This document is an electrical panel schedule prepared by Kohrs Lonnemann Heil Engineers, PSC for the Commonwealth of Kentucky's Department for Facilities & Support Services, Division of Engineering, in support of a classroom center renovation project at Gateway Urban Campus, 438-440 Scott Street, Covington, Kentucky. The document provides comprehensive electrical panel schedules for the facility's power and lighting distribution, detailing multiple electrical panels (1A, 1B, 1C, 2A, 2C, 3A, 3B, BA, and DP1) with their respective circuit configurations, demand calculations, and load classifications. The project encompasses comprehensive electrical infrastructure planning for a multi-floor facility that includes cosmetology salons, massage clinical labs, classrooms, offices, and support spaces across basement and three above-grade floors, with the design prepared as of December 18, 2015.

The electrical design specifications indicate a three-phase, 208-volt system with total estimated demand amperage of 906 amps at the main distribution panel (DP1) and total connected load of 317.8 kilowatts across all panels. Circuit breaker requirements include HACR-rated breakers for all motor loads, locking-type breakers for life safety and night lighting circuits, and specialized breakers including GFI, shunt trip, and arc fault interrupter breakers where required. The facility design accommodates future additions, including dedicated circuits for hand dryers on multiple floors and future HVAC equipment. Load classifications include lighting, receptacles, miscellaneous equipment, and motor loads with appropriate demand factors applied. The document reflects multiple revisions through October 2014, addressing updates to styling stations and third-floor electrical infrastructure.

View the file

Other files

File Type Posted
66-67 - CT0.0.pdf PDF
51-49 - HV1.3.pdf PDF
8-13 - A1-1 - FIRST FLOOR DEMOLITION AND NEW WORK PLANS.pdf PDF
34-35 - PD1.1.pdf PDF
30-30 - A8-2 - Basement - FINISHES.pdf PDF
29-29 - A8-1 - ROOM FINISH PLANS (N-I-C- FURNITURE LAYOUT).pdf PDF
12-11 - S4-2 - FRAMING DETAILS.pdf PDF
15-8 - S2-5 - ROOF FRAMING PLAN.pdf PDF
73-19 - A3-0 - BUILDING ELEVATIONS.pdf PDF
49-51 - HV2.0.pdf PDF
72-72 - CT5.2.pdf PDF
67-69 - CT1.2.pdf PDF
3-6 - S2-3 - SECOND FLOOR FRAMING PLAN.pdf PDF
23-24 - A5-2 - MISCELLANEOUS DETAILS.pdf PDF
43-46 - HV1.0.pdf PDF
17-3 - S1-1 - GENERAL NOTES.pdf PDF
13-18 - A2-1 - 2ND 3RD FLR REFLECTED CLG PLANS.pdf PDF
28-31 - A8-3 - 1st FLOOR - FINISHES.pdf PDF
21-23 - A5-1 - MISCELLANEOUS STAIR DETAILS.pdf PDF
70-71 - CT5.1.pdf PDF
36-37 - PL1.1.pdf PDF
42-44 - FP1.1.pdf PDF
31-32 - A8-4 - 2nd Floor - FINISHES.pdf PDF
32-33 - A8-5 - 3rd Floor - FINISHES.pdf PDF
50-52 - HV2.1.pdf PDF
38-40 - PL1.4.pdf PDF
35-34 - PD1.0.pdf PDF
69-70 - CT4.1.pdf PDF
39-39 - PL1.3.pdf PDF
11-12 - A1-0 - BASEMENT DEMOLITION AND NEW WORK PLANS.pdf PDF
68-68 - CT1.0.pdf PDF
25-26 - A6-1 - ENLARGED PLANS AND INTERIOR ELEVATIONS.pdf PDF
63-64 - EL1.0.pdf PDF
19-10 - S4-1 - FRAMING DETAILS.pdf PDF
65-66 - EL2.0.pdf PDF
2-2 - A0-1 - CODE INFO AND WALL TYPES.pdf PDF
9-14 - A1-2 - SECOND FLOOR DEMOLITION AND NEW WORK PLANS.pdf PDF
76-Elevator Inspection 2026-03-25-12-13-48.pdf PDF
58-59 - EP1.3.pdf PDF
46-47 - HV1.1.pdf PDF
57-58 - EP1.2.pdf PDF
61-62 - EP3.0.pdf PDF
80-438 Scott Full Inspection Report (PDF).pdf PDF
7-5 - S2-2 - FIRST FLOOR FRAMING PLAN.pdf PDF
53-54 - HV3.1.pdf PDF
4-9 - S3-1 - TYPICAL DETAILS.pdf PDF
1-4 - S2-1 - FOUNDATION PLAN.pdf PDF
24-25 - A6-0 - ENLARGED PLANS AND INTERIOR ELEVATIONS.pdf PDF
48-50 - HV1.4.pdf PDF
20-21 - A4-1 - BUILDING SECTIONS.pdf PDF
Show 40 more

Latest 50 of 80 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

APPROVED FOR PROGRAM CONCEPT ONLY

APPROVED FOR PROGRAM CONCEPT ONLY

DATE

DATE

ENGINEERING

DIVISION OF

AGENCY

AUTHORIZED AGENT

FOR INTENT ONLY

DIV. OF ENGR.

REVIEWED

ENGR. ACCT NO.

DRAWING NO.

DATE

A&E FILE NO.

CHECKED BY

SHEET DRAWN BY

RECORD DATE

DATEREVISIONS

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES & SUPPORT SERVICES

DIVISION OF ENGINEERING

FRANKFORT, KENTUCKY

WWW.KLHENGRS.COM

ENGINEERS, PSC

MECHANICAL/ELECTRICAL ENGINEERS

KOHRS LONNEMANN HEIL

LEXINGTON, KENTUCKY

COLUMBUS, OHIO

DAYTON, OHIO

NEW YORK, NEW YORK

1538 ALEXANDRIA PIKE, SUITE

11 FT. THOMAS, KENTUCKY

41075 800-354-9783 859-442-8050

859-442-8058 FAX

KLH PRO. NO.

11369.04

PROFESSIONAL SERVICES CLASSROOM CENTER

/1

/2

:1 :2

P

M

EP4.0

ELECTRIC PANEL SCHEDULES

470-C5N5-NC11-01

GATEWAY URBAN CAMPUS

438-440 Scott St., Covington, KY 41011

12/18/15

201114.02

DTJ

SNF

PANEL SCHEDULE LEGEND

* = PROVIDE GFI CIRCUIT BREAKER

** = PROVIDE SHUNT TRIP CIRCUIT BREAKER

*** = PROVIDE ARC FAULT CIRCUIT INTERRUPTER BREAKER

PANEL SCHEDULE GENERAL NOTES

A. PROVIDE HACR RATED BREAKERS ON ALL MOTOR LOADS.

B. PROVIDE LOCKING TYPE BREAKER FOR ALL LIFE SAFETY AND NIGHT LIGHTING

BRANCH CIRCUITS.

Total Estimated Demand Amps: 163.1 A

Total Estimated Demand: 58.7 kVA

Total Connected Load: 53.4 kVA

Panel Totals

Misc 23114 VA 100.00% 23114 VA

Lighting 21288 VA 125.00% 26610 VA

Spare 200 VA 100.00% 200 VA

Receptacle 8820 VA 100.00% 8820 VA INCLUDES LOAD FROM PANEL 1B

Load Classification Connected Load Demand Factor Estimated Demand Additional Notes:

Total Amps: 152 A 153 A 141 A

Total Load: 18.1 kVA 18.1 kVA 17.0 kVA

53 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 54

51 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 52

49 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 50

47 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 48

45 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 46

43 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 44

41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42

39 Misc 20 A 1 120 VA 720 VA 1 20 A Receptacle COSMETOLOGY SALON 101 40

37 Receptacle CORRIDOR 100B 20 A 1 360 VA 38

35 Receptacle RECEPTION 100A 20 A 1 540 VA 360 VA 1 20 A Receptacle RECEPTION 100A 36

33 Receptacle WAITING AREA 100 20 A 1 540 VA 720 VA 1 20 A Receptacle COSMETOLOGY SALON 101 34

31 Receptacle MANICURE/PEDICURE AREA 100D 20 A 1 720 VA 720 VA 1 20 A Receptacle Room 100C, 100D 32

29 Misc MANICURE/PEDICURE AREA 100D 20 A 1 360 VA 720 VA 1 20 A Receptacle MANICURE/PEDICURE AREA 100D 30

27 Misc COSMETOLOGY SALON 101 - HAIR... 20 A 1 1000... 360 VA 1 20 A Misc MANICURE/PEDICURE AREA 100D 28

25 Misc COSMETOLOGY SALON 101 - HAIR... 20 A 1 1000... 1000... 1 20 A Misc COSMETOLOGY SALON 101 - HAIR... 26

23 Misc COSMETOLOGY SALON 101 - HAIR... 20 A 1 1000... 1000... 1 20 A Misc COSMETOLOGY SALON 101 - HAIR... 24

21 Misc COSMETOLOGY SALON 101 - HAIR... 20 A 1 1000... 1000... 1 20 A Misc COSMETOLOGY SALON 101 - HAIR... 22

19 1000... 1 20 A Misc COSMETOLOGY SALON 101 - HAIR... 20

17 Receptacle COSMETOLOGY SALON 101 20 A 1 180 VA 18

15 16

13 14

11 12

9 10

7 2400... 720 VA 1 20 A Receptacle Room 104 8

Misc STORAGE 104 - DRYER 30 A 2

2400... 500 VA 1 20 A Misc STORAGE 104 - WASHER 6

3 * Misc CORRIDOR 100E - EWC 20 A 1 500 VA 540 VA 1 20 A Receptacle Room 100E, 100B 4

1 EF-1 Receptacle DISPENSARY 102 20 A 1 820 VA 360 VA 1 20 A Receptacle Room 105, 106 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes: POWER / LIGHTING

Supply From: DP1 Voltage: 208V 3PH Phase: 3 Wire: 4 Location: EXISTING MECHANICAL ROOM 004

Panel Name: 1A

Total Estimated Demand Amps: 70.7 A

Total Estimated Demand: 25.5 kVA

Total Connected Load: 24.5 kVA

Panel Totals

Receptacle 7200 VA 100.00% 7200 VA

Misc 13261 VA 100.00% 13261 VA

Lighting 4007 VA 125.00% 5009 VA

Load Classification Connected Load Demand Factor Estimated Demand Additional Notes:

Total Amps: 61 A 79 A 64 A

Total Load: 7.4 kVA 9.4 kVA 7.7 kVA

53 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 54

51 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 52

49 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 50

47 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 48

45 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 46

43 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 44

41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42

39 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 40

37 495 VA 0 VA 1 20 A Spare 38

Misc 2ND FLOOR ACU / HRB UNITS - BOH 20 A 2

495 VA 1300... 1 20 A Misc MEN 208 - FUTURE HAND DRYER 36

33 666 VA 1300... 1 20 A Misc WOMEN 206 - FUTURE HAND DRYER 34

Misc 2ND FLOOR ACU / HRB UNITS - FOH 20 A 2

666 VA 720 VA 1 20 A Receptacle OFFICE 2 205 32

29 30

27 28

25 26

23 24

21 Receptacle OFFICE 2 205 20 A 1 900 VA 22

19 Lighting CORRIDOR 200 - TRACK 20 A 1 600 VA 20

17 Lighting OFFICE 2 205 20 A 1 1398... 96 VA 1 20 A Lighting CORRIDOR 200 - TRACK 18

15 Lighting Room 200A, 200, 205, 206A, 206, 207,... 20 A 1 1150... 764 VA 1 20 A Lighting Room 201, 203 16

13 CLASSROOM 201 20 A 1 1040... 1080... 1 20 A OFFICE 1 203 14

11 Receptacle CLASSROOM 201 20 A 1 540 VA 360 VA 1 20 A Receptacle CLASSROOM 201 12

9 Receptacle Room 200, 200A 20 A 1 540 VA 720 VA 1 20 A Receptacle Room 200, 206A 10

7 Receptacle FACIAL / COUPLE MASSAGE 207 20 A 1 1260... 360 VA 1 20 A Receptacle Room 208, 206 8

5 2400... 1080... 1 20 A OFFICE 2 205 6

Misc FRESHMAN CLINIC 202 - DRYER 30 A 2

2400... 1000... 1 20 A Misc FRESHMAN CLINIC 202 - WASHER 4

1 EF-2 Receptacle DISPENSARY 204 20 A 1 640 VA 500 VA 1 20 A * Misc CORRIDOR 200A - EWC 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes: POWER / LIGHTING

Supply From: DP1 Voltage: 208V 3PH Phase: 3 Wire: 4 Location: CLOSET 209

Panel Name: 2A

Total Estimated Demand Amps: 64.5 A

Total Estimated Demand: 23.2 kVA

Total Connected Load: 22.4 kVA

Panel Totals

Receptacle 7200 VA 100.00% 7200 VA

Misc 11660 VA 100.00% 11660 VA

Lighting 3498 VA 125.00% 4372 VA

Load Classification Connected Load Demand Factor Estimated Demand Additional Notes:

Total Amps: 71 A 71 A 50 A

Total Load: 8.1 kVA 8.2 kVA 6.0 kVA

41 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 42

39 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 40

37 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 38

35 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 36

33 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 34

31 Spare 20 A 1 0.0 kVA 0.0 kVA 32

29 Spare 20 A 1 0.0 kVA 0.0 kVA 2 30 A Spare

27 Misc MASSAGE CLINICAL LAB 302 20 A 1 1.4 kVA 0.0 kVA 1 20 A Spare 28

25 Misc MASSAGE CLINICAL LAB 302 20 A 1 1.4 kVA 1.3 kVA 1 20 A Misc WOMEN 305 - FUTURE HAND DRYER 26

23 Receptacle Room 300A, 300, 303 20 A 1 0.4 kVA 1.3 kVA 1 20 A Misc MEN 306 - FUTURE HAND DRYER 24

21 Lighting Room 300A, 306, 305, 303, 304, 302C 20 A 1 0.7 kVA 1.7 kVA 1 20 A Lighting Room 301A, 301B, 301C, 301, 300,... 22

19 Receptacle MASSAGE CLINICAL LAB 302 20 A 1 1.4 kVA 1.3 kVA 1 20 A Lighting MASSAGE CLINICAL LAB 302 20

17 Receptacle MASSAGE CLINICAL LAB 302 20 A 1 1.4 kVA 1.4 kVA 1 20 A Receptacle MASSAGE CLINICAL LAB 302 18

15 Receptacle MASSAGE CLINICAL LAB 302 20 A 1 1.1 kVA 1.4 kVA 1 20 A Receptacle MASSAGE CLINICAL LAB 302 16

13 Receptacle CLIENT MASSAGE 301E 20 A 1 0.5 kVA 0.4 kVA 1 20 A Receptacle 14

11 Receptacle CLIENT MASSAGE 301C 20 A 1 0.5 kVA 0.7 kVA 1 20 A Receptacle CLIENT MASSAGE 301D 12

9 Receptacle CLIENT MASSAGE 301A 20 A 1 0.5 kVA 0.5 kVA 1 20 A Receptacle CLIENT MASSAGE 301B 10

7 Receptacle Room 305, 306 20 A 1 0.4 kVA 0.2 kVA 1 20 A Receptacle STORAGE 304 8

5 Receptacle LINENS 301F 20 A 1 0.2 kVA 0.2 kVA 1 20 A Receptacle CORRIDOR 301 6

3 Receptacle Room 302A, 302B 20 A 1 0.4 kVA 0.5 kVA 1 20 A Receptacle CORRIDOR 301 4

1 Receptacle OFFICE 302C 20 A 1 0.9 kVA 0.5 kVA 1 20 A * Misc CORRIDOR 300A - EWC 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes: POWER / LIGHTING

Supply From: DP1 Voltage: 208V 3PH Phase: 3 Wire: 4 Location: CLOSET 307

Panel Name: 3A

Total Estimated Demand Amps: 176.8 A

Total Estimated Demand: 63.7 kVA

Total Connected Load: 60.0 kVA

Panel Totals

Receptacle 180 VA 100.00% 180 VA

Motor 57908 VA 106.34% 61579 VA

Misc 1926 VA 100.00% 1926 VA

Load Classification Connected Load Demand Factor Estimated Demand Additional Notes:

Total Amps: 176 A 178 A 153 A

Total Load: 20.7 kVA 21.0 kVA 18.3 kVA

41 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 42

39 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 40

37 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 38

35 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 36

33 Misc TEMP Control 20 A 1 0.2 kVA 0.0 kVA 1 20 A Spare 34

31 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 32

29 Spare 20 A 1 0.0 kVA 30

27 0.4 kVA 28

Misc 3RD FLOOR HRB / ACU UNITS - BOH 20 A 2

0.4 kVA 26

23 Receptacle ROOFTOP EQUIPMENT 20 A 1 0.2 kVA 24

21 0.9 kVA 4.9 kVA 22

Misc 3RD FLOOR HRB / ACU UNITS - FOH 20 A 2

0.9 kVA 4.9 kVA 20

17 0.0 kVA 4.9 kVA

3 60 A DOAS-1

15 0.0 kVA 1.3 kVA 16

Spare 50 A 3

0.0 kVA 1.3 kVA 2 20 A CU-B-02 Rooftop Small Condenser

11 3.5 kVA 2.8 kVA 12

9 3.5 kVA 2.8 kVA 10

CU-01C East 50 A 3

3.5 kVA 2.8 kVA

3 40 A CU-01A West

5 2.9 kVA 4.1 kVA 6

3 2.9 kVA 4.1 kVA 4

CU-02A West 35 A 3

2.9 kVA 4.1 kVA

3 50 A CU-02B East

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes: MECHANICAL

Supply From: DP1 Voltage: 208V 3PH Phase: 3 Wire: 4 Location: CLOSET 307

Panel Name: 3B

Total Estimated Demand Amps: 42.0 A

Total Estimated Demand: 15.1 kVA

Total Connected Load: 14.6 kVA

Panel Totals

Spare 30 VA 100.00% 30 VA

Receptacle 2700 VA 100.00% 2700 VA

Motor 500 VA 125.00% 625 VA

Misc 9738 VA 100.00% 9738 VA

Lighting 1629 VA 125.00% 2036 VA

Load Classification Connected Load Demand Factor Estimated Demand Additional Notes:

Total Amps: 59 A 28 A 43 A

Total Load: 6.8 kVA 3.3 kVA 5.0 kVA

41 Receptacle EXISTING MECHANICAL ROOM 004 20 A 1 0.7 kVA 0.0 kVA 1 20 A Spare 42

39 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 40

37 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 38

35 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 36

33 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 34

31 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 32

29 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 30

27 Spare 20 A 1 0.0 kVA 0.2 kVA 1 20 A Receptacle EXISTING MECHANICAL ROOM 004 28

25 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 26

23 Spare 20 A 1 0.0 kVA 1.0 kVA 1 20 A Misc SP1 24

21 ELEVATOR SHUNT TRIP 20 A 1 0.0 kVA 0.5 kVA 1 20 A Misc CIRCULATION PUMP 22

19 GAS WATER HEATERS 20 A 1 0.2 kVA 0.3 kVA 1 20 A ELEVATOR PIT Recept & Light 20

17 Lighting Room 004, 002 20 A 1 0.5 kVA 0.9 kVA 1 20 A Lighting STUDENT LOUNGE 001 18

15 Receptacle STUDENT LOUNGE 001 20 A 1 0.4 kVA 0.5 kVA 1 20 A Receptacle STUDENT LOUNGE 001 16

13 * Misc STUDENT LOUNGE 001 - VM 20 A 1 1.8 kVA 1.0 kVA 1 20 A * Misc STUDENT LOUNGE 001 - VM 14

11 Misc STUDENT LOUNGE 001 - MW 20 A 1 1.3 kVA 0.5 kVA 12

9 Misc EXISTING ELEVATOR E 20 A 1 0.5 kVA 0.5 kVA 2 20 A Misc BASEMENT ACU UNITS

7 Misc SERVER - UPS 30 A 1 2.9 kVA 0.0 kVA 1 20 A Spare 8

5 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 6

3 ELEVATOR LIGHTING 20 A 1 0.5 kVA 0.2 kVA 1 20 A Receptacle EXISTING ELEVATOR MACHINE... 4

1 FACP 20 A 1 0.5 kVA 0.2 kVA 1 20 A Receptacle EXISTING STORAGE 002 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes: POWER / LIGHTING

Supply From: DP1 Voltage: 208V 3PH Phase: 3 Wire: 4 Location: EXISTING MECHANICAL ROOM 004

Panel Name: BA

Total Estimated Demand Amps: 906.0 A

Total Estimated Demand: 326.4 kVA

Total Connected Load: 317.8 kVA

Panel Totals

Spare 230 VA 100.00% 230 VA

Receptacle 26100 VA 69.16% 18050 VA

Motor 94392 VA 109.53% 103388 VA

Misc 166699 VA 100.00% 166699 VA

Lighting 30422 VA 125.00% 38027 VA SEE SINGLE LINE DIAGRAM FOR ADDITIONAL INFORMATION.

Load Classification Connected Load Demand Factor Estimated Demand Additional Notes:

Total Amps: 926 A 926 A 826 A

Total Load: 109.6 kVA 109.5 kVA 99.1 kVA

41 42

39 40

37 38

35 15.0... 36

33 19.8... 34

2C 200 A 3

18.7... 32

29 18.2... 30

27 17.7... 28

1C 200 A 3

17.7... 26

23 12.0... 24

21 12.0... 22

ELEVATOR 200 A 3

12.0... 20

17 18.3... 0.0 kVA 18

15 21.0... 0.0 kVA 16

3B 400 A 3

20.7... 0.0 kVA

3 60 A SPD

11 7.7 kVA 6.0 kVA 12

9 9.4 kVA 8.2 kVA 10

2A 200 A 3

7.4 kVA 8.1 kVA

3 200 A 3A

5 5.0 kVA 17.0... 6

3 3.3 kVA 18.1... 4

BA 200 A 3

6.8 kVA 18.1...

3 400 A 1A - 1B

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Supply From: Voltage: 208V 3PH Phase: 3 Wire: 4 Location: EXISTING MECHANICAL ROOM 004

Panel Name: DP1

Total Estimated Demand Amps: 100.2 A

Total Estimated Demand: 36.1 kVA

Total Connected Load: 30.8 kVA

Panel Totals

Spare 200 VA 100.00% 200 VA

Receptacle 180 VA 100.00% 180 VA

Misc 9094 VA 100.00% 9094 VA

Lighting 21288 VA 125.00% 26610 VA

Load Classification Connected Load Demand Factor Estimated Demand Additional Notes:

Total Amps: 77 A 98 A 83 A

Total Load: 9.2 kVA 11.6 kVA 9.9 kVA

41 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 42

39 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 40

37 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 38

35 Spare 20 A 1 0.0 kVA 0.0 kVA 1 20 A Spare 36

33 Misc MEN 106 - FUTURE HAND DRYER 20 A 1 1.3 kVA 0.2 kVA 1 20 A Lighting MANICURE/PEDICURE AREA 100D 34

31 Misc WOMEN 105 - FUTURE HAND DRYER 20 A 1 1.3 kVA 1.5 kVA 32

29 0.9 kVA 1.5 kVA 2 20 A Misc ECH-1

ACU-1-02 P-1 Misc HVAC 103 15 A 2

0.9 kVA 0.9 kVA 28

25 Lighting FOH STAIRWELLS 20 A 1 0.3 kVA 0.9 kVA 2 15 A ACU-1-01 P-2 Misc HVAC 103

23 Lighting Room 100E, 103, 102, 104, 106, 105, 107 20 A 1 0.9 kVA 0.6 kVA 1 20 A EXTERIOR LIGHTING 24

21 Lighting WAITING AREA 100 20 A 1 0.9 kVA 0.3 kVA 1 20 A Lighting BOH STAIRWELL 22

19 Spare 20 A 1 0.0 kVA 0.9 kVA 1 20 A Lighting CORRIDOR 100B 20

17 Spare 20 A 1 0.0 kVA 1.4 kVA 1 20 A Lighting MANICURE/PEDICURE AREA 100D 18

15 Lighting WAITING AREA 100 20 A 1 0.6 kVA 1.4 kVA 1 20 A Lighting MANICURE/PEDICURE AREA 100D 16

13 Spare 20 A 1 0.0 kVA 0.4 kVA 1 20 A Lighting RECEPTION 100A 14

11 Lighting COSMETOLOGY SALON 101 20 A 1 1.5 kVA 0.9 kVA 1 20 A Lighting CORRIDOR 100B 12

9 Lighting COSMETOLOGY SALON 101 20 A 1 1.1 kVA 1.1 kVA 1 20 A Lighting COSMETOLOGY SALON 101 10

7 Lighting COSMETOLOGY SALON 101 20 A 1 1.1 kVA 1.1 kVA 1 20 A Lighting COSMETOLOGY SALON 101 8

5 Lighting 20 A 1 1.1 kVA 1.1 kVA 1 20 A Lighting COSMETOLOGY SALON 101 6

3 Lighting COSMETOLOGY SALON 101 20 A 1 1.5 kVA 1.5 kVA 1 20 A Lighting COSMETOLOGY SALON 101 4

1 LCP 20 A 1 0.2 kVA 1.5 kVA 1 20 A Lighting COSMETOLOGY SALON 101 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes: POWER / LIGHTING

Supply From: 1A Voltage: 208V 3PH Phase: 3 Wire: 4 Location: EXISTING MECHANICAL ROOM 004

Panel Name: 1B

Total Estimated Demand Amps: 148.5 A

Total Estimated Demand: 53.5 kVA

Total Connected Load: 53.5 kVA

Panel Totals

Misc 53500 VA 100.00% 53500 VA

Load Classification Connected Load Demand Factor Estimated Demand Additional Notes:

Total Amps: 147 A 147 A 152 A

Total Load: 17.7 kVA 17.7 kVA 18.2 kVA

41 Spare 0 A 1 0 VA 0 VA 1 0 A Spare 42

39 Misc 1ST FL STYLING STATION 20 A 1 800 VA 800 VA 1 20 A Misc 1ST FL STYLING STATION 40

37 Misc 1ST FL STYLING STATION 20 A 1 800 VA 800 VA 1 20 A Misc 1ST FL STYLING STATION 38

35 Misc 1ST FL STYLING STATION 20 A 1 1875... 1875... 1 20 A Misc 1ST FL STYLING STATION 36

33 Misc 1ST FL STYLING STATION 20 A 1 1875... 1875... 1 20 A Misc 1ST FL STYLING STATION 34

31 Misc 1ST FL STYLING STATION 20 A 1 800 VA 800 VA 1 20 A Misc 1ST FL STYLING STATION 32

29 Misc 1ST FL STYLING STATION 20 A 1 1875... 1875... 1 20 A Misc 1ST FL STYLING STATION 30

27 Misc 1ST FL STYLING STATION 20 A 1 800 VA 800 VA 1 20 A Misc 1ST FL STYLING STATION 28

25 Misc 1ST FL STYLING STATION 20 A 1 1875... 1875... 1 20 A Misc 1ST FL STYLING STATION 26

23 Misc 1ST FL STYLING STATION 20 A 1 800 VA 800 VA 1 20 A Misc 1ST FL STYLING STATION 24

21 Misc 1ST FL STYLING STATION 20 A 1 1875... 1875... 1 20 A Misc 1ST FL STYLING STATION 22

19 Misc 1ST FL STYLING STATION 20 A 1 800 VA 800 VA 1 20 A Misc 1ST FL STYLING STATION 20

17 Misc 1ST FL STYLING STATION 20 A 1 1875... 1875... 1 20 A Misc 1ST FL STYLING STATION 18

15 Misc 1ST FL STYLING STATION 20 A 1 800 VA 800 VA 1 20 A Misc 1ST FL STYLING STATION 16

13 Misc 1ST FL STYLING STATION 20 A 1 1875... 1875... 1 20 A Misc 1ST FL STYLING STATION 14

11 Misc 1ST FL STYLING STATION 20 A 1 800 VA 800 VA 1 20 A Misc 1ST FL STYLING STATION 12

9 Misc 1ST FL STYLING STATION 20 A 1 1875... 1875... 1 20 A Misc 1ST FL STYLING STATION 10

7 Misc 1ST FL STYLING STATION 20 A 1 800 VA 800 VA 1 20 A Misc 1ST FL STYLING STATION 8

5 Misc 1ST FL STYLING STATION 20 A 1 1875... 1875... 1 20 A Misc 1ST FL STYLING STATION 6

3 Misc 1ST FL STYLING STATION 20 A 1 800 VA 800 VA 1 20 A Misc 1ST FL STYLING STATION 4

1 Misc 1ST FL STYLING STATION 20 A 1 1875... 1875... 1 20 A Misc 1ST FL STYLING STATION 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Supply From: DP1 Voltage: 208V 3PH Phase: 3 Wire: 4 Location: DISPENSARY 102

Panel Name: 1C

Total Estimated Demand Amps: 148.5 A

Total Estimated Demand: 53.5 kVA

Total Connected Load: 53.5 kVA

Panel Totals

Misc 53500 VA 100.00% 53500 VA

Load Classification Connected Load Demand Factor Estimated Demand Additional Notes:

Total Amps: 161 A 170 A 125 A

Total Load: 18.7 kVA 19.8 kVA 15.0 kVA

41 Spare 0 A 1 0.0 kVA 0.0 kVA 1 0 A Spare 42

39 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 40

37 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 38

35 Misc 2ND FL STYLING STATION 20 A 1 0.8 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 36

33 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 1.9 kVA 1 20 A Misc 2ND FL STYLING STATION 34

31 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 32

29 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 30

27 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 28

25 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 26

23 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 24

21 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 22

19 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 20

17 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 18

15 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 16

13 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 14

11 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 12

9 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 10

7 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 8

5 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 6

3 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 4

1 Misc 2ND FL STYLING STATION 20 A 1 1.9 kVA 0.8 kVA 1 20 A Misc 2ND FL STYLING STATION 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Supply From: DP1 Voltage: 208V 3PH Phase: 3 Wire: 4 Location: FRESHMAN CLINIC 202

Panel Name: 2C

2 PR-014 - Updated Electric Panels

8/7/2014

3 PR-016 - Styling Stations

8/8/2014

5 PR-22 - Third Floor Electric

10/14/2014

File details come from the government source that posted it. Updated .