DOOR INSTALLER.
CONDUIT ROUTED VERTICALLY FROM LEVEL 01. REFERENCE SHEET 20EP101 FOR
ADDITIONAL INFORMATION.
EXISTING EQUIPMENT SHALL BE RELOCATED AS SHOWN IN DETAIL '2' ON THIS
SHEET.
RELOCATED EQUIPMENT. EXTEND CONDUIT AND WIRE AND PROVIDE ALL
APPURTENANCES TO RESTORE FUNCTIONALITY TO UNIT AS REQUIRED.
PROVIDE RACEWAYS AND CONDUCTORS PER MANUFACTURER'S REQUIREMENTS.
REFERENCE MECHANICAL DRAWINGS AND COORDINATE WITH MECHANICAL
CONTRACTOR AS REQUIRED.
CONDUIT ROUTED VERTICALLY TO LEVEL 03. REFERENCE SHEET 20EP103 FOR
ADDITIONAL INFORMATION.
CONDUIT ROUTED VERTICALLY TO FLOOR 03 FROM LEVEL 01. REFERENCE SHEET
20EP101 FOR ADDITIONAL INFORMATION.
1. DEMOLITION PLANS/NOTES ARE BASED ON SITE INVESTIGATIONS AND RECORD
DRAWINGS. IF DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK, PROMPTLY
NOTIFY VA AND ENGINEER OF SAID DISCREPANCY.
2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER, LIGHTING AND ASSOCIATED CIRCUITRY AS REQUIRED.
ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE
DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS
OTHERWISE NOTED.
3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS AND
RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED, AND IN ALL LOCATIONS
WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION,
UNLESS OTHERWISE NOTED.
4. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM
SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED
EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER
AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO
ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL
REMAIN ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL
CONFORM WITH VA STANDARDS.
5. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING; PROVIDE CORE DRILLING AS REQUIRED.
COORDINATE WITH ARCHITECTURAL AND STRUCTURAL DRAWINGS AS REQUIRED.
6. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL
PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.
8. CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL FEEDERS WHERE FEEDER
RUNS EXCEED 250FT OR HAVE MORE THAN 270 DEGREES OF TOTAL BEND. PULL
BOX PLACEMENTS AND SIZING BY CONTRACTOR. COORDINATE PULL BOX
LOCATIONS WITH ALL OBSTRUCTIONS, TRADES, AND VA AS REQUIRED.
9. ALL RECEPTACLES AND SWITCHES SHALL BE PROVIDED WITH PANEL AND CIRCUIT
LABELING LOCATED DIRECTLY ON THE WALL PLATE; IE:"P4-1", PANEL "4", CIRCUIT
"1". REFERENCE WIRING DEVICE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
Revisions: Date:
KEY NOTES
PROVIDE TBB AS INDICATED; WHERE CONDUCTOR IS SUBJECT TO PHYSICAL
DAMAGE, CONDUCTOR SHALL BE ROUTED THROUGH RMC. REFERENCE
TELECOMMUNICATIONS BONDING RISER DIAGRAM ON SHEET EG603 FOR ADDITIONAL
INFORMATION.
PROVIDE SBC AS INDICATED; WHERE CONDUCTOR IS SUBJECT TO PHYSICAL
DAMAGE, CONDUCTOR SHALL BE ROUTED THROUGH RMC. REFERENCE
TELECOMMUNICATIONS BONDING RISER DIAGRAM ON SHEET EG603 FOR ADDITIONAL
INFORMATION.
B
B
B
B
B
B
B
BBBBBBB
A A
B B
A A
B B
AREA SHOWN
B22
D
ELEC.
B22
155 SF
SWBD "23R_SWBD" 1
PRIMARY BONDING
BUSBAR (PBB)
EP504
PANEL 'MEPB'
23R-P-02A
TRANSFORMER
"XFMR-23R-B09B"
TO SHEET 23REP100B
HOUSEKEEPING PAD
23R-P-02C
CONTROL PANEL
ATS '23R_ATS'
PANEL 'ERPB'
PANEL 'LPB'
PANEL 'RPBA'
PANEL 'RPBB'
23R-P-02B
ENCLOSED CIRCUIT BREAKER
"ECB-XFMR-23R-B09B"
D
ELEC.
B22
155 SF
ATS '23R_ATS'
SWBD "23R_SWBD"
PANEL 'ERPB'
PANEL 'LPB'
PANEL 'RPBA'
PANEL 'MEPB'
PANEL 'RPBB'
CONTROL PANEL
A SIDE POWER, CONCEALED WHERE POSSIBLE
B SIDE POWER, CONCEALED WHERE POSSIBLE
A SIDE POWER, UNDERGROUND / UNDERFLOOR
B SIDE POWER, UNDERGROUND / UNDERFLOOR
PROVIDED TO INDICATE 'A' AND 'B' SIDE SOURCED POWER FEEDERS.
REFERENCE GENERAL SYMBOL LEGEND FOR ADDITIONAL
INFORMATION.
LEGEND
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/0
/2
:4
:3 a m
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /E
E
B L D
G
B A
S E
M E
N T
.r v t
23REP400Ba
BLDG 23R - LEVEL 00B - ENLARGED
ELECTRICAL PLANS
23R
DCW/NVP RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
KEY PLAN
GENERAL NOTES
PROJECT
NORTH
EXISTING EQUIPMENT SHALL BE MODIFIED. UTILIZE SPACE(S) TO PROVIDE CIRCUIT
BREAKERS TO SERVE ADDED LOAD. REFERENCE ASSOCIATED BUILDING '23R' ONE-
LINE DIAGRAM FOR ADDITIONAL INFORMATION.
PROVIDE PRIMARY BONDING BUSBAR. REFERENCE TELECOMMUNICATIONS BONDING
RISER DIAGRAM(S) FOR ADDITIONAL INFORMATION.
PROVIDE TBB AS INDICATED; WHERE CONDUCTOR IS SUBJECT TO PHYSICAL
DAMAGE, CONDUCTOR SHALL BE ROUTED THROUGH RMC. REFERENCE
TELECOMMUNICATIONS BONDING RISER DIAGRAM ON SHEET EG604 FOR ADDITIONAL
INFORMATION.
PROVIDE TBC AS SHOWN. REFERENCE TELECOM BONDING RISER DIAGRAM ON
SHEET EG604 FOR ADDITIONAL INFORMATION.
HOUSEKEEPING PAD, 3-1/2" WITH CHAMFERED EDGE, SIZE PER EQUIPMENT FOOT
PRINT. PROVIDE 5000PSI CONCRETE WITH #4 REBAR, 12" OC, REBAR SHALL BE TIED,
COORDINATE REBAR INSTALLATION WITH CONDUIT INSTALLATIONS AS REQUIRED.
KEY NOTES
1/2" = 1'-0"23REP100B
2 RM B22 - ELECTRICAL PLAN
1/2" = 1'-0"23REP100B
1 RM B22 - DEMOLITION ELECTRICAL PLAN 1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
Revisions: Date:
1. DEMOLITION PLANS/NOTES ARE BASED ON SITE INVESTIGATIONS AND RECORD
DRAWINGS. IF DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK, PROMPTLY
NOTIFY VA AND ENGINEER OF SAID DISCREPANCY.
2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER, LIGHTING AND ASSOCIATED CIRCUITRY AS REQUIRED.
ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE
DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS
OTHERWISE NOTED.
3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS AND
RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED, AND IN ALL LOCATIONS
WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION,
UNLESS OTHERWISE NOTED.
4. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM
SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED
EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER
AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO
ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL
REMAIN ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL
CONFORM WITH VA STANDARDS.
5. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING; PROVIDE CORE DRILLING AS REQUIRED.
COORDINATE WITH ARCHITECTURAL AND STRUCTURAL DRAWINGS AS REQUIRED.
6. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL
PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.
8. CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL FEEDERS WHERE FEEDER
RUNS EXCEED 250FT OR HAVE MORE THAN 270 DEGREES OF TOTAL BEND. PULL
BOX PLACEMENTS AND SIZING BY CONTRACTOR. COORDINATE PULL BOX
LOCATIONS WITH ALL OBSTRUCTIONS, TRADES, AND VA AS REQUIRED.
9. ALL RECEPTACLES AND SWITCHES SHALL BE PROVIDED WITH PANEL AND CIRCUIT
LABELING LOCATED DIRECTLY ON THE WALL PLATE; IE:"P4-1", PANEL "4", CIRCUIT
"1". REFERENCE WIRING DEVICE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
BBBBBBB
B
B
B
B
A
A
A
A
A
A
AAAAAAA
A A A A A
AAAAAAA
AA
EP502
B
B
B
B B B B B
A
A
A
A
A
A
A
A
A
A
A
A
B B B B B B
Mo
A A
B B
A A
B B
B
TYP.
TERMINAL UNIT
B
EP504
23R-VRF-02-B09
23R-B09B
23R-B09A
23R-VRF-01-B09
FROM SHEET
23REP100G
ACCESS CONTROL
PANEL "23R-ACP-B09"
23R-B09A-25
TR
B09
102 SF
C
C
23R-B09A-25
P-TR-1B
P-TR-1A
23R-P-02C
23R-P-01
23R-B09A-7,9
23R-B09A-11,13
FROM SHEET
23REP100B
23R-P-03
FROM SHEET
23REP100B
AREA SHOWN
TYP.
B
23R-B09B
23R-B09A
L6
L6
L6
L6
B
TR
B09
102 SF
EP508
TYP.
EP508
23R-B09A-4
NIC
B09
STORAGE
B09
101 SF
STORAGE
B09
101 SF
A SIDE POWER, CONCEALED WHERE POSSIBLE
B SIDE POWER, CONCEALED WHERE POSSIBLE
A SIDE POWER, UNDERGROUND / UNDERFLOOR
B SIDE POWER, UNDERGROUND / UNDERFLOOR
PROVIDED TO INDICATE 'A' AND 'B' SIDE SOURCED POWER FEEDERS.
REFERENCE GENERAL SYMBOL LEGEND FOR ADDITIONAL
INFORMATION.
LEGEND
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/0
/2
:4
:4 a m
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /E
E
B L D
G
B A
S E
M E
N T
.r v t
23REP400Bb
BLDG 23R - LEVEL 00B - ENLARGED
ELECTRICAL PLANS
23R
DCW/NVP RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
1/2" = 1'-0"23REP100B
1 RM B09 - ELECTRICAL DEMOLITION PLAN
1/2" = 1'-0"23REP100B
2 RM B09 - ELECTRICAL PLAN
KEY PLAN
GENERAL NOTES
PROJECT
NORTH
1/2" = 1'-0"23REP100B
3 RM B09 - LIGHTING DEMOLITION PLAN
1/2" = 1'-0"23REP100B
4 RM B09 - LIGHTING AND RECEPTACLE PLAN
EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED CONDUIT AND WIRE
SHALL BE DEMOLISHED BACK TO SOURCE.
SOURCE A POWER PANELBOARD "23R-B09A".
SOURCE B POWER PANELBOARD "23R-B09B".
PROVIDE SECONDARY BONDING BUSBAR. REFERENCE TELECOMMUNICATIONS
BONDING RISER DIAGRAM(S) FOR ADDITIONAL INFORMATION.
OVERHEAD TR RACK SOURCE A AND SOURCE B POWER RECEPTACLE.
FURNISH AND INSTALL BOXED POWER SUPPLIES AS INDICATED ABOVE
ACCESSIBLE CEILINGS. VERIFY LOCATIONS WITH ARCHITECT. PROVIDE (1) POWER
SUPPLY FOR EACH DOOR OPENING. PROVIDE 120V POWER TO ADEQUATE SERVE
DOORS WITH ELECTRIFIED DOOR HARDWARE AND MAKE CONNECTIONS AS
REQUIRED. SEE REQUIREMENTS IN "08 71 00 - DOOR HARDWARE". COORDINATE
WITH ARCHITECT AND DOOR INSTALLER.
PROVIDE RACEWAYS AND CONDUCTORS PER MANUFACTURER'S REQUIREMENTS.
REFERENCE MECHANICAL DRAWINGS AND COORDINATE WITH MECHANICAL
CONTRACTOR AS REQUIRED.
TELECOM RACK IS NIC PER DESIGN ALERT 16. SPARE CIRCUIT BREAKER HAS BEEN
PROVIDED FOR FUTURE EQUIPMENT. REFERENCE ASSOCIATED PANEL
SCHEDULES FOR ADDITIONAL INFORMATION.
PROVIDE TBB AS INDICATED; WHERE CONDUCTOR IS SUBJECT TO PHYSICAL
DAMAGE, CONDUCTOR SHALL BE ROUTED THROUGH RMC. REFERENCE
TELECOMMUNICATIONS BONDING RISER DIAGRAM ON SHEET EG604 FOR
ADDITIONAL INFORMATION.
PROVIDE SBC AS INDICATED; WHERE CONDUCTOR IS SUBJECT TO PHYSICAL
DAMAGE, CONDUCTOR SHALL BE ROUTED THROUGH RMC. REFERENCE
TELECOMMUNICATIONS BONDING RISER DIAGRAM ON SHEET EG604 FOR
ADDITIONAL INFORMATION.
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
KEY NOTES
Revisions: Date:
1. DEMOLITION PLANS/NOTES ARE BASED ON SITE INVESTIGATIONS AND RECORD
DRAWINGS. IF DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK, PROMPTLY
NOTIFY VA AND ENGINEER OF SAID DISCREPANCY.
2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER, LIGHTING AND ASSOCIATED CIRCUITRY AS REQUIRED.
ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE
DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS
OTHERWISE NOTED.
3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS AND
RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED, AND IN ALL LOCATIONS
WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION,
UNLESS OTHERWISE NOTED.
4. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM
SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED
EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER
AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO
ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL
REMAIN ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL
CONFORM WITH VA STANDARDS.
5. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING; PROVIDE CORE DRILLING AS REQUIRED.
COORDINATE WITH ARCHITECTURAL AND STRUCTURAL DRAWINGS AS REQUIRED.
6. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL
PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.
8. CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL FEEDERS WHERE FEEDER
RUNS EXCEED 250FT OR HAVE MORE THAN 270 DEGREES OF TOTAL BEND. PULL
BOX PLACEMENTS AND SIZING BY CONTRACTOR. COORDINATE PULL BOX
LOCATIONS WITH ALL OBSTRUCTIONS, TRADES, AND VA AS REQUIRED.
9. ALL RECEPTACLES AND SWITCHES SHALL BE PROVIDED WITH PANEL AND CIRCUIT
LABELING LOCATED DIRECTLY ON THE WALL PLATE; IE:"P4-1", PANEL "4", CIRCUIT
"1". REFERENCE WIRING DEVICE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
A
A
A
A
A
A
A
A A
B B
A A
B B
E
ELEC.
G03
153 SF
PANEL "ERPG"
PANEL "LPG"
PANEL 'ELP'
PANEL "23R_ERDP"
TRANSFORMER
"23R_ERDP"
PANEL 'EDP'
PANEL "RPG"
PANEL "DP"
XFMR "T-1"
AREA SHOWN
E
ELEC.
G03
153 SF
TO SHEET 23REP100G
PANEL "RPG"
PANEL "DP"
XFMR "T-1"
PANEL 'EDP'
TRANSFORMER
"23R_ERDP"
PANEL "23R_ERDP"
PANEL "ERPG"
PANEL 'ELP'
PANEL "LPG"
23R-P-01
23R-P-04
G03
A SIDE POWER, CONCEALED WHERE POSSIBLE
B SIDE POWER, CONCEALED WHERE POSSIBLE
A SIDE POWER, UNDERGROUND / UNDERFLOOR
B SIDE POWER, UNDERGROUND / UNDERFLOOR
PROVIDED TO INDICATE 'A' AND 'B' SIDE SOURCED POWER FEEDERS.
REFERENCE GENERAL SYMBOL LEGEND FOR ADDITIONAL
INFORMATION.
LEGEND
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/0
/2
:5
:4 a m
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /E
E
B L D
G
G R
O U
N D
F L
O O
R .r v t
23REP400G
BLDG 23R - LEVEL 00G - ENLARGED
ELECTRICAL PLANS
23R
DCW/NVP RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
1/2" = 1'-0"23REP100G
1 RM G03 - ELECTRICAL DEMOLITION PLAN 2'0 4' 6'
PROJECT
NORTH
2'0 4' 6'
PROJECT
NORTH
PROJECT
NORTH
EXISTING PANELBOARD SHALL BE DEMOLISHED AND REPLACED AS INDICATED.
PRESERVE AND PROTECT EXISTING BRANCH CIRCUITS FOR RE-TERMINATION TO
REVISED EQUIPMENT; PROVIDE JUNCTION BOXES (QUANTITY AS REQUIRED) TO
HOUSE CONDUCTOR TERMINATIONS. SIZE JUNCTION BOXES PER NEC. COORDINATE
FINAL JUNCTION BOX LOCATIONS WITH EXISTING CONDITIONS AND EQUIPMENT AS
REQUIRED. REFERENCE ASSOCIATED ONE-LINE DIAGRAMS FOR ADDITIONAL
INFORMATION.
GENERAL NOTES
KEY PLAN
KEY NOTES
1. DEMOLITION PLANS/NOTES ARE BASED ON SITE INVESTIGATIONS AND RECORD
DRAWINGS. IF DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK, PROMPTLY
NOTIFY VA AND ENGINEER OF SAID DISCREPANCY.
2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER, LIGHTING AND ASSOCIATED CIRCUITRY AS REQUIRED. ALL
RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED
SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.
3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS AND
RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED, AND IN ALL LOCATIONS
WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION,
UNLESS OTHERWISE NOTED.
4. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM
SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED
EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER
AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO
ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL REMAIN
ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL CONFORM WITH
VA STANDARDS.
5. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING; PROVIDE CORE DRILLING AS REQUIRED. COORDINATE
WITH ARCHITECTURAL AND STRUCTURAL DRAWINGS AS REQUIRED.
6. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL
PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.
8. CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL FEEDERS WHERE FEEDER RUNS
EXCEED 250FT OR HAVE MORE THAN 270 DEGREES OF TOTAL BEND. PULL BOX
PLACEMENT AND SIZING BY CONTRACTOR. COORDINATE PULL BOX LOCATIONS WITH
ALL OBSTRUCTIONS, TRADES, AND VA AS REQUIRED.
9. ALL RECEPTACLES AND SWITCHES SHALL BE PROVIDED WITH PANEL AND CIRCUIT
LABELING LOCATED DIRECTLY ON THE WALL PLATE; IE:"P4-1", PANEL "4", CIRCUIT "1".
REFERENCE WIRING DEVICE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
1/2" = 1'-0"23REP100G
2 RM G03 - ELECTRICAL PLAN
A
A
A
BB
A
A
AA
B B
B B B B B B B
A A A A A A A
AA
A A
B B
A A
B B
AREA OF WORK
E127-25
F
ELECT. EQUP.
E127-25
121 SF
PANEL '25LPN-GA'
PANEL '25-MDP-GA'
JUNCTION BOXES
PANEL '25LPE-GA'
PANEL '25RPN-GA'
PANEL '25RPE-GA'
FACP
JUNCTION BOX
UNKNOWN EQUIPMENT
F
ELECT. EQUP.
E127-25
121 SF
PRIMARY BONDING
BUSBAR (PBB)
EP504
25-P-02A
TO SHEET 25EP101
25-P-01A
PANEL '25LPN-GA'
PANEL '25_MDP-GA'1
JUNCTION BOXES
PANEL '25LPE-GA'
PANEL '25RPN-GA'
PANEL '25RPE-GA'
FACP
JUNCTION BOX
UNKNOWN EQUIPMENT
25-P-02C
25-P-01C
TO SHEET 25EP101
HOUSEKEEPING PAD
EP501
TRANSFORMER '25-PG103-25B' (ABOVE)
TRANSFORMER '25-PG103-25A'
25-P-01B
ENCLOSED CIRCUIT BREAKER
"ECB-25-PG103-25B" (BELOW)
ENCLOSED CIRCUIT BREAKER
"ECB-25-PG103-25A"
25-P-02B
A SIDE POWER, CONCEALED WHERE POSSIBLE
B SIDE POWER, CONCEALED WHERE POSSIBLE
A SIDE POWER, UNDERGROUND / UNDERFLOOR
B SIDE POWER, UNDERGROUND / UNDERFLOOR
PROVIDED TO INDICATE 'A' AND 'B' SIDE SOURCED POWER FEEDERS.
REFERENCE GENERAL SYMBOL LEGEND FOR ADDITIONAL
INFORMATION.
LEGEND
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/0
/2
:0
:3 a m
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /E
E
B L D
G
.r v t
25EP401a
BLDG 25 - LEVEL 01 - ENLARGED ELECTRICAL
PLANS
DCW/NVP RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
KEY NOTES
KEY PLAN
GENERAL NOTES
1. DEMOLITION PLANS/NOTES ARE BASED ON SITE INVESTIGATIONS AND RECORD
DRAWINGS. IF DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK, PROMPTLY
NOTIFY VA AND ENGINEER OF SAID DISCREPANCY.
2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER, LIGHTING AND ASSOCIATED CIRCUITRY AS REQUIRED.
ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE
DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS
OTHERWISE NOTED.
3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS, AND
RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL LOCATIONS
WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION,
UNLESS OTHERWISE NOTED.
4. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM
SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED
EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER
AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO
ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL
REMAIN ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL
CONFORM WITH VA STANDARDS.
5. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING; PROVIDE CORE DRILLING AS REQUIRED.
COORDINATE WITH ARCHITECTURAL AND STRUCTURAL DRAWINGS AS REQUIRED.
6. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORM
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL
PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.
8. CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL FEEDERS WHERE FEEDER
RUNS EXCEED 250FT OR HAVE MORE THAN 270 DEGREES OF TOTAL BEND. PULL
BOX PLACEMENT AND SIZING BY CONTRACTOR. COORDINATE PULL BOX LOCATIONS
WITH ALL OBSTRUCTIONS, TRADES, AND VA AS REQUIRED.
9. ALL RECEPTACLES AND SWITCHES SHALL BE PROVIDED WITH PANEL AND CIRCUIT
LABELING LOCATED DIRECTLY ON THE WALL PLATE; IE:"P4-1", PANEL "4", CIRCUIT
"1". REFERENCE WIRING DEVICE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
PROJECT
NORTH
EXISTING EQUIPMENT SHALL BE MODIFIED. REFERENCE ASSOCIATED BUILDING '25'
ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.
PROVIDE PRIMARY BONDING BUSBAR. REFERENCE TELECOMMUNICATIONS
BONDING RISER DIAGRAM ON SHEET EG604 FOR ADDITIONAL INFORMATION.
PROVIDE TBB AS INDICATED; WHERE CONDUCTOR IS SUBJECT TO PHYSICAL
DAMAGE, CONDUCTOR SHALL BE ROUTED THROUGH RMC. REFERENCE
TELECOMMUNICATIONS BONDING RISER DIAGRAM ON SHEET EG604 FOR
ADDITIONAL INFORMATION.
PROVIDE TBC AS SHOWN. REFERENCE TELECOM BONDING RISER DIAGRAM ON
SHEET EG604 FOR ADDITIONAL INFORMATION.
CONTRACTOR SHALL WALL MOUNT TRANSFORMER "25-PG103-25B" ABOVE
ENCLOSED CIRCUIT BREAKER "ECB-25-PG103-25B".
1/2" = 1'-0"25EP101
1 RM E-127-25 - DEMOLITION ELECTRICAL PLAN
1/2" = 1'-0"25EP101
2 RM E-127-25 - ELECTRICAL PLAN
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
B B B
AAAA
A
A
A
B
B
BBBBBBB
B
B
B
B
B
B
B
B
B
B
B
B
AAAAAAAAAA
A
A
A
A
BBB
AAAAAAAAAA
A
A
A
EP502
Mo
A A
B B
A A
B B
AREA OF WORK
PG103-25
G
TYP.
G
TR
PG103-25
97 SF
25-AC-01-PG103-25
25-PG103-25B
25-PG103-25A
TO SHEET 25EP101
EP504
ACCESS CONTROL
PANEL "25-ACP-PG103-25"
25-PG103-25A-25
P-TR-1B
P-TR-1A
C
C
25-PG103-25A-25
25-P-01C
25-P-02C
25-P-03
G
TYP.
G
TR
PG103-25
97 SF
25-PG103-25B
25-PG103-25B-4
EP508
EP508
TYP.
L4E L4E
2 2
25-PG103-25A
MAINTENANCE
EQUIPMENT
PG101-25
256 SF
MAINTENANCE
EQUIPMENT
PG101-25
256 SF
A SIDE POWER, CONCEALED WHERE POSSIBLE
B SIDE POWER, CONCEALED WHERE POSSIBLE
A SIDE POWER, UNDERGROUND / UNDERFLOOR
B SIDE POWER, UNDERGROUND / UNDERFLOOR
PROVIDED TO INDICATE 'A' AND 'B' SIDE SOURCED POWER FEEDERS.
REFERENCE GENERAL SYMBOL LEGEND FOR ADDITIONAL
INFORMATION.
LEGEND
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/0
/2
:0
:2 a m
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /E
E
B L D
G
.r v t
25EP401b
BLDG 25 - LEVEL 01 - ENLARGED ELECTRICAL
PLANS
DCW/NVP RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
KEY NOTES
KEY PLAN
GENERAL NOTES
1. DEMOLITION PLANS/NOTES ARE BASED ON SITE INVESTIGATIONS AND RECORD
DRAWINGS. IF DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK, PROMPTLY
NOTIFY VA AND ENGINEER OF SAID DISCREPANCY.
2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER, LIGHTING AND ASSOCIATED CIRCUITRY AS REQUIRED.
ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE
DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS
OTHERWISE NOTED.
3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS, AND
RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL LOCATIONS
WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION,
UNLESS OTHERWISE NOTED.
4. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM
SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED
EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER
AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO
ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL
REMAIN ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL
CONFORM WITH VA STANDARDS.
5. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING; PROVIDE CORE DRILLING AS REQUIRED.
COORDINATE WITH ARCHITECTURAL AND STRUCTURAL DRAWINGS AS REQUIRED.
6. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORM
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL
PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.
8. CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL FEEDERS WHERE FEEDER
RUNS EXCEED 250FT OR HAVE MORE THAN 270 DEGREES OF TOTAL BEND. PULL
BOX PLACEMENT AND SIZING BY CONTRACTOR. COORDINATE PULL BOX LOCATIONS
WITH ALL OBSTRUCTIONS, TRADES, AND VA AS REQUIRED.
9. ALL RECEPTACLES AND SWITCHES SHALL BE PROVIDED WITH PANEL AND CIRCUIT
LABELING LOCATED DIRECTLY ON THE WALL PLATE; IE:"P4-1", PANEL "4", CIRCUIT
"1". REFERENCE WIRING DEVICE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
PROJECT
NORTH
EXISTING EQUIPMENT SHALL BE DEMOLISHED. ASSOCIATED CONDUIT AND WIRE
SHALL BE DEMOLISHED BACK TO SOURCE.
SOURCE A POWER PANELBOARD "25-PG103-25A".
SOURCE B POWER PANELBOARD "25-PG103-25B".
PROVIDE SECONDARY BONDING BUSBAR. REFERENCE TELECOMMUNICATIONS
BONDING RISER DIAGRAM(S) FOR ADDITIONAL INFORMATION.
OVERHEAD TR RACK SOURCE A AND SOURCE B POWER RECEPTACLE.
FURNISH AND INSTALL BOXED POWER SUPPLIES AS INDICATED ABOVE
ACCESSIBLE CEILINGS. VERIFY LOCATIONS WITH ARCHITECT. PROVIDE (1) POWER
SUPPLY FOR EACH DOOR OPENING. PROVIDE 120V POWER TO ADEQUATELY
SERVE DOORS WITH ELECTRIFIED DOOR HARDWARE AND MAKE CONNECTIONS AS
REQUIRED. SEE REQUIREMENTS IN 08 71 00 - DOOR HARDWARE. COORDINATE WITH
ARCHITECT AND DOOR INSTALLER.
INTERIOR MECHANICAL UNIT POWERED FROM ASSOCIATED EXTERIOR UNIT.
PROVIDE CONDUIT AND WIRE PER MANUFACTURER'S REQUIREMENTS. REFERENCE
MECHANICAL DRAWINGS AND COORDINATE WITH MECHANICAL CONTRACTOR AS
REQUIRED.
PROVIDE TBB AS INDICATED; WHERE CONDUCTOR IS SUBJECT TO PHYSICAL
DAMAGE, CONDUCTOR SHALL BE ROUTED THROUGH RMC. REFERENCE
TELECOMMUNICATIONS BONDING RISER DIAGRAM ON SHEET EG604 FOR
ADDITIONAL INFORMATION.
PROVIDE SBC AS INDICATED; WHERE CONDUCTOR IS SUBJECT TO PHYSICAL
DAMAGE, CONDUCTOR SHALL BE ROUTED THROUGH RMC. REFERENCE
TELECOMMUNICATIONS BONDING RISER DIAGRAM ON SHEET EG604 FOR
ADDITIONAL INFORMATION.
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
PROJECT
NORTH
1'0 2' 4'
1/2" = 1'-0"25EP101
1 RMPG101-25 - DEMOLITION ELECTRICAL PLAN
1/2" = 1'-0"25EP101
2 RM PG103-25 - ELECTRICAL PLAN
1/2" = 1'-0"25EP101
3 RM PG101-25 - DEMOLITION LIGHTING PLAN
1/2" = 1'-0"25EP101
4 RM PG103-25 - LIGHTING AND RECEPTACLE PLAN
Revisions: Date:
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
AA
BBBBBBB
A A A A A A A A A
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
J
AAAAAAA
A
A
AAAAAAA
B B B B B B
B
B
AA
A A
B
B
B
B
B
EP502
Mo
A A
B B
A A
B B
AREA SHOWN
B C D
PANEL '28-LA-D-G-A'
75kVA XFMR (BELOW)
TELECOM CABINET
PANEL 'EP-28'ATS-28
XFMR 'TE-28' (ABOVE)
DISCONNECTS
(BELOW)
DISCONNECT (ABOVE)
JUNCTION BOX
''LIGHTING CONTRACTOR A''
(ABOVE)
JUNCTION BOX
''LIGHTING CONTRACTOR B''
(ABOVE)
GENERAL
WAREHOUSE
STORAGE
WAREHOUSE-28
4701 SF
GE CONTROLS PANEL
TYP.
TYP.
TELECOM RACK
B C D
TR
TELECOM ROOM-28
80 SF
PANEL '28-LA-D-G-A'
75kVA TRANSFORMER (BELOW)
TELECOM CABINET
ATS-28
TRANSFORMER 'T-E28'
DISCONNECT 'T-E28'
DISCONNECT (ABOVE)
PANEL '28-MDP' JUNCTION BOX
''LIGHTING CONTRACTOR B''
(ABOVE)
JUNCTION BOX
''LIGHTING CONTRACTOR A''
(ABOVE)
GENERAL
WAREHOUSE
STORAGE
WAREHOUSE-28
4701 SF
PANEL 'EP-28'
PRIMARY BONDING
BUSBAR (PBB)
EP504
28-P-02
28-P-01B
28-P-04
28-P-03
28-P-05
28-P-08
28-P-06
28-P-07
HOUSEKEEPING PAD 15
28-P-01A
ENCLOSED CIRCUIT BREAKER
"ECB-28_LA-D-G-AA"
WAREHOUSE-28
TELECOM ROOM-28
B
28-VRF-01-TELECOM RM-28
TR
TELECOM ROOM-28
80 SF
28-TELECOM
RM-28B
28-TELECOM RM-28A
28-VRF-02-TELECOM
ROOM-28
28-TELECOM RM-28A
ACCESS CONTROL
PANEL "28-ACP-TELECOM RM 28"
EP504
28-CU-01-TELECOM ROOM-28
28-TELECOM RM-28A-27
28-TELECOM RM-28A
C
C
P-TR-1B
P-TR-1A
28-P-09
28-TELECOM RM-28A-14,16
28-TELECOM RM-28A-10,12
GE CONTROLS PANEL
B
L4 L4
TR
TELECOM ROOM-28
80 SF
28-TELECOM RM-28B
28-TELECOM RM-28A
28-TELECOM RM-28A-41
EP508
EP508
TYP.
2 2
A SIDE POWER, CONCEALED WHERE POSSIBLE
B SIDE POWER, CONCEALED WHERE POSSIBLE
A SIDE POWER, UNDERGROUND / UNDERFLOOR
B SIDE POWER, UNDERGROUND / UNDERFLOOR
PROVIDED TO INDICATE 'A' AND 'B' SIDE SOURCED POWER FEEDERS.
REFERENCE GENERAL SYMBOL LEGEND FOR ADDITIONAL
INFORMATION.
LEGEND
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/0
/2
:2
:4 a m
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /E
E
B L D
G
.r v t
28EP401
BLDG 28 - LEVEL 01 - ENLARGED ELECTRICAL
PLANS
DCW/NVP RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
GENERAL NOTES
KEY PLAN
KEY NOTES
EXISTING EQUIPMENT SHALL BE DEMOLISHED. ASSOCIATED CONDUIT AND WIRE
SHALL BE DEMOLISHED BACK TO SOURCE.
DEMOLISH EXISTING CONDUCTORS AND RACEWAYS AS INDICATED.
SOURCE A POWER PANELBOARD "28-TELECOM ROOM 28A".
SOURCE B POWER PANELBOARD "28-TELECOM ROOM 28B".
OVERHEAD TR RACK SOURCE A AND SOURCE B POWER RECEPTACLE.
FURNISH AND INSTALL BOXED POWER SUPPLIES AS INDICATED ABOVE ACCESSIBLE
CEILINGS. VERIFY LOCATIONS WITH ARCHITECT. PROVIDE (1) POWER SUPPLY FOR
EACH DOOR OPENING. PROVIDE 120V POWER TO ADEQUATELY SERVE DOORS WITH
ELECTRIFIED DOOR HARDWARE AND MAKE CONNECTIONS AS REQUIRED. SEE
REQUIREMENTS IN "08 71 00 - DOOR HARDWARE". COORDINATE WITH ARCHITECT AND
DOOR INSTALLER.
PROVIDE RACEWAYS AND CONDUCTORS PER MANUFACTURER'S REQUIREMENTS.
REFERENCE MECHANICAL DRAWINGS AND COORDINATE WITH MECHANICAL
CONTRACTOR AS REQUIRED.
PROVIDE SERVICE RECEPTACLE, 20A, 120V, GFCI, HOUSED IN WEATHER RATED DIE-
CAST ALUMINUM WHILE-IN-USE COVER.
EXISTING EQUIPMENT SHALL BE MODIFIED. REFERENCE ASSOCIATED BUILDING '28'
ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.
EXISTING PANELBOARD SHALL BE DEMOLISHED AND REPLACED AS INDICATED.
PRESERVE AND PROTECT EXISTING BRANCH CIRCUITS FOR RE-TERMINATION TO
REVISED EQUIPMENT; PROVIDE JUNCTION BOXES (QUANTITY AS REQUIRED) TO
HOUSE CONDUCTOR TERMINATIONS. SIZE JUNCTION BOXES PER NEC. COORDINATE
FINAL JUNCTION BOX LOCATIONS WITH EXISTING CONDITIONS AND EQUIPMENT AS
REQUIRED. REFERENCE ASSOCIATED ONE-LINE DIAGRAMS FOR ADDITIONAL
INFORMATION.
PROVIDE PRIMARY BONDING BUSBAR. REFERENCE TELECOMMUNICATIONS BONDING
RISER DIAGRAM ON SHEET EG603 FOR ADDITIONAL INFORMATION.
PROVIDE TBB AS INDICATED; WHERE CONDUCTOR IS SUBJECT TO PHYSICAL
DAMAGE, CONDUCTOR SHALL BE ROUTED THROUGH RMC. REFERENCE
TELECOMMUNICATIONS BONDING RISER DIAGRAM ON SHEET EG603 FOR ADDITIONAL
INFORMATION.
PROVIDE TBC AS SHOWN. REFERENCE TELECOM BONDING RISER DIAGRAM ON
SHEET EG603 FOR ADDITIONAL INFORMATION.
PROVIDE SECONDARY BONDING BUSBAR. REFERENCE TELECOMMUNICATIONS
BONDING RISER DIAGRAM(S) FOR ADDITIONAL INFORMATION.
PROJECT
NORTH
- 1/4" = 1'-0"
3 RM WAREHOUSE-28 - ELECTRICAL PLAN - EXISTING
- 1/4" = 1'-0"
4 RM WAREHOUSE-28 - ELECTRICAL PLAN - REVISED2'0 4' 8'
PROJECT
NORTH
2'0 4' 8'
PROJECT
NORTH
- 1/4" = 1'-0"
1 RM TELECOM ROOM-28 - ELECTRICAL PLAN
- 1/4" = 1'-0"
2 RM TELECOM ROOM-28 - LIGHTING AND RECEPTALE PLAN2'0 4' 8'
PROJECT
NORTH
2'0 4' 8'
PROJECT
NORTH
Revisions: Date:
1. DEMOLITION PLANS/NOTES ARE BASED ON SITE INVESTIGATIONS AND RECORD
DRAWINGS. IF DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK, PROMPTLY
NOTIFY VA AND ENGINEER OF SAID DISCREPANCY.
2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER, LIGHTING AND ASSOCIATED CIRCUITRY AS REQUIRED. ALL
RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED
SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.
3. CONTRACTOR SHALL REMOVE ALL ELECTRICAL EQUIPMENT, CONDUCTORS AND
RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED, AND IN ALL LOCATIONS
WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION OF
MILLWORK.
4. CONTRACTOR SHALL DISPOSE OF THE REMOVED DEVICES. DISPOSAL OF DEVICES
SHALL COMPLY WITH ALL APPROPRIATE CODES.
5. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
6. FIELD VERIFY ALL RACEWAY DEMOLITION AND INSTALLATIONS PRIOR TO
PERFORMING WORK.
7. CONTRACTOR TO COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM
SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED
EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER
AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO
ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL REMAIN
ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL CONFORM WITH
VA STANDARDS.
8. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING; PROVIDE CORE DRILLING AS REQUIRED. COORDINATE
WITH ARCHITECTURAL AND STRUCTURAL DRAWINGS AS REQUIRED.
9. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.
FOR TR ROOM PANEL SCHEDULES REFERENCE THE TYPICAL A AND B POWER
SCHEDULE CLASSIFICATION FOR ADDITION INFORMATION.
10. THE CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL
PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING FURNITURE, INCLUDING
TRANSPORTATION, FOR ALL WORK TO DESIRED VA STORAGE LOCATION.
COORDINATE WITH VA AS REQUIRED.
12. ALL RECEPTACLES AND SWITCHES SHALL BE PROVIDED WITH PANEL AND CIRCUIT
LABELING LOCATED DIRECTLY ON THE WALL PLATE, I.E., "P4-1", PANEL "4", CIRCUIT "1".
REFERENCE WIRING DEVICE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
KEY NOTES
HOUSEKEEPING PAD, 3-1/2" WITH CHAMFERED EDGE, SIZE PER EQUIPMENT FOOT
PRINT. PROVIDE 5000PSI CONCRETE WITH #4 REBAR, 12" OC, REBAR SHALL BE TIED
COORDINATE REBAR INSTALLATION WITH CONDUIT INSTALLATIONS AS REQUIRED.
PROVIDE SBC AS INDICATED; WHERE CONDUCTOR IS SUBJECT TO PHYSICAL
DAMAGE, CONDUCTOR SHALL BE ROUTED THROUGH RMC. REFERENCE
TELECOMMUNICATIONS BONDING RISER DIAGRAM ON SHEET EG603 FOR ADDITIONAL
INFORMATION.
AAAAAAA
AAAAAAA
B B B
BBBBBBBBBBBBBB
Mo
A A
B B
A A
B B
A
B
VFD's
PANEL '34-DP-M'
PANEL '34ESM1'
PANEL '34-B-E-C'
XFMR 'TXB' (ABOVE)
34B-E-B
CONTROL PANEL (BELOW)
XFMR 'TXC' (ABOVE)
A
B
EP504
STORAGE (TE)
SP3401-34
1999 SF
ACCESS CONTROL
PANEL "34-ACP-SP3401-34"
SP3401-34-25
E E
EP502
34-TF-01-SP3401-34
VFD's
PANEL '34-DP-M'
PANEL '34ESM1'
PANEL '34-B-E-C'
XFMR 'TXC' (ABOVE)
XFMR 'TXB' (ABOVE)
PANEL '34B-E-B' (BELOW)
CONTROL PANEL (BELOW)
TRANSFORMER "XF-SP3401-34"
PANELBOARD "SP3401-34"
34-P-03A
34-P-03B
34-P-01
34-P-02
34-P-04
SP3401-34-7
SP3401-34-25
HOUSEKEEPING PAD6
34-P-05
34-P-06
ENCLOSED CIRCUIT
BREAKER ''ECB-SP3401-34''
A
B
TYP.
A
B
L7E
STORAGE (TE)
SP3401-34
1999 SF
EP508
EP508
SP3401-34-3
PANELBOARD "SP3401-34" 11
SP3401-34
AREA SHOWN
STORAGE
SP3401-34
1999 SF
STORAGE
SP3401-34
1999 SF
A SIDE POWER, CONCEALED WHERE POSSIBLE
B SIDE POWER, CONCEALED WHERE POSSIBLE
A SIDE POWER, UNDERGROUND / UNDERFLOOR
B SIDE POWER, UNDERGROUND / UNDERFLOOR
PROVIDED TO INDICATE 'A' AND 'B' SIDE SOURCED POWER FEEDERS.
REFERENCE GENERAL SYMBOL LEGEND FOR ADDITIONAL
INFORMATION.
LEGEND
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/0
/2
:0
:5 a m
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /E
E
B L D
G
.r v t
34EP400
BLDG 34 - LEVEL 00 - ENLARGED ELECTRICAL
PLANS
DCW/NVP RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
KEY NOTES
KEY PLAN
GENERAL NOTES
1. DEMOLITION PLANS/NOTES ARE BASED ON SITE INVESTIGATIONS AND RECORD
DRAWINGS. IF DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK, PROMPTLY
NOTIFY VA AND ENGINEER OF SAID DISCREPANCY.
2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL
FIELD VERIFY ALL POWER, LIGHTING AND ASSOCIATED CIRCUITRY AS REQUIRED. ALL
RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED
SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS
OTHERWISE NOTED.
3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS AND
RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED, AND IN ALL LOCATIONS
WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION,
UNLESS OTHERWISE NOTED.
4. CONTRACTOR SHALL COORDINATE NORMAL/ESSENTIAL ELECTRICAL SYSTEM
SHUTDOWNS AND PHASING WITH THE VA PRIOR TO PERFORMING REQUIRED
EQUIPMENT UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY POWER
AND DETERMINE TIE-IN/CONNECTION PLAN WITH EXISTING EQUIPMENT. POWER TO
ALL EXISTING ESSENTIAL EQUIPMENT CANNOT BE INTERRUPTED AND SHALL REMAIN
ACTIVE DURING CONSTRUCTION. BACKUP POWER AND TIE-IN SHALL CONFORM WITH
VA STANDARDS.
5. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE
RATING OR NEW FIRE RATING; PROVIDE CORE DRILLING AS REQUIRED. COORDINATE
WITH ARCHITECTURAL AND STRUCTURAL DRAWINGS AS REQUIRED.
6. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.
7. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL
PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.
8. CONTRACTOR SHALL PROVIDE PULL BOXES FOR ALL FEEDERS WHERE FEEDER
RUNS EXCEED 250FT OR HAVE MORE THAN 270 DEGREES OF TOTAL BEND. PULL BOX
PLACEMENT AND SIZING BY CONTRACTOR. COORDINATE PULL BOX LOCATIONS WITH
ALL OBSTRUCTIONS, TRADES, AND VA AS REQUIRED.
9. ALL RECEPTACLES AND SWITCHES SHALL BE PROVIDED WITH PANEL AND CIRCUIT
LABELING LOCATED DIRECTLY ON THE WALL PLATE, I.E., "P4-1", PANEL "4", CIRCUIT
"1". REFERENCE WIRING DEVICE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
PROJECT
NORTH
PROVIDE SECONDARY BONDING BUSBAR. REFERENCE TELECOMMUNICATIONS
BONDING RISER DIAGRAM(S) FOR ADDITIONAL INFORMATION.
TE POWER RECEPTACLE. 120V, 30A, 1PH, L5-30 OUTLET.
FURNISH AND INSTALL BOXED POWER SUPPLIES AS INDICATED ABOVE ACCESSIBLE
CEILINGS. VERIFY LOCATIONS WITH ARCHITECT. PROVIDE (1) POWER SUPPLY FOR
EACH DOOR OPENING. PROVIDE 120V POWER TO ADEQUATELY SERVE DOORS WITH
ELECTRIFIED DOOR HARDWARE AND MAKE…