Amendment 2 Attachment 3 - A-002 - PARTITION TYPES.pdf

PDF 104 KB Posted

Attached to
137th SOW - Building 1040 Repair / Renovation Project
Solicitation number
W50S8T25BA011
Issued by

About this file

This is an architectural drawing showing partition type details and specifications for Building 1040 renovation at Will Rogers Air National Guard Base. The drawing provides comprehensive details for various wall partition types including standard drywall, security/access control, chase walls, furring, interior non-rated, masonry, and rated interior partitions.

The drawing includes specific construction requirements such as: all gypsum board must be 5/8" Type 'X' unless noted otherwise; abuse-resistant gypsum board is required in corridors up to 8'-0" above finished floor; glas-mat backed gypsum board is required in wet walls, restrooms, kitchens, janitor closets and loading dock areas; continuous 16 gauge deflection track is required at interior partitions extended to deck; and sound attenuation batts must be unfaced, 2.5 PCF, installed continuously and pinned to prevent sagging. The drawing provides detailed partition type sections showing components like metal studs, gypsum board layers, insulation, and finishing requirements. Security-related specifications are included for areas requiring controlled access, including requirements for floor-to-deck walls, hard ceilings, cypher locks, and protection from visual observation through windows less than 18' from grade.

View the file

Other files

File Type Posted
Abstract (Final).pdf PDF
Amendment 3 Attachment 1 - Bldg 1040 Reno Questions and Answers.docx DOCX document
Solicitation Amendment 3 W50S8T25BA0110003.pdf PDF
NEW 6 Mar 25 Oklahoma NGB-WRWA - 100 CD Set Part 1.pdf PDF
NEW 6 Mar 25 Oklahoma NGB-WRWA - 100 CD Set Part 2.pdf PDF
Amendment 2 Attachment 2 - 09 72 00.pdf PDF
Amendment 2 Attachment 5 - IN600 - INTERIORS MATERIALS LEGEND.pdf PDF
Amendment 2 Attachment 6 - Bldg 1040 Reno Questions and Answers.xlsx XLSX spreadsheet
Amendment 2 Attachment 1 - Addendum 02 Narrative.docx DOCX document
Solicitation Amendment 2 W50S8T25BA0110002.pdf PDF
Amendment 2 Attachment 4 - 08 11 16.pdf PDF
06 20 00.pdf PDF
21 13 13.pdf PDF
IN101 - FLOOR FINISH PLAN - SECTOR A.pdf PDF
Bldg 1040 Reno Questions and Answers - FSB and GOV Reponses.xlsx XLSX spreadsheet
EL101 - ELECTRICAL INTERIOR LIGHTING PLAN - SECTOR A.pdf PDF
AE102 - FLOOR PLAN - SECTOR A.pdf PDF
AE502 - DETAILS.pdf PDF
AE403 - ENLARGED PLANS.pdf PDF
10 21 13.pdf PDF
10 51 13.pdf PDF
08 41 13.pdf PDF
AE103 - FLOOR PLAN - SECTOR B.pdf PDF
08 81 00.pdf PDF
AE411 - INTERIOR ELEVATIONS.pdf PDF
AE402 - ENLARGED PLANS.pdf PDF
AE601 - DOOR SCHEDULE AND DETAILS.pdf PDF
26 05 73.pdf PDF
08 11 16.pdf PDF
AE602 - OLI 1 - EXTERIOR WINDOW FRAMES.pdf PDF
Addendum 01 Narrative.docx DOCX document
08 71 00.pdf PDF
IN102 - FLOOR FINISH PLAN - SECTOR B.pdf PDF
Solicitation Amendment 1 W50S8T25BA0110001 SF 30.pdf PDF
06 41 16.00 10.pdf PDF
AE201 - BUILDING ELEVATIONS.pdf PDF
TABLE OF CONTENTS.pdf PDF
A-002 - PARTITION TYPES.pdf PDF
01 45 35.pdf PDF
FA601 - FIRE ALARM - MASS NOTIFICATION RISER DIAGRAM.pdf PDF
AE151 - REFLECTED CEILING PLAN - SECTOR A.pdf PDF
AE600 - ROOM FINISH SCHEDULE.pdf PDF
10 51 16.pdf PDF
30 Jan 25 Site Visit Sign In Sheet.pdf PDF
BLDG 1040 Renovation Site Visit Slides 30 January 25.pptx PPTX presentation
ATTACHMENT 3 - 2024.09.12_OK-ANG_SQUADOPS B1040_TYPE B3_SPECIFICATIONS VOL. 2.pdf PDF
Solicitation - W50S8T25BA011.pdf PDF
ATTACHMENT 2 - 2024.09.12_OK-ANG_SQUADOPS B1040_TYPE B3_SPECIFICATIONS VOL. 1.pdf PDF
Bidders Checklist.docx DOCX document
ATTACHMENT 1 - 2024.09.12_OK-ANG_SQUADOPS B1040_TYPE B3_DRAWINGS.pdf PDF
Show all 50

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PARTITION TYPE NOTES

A. STUD GAUGE IN PARTITION SCHEDULE IS A

MINIMUM.

B. STUD SPACING IN PARTITION SCHEDULE IS

MAXIMUM.

C. ALL GYPSUM BOARD SHALL BE 5/8" TYPE 'X' UNLESS

NOTED OTHERWISE HERE OR REQUIRED FOR

ACOUSTIC ASSEMBLY. INTERIOR PARTITIONS AT

CORRIDORS ARE TO USE ABUSE-RESISTANT GYP

BD TO 8'-0" AFF. INTERIOR PARTITIONS AT WET

WALLS, RESTROOMS, KITCHENS, JANITOR

CLOSETS, AND LOADING DOCK AREAS ARE TO USE

GLAS-MAT BACKED GYP BD.

D. PROVIDE CONTINUOUS 16 GAUGE DEFLECTION

TRACK (2 1/2" DEEP LEG TRACK) AND 20 GAUGE

UPPER HORIZONTAL SPACER BARS AT ALL

INTERIOR PARTITIONS EXTENDED TO DECK.

E. SUBSTITUTE 5/8" TYPE 'X' FIRE RESISTANT TILE

BACKER BOARD AT ALL LOCATIONS SCHEDULED TO

RECEIVE WALL TILE.

F. ALL GYPSUM WALL BOARD SHALL BE CUT TIGHT TO

FIT AND SEALED COMPLETELY AIRTIGHT WITH

REQUIRED SEALANT FOR EITHER FIRE RATING OR

SOUND ATTENUATION AT ALL MEP PENETRATIONS

THRU INTERIOR PARTITIONS SCHEDULED TO DECK.

G. FILL ALL PERIMETER VOIDS AND HEAD OF WALL

METAL DECK FLUTES WITH FIRESAFING INSULATION

AT ALL FIRE RATED WALLS TO ACHIEVE COMPLETE

CLOSURE AND SEAL BOTH SIDES WITH ELASTIC

FIRESTOPPING SPRAY MASTIC.

H. ALL SOUND ATTENUATION BATTS SHALL BE

UNFACED, 2.5 PCF, INSTALLED CONTINUOUS

VERTICALLY, CUT TIGHT TO FIT AND FILL THE STUD

CAVITY, AND PINNED IN PLACE TO PREVENT

SAGGING.

I. PROVIDE GLAS-MAT BACKED GYPSUM BOARD AT

THE FOLLOWING LOCATIONS:

a. MECHANICAL ROOMS

b. PLUMBING WET WALLS AT JANITOR ROOMS AND

RESTROOMS

c. LOADING DOCK AND RELATED CORRIDOR

J. PROVIDE IMPACT RESISTANT GYPSUM BOARD AT

ALL CORRIDOR WALLS, UP TO 8'-0" AFF.

K. THE TERM "TO DECK" IN THE PARTITION SCHEDULE

REFERS TO THE ENTIRE WALL ASSEMBLY

CONTINUING TO THE DECK ABOVE. WHEN THIS IS

MARKED "NO" THEN THE WALL IS TO STOP 6" ABOVE

THE CEILING UNLESS NOTED OTHERWISE. OTHER

HEAD OF WALL CONDITIONS WILL BE NOTED IN THE

PARTITION SCHEDULE - TYPE COMMENTS OR ON

THE PLANS.

L. THE ASSEMBLY CODES IN THE TYPE COMMENTS

ARE USED AS A BASIS OF DESIGN AND NOT THE

ONLY METHOD OF ACHIEVING THE DESIRED

PERFORMANCE CRITERIA OF A WALL ASSEMBLY.

M. DRYWALL CONTROL JOINT LOCATIONS ARE

MARKED WITH A 'CJ' ON THE PLAN. DRYWALL

CONTROL JOINTS ARE TO BE PLACED A MINIMUM

OF 30'-0" ON CENTERS AT ALL UNINTERRUPTED

LENGTHS OF DRYWALL AND CENTERED ON BOTH

SIDES OF DOOR FRAMES AT ALL INT DOORS TO

TRUE TOP OF WALL. SEE DETAIL 'B2/SHEET AE601'.

N. ALL EXISTING AND NEW PENETRATIONS THROUGH

THE PARTITION MUST BE FIRE-STOPPED AS A 1-

HOUR ASSEMBLY PER UFC 1-600-01 & NFPA 221.

O. BASE CONTRACTING OFFICER IS TO IDENTIFY

AREAS WITHIN PARTITION TYPE 'B' THAT REQUIRE

SECURE STANDARDS, INCLUDING:

1. FLOOR TO DECK WALLS AS PERMANENT

CONSTRUCTION

2. HARD CEILING AREAS

3.X-10 CYPHER LOCKS

4. WINDOWS LESS THAN 18' FROM GRADE NEED TO

HAVE PROTECTION FROM FORCED ENTRY OR IDS

AND NOT ALLOW VISUAL OBSERVATION

5. OPENINGS GREATER THAN 96" SQUARE MUST

HAVE MAN-BARS

6.IDS REQUIREMENTS AS DETAILED IN THE IDS

APPENDIX

7. VISUAL OR ACCESS CONTROLS.

A1*

"*" DENOTES WALL IS

TO DECK ABOVE

DENOTES GENERIC

SIZE OF STRUCTURAL

ELEMENT

WALL SERIES. SEE

LEGEND ON THIS

SHEET

A3*

NON-RATED PARTITION AS SHOWN ABOVE

WITH UNFACED ACOUSTICAL BATTS AND

EXTENDING GYPSUM BOARD TO DECK

FINISH

FLOOR

5/8" GYP BD

SCHEDULED CLG

STEEL RUNNER

CHANNEL

1-5/8" STUDS

AT 16" OC

NON-RATED FURRING

PARTITION WITH 1-5/8"

FURRING CHANNELS

C1

EXISTING WALL

OR CMU WALL

6" M

IN

BASE AS

SCHEDULED

STEEL

RUNNER

CHANNEL

NON-RATED PARTITION AS SHOWN

ABOVE WITH 6" STUDS IN LIEU OF

3-5/8" STUDS

FINISHED FLOOR

FINISH

FLOOR

5/8" GYP BD

SCHEDULED CLG

STEEL RUNNER

CHANNEL

1-5/8" STUDS

AT 16" OC

NON-RATED 1-5/8" FURRING

PARTITIONF1

F2

NON-RATED FURRING

PARTITION WITH 2-1/2" STUDS IN

LIEU OF 1-5/8" STUDS

6" M

IN

BASE AS

SCHEDULED

STEEL

RUNNER

CHANNEL

F3

NON-RATED FURRING

PARTITION WITH 3-5/8" STUDS IN

LIEU OF 1-5/8" STUDS

F6

NON-RATED FURRING

PARTITION WITH 6" STUDS IN

LIEU OF 1-5/8" STUDS

I3 NON-RATED PARTITION AS SHOWN ABOVE

5/8" GYP BD

(BOTH SIDES)

FINISH

FLOOR

SCHEDULED CLG

STEEL RUNNER

CHANNEL

BASE AS

SCHEDULED

3-5/8" STUDS

AT 16" OC

I6

NON-RATED PARTITION AS SHOWN

ABOVE WITH 6" STUDS IN LIEU OF

3-5/8" STUDS

6" M

IN

FINISHED FLOOR

5/8" GYP BD

(BOTH SIDES)

FINISH

FLOOR

EXISTING

DECK

SCHEDULED CLG

STEEL RUNNER

CHANNEL

BASE AS

SCHEDULED

6" STUDS AT

16" OC

R3

1HR RATED PARTITION WITH 3 5/8"

STUD, 5/8" ACOUSTIC GYP BD ON

BOTH SIDES - 1HR W/BATTS. (UL-

U419)

6" BATT

INSULATION

PROVIDE UL

ASSEMBLY HW-D-0042

TO DECK

FINISH FLOOR

EXISTIN

G DECK

CONT 16 GA CFMF

LONG LEG DEF

TRACK

SCHEDULED CLG

STEEL RUNNER

CHANNEL

SCHEDULED

BASE

3 5/8" 20 GA

CFM STUDS

@ 16" OC

1"

ANY APPLICABLE

LISTED UL H-O-W

SYSTEM DESIGN

A6*

PROVIDE 3 5/8"

METAL STUD

FRAMING BRACING

TO STRUCTURE @

4'-0" CTRS MAX. -

SIDE DETERMINED

IN FIELD

PROVIDE 3 5/8"

METAL STUD

FRAMING BRACING

TO STRUCTURE @

4'-0" CTRS MAX. -

SIDE DETERMINED

IN FIELD

5/8" GWB (2

LAYERS BOTH

SIDES)

STAGGER

JOINTS

B1*

FINISH FLOOR

EXISTING DECK

SCHEDULED

CLG

STEEL RUNNER

CHANNEL ON

BUTYL TAPE BASE

6" 16 GA. STEEL

STUDS @ 16" OC

SCHEDULED

BASE

UNFACED BLANKET

INSULATION

PINNED IN PLACE

CONTROLLED SIDE

UNCONTROLLED SIDE

(WHERE APPLICABLE)

STC-58 RATED PARTITION AS SHOWN WITH 6" STEEL

STUDS AND UNFACED BLANKET INSULATION

STC DESIGN: UL-419 STC 58

1"

ACOUSTICAL

SEALANT (BOTH

SIDES)

PROVIDE UL

ASSEMBLY

HW-D-0042 TO

DECK

NOTE: THERE MAY BE SCHEDULED FINISHES ABOVE THE CEILINGS -

REFER TO THE ROOM FINISH SCHEDULE.

1. THE CONTRACTOR SHALL COORDINATE FULLY WITH FACILITY

ACCREDITING OFFICER (AO) PRIOR TO AND DURING CONSTRUCTION.

NON-RATED FURRING

PARTITION WITH 3-5/8"

FURRING CHANNELS

C3

NOTE: EXAMINE ALL AREAS WHERE WALL ABUTS EXISTING

CONSTRUCTION, INCLUDING AT HEAD OF WALL. NOTIFY A/E OR

CONTRACTING OFFICER WHERE EXISTING CONTRUCTION DOES NOT

FACILITATE SECURE SOUND ENCLOSURE.

NOTE: DOUBLE LAYER OF GYP BD

MUST REMAIN CONTINUOUS AT ALL

CORNERS AND WALL INTERSECTIONS.

DO NOT ANCHOR STUDS FROM OTHER

PARTITIONS INTO PARTITION TYPE 'B1'

WALLS. SEPARATE WITH 1/2" SEALANT

ON BACKER ROD.

B1*

R6

1HR RATED PARTITION WITH 6"

STUD, 5/8" ACOUSTIC GYP BD ON

BOTH SIDES - 1HR W/BATTS. SET

'R6' PARTITION ON TOP OF

EXISTING CMU CONSTRUCTION

AND CLOSE TO DECK ABOVE

1/2" RESILIENT

CHANNEL, 25 GA.

(ONE-SIDE)

F2W

NON-RATED FURRING

PARTITION WITH 2-1/2" STUDS

AND 1/8" WIRE SECURITY MESH

STEEL CLIP ANGLES

@ 32" OC AT EXIST

CONSTRUCTION

UNFACED BLANKET

INSULATION

PINNED IN PLACE

UNFACED

BLANKET

INSULATION

PINNED IN

PLACE

CONT 16 GA CFMF

LONG LEG DEF

TRACK

CONT 16 GA CFMF

LONG LEG DEF

TRACK

"A" SERIES - STANDARD DRYWALL PARTITION

CONSTRUCTION TO DECK. MAY OR MAY NOT NEED

FIRE RATING.

"B" SERIES - SECURITY AND ACCESS STC IS A

PRIORITY. MAY OR MAY NOT NEED FIRE RATING.

"C" SERIES - CHASE WALL OR FURRING AGAINST

EXISTING CONSTRUCTION

"F" SERIES - FURRING

"I" SERIES - STANDARD INTERIOR PARTITION NOT TO

DECK. NO FIRE RATING, NO STC RATING.

"M" SERIES - MASONRY - FIRE RATED

FIRE RATING IS PRIORITY. MAY OR MAY NOT NEED

STC.

"R" SERIES - RATED INTERIOR PARTITION

WALL SERIES LEGEND

WHERE THERE IS AN ACCESSIBLE CONCEALED FLOOR, FLOOR-CEILING OR

ATTIC SPACE, FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE

BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE

PROTECT OPENINGS OR PENETRATIONS SHALL BE EFFECTIVELY AND

PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING IN THE CONCEALED

SPACE ABOVE INSTALLED CEIILNG SUCH IDENTIFICATION SHALL:

1. BE LOCATED WITHIN 15'-0" OF THE END OF EACH WALL AND AT INTERVALS

NOT EXCEEDING 30'-0" MEASURED HORIZONTALLY ALONG THE WALL OR

PARTITION.

2. INCLUDE LETTERING NOT LESS THAN 3 INCHES IN HEIGHT WITH A MINIMUM

3/8 INCH STROKE IN A CONTRASTING COLOR INCORPORATING THE SUGGESTED

WORDING, "FIRE AND/OR SMOKE BARRIER - PROTECT ALL OPENINGS," OR

OTHER WORDING.

NOTE: IN SPACE WITH NO CEILING THE MARKINGS SHALL BE 12'-0" ABOVE

FINISHED FLOOR. MARKING SHALL BE LEVEL. LETTER COLOR SHALL BE RED.

MARKING SHALL BE ON BOTH SIDES OF THE WALL OR PARTITION.

PARTITION MARKING NOTES:

UFC 3-600-01 (8 AUGUST 2016, CHANGE 6, 6 MAY 2021) SECTION 7-2 AND

2021 IBC, SECTION 703.7

5801 Broadway Extension, Suite 500 Oklahoma City, OK 73118-7436

405.840.2931 | fsb-ae.com

Frankfurt-Short-Bruza Associates,P.C.

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

C

B

A

D

C

B

A

54321

2020-484-00

NDM

Re pa ir/ Co nv er t S qu ad O ps Ok lah om a C ity

, O K

NG

BJ

V/

OK

A

NG

PN: YZEU142025

C :\U sers\bkg\D o cum ents\M y R evit\048400_AR C

H

_BG

allagher5SB23.rvt

2/26/2025 11:30 :24 AM

12 SEPTEMBER 2024

PARTITION TYPES

A-002

MJT

BKG

JO

SCALE: NTS

PARTITION TAG LEGENDD3

SCALE: 1 1/2" = 1'-0"

WALL TYPESB2

6" 1'-6"1'0

1 1/2" = 1'-0"

2 ADDENDUM 01 02/17/2025

3 ADDENDUM 02 02/27/2025

File details come from the government source that posted it. Updated .