49-51 - HV2.0.pdf
PDF 617 KB Posted
- Solicitation number
- RFP260305
- Issued by
- Hart County, Kentucky
About this file
This is an HVAC (Heating, Ventilation, and Air Conditioning) technical details and specifications document prepared by the Commonwealth of Kentucky's Department for Facilities & Support Services, Division of Engineering, in collaboration with KLH Engineers for the Gateway Urban Campus project located at 438-440 Scott Street in Covington, Kentucky. The document contains detailed mechanical specifications and installation requirements for various HVAC components and systems that would be incorporated into the Professional Services Classroom Center renovation or construction project, with the engineering file numbered 11369.04 and drawing number 470-C5N5-NC11-01 dated December 18, 2015.
The specifications include technical details for condensate drain trap systems, refrigerant piping installation and VRV (Variable Refrigerant Volume) systems, rooftop equipment support and mounting, ductless air conditioning units, flex duct diffuser installation, fire dampers, dryer exhaust systems, and transfer grilles. Each specification includes keyed notes, dimensions, material requirements, installation procedures, and compliance standards such as NFPA 90A. The document specifies requirements for proper drainage slopes, trap accessibility for cleaning, insulation requirements for outdoor units, equipment positioning minimum distances from roof edges (10 feet minimum), curb specifications for rooftop units maintaining 10 inches above finished roofing, and various clearance and safety requirements. No pricing, award dates, response deadlines, or contract term information is contained within this technical specifications document.
View the file
Other files
Show 40 more
Latest 50 of 80 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
K = MINIMUM OF 1/2"
M = 1/2" PLUS MAXIMUM TOTAL STATIC
PRESSURE
A. LOCATE TRAPS SO AS TO BE ACCESSIBLE
FOR CLEANING
B. CONDENSATE PIPING SHALL GRADUALLY
SLOPE DOWN FROM DRAIN TRAP
C. CONFIRM TRAP REQUIREMENTS WITH
EQUIPMENT MANUFACTURER
D. REFER TO SPECIFICATIONS FOR
MATERIAL AND INSULATION
REQUIREMENTS
H = (1" FOR EACH 1" OF MAXIMUM NEGATIVE
STATIC PRESSURE) + 1"
J = HALF OF H
L = H + J + PIPE DIAMETER + INSULATION
NOTE: OUTDOOR UNITS AND UNITS LOCATED IN UNCONDITIONED SPACES WHICH PROVIDE COOLING IN THE
WINTER MUST HAVE HEAT TRACE ON CONDENSATE PIPING.
VERIFY WITH AHJ
NEGATIVE PRESSURE
POSITIVE PRESSURE
L
J
CAP
CAP
CONNECTION
OF AIR UNIT DRAIN
PIPE FULL SIZE
AIR UNIT CASING
SEE NOTE 2
FLOW
H
GENERAL NOTES:
M
CAP
CAP
CONNECTION
OF AIR UNIT DRAIN
PIPE FULL SIZE
AIR UNIT CASING
SEE NOTE 2
FLOW
K
SCALE:
COND. DRAIN TRAP POSITIVE & NEGATIVE
NONE
232113.23-05
1. 2"x4" TREATED NAILER
2. ANCHOR TO DECK
3. 1" LINED
4. OPENING THRU ROOF. SIZE BASED ON PIPING
INSTALLATION REQUIREMENTS
5. DOUBLE WALL 1/2" INSULATED CAP
6. 20 GAUGE GALV. SHEET METAL
7. CANT REQUIRED FOR BUILT-UP ROOFING.
DELETE CANT FOR ANY NON BUILT-UP
ROOFING SYSTEM AND FLASH TO BELOW
CURB CAP
8. SECURE CAP TO BASE W/ 1 SCREW PER SIDE
9. 24 GAUGE GALV. SHEET METAL THIMBLE FOR
PIPE PASSAGE CAULK THIMBLE AT DOG
HOUSE & AT PIPE PENETRATION
KEYED NOTES:
SCALE:
DOG HOUSE FOR REFRIGERANT PIPING
NONE
232313.00-01
6. SECURE TO CEILING PER MANUFACTURER'S
RECOMMENDATIONS AND PER CEILING FINISH.
PROVIDE GRID CLIPS PER MFG'R REQUIREMENTS.
PROVIDE FRAMING FOR DRYWALL
INSTALLATION.
7. HANGER, SECURE TO STRUCTURE AND
DUCTWORK
8. PEEL BACK INSULATION AND PROVIDE STRAPPING
AND SHEET METAL SCREWS AT FLEX CONNECTION TO
DUCT. THEN PROVIDE STRAPPING AROUND
INSULATION.
9. SUPPORT FLEX TO PREVENT COLLAPSING
1. MAXIMUM LENGTH OF INSUL. FLEX DUCT
EQUALS 5 FEET. FLEX NOT PERMITTED IN
INACCESSIBLE CEILINGS
2. INSULATED DUCT, COLLAR AND DIFFUSER BY
HVAC CONTRACTOR
3. SCOOP
4. SPIN IN FITTING WITH MANUAL VOLUME
DAMPER
5. INTERNAL BUTTERFLY DAMPER FOR
DRYWALL APPLICATIONS ONLY.
(PROVIDE KEY FOR ADJUSTMENT)
KEYED NOTES:
MAIN
SUPPLY
DUCT
INSULATION
SCALE:
DIFFUSER INSTALLATION (TYPICAL)
NONE
233713.00-04
1. ANCHOR UNIT TO CURB
2. PRESSURE TREATED WOOD NAILER
3. VIBRATION ISOLATORS
4. ROOF DECK
5. PREFABRICATED EQUIPMENT SUPPORT
6. SINGLE MEMBRANE ROOFING; FLASH PER
MFG'R RECOMMENDATIONS. FLASH UP AND
OVER WOOD NAILOR
7. PREFABRICATED DOG HOUSE
8. SEAL AND FLASH OPENING
A. ON PROJECTS WITH BUILT -UP ROOFS, ADD
CANT ON EQUIPMENT SUPPORTS AND
PREFABRICATE PIPING CHASE
B. PLACE EQUIPMENT ACROSS BAR JOIST OR
ADD ADDITIONAL STRUCTURAL STEEL AS
NECESSARY TO CARRY EQUIPMENT WEIGHT
C. LOCATE A MINIMUM OF 10'-0" FROM EDGE OF
ROOF
GENERAL NOTES:KEYED NOTES:
12"
MIN.
MIN.
12"
CU-?
UNIT
ROOFTOP
SCALE:
EQUIPMENT SUPPORT
NONE
236313.00-02
A. CONTRACTOR SHALL PROVIDE CURB TO
MAINTAIN 10" MINIMUM ABOVE FINISHED
ROOFING SYSTEM, PROVIDE ADDITIONAL
BLOCKING AS REQUIRED TO ACCOMODATE
ROOF INSULATION THICKNESS
A. CONTRACTOR SHALL PROVIDE CURB TO
MAINTAIN 10" MINIMUM ABOVE FINISHED
ROOFING SYSTEM, PROVIDE ADDITIONAL
BLOCKING AS REQUIRED TO ACCOMODATE
ROOF INSULATION THICKNESS.
1. ROOFTOP AIR CONDITIONING
UNIT W/ HOT WATER REHEAT &
DX COOLING LOCATE A MINIMUM
OF 10'-0" FROM EDGE OF ROOF
2. CANVAS FLEXIBLE CONNECTION
3. 1" ACOUSTIC LINED DUCTS
PROVIDE RADIUSED ELBOW
4. 4X4 ANGLE FASTENED TO ROOF
DECK AND STRUCTURAL SYSTEM
PROVIDE SUPPORTS AS
REQUIRED
5. FACTORY FABRICATED 2"
INSULATED & SHEETMETAL LINED
CURB (BY SAME MFG'R AS UNIT)
6. FASTEN TO CURB DECK
7. BAR JOIST
8. SECURE TO CURB
9. TREATED WOOD NAILER
10. EXTEND ROOFING UP AND OVER
NAILOR. CURB TYPE AND
FLASHING PER ROOFING
MANUFACTURER'S
REQUIREMENTS.
11. CANT STRIP
12. ROOF DECK
13. ACTIVE CURB W/ PLENUM
FOR RETURN CONNECTION
14. HOT WATER SUPPLY AND
RETURN PIPING
15. CONDENSATE TRAP - SEE
CONDENSATE DRAIN TRAP
DETAIL
16. HIGH WATER ALARM IN
CONDENSATE DRAIN PAN. WIRE
TO BREAK 24 VOLT CONTROL
POWER IN THE CASE OF A HIGH
WATER EVENT.
KEYED NOTES:
GENERAL NOTES:
S.A.
R.A.R.A.
S.A.
GENERAL NOTES:
KEYED NOTES:
SCALE:
ROOF CURB & MOUNTING
NONE
237433.00-03
SCALE:
VRV OUTDOOR CONDENSING UNIT MOUNTING DETAIL
NONE
238126.03
SCALE:
REFNET INSTALLATION
NONE
232313.00-02
SCALE:
VRV BRANCH SELECTOR BOXES
NONE
232313.00-02
13-3/4" or more
13-3/4" or more o r m o r e
(8-5/8)
(8-9/16)
16-7/8
(8-9/16)
10" or more o r m o r e
10" or more o r m o r e
18"
A. ELECTRIC BOX CAN ALSO BE FIXED ON
THE OTHER SIDE OF THE UNIT.
B. BE SURE TO INSTALL AN INSPECTION
DOOR A THE ELECTRIC BOX SIDE.
C. MAINTAIN ALL NEC REQUIRED
CLEARANCES FOR THE ELECTRIC BOX.
GENERAL NOTES:
1. SUCTION GAS PIPE CONNECTION PORT
2. HP/LP GAS PIPE CONNECTION PORT
3. LIQUID PIPE CONNECTION PORT
4. GAS PIPE CONNECTION PORT
5. LIQUID PIPE CONNECTION PORT
6. ELECTRIC BOX (NOTE 1)
7. SUSPENSION BRACKETS
8. GROUNDING TERMINAL
9. ATTACHED PIPE (1) (NOTE 3)
10. ATTACHED PIPE (2) (NOTE 3)
11. PLATED NUT & WASHER TOP & BOTTOM,
TYP.
12. ALL THREAD ROD, TYP.
13. EXPANSION ANCHOR, TYP.
14. FULL PORT SHUT-OFF BALL VALVE
15. SCHRADER VALVE (TYP. ON LIQUID LINE
OF ALL BRANCHES)
KEYED NOTES:
1. CANVAS FLEXIBLE CONNECTION
2. RETURN PLENUM, PROVIDE 1/2" ACOUSTIC
LINING
3. 4" CONCRETE PAD
4. PROVIDE RETURN PLENUM UNDER UNIT FOR
SUPPLY AIR FLOW GREATER THAN 1800 CFM.
PROVIDE SUPPORT ANGLES IN CORNERS OF
UNIT. MOVER FILTER TO UNIT BOTTOM AIR
INLET
5. COPPER CONDENSATE DRAIN, MINIMUM 1"
DEEP
6. CONDENSATE DRAIN, COPPER PIPING, PIPE
TO FLOOR DRAIN TRAP
7. EVAPORATOR COIL
8. SUPPLY PLENUM
9. REFRIGERANT LINES PROVIDE 3/4" ARMAFLEX
ON SUCTION LINE
10. AIR CONDITIONER WITH EVAP. COIL AND
SUPPLEMENTAL HEAT AS REQ'D
11. FILTER AND RACK - INSTALL AT SIDE OF UNIT
< 1800 CFM AND INSTALL AT BOTTOM OF UNIT
>=1800 CFM.
12. HIGH WATER ALARM IN CONDENSATE DRAIN
PAN. WIRE TO BREAK 24 VOLT CONTROL
POWER IN THE CASE OF A HIGH WATER
EVENT.
KEYED NOTES:
SCALE:
AIR CONDITIONER
NONE
238126.00-01
1. DX COOLING COIL
2. CONDITIONED OUTLET AIR
3. AIR FILTER
4. FAN MOTOR
5. 3/4" CONDENSATE DRAIN WITH TRAP
6. REFRIGERANT LINES (NOT TO BE EXPOSED
TO OCCUPANT), MAXIMUM PIPING LENGTH
EQUAL TO 100FT. MAXIMUM ELEVATION
DIFFERENCE EQUAL TO 50 FT. INSULATE
SUCTION AND LIQUID LINES.
7. OUTLET LOUVER
8. INLET AIR
SIDE VIEW
KEYED NOTES:
WALL
FRONT VIEW
3'-0" MINIMUM CLEARANCE
FOR SERVICE AND AIR FLOW.
SCALE:
DUCTLESS AIR CONDITIONING UNIT WALL
NONE
238126.00-06
1. 1.5"x1.5" ANGLE (18 GA.) FASTEN TO
ALL FOUR SIDES OF FIRE DAMPER
(6" O.C.). DO NOT FASTEN TO WALLS
2. "SLIP BREAK AWAY" CONNECTIONS.
DO NOT USE "C" DRIVES, SCREWS
OR RIVETS
3. FIRE DAMPER WITH WALL SLEEVE,
(GAUGE PER MANUFACTURER)
INTEGRAL WITH DAMPER OR
FURNISHED SEPARATELY, FASTEN
DAMPER TO SLEEVE
4. ACCESS DOOR IN DUCT
5. PROVIDE ARCHITECTURAL ACCESS
PANEL IN NON-ACCESSIBLE WALLS
OR CEILINGS
6. FASTNERS, 4 SIDES, 6" O.C. AT
STUD & DRYWALL USE #10 SCREWS,
PENETRATE STUD 1/2" MIN. AT
MASONRY, USE #10 SELF-TAPPING
CONCRETE SCREWS, PENETRATE
WALL 1-1/2" MIN.
A. INSTALLATION TO CONFORM TO
NFPA 90A AND INSTRUCTIONS
B. FLOOR INSTALLATION IS SIMILAR
TO THAT SHOWN
C. FIRE DAMPERS TO BEAR THE UL
LABEL
GENERAL NOTES:
KEYED NOTES:
16" MAX3"
8" MAX
SCALE:
FIRE DAMPER (TYPE A)
NONE
233313.00-12
10"
2"
4"
1"
1. 4" OUTLET FOR INLINE USE CENTERED ON
TOP (OPTIONAL)
2. 4" OUTLET FOR SIDE OUTLET USE CENTERED
ON SIDE
3. 2"x9.5" DRAWER FOUR SIDES WITH 9.5"x9.5"
BOTTOM
4. DRAWER BOTTOM SHOULD BE 1/4"
PERFORATED PLATE FOR LINT TRAPPING
5. 4" INLET
6. 1"x1"x9" 20 GAUGE ANGLE ALL FOUR
CORNERS
7. 10"x3" DRAWER FACE PROVIDE 1/8" GASKET
AT DRAWER FACE PERIMETER
8. HANDLE
KEYED NOTES:
(10" DEEP)
SCALE:
DRYER VENT LINT TRAP
NONE
233500.00-02
5. MAXIMUM 25'-0" EQUIVALENT FEET FROM
DRYER TO OUTLET TERMINAL
6. METALLIC FLEXIBLE DUCT CONNECTOR
MAX. 6'-0" (NOT ALLOWED IN CONCEALED
LOCATIONS)
7. PROVIDE CLEANOUT IN EACH VERTICAL
RISER
8. SECURE ALONG WALL W/ STRAPS
1. TERMINATE THRU ROOF OR WALL W/CAP
WITH 10' CLEAR FROM INTAKES OR
BUILDING OPENINGS.
2. BACKDRAFT DAMPER
3. ALTERNATE ROUTE THRU SIDE WALL
4. 4"Ø SHEETMETAL SMOOTH INTERIOR DUCT
WITH JOINTS IN DIRECTION OF AIRFLOW &
NO OBSTRUCTION TO AIRFLOW
KEYED NOTES:
DRYER
INTERIOR WALL
EXTERIOR WALL
SCALE:
DRYER EXHAUST
NONE
233500.00-01 y x
1.
" ACOUSTIC LINING, SEAL AROUND ALL
WALL PENETRATIONS
2. SEE NEW WORK PLAN FOR REGISTER
3. INTERIOR WALL/PARTITION
A. SEE NEW WORK PLAN FOR DUCT SIZE
B. x + y DIMENSIONS SHALL BE
DETERMINED FROM FLOOR PLANS
GENERAL NOTES: KEYED NOTES:
SCALE:
TRANSFER GRILLE
NONE
233713.00-19
DATE
DATE
ENGINEERING
DIVISION OF
AGENCY
AUTHORIZED AGENT
DIV. OF ENGR.
REVIEWED
ENGR. ACCT NO.
DRAWING NO.
DATE
A&E FILE NO.
CHECKED BY
SHEET DRAWN BY
RECORD DATE
DATEREVISIONS
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES & SUPPORT SERVICES
DIVISION OF ENGINEERING
FRANKFORT, KENTUCKY
WWW.KLHENGRS.COM
ENGINEERS, PSC
MECHANICAL/ELECTRICAL ENGINEERS
KOHRS LONNEMANN HEIL
LEXINGTON, KENTUCKY
COLUMBUS, OHIO
DAYTON, OHIO
NEW YORK, NEW YORK
1538 ALEXANDRIA PIKE, SUITE
11 FT. THOMAS, KENTUCKY
41075 800-354-9783
859-442-8050
859-442-8058 FAX
KLH PRO. NO.
11369.04
470-C5N5-NC11-01
GATEWAY URBAN CAMPUS
438-440 Scott St., Covington, KY 41011
12/18/15
201114.02
PROFESSIONAL SERVICES CLASSROOM CENTER
HV2.0
H.V.A.C. DETAILS