This document is a Culvert Inspection Report for a concrete box culvert carrying the Natchez Trace Parkway over a stream at Mile Point 140.90 in Mississippi. The culvert is in fair structural condition, with moderate vertical cracking and spalling observed on the wingwalls. Recommended maintenance actions include removing debris from the upstream end, cleaning and sealing exposed rebar, and performing other minor repairs. The preliminary cost estimate for maintenance and rehabilitation is $15,000. The culvert has an adequate design load capacity to carry the required vehicle loads. This report provides detailed condition assessments, load ratings, and recommended actions to maintain the structural integrity of the culvert.
View the file
Other files
Show 40 more
Latest 50 of 53 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CULVERT INSPECTION REPORT
CULVERT AT MP 140.90
NATCHEZ TRACE PARKWAY OVER STREAM
NATCHEZ TRACE PARKWAY
LS
STRUCTURE NO. 5570-321P
INSPECTION TYPE: ROUTINE
INSPECTION DATE: 3/15/2022
WU
Report prepared by:
Federal Highway Administration Federal Lands Bridge Office Bridge Inspection and Management Program 21400 Ridgetop Circle Sterling, Virginia 20166 https://bridge.flhd.fhwa.dot.gov
MILE POINT: 140.90
KILOMETER POINT: 226.71
https://bridge.flhd.fhwa.dot.gov
STRUCTURE SUMMARY STRUCTURE NO. 5570-321P
CULVERT AT MP 140.90 INSPECTION DATE: 03/15/2022
CULVERT IDENTIFICATION AND DESCRIPTION
MAIN SPAN MATERIAL:
FOUNDATION:
STRUCT. TOTAL LENGTH:
MAX. SPAN LENGTH:
PROJ./PLAN REF. NO:
NPS ROAD CLASS:
STRUCTURE HISTORY:
2 - CONCRETE CONTINUOUS NO. OF BARRELS:
2 - SPREAD FTG ON BEARING BARREL LENGTH: ............. 68 FT (20.73 M)
21.0 FT (6.4 M) SKEW ANGLE: ................... 0 °
10.5 FT (3.2 M) YEAR BUILT:
3M2 YEAR RECONSTRUCTED:
1 - PRINCIPAL PARK ROAD
2010-ROADWAY RESURFACED.
LOCATION
NATCHEZ TRACE PARKWAY MILE POINT: .. 140.90 (KM PT 226.71)
STATE: ................................ 284 - MISSISSIPPI LOCATION: .... 5.9 MILES NORTH OF MS ROUTE 16
FACILITY CARRIED: .......... NATCHEZ TRACE PARKWAY
FEATURE INTERSECTED: STREAM
INSPECTION TEAM: T. Arnold, M. Delveaux
CONDITION ASSESSMENT:
Michael Delveaux (757) 716-9400
REPORT REVIEW:
Marcus Miller
REPORT APPROVAL: Date: 07/13/2022
Jorgomai Ceesay
STRUCTURE EVALUATION SUMMARY
This double barrel concrete box culvert is in fair structural condition due to moderate vertical cracking of the wingwalls. The cracking at the northeast wingwall is up to 1" wide, with delamination and spalling with exposed rebar along the crack. The cracking at the northwest wingwall is up to 1/2" wide. There are also several isolated areas of exposed rebar on the slab underside at west end of north barrel and at north face of the intermediate wall near east end.
Corrective action should be taken as outlined in this report to prevent the possible development of more serious or costly problems in the future.
RECOMMENDATIONS AND ESTIMATED COSTS STRUCTURE NO. 5570-321P
CULVERT AT MP 140.90 INSPECTION DATE : 03/15/2022
PRIORITY OF IMPROVEMENT226
A (Critical) - Structure is closed, in immediate damage of collapse, or presents a critical safety danger.
B (Major) - Structure is seriously deficient or presents a safety hazard, but can remain open at reduced loads or with frequent inspections.
C (Moderate) - Structure is deficient, functionally obsolete, or requires substantial repairs to prevent a serious deficiency or unsafe condition.
D (Minor) - Structure is generally in good condition. Preventive maintenance may be required.
E (Special) - Structure is under construction or reconstruction.
D
Item No.
Maintenance Recommendations
(GENERALLY NOT FLHP ELIGIBLE)
QTY. UNIT UNIT
COST
PRELIM.
COST
ESTIMATE
61.4
REMOVE DEBRIS FROM UPSTREAM END OF NORTH
BARREL 1 LS 5000 5000
PRELIM. MAINTENANCE TOTAL : 5000
Item No.
REHABILITATION/RECONSTRUCTION
(TYPICALLY NEEDED WITHIN 5 YEARS)
QTY. UNIT
UNIT
COST
PRELIM. COST ESTIMATES
REHAB RECONSTR
62.1,62.4 CLEAN AND SEAL EXPOSED REBAR IN
BARRELS WITH APPROVED PROTECTIVE
COATING.
1 LS 5000 5000
CONTRACT COSTS FOR MOBILIZATION,
TRAFFIC CONTROL, DESIGN, AND
CONSTRUCTION ENGINEERING.
1 LS 5000 5000
PRELIM. REHABILITATION/RECONSTRUCTION TOTAL : 10000
COST ESTIMATE SUMMARY
PRELIM. MAINTENANCE TOTAL :
PRELIM. REHABILITATION TOTAL :
PRELIM. RECONSTRUCTION TOTAL : .. 0
TOTAL ITEMIZED COSTS:
PRELIMINARY ESTIMATE TOTAL * :
(*Includes typical contract costs for mobilization, traffic control and design/construction engineering: but does not include detour bridges, work beyond the bridge limits, or work not listed above. Estimates are approximate and are for planning purposes only; they should not be used as a complete or final engineers estimate.)
Remarks : Cost estimates assume that recommended actions will be combined with similar work being performed on other structures.
FIELD INSPECTION REPORT STRUCTURE NO. 5570-321P
CULVERT AT MP 140 90 INSPECTION DATE: 03/14/2022
CONDITION RATING CODES FOR ITEMS 58 - 62, 222, 223
N NOT APPLICABLE 3 SERIOUS CONDITION - loss of section, deterioration, spalling, or scour have seriously affected primary structural components. Local failures are possible. Fatigue cracks in steel or 9 EXCELLENT CONDITION shear cracks in concrete may be present.
8 VERY GOOD CONDITION - no problems noted. 2 CRITICAL CONDITION - advanced deterioration of primary structural elements. Fatigue cracks in steel or shear cracks in concrete may be present or scour may have removed
7 GOOD CONDITION - some minor problems. substructure support. Unless closely monitored it may be necessary to close the structure until corrective action can be taken.
6 SATISFACTORY CONDITION - structural elements show some minor deterioration.
1 “IMM NENT” FAILURE CONDITION - major deterioration or section loss present in critical
5 FA R CONDITION - all primary structural elements are sound but may have minor structural components or obvious vertical or horizontal movement affecting structure stability.
section loss, cracking, spalling, or scour. Structure is closed to
4 POOR CONDITION - advanced section loss, deterioration, spalling, or scour. 0 FA LED CONDITION - out of service; beyond corrective action.
CONDITION RATING CODE EQUIVALENTS FOR SUB-ELEMENTS
G = GOOD (CODES 7 - 9) F = FAIR (CODES 5 - 6) P = POOR (CODES 0 - 4)
61. CHANNEL 6 222. APPROACHES 7
1. ALIGNMENT: F 1. APPROACH SLABS: N
2. EROSION AND/OR SCOUR: F 2. RELIEF JOINTS: N
3. CHANNEL PROTECTION: N 3. APPROACH GUARDRAIL: N
4. WATERWAY OBSTRUCTIONS: F 4. SURFACING: G
5. OTHER: N 5. EROSION: G
6. ADEQUACY OF OPENING: 1- SUFF 6. SETTLEMENT: G
7. NORMAL VELOCITY: 3 - LOW 7. SIGNS: G
8. AVERAGE CLEAR OPENING: 4 FT 8. ALIGNMENT: G
9. STREAM BED COMPOSITION: 9. OTHER: N
SILT SAND 223. RETAINING WALL N
62. CULVERT 6
1. BARREL(S): F
2. FOOTINGS: N
3. HEADWALLS: G
4. WINGWALLS: F
5. DEBRIS AND/OR SLIT: F
6. EROSION AND/OR SCOUR: G
7. SETTLEMENT AND/OR DEFLECTION: G
8. ADEQUACY OF COVER: G
9. PARAPETS AND/OR RAILINGS: N
10. ROADWAY SURFACE: G
11. RIDEABILITY: G
12. OTHER: VEGETATION F
1. WALL:
2. WEEP HOLES:
3. FOUNDATION:
4. EROSION AND/OR SCOUR:
5. SETTLEMENT OR DEFLECTION:
6. OTHER
36. TRAFFIC AND SAFETY FEATURES
A. BRIDGE RAILINGS: N
B. TRANSITIONS: N
C. APPROACH GUARDRAILS: N
D. APPROACH GUARDRAIL ENDS: N
TRAFFIC SAFETY RATING CODES
0 - Does not meet standards or a safety features is required and none is provided.
1 - Meets currently acceptable standards.
N - Not applicable or a safety features is not required.
(cont'd)FIELD INSPECTION REPORT - CULVERT STRUCTURE NO. 5570-321P
ITEM REFERENCE AND REMARKS
61.1
61.2
62.6
CULVERT NOT ALIGNED WITH CHANNEL CAUSING MINOR SCOUR AT SOUTH BARREL WITH APPROXIMATELY 3" (PREVIOUSLY 8") OF FLOOR EXPOSED AT WEST SIDE. MODERATE SLOUGHING ALONG SOUTH UPSTREAM CHANNEL BANK WITH SEVERAL
UNDERMINED TREES.
61.2 SEE BRIDGE FILE FOR SCOUR EVALUATION.
62.1 MINOR SPALLING WITH EXPOSED REBAR, WITH UP TO 10% SECTION LOSS, AT SEVERAL LOCATIONS ON TOP SLAB AND ON BARREL WALLS. MINOR CRACKING WITH EFFLORESCENCE AND LEAKAGE AT END CONSTRUCTION JOINTS IN TOP SLAB. MINOR
HORIZONTAL CRACK, WITH EFFLORESCENCE, IN WEST END OF NORTH WALL OF NORTH BARREL.
MINOR VOID IN SOUTH ENDWALL, 5' FROM UPSTREAM OPENING.
62.4 MODERATE VERTICAL CRACKING (UP TO 3/4" WIDE) OF NORTHEAST WINGWALL, WITH VEGETATION GROWTH WITHIN CRACK;
MINOR DELAMINATION AND SPALLING WITH EXPOSED REBAR. MINOR SPALL WITH EXPOSED REBAR ON TOP OF NORTHEAST
WINGWALL (NOT OBSERVED DUE TO VEGEATION GROWTH).
MODERATE VERTICAL CRACKING (UP TO 1/2" WIDE) OF NORTHWEST WINGWALL, WITH VEGETATION GROWTH WITHIN CRACK, AND ASSOCIATED SPALLING ALONG CRACK. MINOR MOWER SCRAPES ALONG NORTHWEST WINGWALL.
MINOR HORIZONTAL AND VERTICAL CRACKING OF SOUTHEAST WINGWALL; LEACHING AT SEVERAL LOCATIONS. MINOR
SPALLING AT SOUTHEAST WINGWALL END.
MINOR VERTICAL CRACKING OF SOUTHWEST WINGWALL.
62.5 MINOR SILT ACCUMULATION THROUGHOUT BARRELS. MINOR DEBRIS ACCUMULATION AT WEST SIDE OF SOUTH BARREL.
62.6 MINOR EROSION BEHIND AND AT ENDS OF NORTHWEST, NORTHEAST, AND SOUTHEAST WINGWALLS.
62.10
222.4
MINOR FULL LENGTH TRANSVERSE CRACKING OF PAVEMENT AT BOTH ENDS OF CULVERT.
MINOR LONGITUDINAL CRACKING OF PAVEMENT OVER CULVERT.
62.12 SMALL TREE GROWING FROM EAST SIDE OF INTERMEDIATE WALL.
61.4 SEVERAL DOWNED TREES ALONG UPSTREAM CHANNEL.
STRUCTURE LOAD RATING STRUCTURE NO. 5570-321P
TRUCK TYPE
INVENTORY RATING (NORMAL TRAFFIC) OPERATING RATING (MAXIMUM LOAD)
TONS METRIC TONS TONS METRIC TONS
H 78 71 130 118
HS 144 131 241 219
TYPE 3 127 115 212 192
TYPE 3S2 178 161 297 269
TYPE 3-3 211 191 351 318
DESIGN LOADING: 4 - H 20
X CAPACITY MEETS OR EXCEEDS DESIGN LOAD
CAPACITY IS LESS THAN DESIGN LOAD
ORIGINAL LOAD RATING CALCULATION APPLICABLE
ORIGINAL LOAD RATING CALCULATION REVISED
DATE OF LOAD RATING CALCULATION: 03/14/2016
LOAD RATING CONTROLLED BY: TOP SLAB - POSITIVE MOMENT
REMARKS: SEE STRUCTURE FILE FOR LOAD RATING CALCULATIONS.
STRUCTURE INVENTORY AND APPRAISAL STRUCTURE NO. 5570-321P
STRUCTURE IDENTIFICATION
(201) PARK: NATCHEZ TRACE PARKWAY
(202) STRUCTURE NAME:..............CULVERT AT MP 140.90
(203) STRUCTURE KIND:............... 2 - CULVERT
(204) STRUCTURE NUMBER:.........5570-321 P
4 - SOUTHEAST(205) NPS REGION:
(206) ROUTE CODE NUMBER:
(207) ROAD SECTION NO:
(208) NPS ROAD CLASS:............... 1 - PRINCIPAL PARK ROAD
(209) WITHIN NPS BNDRY?:.......... Yes
(210) OPERATING UNIT:.................KOSCIUSKO
(211) PROJECT NO(S):................... 3M2
(212) DRAWING NUMBERS:
(21) MAINTAINED BY:......................66 - NATIONAL PARK SERVICE
(22) OWNER:................................... 66 - NATIONAL PARK SERVICE
(1) STATE:
(2) STATE HWY. AGENCY DIST:
(3) COUNTY CODE:
(4) CITY / PLACE CODE:
(5) INVENTORY ROUTE:
(6) FEATURES INTERSECTED:
(7) FACILITY CARRIED:
(8) STATE STRUCTURE NO:
(9) LOCATION:
(10) INV. RTE. - MIN. VERT. CLR:
(11) MILE POINT:
(27) YEAR BUILT:
(106) YEAR RECONSTRUCTED:
(20) TOLL:
(37) HISTORIC DESIGNATION:
284 - MISSISSIPPI
28079 LEAKE
00000
1 6 1 00001 0
STREAM
NATCHEZ TRACE PARKWAY
5570321P0000000
5 9 MILES NORTH OF MS ROUTE 16
99.99 FT ( 99.99 M)
140.9 (KM PT: 226.7)
0 1
3 - ON FREE ROAD
5 - NOT ELIGIBLE
STRUCTURE DESCRIPTION, FOUNDATION, AND DECK TYPE
(43A) MAIN STR. MATERIAL:..........2 - CONCRETE CONTINUOUS (44A) APPR. STR. MATERIAL:............ 0 - Other
(43B) MAIN STR. TYPE:.................. 19 - CULVERT (INCLUDES FRAME (44B) APPR. STR. TYPE:.................... 00 - OTHER
CULVERTS)
(45) NO. OF MAIN SPANS:..............002 (46) NO OF APPROACH SPANS:
(48) MAX. SPAN LENGTH:..............10.5 FT ( 3.2 M)
(49) STRUCTURE LENGTH:........... 21.0 FT ( 6.4 M) (108) WEAR SURFACE/PROTECT SYSTEM:
(216A) ABUTMENT #1 FDN:........... 2 - SPREAD FTG ON BEARING MAT'L A) TYPE WEARING SURFACE:.. N - NA
(216B) ABUTMENT #2 FDN:........... 2 - SPREAD FTG ON BEARING MAT'L B) TYPE MEMBRANE:................. N - NA
(217A) PREDOM. PIER FDN:.......... 2 - SPREAD FTG ON BEARING MAT'L C) TYPE PROTECTION:.............. N - NA
(217B) SECOND. PIER FDN:.......... 2 - SPREAD FTG ON BEARING MAT'L (218) IS SALT USED?.......................... NO
(107) DECK TYPE:.......................... N - NOT APPLICABLE
LOAD RATING AND POSTING
(31) DESIGN LOAD:.........................4 - H 20 (41) LOAD RESTRICTION:.................. A - OPEN
(66) INVENTORY RATING:..............99.9 METRIC TONS) (70) BRIDGE POSTING:...................... 5 - EQUAL TO OR ABOVE LEGALTONS ( 90.6
LOADS
(64) OPERATING RATING:..............99.9 TONS ( 90.6 METRIC TONS)
INSPECTION DATES
(90) INSPECTION DATE: 11/07/2018 (91) FREQ. OF INSP: 48 MONTHS (92 / 93) CRITICAL FEATURE INSPECTION (CFI):
(219) ADD. STUDIES NEEDED: N - 0 - NONE (A) FRACTURE CRITICAL:.......... N
(220) SPECIAL STUDY TYPE: 0 - NONE INSP. EVERY MONTHS - LAST INSP:
(221) SPECIAL STUDY DATE: (B) UNDERWATER:..................... N
INSP. EVERY MONTHS - LAST INSP:
(C) SPECIAL INSPECTION:........ N
INSP. EVERY MONTHS - LAST INSP:
https://RATING:
https://RATING:
https://LENGTH:
STRUCTURE INVENTORY AND APPRAISAL STRUCTURE NO. 5570-321P
GEOMETRY, TRAFFIC, AND NAVIGATIONAL DATA
(16) LATITUDE:................................ 32° 47'04.40" (51) CURB TO CURB WIDTH:............ 0 0 FT ( 0 M)
(17) LONGITUDE:............................ 89°41 '20 50" (52) DECK WIDTH:.......................... 0 0 FT ( 0 M)
(19) DETOUR LENGTH:.................. 17 MI ( 27 KM) (32) APPR. ROADWAY WIDTH:...... 32.0 FT ( 9.8 M)
(28A) LANES ON STRUCT:.............02 (213) APPR. PAVEMENT WIDTH:... 22.0 FT ( 6.7 M)
(28B) LANES UNDER STRUCT:......00 LEFT SHOULDER:............... 5 0 FT ( 1.5 M)
(42A) SERVICE ON:.........................1 - HIGHWAY RIGHT SHOULDER:.......... 5 0 FT ( 1.5 M)
(42B) SERVICE UNDER:................. 5 - WATERWAY (33) BRIDGE MEDIAN:.................... 0 - NO MEDIAN
(29) AVG DAILY TRAFFIC:..............1641 (34) SKEW ANGLE:......................... 0 °
(30) YEAR OF ADT:......................... 2012 (35) STRUCTURE FLARED:............ 0 - NO FLARE
(114) FUTURE ADT:.........................1805 (47) TOTAL HORIZ. CLEARANCE:.. 32 FT ( 9.8 M)
(115) YEAR OF FUTURE ADT:........2032 (50) SIDEWALKS
(101) PARALLEL STRUCTURE:......N - NO PARALLEL STRUCTURE LEFT:.................................... 0 0 FT ( 0 M)
(38) NAVIGATION CONTROL:.........0 - NO NAVIGATION CONTROL ON RIGHT:.................................. 0 0 FT ( 0 M)
WATERWAY (BRIDGE PERMIT NOT
REQUIRED)
(39) VERTICAL CLEARANCE:.........0 FT ( 0 M) (214) BRIDGE RAIL TYPE
0 - N/A(40) HORIZ. CLEARANCE:..............0 FT ( 0 M) RAIL CONFIGURATION:
(111) ABUT OR PIER PROT:........... MATERIAL:........................... 0 - N/A
LATERAL UNDERCLEARANCE: DESIGN TYPE:..................... 0 - N/A
(55) RIGHT:...............................00 FT ( 0 M) (215) BRIDGE RAIL HEIGHT:.......... .00 FT ( 0 M)
(56) LEFT:................................ 0 FT ( 0 M) (53) MIN. VRT. CLR. OVER DECK: 99.99 FT ( 99.99 M)
(54) MIN. VRT. UNDRCLRANCE:... .00 FT ( 0 M)
CONDITION AND APPRAISAL DATA, PROPOSED IMPROVEMENTS, AND COST
(58) DECK:....................................... N (67) STRUCTURAL EVALUATION:
(59) SUPERSTRUCTURE:...............N (68) DECK GEOMETRY:......................N
(60) SUBSTRUCTURE:.......... N (69) UNDERCLEARANCES:................ N
(61) CHANNEL:................................6 (71) WATERWAY ADEQUACY:
(62) CULVERT:.................................6 (72) APPROACH ALIGNMENT:
(222) APPROACHES:...................... 7 (113) SCOUR CRITICAL:.................... 5 - SCOUR WITHIN LIMITS OF
FOOTING OR PILES
(223) RETAINING WALL:.................N (225) PURPOSE OF IMPROVEMENT: 2 - REHAB/RECONSTRUCTION
(36) TRAFFIC SAFETY FEAT: N N N N (226) PRIORITY OF IMPROVEMENT: D - MINOR
(75A) TYPE OF WORK:................... (227) MAINTENANCE COST:.............$ 5000
(75B) WORK DONE BY:.................. (228) REHAB / RECNSTR COST:..... $ 10000
(76) IMPROVEMENT LENGTH:....... FT ( 0 M) (229) CONSTRUCTION COST:.......... $ 0
ADDITIONAL INFORMATION
(230) STRUCTURE HISTORY:
2010-ROADWAY RESURFACED.
(231) ADDITIONAL CONSIDERATIONS:
(330) ADDITIONAL CONFIGURATION INFORMATION:
https://47'04.40
Inspector: Michael Delveaux Structure Number: 5570321P0000000
Inspection Date: 03/15/2022 Facility Carried: NATCHEZ TRACE PAR
Culvert Inspection Report
Pictures
PHOTO 3
Description LOOKING NORTHBOUND TOWARD TUPELO
PHOTO 4
Description EAST (DOWNSTREAM) SIDE; NOTE VEGETATION GROWTH IN FRONT OF CULVERT
OUTLET
Culvert Inspection Report
Pictures
PHOTO 5
Description GENERAL TOPSIDE VIEW LOOKING NORTH; TAKEN FROM PREVIOUS REPORT
PHOTO 6
Description CRACKS IN WEARING SURFACE, NORTHBOUND LANE NEAR SOUTH END SHOWN
Culvert Inspection Report
Pictures
PHOTO 7
Description GENERAL VIEW OF SOUTH ENDWALL LOOKING WEST
PHOTO 8
Description GENERAL VIEW LOOKING EAST THROUGH SOUTH BARREL; NOTE DEBRIS
ACCUMULATION
Culvert Inspection Report
Pictures
PHOTO 9
Description SCOUR EXPOSING BARREL FLOOR AT WEST END OF SOUTH BARREL
PHOTO 10
Description GENERAL VIEW OF INTERMEDIATE WALL LOOKING EAST; NORTH FACE SHOWN
Culvert Inspection Report
Pictures
PHOTO 11
Description VERTICAL CRACKING AND SPALLING OF NORTHWEST WINGWALL; CONCRETE IS SOUND
PHOTO 12
Description UP TO 1" WIDE CRACK AT NORTHEAST WINGWALL EXTENDING FULL HEIGHT
Culvert Inspection Report
Pictures
PHOTO 13
Description SPALL WITH EXPOSED REBAR IN BARREL CEILING AT WEST END OF SOUTH BARREL
PHOTO 14
Description VOID IN SOUTH ENDWALL, 5' FROM UPSTREAM OPENING
Culvert Inspection Report
Pictures
PHOTO 15
Description SPALL WITH EXPOSED REBAR IN CEILING OF NORTH BARREL NEAR WEST END
PHOTO 16
Description UPSTREAM CHANNEL; NOTE DOWNED TREES ACROSS CHANNEL
Culvert Inspection Report
Pictures
PHOTO 17
Description DOWNSTREAM CHANNEL