PDX 2026-513 (52) E2.01.pdf
PDF 484 KB Posted
- Solicitation number
- 145968
- Issued by
- Multnomah County, Oregon
About this file
This is an electrical floor plan drawing for the Portland International Airport Customs and Border Protection Improvements - Phase 2 project in Oregon. The drawing, designated as sheet E2.01, depicts the deplaning level sector 01 electrical layout at a scale of 1/8" = 1'-0" and was prepared by DBC Architecture Inc. The plan illustrates the installation of electrical infrastructure including multiple electrical panels (2D1D, 2D1B, 4D1B, and E4D1B), junction boxes, duplex receptacles, power poles, conduit systems, and related electrical components required to support customs and border protection operations in the deplaning area. The drawing includes detailed key notes specifying nine primary installation requirements, such as providing junction boxes with flexible metal conduit, mounting duplex receptacles to casework, installing power poles with receptacles, coordinating poke-thru locations with architectural drawings, and modifying existing Walker duct systems to extend power and data capabilities to new booth installations. The design incorporates existing infrastructure elements, including a 3-channel Walker duct system, which requires modification through saw cutting and extension to accommodate new electrical service routes. X-ray inspection of the existing floor slab is required prior to any saw cutting operations to ensure safety and prevent damage to hidden structural elements.
The drawing was prepared under design number 2025D042 with project number PDX 2026-513 and was dated September 2026. The document identifies three additive alternate packages associated with the project scope. The drawing was digitally signed by Benjamin E. Perry, a licensed professional engineer in Oregon (License #102, expiring 12-31-2026), and reviewed by M. Henning and E. Close. The plan includes coordination requirements with the Port of Portland for exact placement of receptacles, poke-thru locations, and conduit terminations prior to rough-in installation. Conductor sizing specifications mandate a minimum #10AWG conductor size for all circuits within the Walker duct system to comply with derating requirements, ensuring proper electrical capacity and safety compliance throughout the installation.
View the file
Other files
Show 40 more
Latest 50 of 88 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
D1660
JAND1655
CORR.
D14920
EQUIP
D1650
ELEV
D1658
BREAK
D1656
LOCKERS
D1657
LOCKERS
D1664
WOMENS
D1666
MENS
D1654
MECH
D1652
STAIRS
D1706
OFFICE
D1646
ESC
D1680
OFFICE
D1675
ISOLATION
D1679
EQUIPMENT
D1672
MENS
D1670
WOMENS
D1687
HOLD
D1686
HOLD
D1683
OFFICE
D1663
OFFICE
D1662
CORR
D1674
HEALTH
D1678
SUPERVISOR
D1676
TOILET
D1700
SECOND CHECK
D1702
INTERVIEW
D1704
INTERVIEW
D1605
OFFICE
D14573
OFFICE
D1671
CORR
D1600
IMMIGRATION
D1653
STAIRS
D1682
CORR
S
J
J
J
J
J
J
J
J
J
(E)
(E)
(E)
(E)
J
J
2D1B:19
2D1B:28
2D1B:30
2D1B:28
S
J
(E)
D50 D49 D48 D47 D46
DE
DD
DC
DB
DA
9/8/2026
C
AN
Y O
U S
EE
T
H E
AI
R
PL
AN
ES
T H
E
AD
JA
C
EN
T
SA
M
PL
ES
S H
O W
T H
R
EE
D
IF
FE
R
EN
T
LE
VE
LS
O
F
SH
AD
IN
G
SE
TT
IN
G
S
FO
R V
IE
W
IN
G
A N
D P
R
IN
TI
N
G D
R
AW
IN
G
C O
N
TE
N T
AR
E
O
PT
IM
IZ
ED
W
H
EN
AL
L
TH
R
EE
P
LA
N
ES
A
R E
VI
SI
BL
E.
T H
IS
G
U
ID
AN
C
E
IS
P R
O
VI
D
ED
F O
R R
EF
ER
EN
C
E O
N
LY
PRINTED:
lig ht da rk gr ay bl ac k
DESIGN NUMBER PROJECT NUMBER
2"
G R
AP
H
IC
S
C
AL
E
- F
O R
R
EF
ER
EN
C E
O N
LY
gr ay
1:38:12 PM ECLOSE g:\projects\339 - dbc architecture inc\3392601 - pdx cbp improvements\design\(2) drawings\current\pdx cbp improvements\sheets\e2.01 deplaning level - sector 01 - floor plan - electrical.dwg
DISC. SHT. NO.
DRAWING SCALE IS REDUCED 50% WHEN SHEET SIZE IS 11" x 17"
DESIGN BY
DRAWN BY
CHECKED BY
DATE
SHEET NO.
SUBMITTED BY
DRAWING NO.
TYPE:
1/
4" 1/
2" 1"
1/
4" 1/
2" 1"
DATE BY REVISION APPDATE BY REVISION APP ##
IF ELECTRONIC SIGNATURE IS BROKEN OR MISSING - THIS IS NOT A LEGAL DRAWING
KEY PLAN
SCALE: N.T.S.
N
THE AREA BELOW IS TO BE LEFT BLANK - FOR
USE BY CITY FOR PERMIT REVIEW STAMP ONLY-
Salem 503-584-1576 www.landisconsulting.com
PORTLAND INTERNATIONAL AIRPORT
CUSTOMS AND BORDER PROTECTION IMPROVEMENTS - PHASE 2
PDX 2026-5132025D042 103146
M. HENNING
E. CLOSE
B. PERRY
SEPTEMBER 2026
JAY OSTLUND
CD
PDERETSI
GER LA
NOI
SSEFOR
OREGON
86683
NIG
N
E R
EE
8 , 2
M A Y
PERRY
B
EN
JAMI N
E.
EXPIRES: 12-31-2026
Digitally Signed
DEPLANING LEVEL - SECTOR 01 - FLOOR PLAN - ELECTRICAL
E2.01
N
SCALE:
DEPLANING LEVEL - SECTOR 01 - FLOOR PLAN - ELECTRICAL
1/8" = 1'-0"1
SCALE: IN FEET
0' 4' 8' 16' 24'
(E) PANEL 2D1D
(E) PANEL 2D1B
(E) PANEL 4D1B
(E) PANEL E4D1B
(E) PANEL E2D1B
U2P1D-44DA:22
U2P1D-44DA:22
U2P1D-44DA:26
U2P1D-44DA:26
U2P1D-44DA:18
U2P1D-44DA:18
U2P1D-44DA:16
U2P1D-44DA:20
U2P1D-44DA:16
#KEY NOTE(S) :
1. PROVIDE JUNCTION BOX ON ACCESS AREA TO
POWER COMPARTMENT IN EXISTING 3-CHANNEL
WALKER DUCT. PROVIDE FLEXIBLE METAL
CONDUIT AND (3) #10AWG CONDUCTORS TO
DUPLEX RECEPTACLE SHOWN.
2. MOUNT DUPLEX RECEPTACLE TO CASEWORK.
COORDINATE EXACT LOCATION WITH PORT PRIOR
TO ROUGH-IN.
3. PROVIDE 2-CHANNEL POWER POLE WITH (2)
DUPLEX RECEPTACLES AS SHOWN.
4. PROVIDE POKE THRU INSTALLED ON ENPLANING
LEVEL. PROVIDE NEW CONDUIT AS SHOWN AND
CONNECT TO NEW POKE THRU. COORDINATE
EXACT LOCATION OF POKE THRU WITH
ARCHITECTURAL DRAWINGS.
5. PROVIDE 6" X 6" X 4" JUNCTION BOX MOUNTED TO
STRUCTURAL CEILING.
6. UTILIZE EXISTING CONDUIT FOR HOMERUN BACK
TO EXISTING PANEL U2P1D-44DA. PROVIDE NEW
(10) #10AWG AND (2) #10AWG GROUND
CONDUCTORS AND CONNECT COMPLETE.
7. PROVIDE 1.0" CONDUIT WITH PULL STRING FROM
EXISTING PANEL 2D1D FOR FUTURE PATRON
COUNTER. ROUTE CONDUIT ABOVE CEILING.
8. TERMINATE NEW CONDUIT ABOVE EXISTING
ACCESS HATCH IN CEILING OF EXISTING
RESTROOM. COORDINATE EXACT LOCATION OF
CONDUIT TERMINATION WITH PORT.
9. SAWCUT EXISTING CONDUIT AND PROVIDE NEW
3-CHANNEL WALKER DUCT AS SHOWN. MODIFY
END OF EXISTING WALKER DUCT TO ALLOW
CHANNEL CONTINUATION IN NEW WALKER DUCT.
INTENT IS TO EXTEND WALKER DUCT THE
REQUIRED DISTANCE TO FEED NEW BOOTH WITH
POWER AND DATA. X-RAY EXISTING FLOOR SLAB
PRIOR TO SAW CUTTING.
C O
N
TI
N U
ED
O
N S
H
EE
T E2
.0
C O
N
TI
N U
ED
O
N S
H
EE
T E2
.0
2D1B:12 2D1B:12
2D1B:12 2D1B:12
2D1B:12 2D1B:12
2D1B:32
2D1B:32
2D1B:32
2D1B:32
2D1B:32
2D1B:32
3 3
3 3
3 3
(E) 3-CHANNEL WALKERDUCT
(E) 3-CHANNEL
WALKERDUCT
(1) 0.75"C
(1) 0.75"C
(1) 0.75"C
NOTE:
1. PROVIDE #10AWG MINIMUM CONDUCTOR SIZE FOR
ALL CIRCUITS IN WALKER DUCT FOR DERATING.
U2P1D-44DA:30
8 8
7 7
U2P1D-44DA:20
ADDITIVE ALTERNATE #3
ADDITIVE ALTERNATE #2
ADDITIVE ALTERNATE #1
| 2026-09-08T14:32:23-0700 | |
| Digitally Signed | |
| Benjamin Earl Perry |
File details come from the government source that posted it. Updated .