36-37 - PL1.1.pdf

PDF 642 KB Posted

Attached to
Surplus Real Property Sale For Economic Development; 438 Scott Boulevard
Solicitation number
RFP260305
Issued by
Hart County, Kentucky

About this file

This is a plumbing design drawing for new first-floor mechanical, electrical, and plumbing (MEP) systems prepared by the Commonwealth of Kentucky's Finance and Administration Cabinet, Department for Facilities & Support Services, Division of Engineering, in partnership with KLH Engineers, PSC for the Gateway Urban Campus project located at 438-440 Scott Street in Covington, Kentucky. The drawing details comprehensive plumbing installation requirements for a cosmetology salon and related tenant spaces, including fixture locations, piping routes, drain configurations, supply line specifications, and venting systems. The design encompasses multiple plumbing fixtures across diverse spaces including a reception area, waiting area, consultation room, manicure/pedicure area, cosmetology salon, restrooms, dispensary, HVAC room, storage, and custodial areas. The document specifies detailed piping sizes (ranging from 1/2 inch to 4 inches), fixture connections, trap configurations, and coordination requirements between plumbing and other mechanical trades.

Key specifications include sanitary and vent piping for floor drains, water supply lines with hot and cold water distribution at various temperatures (100°F and 140°F), gas piping for equipment, and storm drainage systems. The drawing establishes critical installation requirements including pressure-reducing valves, vacuum breaker connections on hair wash sinks, trap seal primers on floor drains, and coordination protocols with HVAC, electrical, and sprinkler contractors. The contractor is required to conduct a site visit prior to bidding to verify existing conditions and identify any discrepancies between plans and field conditions, with immediate notification to the engineer required if variations are discovered. All work must comply with applicable local and state codes, with piping installation concealed wherever possible and fire-resistant, watertight sealing required at all penetrations.

View the file

Other files

File Type Posted
66-67 - CT0.0.pdf PDF
51-49 - HV1.3.pdf PDF
8-13 - A1-1 - FIRST FLOOR DEMOLITION AND NEW WORK PLANS.pdf PDF
34-35 - PD1.1.pdf PDF
30-30 - A8-2 - Basement - FINISHES.pdf PDF
29-29 - A8-1 - ROOM FINISH PLANS (N-I-C- FURNITURE LAYOUT).pdf PDF
12-11 - S4-2 - FRAMING DETAILS.pdf PDF
15-8 - S2-5 - ROOF FRAMING PLAN.pdf PDF
73-19 - A3-0 - BUILDING ELEVATIONS.pdf PDF
49-51 - HV2.0.pdf PDF
72-72 - CT5.2.pdf PDF
67-69 - CT1.2.pdf PDF
62-63 - EP4.0.pdf PDF
3-6 - S2-3 - SECOND FLOOR FRAMING PLAN.pdf PDF
23-24 - A5-2 - MISCELLANEOUS DETAILS.pdf PDF
43-46 - HV1.0.pdf PDF
17-3 - S1-1 - GENERAL NOTES.pdf PDF
13-18 - A2-1 - 2ND 3RD FLR REFLECTED CLG PLANS.pdf PDF
28-31 - A8-3 - 1st FLOOR - FINISHES.pdf PDF
21-23 - A5-1 - MISCELLANEOUS STAIR DETAILS.pdf PDF
70-71 - CT5.1.pdf PDF
42-44 - FP1.1.pdf PDF
31-32 - A8-4 - 2nd Floor - FINISHES.pdf PDF
32-33 - A8-5 - 3rd Floor - FINISHES.pdf PDF
50-52 - HV2.1.pdf PDF
38-40 - PL1.4.pdf PDF
35-34 - PD1.0.pdf PDF
69-70 - CT4.1.pdf PDF
39-39 - PL1.3.pdf PDF
11-12 - A1-0 - BASEMENT DEMOLITION AND NEW WORK PLANS.pdf PDF
68-68 - CT1.0.pdf PDF
25-26 - A6-1 - ENLARGED PLANS AND INTERIOR ELEVATIONS.pdf PDF
63-64 - EL1.0.pdf PDF
19-10 - S4-1 - FRAMING DETAILS.pdf PDF
65-66 - EL2.0.pdf PDF
2-2 - A0-1 - CODE INFO AND WALL TYPES.pdf PDF
9-14 - A1-2 - SECOND FLOOR DEMOLITION AND NEW WORK PLANS.pdf PDF
76-Elevator Inspection 2026-03-25-12-13-48.pdf PDF
58-59 - EP1.3.pdf PDF
46-47 - HV1.1.pdf PDF
57-58 - EP1.2.pdf PDF
61-62 - EP3.0.pdf PDF
80-438 Scott Full Inspection Report (PDF).pdf PDF
7-5 - S2-2 - FIRST FLOOR FRAMING PLAN.pdf PDF
53-54 - HV3.1.pdf PDF
4-9 - S3-1 - TYPICAL DETAILS.pdf PDF
1-4 - S2-1 - FOUNDATION PLAN.pdf PDF
24-25 - A6-0 - ENLARGED PLANS AND INTERIOR ELEVATIONS.pdf PDF
48-50 - HV1.4.pdf PDF
20-21 - A4-1 - BUILDING SECTIONS.pdf PDF
Show 40 more

Latest 50 of 80 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

B C D EA G

F

STORAGE

WOMEN

HVAC

DISPENSARY

CORRIDOR

100B

MEN

STAIR

D1

COSMETOLOGY SALON

WAITING AREA

RECEPTION

100A

CONSULTATION

100C

MANICURE/PEDICURE

AREA

100D

EXISTING STAIR

B

CORRIDOR

100E

S

V

S

S

S

V

V

V

S

S

S

S

S S

CUSTODIAL

FD1

FD1

WB1

WC1

WC1

UR1

LV1

LV1

HD1

HD1

HD1

HD1

SK2

DF1

SK1

PS1

PS1

PS1

PS1

HS1

HS1

HS1

HS1

HS1

MS1

1-1/2"VENT

DOWN

1-1/2"VENT

DOWN

1-1/2"VENT

DOWN

V

2"VENT DOWN

1-1/2"VENT

DOWN

2"VENT

DOWN

4"SAN

DOWN

3"SAN. TO FD1

ABOVE

1-1/2"SAN. TO SK3

ABOVE

4"SAN. TO WC1

ABOVE

4"SAN UP

3"VENT UP

2"SAN. TO UR1

ABOVE

1-1/2"VENT

DOWN

1-1/2"VENT

DOWN

1-1/2"SAN. TO

DF1 ABOVE

TO LV1

ABOVE

1-1/2"VENT

DOWN

1-1/2"VENT

DOWN

1-1/2"VENT

DOWN

1-1/2"VENT

DOWN

1-1/2"VENT

UP

3" SAN. TO

FD1 ABOVE

4"SAN. TO WC1

ABOVE

1-1/2"SAN. TO

LV1 ABOVE

4"STORM

DOWN

4"STORM

UP

3"SAN. TO

MS1 ABOVE

ISLAND VENT

FOR HS1

ISLAND VENT

FOR HS1

ISLAND VENT

FOR HS1

TO WB1

ABOVE

2"VENT DOWN

1-1/2"VENT DOWN

2"VENT

UP

1-1/2"SAN.

TO SK1 ABOVE

2"VENT DOWN

2"VENT UP

CO

2"VENT

DOWN

CO

CO

CO

CO

S T

ISLAND VENT

FOR HS1

2"SAN. UP TO

HS2 ABOVE

2"SAN. UP TO

HS2 ABOVE

2"SAN. UP TO

HS2 ABOVE

RUN PIPING TO

AVOID STRUCTURAL

ISSUES. MINIMIZE

THE NUMBER OF

STRUCTURAL

CROSSINGS IN THE

FIELD.

WH EXHAUST

THRU WALL

4" EXHAUST FROM

WATER HEATER

BELOW

B C D EA G

F

1" 100ºHW

1" CW

C W

1 1/4" CW

1" 100ºHW

STORAGE

WOMEN

HVAC

DISPENSARY

CORRIDOR

100B

MEN

STAIR

D1

COSMETOLOGY SALON

WAITING AREA

RECEPTION

100A

CONSULTATION

100C

MANICURE/PEDICURE

AREA

100D

EXISTING STAIR

B

CORRIDOR

100E

CUSTODIAL

WB1

HB

HB

WC1

WC1

UR1

LV1

LV1

SK2

DF1

SK1

MS1

3/4"CW DOWN

TO WC1

3/4"CW DOWN TO UR1

1/2"H&CW UP

TO MS1

1/2"CW DOWN

TO DF1

1/2"H&CW DOWN

TO LV1

1/2"H&CW DOWN

TO LV1

1/2"CW DOWN

TO HB

1/2"CW DOWN

TO HB

3/4"CW DOWN

TO WC1

1/2"H&CW DOWN

TO WB1

1/2"H&CW DOWN

TO SK2

3/4"CW UP

PS1

PS1

PS1

PS1

2"GAS UP

1/2"H&CW

FROM

BELOW

TO PS1

1/2"H&C

W FROM

BELOW

TO PS1

1/2"H&C

W FROM

BELOW

TO PS1

1/2"H&C

W FROM

BELOW

TO PS1

1/2"H&CW UP

TO LV1 ABOVE

1/2"H&CW UP

TO MS1 ABOVE

1/2"H&CW

DOWN TO SK1

1-1/4"H&CW UP 3/4"HWR UP&

DOWN,1-1/4"HW&

1-1/2"CW DOWN

2"GAS DOWN

1/2"H&CW

FROM BELOW

TO HS1

1/2"H&CW

FROM BELOW

TO HS1

1/2"H&CW

FROM BELOW

TO HS1

1/2"H&CW

FROM BELOW

TO HS1

1/2"H&CW

UP TO WB1

/4

C

W

/2

ºH W

1/2" CW

/4

C

W

G

1/2" 100ºHW

1/2" CW

1/2" CW

/4

C

W

/2

ºH W

3/4" CW1" CW

1" CW

1/2" 100ºHW

C W

3/4" 100ºHW

1" CW

C W

ºH

W

INSTALL TP1 TO SERVE

FLOOR DRAINS IN

1ST FLOOR RESTROOMS

1/2" HWR

/2

H

W R

/2

H

W R

3/4" 140ºHW1/2" 140ºHW

/2

ºH W

/2

ºH W

/4

ºH W

140° 3/4"HW UP

/2

ºH W

140° 3/4"HW DOWN

/2

H

W R

1/2" HWR

1/2" HWR

HS1

HS1

HS1

HS1

HS1

1/2"H&CW

FROM BELOW

TO HS1

3/4"H&CW UP

140° 3/4"HW UP

C W

1" CW

3/4" HW

HB

S.C. SPRINKLER CONTRACTOR

P.C. PLUMBING CONTRACTOR

HUB DRAINHD

PRV PRESSURE REDUCING VALVE

RD ROOF DRAIN

INVERT ELEVATIONI.E.

VTR VENT THRU ROOF

FLOOR DRAIN, F.D.

HOSE BIBB (INTERIOR)

BALANCING VALVE

CHECK VALVE

CONTROL/SHUT-OFF VALVE

G GAS PIPE, G

ST STORM PIPING, ST

HOT WATER RETURN PIPING, HWRHWR

HOT WATER PIPING, HWHW

COLD WATER PIPING, CWCW

V VENT PIPING, V

S SANITARY/WASTE PIPING, S, W

SYMBOL DESCRIPTION

PLUMBING LEGEND

CO CLEANOUT

DEMOLITION / NEW WORK LINETYPE LEGEND

= EXISTING WORK TO BE DEMOLISHED (PD SHEETS

ONLY)

= NEW WORK BY CONTRACTOR

= EXISTING WORK TO REMAIN (EX = EXISTING)

EX.???

APPROVED FOR PROGRAM CONCEPT ONLY

APPROVED FOR PROGRAM CONCEPT ONLY

DATE

DATE

ENGINEERING

DIVISION OF

AGENCY

AUTHORIZED AGENT

FOR INTENT ONLY

DIV. OF ENGR.

REVIEWED

ENGR. ACCT NO.

DRAWING NO.

DATE

A&E FILE NO.

CHECKED BY

SHEET DRAWN BY

RECORD DATE

DATEREVISIONS

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES & SUPPORT SERVICES

DIVISION OF ENGINEERING

FRANKFORT, KENTUCKY

WWW.KLHENGRS.COM

ENGINEERS, PSC

MECHANICAL/ELECTRICAL ENGINEERS

KOHRS LONNEMANN HEIL

LEXINGTON, KENTUCKY

COLUMBUS, OHIO

DAYTON, OHIO

NEW YORK, NEW YORK

1538 ALEXANDRIA PIKE, SUITE

11 FT. THOMAS, KENTUCKY

41075 800-354-9783 859-442-8050

859-442-8058 FAX

KLH PRO. NO.

11369.04

PROFESSIONAL SERVICES CLASSROOM CENTER

/1

/2

:3 :3

A

M

PL1.1

PLUMBING - NEW - 1ST FLOOR

C5N5-NC11-01

GATEWAY URBAN CAMPUS

438-440 Scott St., Covington, KY 41011

12/18/15

201114.02

FAC

KPO

KEYED NOTES

18 PEDICURE STATION, PS1, TO DRAIN INTO HUB DRAIN, HD1.

19 PROVIDE AND INSTALL VACUUM BREAKER CONNECTION ON THE

SUPPLY SIDE OF ALL HAIR WASH SINKS, HS1 AND HS2.

SCALE: 1/4" = 1'-0"PL1.1

1 PLUMBING SANITARY AND VENT- NEW - 1ST FLOOR

SCALE: 1/4" = 1'-0"PL1.1

2 PLUMBING SUPPLY - NEW - 1ST FLOOR

GENERAL PLUMBING NEW WORK NOTES

A. BOLD - DASHED LINES INDICATE NEW UNDERGROUND PLUMBING PIPING

AND FADED - DASHED LINES INDICATE EXISTING UNDERGROUND

PLUMBING WORK TO REMAIN.

B. WATER PIPING IN AREAS SUBJECT TO FREEZING TEMPERATURES WILL

NOT BE PERMITTED.

C. WHEREVER POSSIBLE, NEW PIPING AND RELOCATED PIPING SHALL BE

RUN CONCEALED. COORDINATE LOCATION OF ALL PIPING WITH HVAC

AND ELECTRIC SUBCONTRACTOR. COORDINATE CUTTING AND PATCHING

WITH GENERAL CONTRACTOR.

D. WHEREVER FIXTURES REQUIRING PLUMBING CONNECTIONS ARE

FURNISHED BY OWNER OR ARE RELOCATED, PLUMBING

SUBCONTRACTOR SHALL FURNISH AND INSTALL CARRIERS, "P" TRAP

AND STOPS.

E. ALL PIPE DROPS IN SALES AREA FROM ROOF TO LOW WALLS OR

EQUIPMENT SHOULD BE COORDINATED AND GROUP TOGETHER WITH

OTHER MECHANICAL PIPES.

F. NO PIPE ROUTING ALLOWED TO RUN THROUGH ELEVATOR EQUIPMENT

ROOMS.

G. DROP WATER DOWN IN WALL. ROUTE WATER THRU WALL TO SERVE

MULTIPLE FIXTURES ON COMMON WALL. FIXTURE SCHEDULE FOR

FIXTURE REQUIREMENTS.

H. ALL MEP TRADES, INCLUDING SPRINKLER MUST COORDINATE WITH EACH

OTHER PRIOR TO INSTALLATION.

I. PRIOR TO BID, CONTRACTOR SHALL VISIT THE JOB SITE AND FIELD

VERIFY THE EXISTING CONDITIONS. THE MECHANICAL CONTRACTOR

SHALL BE RESPONSIBLE FOR FIELD VERIFYING THE EXISTING STUB-INS,

TAPS, ETC. FOR PLUMBING SYSTEM FOR THE TENANT SPACE. THE

CONTRACTOR SHALL NOTIFY THE ENGINEER IMMEDIATELY OF ANY

DISCREPANCIES FOUND BETWEEN PLANS AND FIELD CONDITIONS IN

ORDER TO PREVENT UNKNOWN ADDITIONAL COSTS TO THE TENANT.

J. PROVIDE SHUTOFF VALVE(S) AT EACH FIXTURE.

K. ALL PLUMBING PIPING DROPS TO PLUMBING FIXTURES SHALL BE

INSTALLED IN WALL SPACE EXCEPT WHERE NOTED.

L. SUSPEND ALL HORIZONTAL WATER AND VENT PIPING AS HIGH AS

POSSIBLE ABOVE CEILING.

M. SAW CUT/CORE DRILL ALL SLAB PENETRATIONS. SEAL AROUND ALL

WALL, FLOOR AND CEILING PIPE PENETRATIONS WITH APPROVED

SEALANT MATERIAL AND ENSURE PENETRATIONS REMAIN FIRE

RESISTANT AND WATERTIGHT.

N. ALL EQUIPMENT, INSTALLATIONS AND MATERIALS SHALL COMPLY WITH

APPLICABLE LOCAL AND STATE CODES.

O. PROVIDE TRAP SEAL PRIMER ON ALL FLOOR DRAINS

File details come from the government source that posted it. Updated .