62-63 - EP4.0.pdf
PDF 270 KB Posted
- Solicitation number
- RFP260305
- Issued by
- Hart County, Kentucky
About this file
This document is an electrical panel schedule prepared by Kohrs Lonnemann Heil Engineers, PSC for the Commonwealth of Kentucky's Department for Facilities & Support Services, Division of Engineering, in support of a classroom center renovation project at Gateway Urban Campus, 438-440 Scott Street, Covington, Kentucky. The document provides comprehensive electrical panel schedules for the facility's power and lighting distribution, detailing multiple electrical panels (1A, 1B, 1C, 2A, 2C, 3A, 3B, BA, and DP1) with their respective circuit configurations, demand calculations, and load classifications. The project encompasses comprehensive electrical infrastructure planning for a multi-floor facility that includes cosmetology salons, massage clinical labs, classrooms, offices, and support spaces across basement and three above-grade floors, with the design prepared as of December 18, 2015.
The electrical design specifications indicate a three-phase, 208-volt system with total estimated demand amperage of 906 amps at the main distribution panel (DP1) and total connected load of 317.8 kilowatts across all panels. Circuit breaker requirements include HACR-rated breakers for all motor loads, locking-type breakers for life safety and night lighting circuits, and specialized breakers including GFI, shunt trip, and arc fault interrupter breakers where required. The facility design accommodates future additions, including dedicated circuits for hand dryers on multiple floors and future HVAC equipment. Load classifications include lighting, receptacles, miscellaneous equipment, and motor loads with appropriate demand factors applied. The document reflects multiple revisions through October 2014, addressing updates to styling stations and third-floor electrical infrastructure.
View the file
Other files
Show 40 more
Latest 50 of 80 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
APPROVED FOR PROGRAM CONCEPT ONLY
APPROVED FOR PROGRAM CONCEPT ONLY
DATE
DATE
ENGINEERING
DIVISION OF
AGENCY
AUTHORIZED AGENT
FOR INTENT ONLY
DIV. OF ENGR.
REVIEWED
ENGR. ACCT NO.
DRAWING NO.
DATE
A&E FILE NO.
CHECKED BY
SHEET DRAWN BY
RECORD DATE
DATEREVISIONS
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES & SUPPORT SERVICES
DIVISION OF ENGINEERING
FRANKFORT, KENTUCKY
WWW.KLHENGRS.COM
ENGINEERS, PSC
MECHANICAL/ELECTRICAL ENGINEERS
KOHRS LONNEMANN HEIL
LEXINGTON, KENTUCKY
COLUMBUS, OHIO
DAYTON, OHIO
NEW YORK, NEW YORK
1538 ALEXANDRIA PIKE, SUITE
11 FT. THOMAS, KENTUCKY
41075 800-354-9783 859-442-8050
859-442-8058 FAX
KLH PRO. NO.
11369.04
PROFESSIONAL SERVICES CLASSROOM CENTER
/1
/2
:1 :2
P
M
EP4.0
ELECTRIC PANEL SCHEDULES
470-C5N5-NC11-01
GATEWAY URBAN CAMPUS
438-440 Scott St., Covington, KY 41011
12/18/15
201114.02
DTJ
SNF
PANEL SCHEDULE LEGEND
* = PROVIDE GFI CIRCUIT BREAKER
** = PROVIDE SHUNT TRIP CIRCUIT BREAKER
*** = PROVIDE ARC FAULT CIRCUIT INTERRUPTER BREAKER
PANEL SCHEDULE GENERAL NOTES
A. PROVIDE HACR RATED BREAKERS ON ALL MOTOR LOADS.
B. PROVIDE LOCKING TYPE BREAKER FOR ALL LIFE SAFETY AND NIGHT LIGHTING
BRANCH CIRCUITS.
Total Estimated Demand Amps: 163.1 A
Total Estimated Demand: 58.7 kVA
Total Connected Load: 53.4 kVA
Panel Totals
Misc 23114 VA 100.00% 23114 VA
Lighting 21288 VA 125.00% 26610 VA
Spare 200 VA 100.00% 200 VA
Receptacle 8820 VA 100.00% 8820 VA INCLUDES LOAD FROM PANEL 1B
Load Classification Connected Load Demand Factor Estimated Demand Additional Notes:
Total Amps: 152 A 153 A 141 A
Total Load: 18.1 kVA 18.1 kVA 17.0 kVA
53 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 54
51 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 52
49 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 50
47 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 48
45 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 46
43 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 44
41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42
39 Misc 20 A 1 120 VA 720 VA 1 20 A Receptacle COSMETOLOGY SALON 101 40
37 Receptacle CORRIDOR 100B 20 A 1 360 VA 38
35 Receptacle RECEPTION 100A 20 A 1 540 VA 360 VA 1 20 A Receptacle RECEPTION 100A 36
33 Receptacle WAITING AREA 100 20 A 1 540 VA 720 VA 1 20 A Receptacle COSMETOLOGY SALON 101 34
31 Receptacle MANICURE/PEDICURE AREA 100D 20 A 1 720 VA 720 VA 1 20 A Receptacle Room 100C, 100D 32
29 Misc MANICURE/PEDICURE AREA 100D 20 A 1 360 VA 720 VA 1 20 A Receptacle MANICURE/PEDICURE AREA 100D 30
27 Misc COSMETOLOGY SALON 101 - HAIR... 20 A 1 1000... 360 VA 1 20 A Misc MANICURE/PEDICURE AREA 100D 28
25 Misc COSMETOLOGY SALON 101 - HAIR... 20 A 1 1000... 1000... 1 20 A Misc COSMETOLOGY SALON 101 - HAIR... 26
23 Misc COSMETOLOGY SALON 101 - HAIR... 20 A 1 1000... 1000... 1 20 A Misc COSMETOLOGY SALON 101 - HAIR... 24
21 Misc COSMETOLOGY SALON 101 - HAIR... 20 A 1 1000... 1000... 1 20 A Misc COSMETOLOGY SALON 101 - HAIR... 22
19 1000... 1 20 A Misc COSMETOLOGY SALON 101 - HAIR... 20
17 Receptacle COSMETOLOGY SALON 101 20 A 1 180 VA 18
15 16
13 14
11 12
9 10
7 2400... 720 VA 1 20 A Receptacle Room 104 8
Misc STORAGE 104 - DRYER 30 A 2
2400... 500 VA 1 20 A Misc STORAGE 104 - WASHER 6
3 * Misc CORRIDOR 100E - EWC 20 A 1 500 VA 540 VA 1 20 A Receptacle Room 100E, 100B 4
1 EF-1 Receptacle DISPENSARY 102 20 A 1 820 VA 360 VA 1 20 A Receptacle Room 105, 106 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes: POWER / LIGHTING
Supply From: DP1 Voltage: 208V 3PH Phase: 3 Wire: 4 Location: EXISTING MECHANICAL ROOM 004
Panel Name: 1A
Total Estimated Demand Amps: 70.7 A
Total Estimated Demand: 25.5 kVA
Total Connected Load: 24.5 kVA
Panel Totals
Receptacle 7200 VA 100.00% 7200 VA
Misc 13261 VA 100.00% 13261 VA
Lighting 4007 VA 125.00% 5009 VA
Load Classification Connected Load Demand Factor Estimated Demand Additional Notes:
Total Amps: 61 A 79 A 64 A
Total Load: 7.4 kVA 9.4 kVA 7.7 kVA
53 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 54
51 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 52
49 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 50
47 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 48
45 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 46
43 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 44
41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42
39 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 40
37 495 VA 0 VA 1 20 A Spare 38
Misc 2ND FLOOR ACU / HRB UNITS - BOH 20 A 2
495 VA 1300... 1 20 A Misc MEN 208 - FUTURE HAND DRYER 36
33 666 VA 1300... 1 20 A Misc WOMEN 206 - FUTURE HAND DRYER 34
Misc 2ND FLOOR ACU / HRB UNITS - FOH 20 A 2
666 VA 720 VA 1 20 A Receptacle OFFICE 2 205 32
29 30
27 28
25 26
23 24
21 Receptacle OFFICE 2 205 20 A 1 900 VA 22
19 Lighting CORRIDOR 200 - TRACK 20 A 1 600 VA 20
17 Lighting OFFICE 2 205 20 A 1 1398... 96 VA 1 20 A Lighting CORRIDOR 200 - TRACK 18
15 Lighting Room 200A, 200, 205, 206A, 206, 207,... 20 A 1 1150... 764 VA 1 20 A Lighting Room 201, 203 16
13 CLASSROOM 201 20 A 1 1040... 1080... 1 20 A OFFICE 1 203 14
11 Receptacle CLASSROOM 201 20 A 1 540 VA 360 VA 1 20 A Receptacle CLASSROOM 201 12
9 Receptacle Room 200, 200A 20 A 1 540 VA 720 VA 1 20 A Receptacle Room 200, 206A 10
7 Receptacle FACIAL / COUPLE MASSAGE 207 20 A 1 1260... 360 VA 1 20 A Receptacle Room 208, 206 8
5 2400... 1080... 1 20 A OFFICE 2 205 6
Misc FRESHMAN CLINIC 202 - DRYER 30 A 2
2400... 1000... 1 20 A Misc FRESHMAN CLINIC 202 - WASHER 4
1 EF-2 Receptacle DISPENSARY 204 20 A 1 640 VA 500 VA 1 20 A * Misc CORRIDOR 200A - EWC 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes: POWER / LIGHTING
Supply From: DP1 Voltage: 208V 3PH Phase: 3 Wire: 4 Location: CLOSET 209
Panel Name: 2A
Total Estimated Demand Amps: 64.5 A
Total Estimated Demand: 23.2 kVA
Total Connected Load: 22.4 kVA
Panel Totals
Receptacle 7200 VA 100.00% 7200 VA
Misc 11660 VA 100.00% 11660 VA
Lighting 3498 VA 125.00% 4372 VA
Load Classification Connected Load Demand Factor Estimated Demand Additional Notes:
Total Amps: 71 A 71 A 50 A
Total Load: 8.1 kVA 8.2 kVA 6.0 kVA
41 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 42
39 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 40
37 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 38
35 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 36
33 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 34
31 Spare 20 A 1 0.0 kVA 0.0 kVA 32
29 Spare 20 A 1 0.0 kVA 0.0 kVA 2 30 A Spare
27 Misc MASSAGE CLINICAL LAB 302 20 A 1 1.4 kVA 0.0 kVA 1 20 A Spare 28
25 Misc MASSAGE CLINICAL LAB 302 20 A 1 1.4 kVA 1.3 kVA 1 20 A Misc WOMEN 305 - FUTURE HAND DRYER 26
23 Receptacle Room 300A, 300, 303 20 A 1 0.4 kVA 1.3 kVA 1 20 A Misc MEN 306 - FUTURE HAND DRYER 24
21 Lighting Room 300A, 306, 305, 303, 304, 302C 20 A 1 0.7 kVA 1.7 kVA 1 20 A Lighting Room 301A, 301B, 301C, 301, 300,... 22
19 Receptacle MASSAGE CLINICAL LAB 302 20 A 1 1.4 kVA 1.3 kVA 1 20 A Lighting MASSAGE CLINICAL LAB 302 20
17 Receptacle MASSAGE CLINICAL LAB 302 20 A 1 1.4 kVA 1.4 kVA 1 20 A Receptacle MASSAGE CLINICAL LAB 302 18
15 Receptacle MASSAGE CLINICAL LAB 302 20 A 1 1.1 kVA 1.4 kVA 1 20 A Receptacle MASSAGE CLINICAL LAB 302 16
13 Receptacle CLIENT MASSAGE 301E 20 A 1 0.5 kVA 0.4 kVA 1 20 A Receptacle 14
11 Receptacle CLIENT MASSAGE 301C 20 A 1 0.5 kVA 0.7 kVA 1 20 A Receptacle CLIENT MASSAGE 301D 12
9 Receptacle CLIENT MASSAGE 301A 20 A 1 0.5 kVA 0.5 kVA 1 20 A Receptacle CLIENT MASSAGE 301B 10
7 Receptacle Room 305, 306 20 A 1 0.4 kVA 0.2 kVA 1 20 A Receptacle STORAGE 304 8
5 Receptacle LINENS 301F 20 A 1 0.2 kVA 0.2 kVA 1 20 A Receptacle CORRIDOR 301 6
3 Receptacle Room 302A, 302B 20 A 1 0.4 kVA 0.5 kVA 1 20 A Receptacle CORRIDOR 301 4
1 Receptacle OFFICE 302C 20 A 1 0.9 kVA 0.5 kVA 1 20 A * Misc CORRIDOR 300A - EWC 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes: POWER / LIGHTING
Supply From: DP1 Voltage: 208V 3PH Phase: 3 Wire: 4 Location: CLOSET 307
Panel Name: 3A
Total Estimated Demand Amps: 176.8 A
Total Estimated Demand: 63.7 kVA
Total Connected Load: 60.0 kVA
Panel Totals
Receptacle 180 VA 100.00% 180 VA
Motor 57908 VA 106.34% 61579 VA
Misc 1926 VA 100.00% 1926 VA
Load Classification Connected Load Demand Factor Estimated Demand Additional Notes:
Total Amps: 176 A 178 A 153 A
Total Load: 20.7 kVA 21.0 kVA 18.3 kVA
41 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 42
39 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 40
37 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 38
35 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 36
33 Misc TEMP Control 20 A 1 0.2 kVA 0.0 kVA 1 20 A Spare 34
31 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 32
29 Spare 20 A 1 0.0 kVA 30
27 0.4 kVA 28
Misc 3RD FLOOR HRB / ACU UNITS - BOH 20 A 2
0.4 kVA 26
23 Receptacle ROOFTOP EQUIPMENT 20 A 1 0.2 kVA 24
21 0.9 kVA 4.9 kVA 22
Misc 3RD FLOOR HRB / ACU UNITS - FOH 20 A 2
0.9 kVA 4.9 kVA 20
17 0.0 kVA 4.9 kVA
3 60 A DOAS-1
15 0.0 kVA 1.3 kVA 16
Spare 50 A 3
0.0 kVA 1.3 kVA 2 20 A CU-B-02 Rooftop Small Condenser
11 3.5 kVA 2.8 kVA 12
9 3.5 kVA 2.8 kVA 10
CU-01C East 50 A 3
3.5 kVA 2.8 kVA
3 40 A CU-01A West
5 2.9 kVA 4.1 kVA 6
3 2.9 kVA 4.1 kVA 4
CU-02A West 35 A 3
2.9 kVA 4.1 kVA
3 50 A CU-02B East
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes: MECHANICAL
Supply From: DP1 Voltage: 208V 3PH Phase: 3 Wire: 4 Location: CLOSET 307
Panel Name: 3B
Total Estimated Demand Amps: 42.0 A
Total Estimated Demand: 15.1 kVA
Total Connected Load: 14.6 kVA
Panel Totals
Spare 30 VA 100.00% 30 VA
Receptacle 2700 VA 100.00% 2700 VA
Motor 500 VA 125.00% 625 VA
Misc 9738 VA 100.00% 9738 VA
Lighting 1629 VA 125.00% 2036 VA
Load Classification Connected Load Demand Factor Estimated Demand Additional Notes:
Total Amps: 59 A 28 A 43 A
Total Load: 6.8 kVA 3.3 kVA 5.0 kVA
41 Receptacle EXISTING MECHANICAL ROOM 004 20 A 1 0.7 kVA 0.0 kVA 1 20 A Spare 42
39 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 40
37 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 38
35 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 36
33 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 34
31 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 32
29 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 30
27 Spare 20 A 1 0.0 kVA 0.2 kVA 1 20 A Receptacle EXISTING MECHANICAL ROOM 004 28
25 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 26
23 Spare 20 A 1 0.0 kVA 1.0 kVA 1 20 A Misc SP1 24
21 ELEVATOR SHUNT TRIP 20 A 1 0.0 kVA 0.5 kVA 1 20 A Misc CIRCULATION PUMP 22
19 GAS WATER HEATERS 20 A 1 0.2 kVA 0.3 kVA 1 20 A ELEVATOR PIT Recept & Light 20
17 Lighting Room 004, 002 20 A 1 0.5 kVA 0.9 kVA 1 20 A Lighting STUDENT LOUNGE 001 18
15 Receptacle STUDENT LOUNGE 001 20 A 1 0.4 kVA 0.5 kVA 1 20 A Receptacle STUDENT LOUNGE 001 16
13 * Misc STUDENT LOUNGE 001 - VM 20 A 1 1.8 kVA 1.0 kVA 1 20 A * Misc STUDENT LOUNGE 001 - VM 14
11 Misc STUDENT LOUNGE 001 - MW 20 A 1 1.3 kVA 0.5 kVA 12
9 Misc EXISTING ELEVATOR E 20 A 1 0.5 kVA 0.5 kVA 2 20 A Misc BASEMENT ACU UNITS
7 Misc SERVER - UPS 30 A 1 2.9 kVA 0.0 kVA 1 20 A Spare 8
5 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 6
3 ELEVATOR LIGHTING 20 A 1 0.5 kVA 0.2 kVA 1 20 A Receptacle EXISTING ELEVATOR MACHINE... 4
1 FACP 20 A 1 0.5 kVA 0.2 kVA 1 20 A Receptacle EXISTING STORAGE 002 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes: POWER / LIGHTING
Supply From: DP1 Voltage: 208V 3PH Phase: 3 Wire: 4 Location: EXISTING MECHANICAL ROOM 004
Panel Name: BA
Total Estimated Demand Amps: 906.0 A
Total Estimated Demand: 326.4 kVA
Total Connected Load: 317.8 kVA
Panel Totals
Spare 230 VA 100.00% 230 VA
Receptacle 26100 VA 69.16% 18050 VA
Motor 94392 VA 109.53% 103388 VA
Misc 166699 VA 100.00% 166699 VA
Lighting 30422 VA 125.00% 38027 VA SEE SINGLE LINE DIAGRAM FOR ADDITIONAL INFORMATION.
Load Classification Connected Load Demand Factor Estimated Demand Additional Notes:
Total Amps: 926 A 926 A 826 A
Total Load: 109.6 kVA 109.5 kVA 99.1 kVA
41 42
39 40
37 38
35 15.0... 36
33 19.8... 34
2C 200 A 3
18.7... 32
29 18.2... 30
27 17.7... 28
1C 200 A 3
17.7... 26
23 12.0... 24
21 12.0... 22
ELEVATOR 200 A 3
12.0... 20
17 18.3... 0.0 kVA 18
15 21.0... 0.0 kVA 16
3B 400 A 3
20.7... 0.0 kVA
3 60 A SPD
11 7.7 kVA 6.0 kVA 12
9 9.4 kVA 8.2 kVA 10
2A 200 A 3
7.4 kVA 8.1 kVA
3 200 A 3A
5 5.0 kVA 17.0... 6
3 3.3 kVA 18.1... 4
BA 200 A 3
6.8 kVA 18.1...
3 400 A 1A - 1B
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Supply From: Voltage: 208V 3PH Phase: 3 Wire: 4 Location: EXISTING MECHANICAL ROOM 004
Panel Name: DP1
Total Estimated Demand Amps: 100.2 A
Total Estimated Demand: 36.1 kVA
Total Connected Load: 30.8 kVA
Panel Totals
Spare 200 VA 100.00% 200 VA
Receptacle 180 VA 100.00% 180 VA
Misc 9094 VA 100.00% 9094 VA
Lighting 21288 VA 125.00% 26610 VA
Load Classification Connected Load Demand Factor Estimated Demand Additional Notes:
Total Amps: 77 A 98 A 83 A
Total Load: 9.2 kVA 11.6 kVA 9.9 kVA
41 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 42
39 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 40
37 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 38
35 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 36
33 Misc MEN 106 - FUTURE HAND DRYER 20 A 1 1.3 kVA 0.2 kVA 1 20 A Lighting MANICURE/PEDICURE AREA 100D 34
31 Misc WOMEN 105 - FUTURE HAND DRYER 20 A 1 1.3 kVA 1.5 kVA 32
29 0.9 kVA 1.5 kVA 2 20 A Misc ECH-1
ACU-1-02 P-1 Misc HVAC 103 15 A 2
0.9 kVA 0.9 kVA 28
25 Lighting FOH STAIRWELLS 20 A 1 0.3 kVA 0.9 kVA 2 15 A ACU-1-01 P-2 Misc HVAC 103
23 Lighting Room 100E, 103, 102, 104, 106, 105, 107 20 A 1 0.9 kVA 0.6 kVA 1 20 A EXTERIOR LIGHTING 24
21 Lighting WAITING AREA 100 20 A 1 0.9 kVA 0.3 kVA 1 20 A Lighting BOH STAIRWELL 22
19 Spare 20 A 1 0.0 kVA 0.9 kVA 1 20 A Lighting CORRIDOR 100B 20
17 Spare 20 A 1 0.0 kVA 1.4 kVA 1 20 A Lighting MANICURE/PEDICURE AREA 100D 18
15 Lighting WAITING AREA 100 20 A 1 0.6 kVA 1.4 kVA 1 20 A Lighting MANICURE/PEDICURE AREA 100D 16
13 Spare 20 A 1 0.0 kVA 0.4 kVA 1 20 A Lighting RECEPTION 100A 14
11 Lighting COSMETOLOGY SALON 101 20 A 1 1.5 kVA 0.9 kVA 1 20 A Lighting CORRIDOR 100B 12
9 Lighting COSMETOLOGY SALON 101 20 A 1 1.1 kVA 1.1 kVA 1 20 A Lighting COSMETOLOGY SALON 101 10
7 Lighting COSMETOLOGY SALON 101 20 A 1 1.1 kVA 1.1 kVA 1 20 A Lighting COSMETOLOGY SALON 101 8
5 Lighting 20 A 1 1.1 kVA 1.1 kVA 1 20 A Lighting COSMETOLOGY SALON 101 6
3 Lighting COSMETOLOGY SALON 101 20 A 1 1.5 kVA 1.5 kVA 1 20 A Lighting COSMETOLOGY SALON 101 4
1 LCP 20 A 1 0.2 kVA 1.5 kVA 1 20 A Lighting COSMETOLOGY SALON 101 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes: POWER / LIGHTING
Supply From: 1A Voltage: 208V 3PH Phase: 3 Wire: 4 Location: EXISTING MECHANICAL ROOM 004
Panel Name: 1B
Total Estimated Demand Amps: 148.5 A
Total Estimated Demand: 53.5 kVA
Total Connected Load: 53.5 kVA
Panel Totals
Misc 53500 VA 100.00% 53500 VA
Load Classification Connected Load Demand Factor Estimated Demand Additional Notes:
Total Amps: 147 A 147 A 152 A
Total Load: 17.7 kVA 17.7 kVA 18.2 kVA
41 Spare 0 A 1 0 VA 0 VA 1 0 A Spare 42
39 Misc 1ST FL STYLING STATION 20 A 1 800 VA 800 VA 1 20 A Misc 1ST FL STYLING STATION 40
37 Misc 1ST FL STYLING STATION 20 A 1 800 VA 800 VA 1 20 A Misc 1ST FL STYLING STATION 38
35 Misc 1ST FL STYLING STATION 20 A 1 1875... 1875... 1 20 A Misc 1ST FL STYLING STATION 36
33 Misc 1ST FL STYLING STATION 20 A 1 1875... 1875... 1 20 A Misc 1ST FL STYLING STATION 34
31 Misc 1ST FL STYLING STATION 20 A 1 800 VA 800 VA 1 20 A Misc 1ST FL STYLING STATION 32
29 Misc 1ST FL STYLING STATION 20 A 1 1875... 1875... 1 20 A Misc 1ST FL STYLING STATION 30
27 Misc 1ST FL STYLING STATION 20 A 1 800 VA 800 VA 1 20 A Misc 1ST FL STYLING STATION 28
25 Misc 1ST FL STYLING STATION 20 A 1 1875... 1875... 1 20 A Misc 1ST FL STYLING STATION 26
23 Misc 1ST FL STYLING STATION 20 A 1 800 VA 800 VA 1 20 A Misc 1ST FL STYLING STATION 24
21 Misc 1ST FL STYLING STATION 20 A 1 1875... 1875... 1 20 A Misc 1ST FL STYLING STATION 22
19 Misc 1ST FL STYLING STATION 20 A 1 800 VA 800 VA 1 20 A Misc 1ST FL STYLING STATION 20
17 Misc 1ST FL STYLING STATION 20 A 1 1875... 1875... 1 20 A Misc 1ST FL STYLING STATION 18
15 Misc 1ST FL STYLING STATION 20 A 1 800 VA 800 VA 1 20 A Misc 1ST FL STYLING STATION 16
13 Misc 1ST FL STYLING STATION 20 A 1 1875... 1875... 1 20 A Misc 1ST FL STYLING STATION 14
11 Misc 1ST FL STYLING STATION 20 A 1 800 VA 800 VA 1 20 A Misc 1ST FL STYLING STATION 12
9 Misc 1ST FL STYLING STATION 20 A 1 1875... 1875... 1 20 A Misc 1ST FL STYLING STATION 10
7 Misc 1ST FL STYLING STATION 20 A 1 800 VA 800 VA 1 20 A Misc 1ST FL STYLING STATION 8
5 Misc 1ST FL STYLING STATION 20 A 1 1875... 1875... 1 20 A Misc 1ST FL STYLING STATION 6
3 Misc 1ST FL STYLING STATION 20 A 1 800 VA 800 VA 1 20 A Misc 1ST FL STYLING STATION 4
1 Misc 1ST FL STYLING STATION 20 A 1 1875... 1875... 1 20 A Misc 1ST FL STYLING STATION 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Supply From: DP1 Voltage: 208V 3PH Phase: 3 Wire: 4 Location: DISPENSARY 102
Panel Name: 1C
Total Estimated Demand Amps: 148.5 A
Total Estimated Demand: 53.5 kVA
Total Connected Load: 53.5 kVA
Panel Totals
Misc 53500 VA 100.00% 53500 VA
Load Classification Connected Load Demand Factor Estimated Demand Additional Notes:
Total Amps: 161 A 170 A 125 A
Total Load: 18.7 kVA 19.8 kVA 15.0 kVA
41 Spare 0 A 1 0.0 kVA 0.0 kVA 1 0 A Spare 42
39 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 40
37 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 38
35 Misc 2ND FL STYLING STATION 20 A 1 0.8 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 36
33 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 1.9 kVA 1 20 A Misc 2ND FL STYLING STATION 34
31 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 32
29 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 30
27 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 28
25 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 26
23 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 24
21 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 22
19 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 20
17 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 18
15 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 16
13 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 14
11 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 12
9 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 10
7 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 8
5 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 6
3 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 4
1 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Supply From: DP1 Voltage: 208V 3PH Phase: 3 Wire: 4 Location: FRESHMAN CLINIC 202
Panel Name: 2C
2 PR-014 - Updated Electric Panels
8/7/2014
3 PR-016 - Styling Stations
8/8/2014
5 PR-22 - Third Floor Electric
10/14/2014
File details come from the government source that posted it. Updated .