Amendment 2 Attachment 3 - A-002 - PARTITION TYPES.pdf
PDF 104 KB Posted
- Solicitation number
- W50S8T25BA011
- Issued by
-
Department of the Army National Guard
About this file
This is an architectural drawing showing partition type details and specifications for Building 1040 renovation at Will Rogers Air National Guard Base. The drawing provides comprehensive details for various wall partition types including standard drywall, security/access control, chase walls, furring, interior non-rated, masonry, and rated interior partitions.
The drawing includes specific construction requirements such as: all gypsum board must be 5/8" Type 'X' unless noted otherwise; abuse-resistant gypsum board is required in corridors up to 8'-0" above finished floor; glas-mat backed gypsum board is required in wet walls, restrooms, kitchens, janitor closets and loading dock areas; continuous 16 gauge deflection track is required at interior partitions extended to deck; and sound attenuation batts must be unfaced, 2.5 PCF, installed continuously and pinned to prevent sagging. The drawing provides detailed partition type sections showing components like metal studs, gypsum board layers, insulation, and finishing requirements. Security-related specifications are included for areas requiring controlled access, including requirements for floor-to-deck walls, hard ceilings, cypher locks, and protection from visual observation through windows less than 18' from grade.
View the file
Other files
Show all 50
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PARTITION TYPE NOTES
A. STUD GAUGE IN PARTITION SCHEDULE IS A
MINIMUM.
B. STUD SPACING IN PARTITION SCHEDULE IS
MAXIMUM.
C. ALL GYPSUM BOARD SHALL BE 5/8" TYPE 'X' UNLESS
NOTED OTHERWISE HERE OR REQUIRED FOR
ACOUSTIC ASSEMBLY. INTERIOR PARTITIONS AT
CORRIDORS ARE TO USE ABUSE-RESISTANT GYP
BD TO 8'-0" AFF. INTERIOR PARTITIONS AT WET
WALLS, RESTROOMS, KITCHENS, JANITOR
CLOSETS, AND LOADING DOCK AREAS ARE TO USE
GLAS-MAT BACKED GYP BD.
D. PROVIDE CONTINUOUS 16 GAUGE DEFLECTION
TRACK (2 1/2" DEEP LEG TRACK) AND 20 GAUGE
UPPER HORIZONTAL SPACER BARS AT ALL
INTERIOR PARTITIONS EXTENDED TO DECK.
E. SUBSTITUTE 5/8" TYPE 'X' FIRE RESISTANT TILE
BACKER BOARD AT ALL LOCATIONS SCHEDULED TO
RECEIVE WALL TILE.
F. ALL GYPSUM WALL BOARD SHALL BE CUT TIGHT TO
FIT AND SEALED COMPLETELY AIRTIGHT WITH
REQUIRED SEALANT FOR EITHER FIRE RATING OR
SOUND ATTENUATION AT ALL MEP PENETRATIONS
THRU INTERIOR PARTITIONS SCHEDULED TO DECK.
G. FILL ALL PERIMETER VOIDS AND HEAD OF WALL
METAL DECK FLUTES WITH FIRESAFING INSULATION
AT ALL FIRE RATED WALLS TO ACHIEVE COMPLETE
CLOSURE AND SEAL BOTH SIDES WITH ELASTIC
FIRESTOPPING SPRAY MASTIC.
H. ALL SOUND ATTENUATION BATTS SHALL BE
UNFACED, 2.5 PCF, INSTALLED CONTINUOUS
VERTICALLY, CUT TIGHT TO FIT AND FILL THE STUD
CAVITY, AND PINNED IN PLACE TO PREVENT
SAGGING.
I. PROVIDE GLAS-MAT BACKED GYPSUM BOARD AT
THE FOLLOWING LOCATIONS:
a. MECHANICAL ROOMS
b. PLUMBING WET WALLS AT JANITOR ROOMS AND
RESTROOMS
c. LOADING DOCK AND RELATED CORRIDOR
J. PROVIDE IMPACT RESISTANT GYPSUM BOARD AT
ALL CORRIDOR WALLS, UP TO 8'-0" AFF.
K. THE TERM "TO DECK" IN THE PARTITION SCHEDULE
REFERS TO THE ENTIRE WALL ASSEMBLY
CONTINUING TO THE DECK ABOVE. WHEN THIS IS
MARKED "NO" THEN THE WALL IS TO STOP 6" ABOVE
THE CEILING UNLESS NOTED OTHERWISE. OTHER
HEAD OF WALL CONDITIONS WILL BE NOTED IN THE
PARTITION SCHEDULE - TYPE COMMENTS OR ON
THE PLANS.
L. THE ASSEMBLY CODES IN THE TYPE COMMENTS
ARE USED AS A BASIS OF DESIGN AND NOT THE
ONLY METHOD OF ACHIEVING THE DESIRED
PERFORMANCE CRITERIA OF A WALL ASSEMBLY.
M. DRYWALL CONTROL JOINT LOCATIONS ARE
MARKED WITH A 'CJ' ON THE PLAN. DRYWALL
CONTROL JOINTS ARE TO BE PLACED A MINIMUM
OF 30'-0" ON CENTERS AT ALL UNINTERRUPTED
LENGTHS OF DRYWALL AND CENTERED ON BOTH
SIDES OF DOOR FRAMES AT ALL INT DOORS TO
TRUE TOP OF WALL. SEE DETAIL 'B2/SHEET AE601'.
N. ALL EXISTING AND NEW PENETRATIONS THROUGH
THE PARTITION MUST BE FIRE-STOPPED AS A 1-
HOUR ASSEMBLY PER UFC 1-600-01 & NFPA 221.
O. BASE CONTRACTING OFFICER IS TO IDENTIFY
AREAS WITHIN PARTITION TYPE 'B' THAT REQUIRE
SECURE STANDARDS, INCLUDING:
1. FLOOR TO DECK WALLS AS PERMANENT
CONSTRUCTION
2. HARD CEILING AREAS
3.X-10 CYPHER LOCKS
4. WINDOWS LESS THAN 18' FROM GRADE NEED TO
HAVE PROTECTION FROM FORCED ENTRY OR IDS
AND NOT ALLOW VISUAL OBSERVATION
5. OPENINGS GREATER THAN 96" SQUARE MUST
HAVE MAN-BARS
6.IDS REQUIREMENTS AS DETAILED IN THE IDS
APPENDIX
7. VISUAL OR ACCESS CONTROLS.
A1*
"*" DENOTES WALL IS
TO DECK ABOVE
DENOTES GENERIC
SIZE OF STRUCTURAL
ELEMENT
WALL SERIES. SEE
LEGEND ON THIS
SHEET
A3*
NON-RATED PARTITION AS SHOWN ABOVE
WITH UNFACED ACOUSTICAL BATTS AND
EXTENDING GYPSUM BOARD TO DECK
FINISH
FLOOR
5/8" GYP BD
SCHEDULED CLG
STEEL RUNNER
CHANNEL
1-5/8" STUDS
AT 16" OC
NON-RATED FURRING
PARTITION WITH 1-5/8"
FURRING CHANNELS
C1
EXISTING WALL
OR CMU WALL
6" M
IN
BASE AS
SCHEDULED
STEEL
RUNNER
CHANNEL
NON-RATED PARTITION AS SHOWN
ABOVE WITH 6" STUDS IN LIEU OF
3-5/8" STUDS
FINISHED FLOOR
FINISH
FLOOR
5/8" GYP BD
SCHEDULED CLG
STEEL RUNNER
CHANNEL
1-5/8" STUDS
AT 16" OC
NON-RATED 1-5/8" FURRING
PARTITIONF1
F2
NON-RATED FURRING
PARTITION WITH 2-1/2" STUDS IN
LIEU OF 1-5/8" STUDS
6" M
IN
BASE AS
SCHEDULED
STEEL
RUNNER
CHANNEL
F3
NON-RATED FURRING
PARTITION WITH 3-5/8" STUDS IN
LIEU OF 1-5/8" STUDS
F6
NON-RATED FURRING
PARTITION WITH 6" STUDS IN
LIEU OF 1-5/8" STUDS
I3 NON-RATED PARTITION AS SHOWN ABOVE
5/8" GYP BD
(BOTH SIDES)
FINISH
FLOOR
SCHEDULED CLG
STEEL RUNNER
CHANNEL
BASE AS
SCHEDULED
3-5/8" STUDS
AT 16" OC
I6
NON-RATED PARTITION AS SHOWN
ABOVE WITH 6" STUDS IN LIEU OF
3-5/8" STUDS
6" M
IN
FINISHED FLOOR
5/8" GYP BD
(BOTH SIDES)
FINISH
FLOOR
EXISTING
DECK
SCHEDULED CLG
STEEL RUNNER
CHANNEL
BASE AS
SCHEDULED
6" STUDS AT
16" OC
R3
1HR RATED PARTITION WITH 3 5/8"
STUD, 5/8" ACOUSTIC GYP BD ON
BOTH SIDES - 1HR W/BATTS. (UL-
U419)
6" BATT
INSULATION
PROVIDE UL
ASSEMBLY HW-D-0042
TO DECK
FINISH FLOOR
EXISTIN
G DECK
CONT 16 GA CFMF
LONG LEG DEF
TRACK
SCHEDULED CLG
STEEL RUNNER
CHANNEL
SCHEDULED
BASE
3 5/8" 20 GA
CFM STUDS
@ 16" OC
1"
ANY APPLICABLE
LISTED UL H-O-W
SYSTEM DESIGN
A6*
PROVIDE 3 5/8"
METAL STUD
FRAMING BRACING
TO STRUCTURE @
4'-0" CTRS MAX. -
SIDE DETERMINED
IN FIELD
PROVIDE 3 5/8"
METAL STUD
FRAMING BRACING
TO STRUCTURE @
4'-0" CTRS MAX. -
SIDE DETERMINED
IN FIELD
5/8" GWB (2
LAYERS BOTH
SIDES)
STAGGER
JOINTS
B1*
FINISH FLOOR
EXISTING DECK
SCHEDULED
CLG
STEEL RUNNER
CHANNEL ON
BUTYL TAPE BASE
6" 16 GA. STEEL
STUDS @ 16" OC
SCHEDULED
BASE
UNFACED BLANKET
INSULATION
PINNED IN PLACE
CONTROLLED SIDE
UNCONTROLLED SIDE
(WHERE APPLICABLE)
STC-58 RATED PARTITION AS SHOWN WITH 6" STEEL
STUDS AND UNFACED BLANKET INSULATION
STC DESIGN: UL-419 STC 58
1"
ACOUSTICAL
SEALANT (BOTH
SIDES)
PROVIDE UL
ASSEMBLY
HW-D-0042 TO
DECK
NOTE: THERE MAY BE SCHEDULED FINISHES ABOVE THE CEILINGS -
REFER TO THE ROOM FINISH SCHEDULE.
1. THE CONTRACTOR SHALL COORDINATE FULLY WITH FACILITY
ACCREDITING OFFICER (AO) PRIOR TO AND DURING CONSTRUCTION.
NON-RATED FURRING
PARTITION WITH 3-5/8"
FURRING CHANNELS
C3
NOTE: EXAMINE ALL AREAS WHERE WALL ABUTS EXISTING
CONSTRUCTION, INCLUDING AT HEAD OF WALL. NOTIFY A/E OR
CONTRACTING OFFICER WHERE EXISTING CONTRUCTION DOES NOT
FACILITATE SECURE SOUND ENCLOSURE.
NOTE: DOUBLE LAYER OF GYP BD
MUST REMAIN CONTINUOUS AT ALL
CORNERS AND WALL INTERSECTIONS.
DO NOT ANCHOR STUDS FROM OTHER
PARTITIONS INTO PARTITION TYPE 'B1'
WALLS. SEPARATE WITH 1/2" SEALANT
ON BACKER ROD.
B1*
R6
1HR RATED PARTITION WITH 6"
STUD, 5/8" ACOUSTIC GYP BD ON
BOTH SIDES - 1HR W/BATTS. SET
'R6' PARTITION ON TOP OF
EXISTING CMU CONSTRUCTION
AND CLOSE TO DECK ABOVE
1/2" RESILIENT
CHANNEL, 25 GA.
(ONE-SIDE)
F2W
NON-RATED FURRING
PARTITION WITH 2-1/2" STUDS
AND 1/8" WIRE SECURITY MESH
STEEL CLIP ANGLES
@ 32" OC AT EXIST
CONSTRUCTION
UNFACED BLANKET
INSULATION
PINNED IN PLACE
UNFACED
BLANKET
INSULATION
PINNED IN
PLACE
CONT 16 GA CFMF
LONG LEG DEF
TRACK
CONT 16 GA CFMF
LONG LEG DEF
TRACK
"A" SERIES - STANDARD DRYWALL PARTITION
CONSTRUCTION TO DECK. MAY OR MAY NOT NEED
FIRE RATING.
"B" SERIES - SECURITY AND ACCESS STC IS A
PRIORITY. MAY OR MAY NOT NEED FIRE RATING.
"C" SERIES - CHASE WALL OR FURRING AGAINST
EXISTING CONSTRUCTION
"F" SERIES - FURRING
"I" SERIES - STANDARD INTERIOR PARTITION NOT TO
DECK. NO FIRE RATING, NO STC RATING.
"M" SERIES - MASONRY - FIRE RATED
FIRE RATING IS PRIORITY. MAY OR MAY NOT NEED
STC.
"R" SERIES - RATED INTERIOR PARTITION
WALL SERIES LEGEND
WHERE THERE IS AN ACCESSIBLE CONCEALED FLOOR, FLOOR-CEILING OR
ATTIC SPACE, FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE
PROTECT OPENINGS OR PENETRATIONS SHALL BE EFFECTIVELY AND
PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING IN THE CONCEALED
SPACE ABOVE INSTALLED CEIILNG SUCH IDENTIFICATION SHALL:
1. BE LOCATED WITHIN 15'-0" OF THE END OF EACH WALL AND AT INTERVALS
NOT EXCEEDING 30'-0" MEASURED HORIZONTALLY ALONG THE WALL OR
PARTITION.
2. INCLUDE LETTERING NOT LESS THAN 3 INCHES IN HEIGHT WITH A MINIMUM
3/8 INCH STROKE IN A CONTRASTING COLOR INCORPORATING THE SUGGESTED
WORDING, "FIRE AND/OR SMOKE BARRIER - PROTECT ALL OPENINGS," OR
OTHER WORDING.
NOTE: IN SPACE WITH NO CEILING THE MARKINGS SHALL BE 12'-0" ABOVE
FINISHED FLOOR. MARKING SHALL BE LEVEL. LETTER COLOR SHALL BE RED.
MARKING SHALL BE ON BOTH SIDES OF THE WALL OR PARTITION.
PARTITION MARKING NOTES:
UFC 3-600-01 (8 AUGUST 2016, CHANGE 6, 6 MAY 2021) SECTION 7-2 AND
2021 IBC, SECTION 703.7
5801 Broadway Extension, Suite 500 Oklahoma City, OK 73118-7436
405.840.2931 | fsb-ae.com
Frankfurt-Short-Bruza Associates,P.C.
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
C
B
A
D
C
B
A
54321
2020-484-00
NDM
Re pa ir/ Co nv er t S qu ad O ps Ok lah om a C ity
, O K
NG
BJ
V/
OK
A
NG
PN: YZEU142025
C :\U sers\bkg\D o cum ents\M y R evit\048400_AR C
H
_BG
allagher5SB23.rvt
2/26/2025 11:30 :24 AM
12 SEPTEMBER 2024
PARTITION TYPES
A-002
MJT
BKG
JO
SCALE: NTS
PARTITION TAG LEGENDD3
SCALE: 1 1/2" = 1'-0"
WALL TYPESB2
6" 1'-6"1'0
1 1/2" = 1'-0"
2 ADDENDUM 01 02/17/2025
3 ADDENDUM 02 02/27/2025