2-2 - A0-1 - CODE INFO AND WALL TYPES.pdf
PDF 459 KB Posted
- Solicitation number
- RFP260305
- Issued by
- Hart County, Kentucky
About this file
This is an architectural drawing set documenting code information and wall types for a renovation project at the Gateway Urban Campus Professional Services Classroom Center, located at 438-440 Scott Street in Covington, Kentucky, prepared by the Commonwealth of Kentucky's Department for Facilities Management, Division of Engineering. The document provides comprehensive design specifications for the interior fit-up of an existing three-story building with basement, totaling 15,002 square feet across four levels (basement: 3,467 SF, first floor: 3,832 SF, second floor: 3,832 SF, third floor: 3,871 SF). The project complies with the Kentucky Building Code 2007 Edition and IECC 2009 standards, utilizing existing Use Group B construction and Construction Type III-B with full sprinkler protection per NFPA 13. The architectural specifications detail multiple functional areas including cosmetology salon, massage clinical labs, classroom facilities, dispensaries, offices, reception areas, and support spaces, with specific occupancy requirements and travel path egress designations indicated throughout the floor plans.
The drawing set establishes detailed wall type specifications (including types 901, 906, 906A, 906RA, 923, 923A, 924, 924A, and 964R) with corresponding fire-resistance ratings ranging from one to two hours, acoustic attenuation requirements, and material standards including metal stud gauges, gypsum board specifications, sealant applications, and deflection track details. Critical specifications include minimum U-value requirements for storefront windows (0.50) and doors (0.85), mandatory fire stopping at all ceiling and floor penetrations, moisture-resistant and cementitious backer board requirements at tile locations, and a metal stud gauge guide for interior partitions based on height and load requirements. The record drawings, approved for program concept on January 5, 2016, incorporate building systems for existing elevators, stairs, HVAC, and sprinkler infrastructure, with detailed base connection and construction methodology documentation to support the renovation and adaptive reuse of the facility for educational and professional services programming.
View the file
Other files
Show 40 more
Latest 50 of 80 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
W D
D W
B C D EA G
578 SF
STUDENT
LOUNGE
1/15
EXISTING
STAIR A
926 SF
EXISTING
STORAGE
1/300
1252 SF
EXISTING
MECHANICAL
ROOM
1/300
VENDING
63 SF
EXISTING
ELEVATOR
MACHINE ROOM
1/300
S0
S0
EXISTING
ELEVATOR
E
E2
E2
F.E.
39' - 6" 46' - 3"
12' - 5" 13' - 3" 46' - 3"
F
B C D EA G
44 SF
HVAC
1/300
110 SF
DISPENSARY
1/100
1333 SF
COSMETOLOGY
SALON
1/100
207 SF
RECEPTION
1/100
223 SF
WAITING AREA
1/100
329 SF
MANICURE/PEDICURE
AREA
1/100
59 SF
CONSULTATION
1/100
139 SF
STORAGE
1/300
59 SF
WOMEN
1/50
59 SF
MEN
1/50
STAIR
D1
S0
EXISTING
ELEVATOR
E
E2
EXISTING STAIRS
F.E.C.
CUSTODIAL
52' - 9" 14' - 9"
15' - 0" 7' - 6" 21' - 6"
4' - 6" 30' - 3" 16' - 0" 23' - 6"
F
212 SF
FACIAL /
COUPLE
MASSAGE
1/100
STAIR
D2
85 SF
DISPENSARY
1/100
62 SF
MEN
1/50
74 SF
WOMEN
1/50
18 SF
CUST.
1/300
97 SF
OFFICE 2
1/100
107 SF
OFFICE 1
1/100
552 SF
CLASSROOM
1/20
1229 SF
FRESHMAN
CLINIC
1/50
B C D EA G
EXISTING STAIR
C2
EXISTING STAIR
B2
EXISTING
ELEVATOR
E
E2
F.E.C.
53' - 6" 26' - 0"
23' - 3" 18' - 8" 14' - 8"
F
B C D EA G
112 SF
CLIENT
MASSAGE
1/100
116 SF
CLIENT
MASSAGE
1/100
103 SF
CLIENT
MASSAGE
1/100
109 SF
CLIENT
MASSAGE
1/100
153 SF
CLIENT
MASSAGE
1/100
77 SF
OFFICE
1/100
96 SF
STORAGE
1/300
STAIR
D3
1330 SF
MASSAGE
CLINICAL LAB
1/50
65 SF
WOMEN
1/50
LINENS
D O
W N
T O
N
D F
L O
O R
LOBBY
CONTINUOUS PRIVACY
CURTAIN AND TRACK
65 SF
MEN
1/50
E2
EXISTING
ELEVATOR
E
EXISTING STAIR
C3
F.E.C.
13' - 0" 13' - 10" 34' - 6"
4' - 5"
61' - 4" 18' - 2"
10' - 3"
F
18' - 2"
/8
ROOM NAME
1/100
100 SF
CODE LEGEND
ROOM SQUARE FOOTAGE
TRAVEL PATH
OCCUPANCY COUNT
OCCUPANCY
CODE COMPLIANCE
CODE: KENTUCKY BUILDING CODE, 2007 EDITION
USE GROUP: B (EXISTING USE GROUP, NO CHANGE)
CONSTRUCTION TYPE: III B (EXISTING BUILDING)
FIRE PROTECTION: FULLY SPRINKLERED PER NFPA 13
BUILDING HEIGHT: EXISTING BUILDING HEIGHT = 3 STORIES W/ BASEMENT
FIT-UP AREA: BASEMENT LEVEL: 3,467 SF
FIRST FLOOR LEVEL: 3,832 SF
SECOND FLOOR LEVEL: 3,832 SF
THIRD FLOOR LEVEL: 3,871 SF
TOTAL: 15,002 SF
IECC 2009 COMPLIANCE DATA
STOREFRONT/CURTAINWALL WINDOWS: MINIMUM U-VALUE = .50
STOREFRONT DOORS: MINIMUM U-VALUE = .85
MIN. FIRE RESISTANCE RATINGS
EXISTING ELEVATOR HOISTWAYS: 2 HOUR
EXISTING ELEVATOR MACHINE ROOM: 2 HOUR
PROVIDE FIRE STOPPING AT ALL CEILINGS AND
FLOOR PENETRATIONS.
S0
E2
INCIDENTAL USE SEPARATION: SEAL ALL
PENETRATIONS AIR TIGHT, WALLS/PARTITIONS
AND HORIZONTAL FLOOR/CEILING ASSEMBLIES
EXISTING TWO HOUR FIRE BARRIER
1 ONE HOUR FIRE BARRIER
EGRESS TRAVEL PATH
38 N/A0901
3 5/8" METAL STUDS AT 16" O.C.
1 LAYER 5/8" GYPSUM BOARD
EXISTING OR NEW
DECKING (FLOOR OR ROOF)
SEE REFLECTED CEILING PLAN
FOR MATERIAL AND HEIGHT
SEE FINISH SCHEDULE
FOR BASE AND FLOOR
WALL TYPE
SCALE: 1 1/2"=1'-0"
WALL U.L. #HRSTC
PROVIDE GYPSUM BOARD "J" TRIM,
TYP. EACH SIDE OF WALL
4 7/8"
DEFLECTION TRACK
U4191
N/A0906
906RA
N/A0906A
SEALANT AT PERIMETER AND PENETRATIONS
EACH SIDE OF WALL (FOR WALL TYPES 906A)
(FOR WALL TYPES 906RA SEALANT SHALL
COMPLY WITH UL ASSEMBLY)
6" METAL STUDS AT 16" O.C.
(6" - 24ga MTL STD @ 12" O.C. FOR WALL TYPE 906.1, REFER TO TYP. BASE OF STUD CONNECTION DETAIL
THIS SHEET)
SOUND ATTENUATION BATTS (FOR WALL
TYPE 906A) - (USE MINERAL FIBER FOR WALL
TYPE 906RA)
1 LAYER 5/8" GYPSUM BOARD (TYPE "X"
FOR WALL TYPES 906RA)
EXISTING OR NEW
DECKING (FLOOR OR ROOF)
SEE REFLECTED CEILING PLAN
FOR MATERIAL AND HEIGHT
FIRESAFING INSULATION (FOR WALL
TYPES 906A & 906RA)
SEE FINISH SCHEDULE
FOR BASE AND FLOOR
WALL TYPE
SCALE: 1 1/2"=1'-0"
WALL U.L. #HRSTC7 1/4"
SEALANT AT PERIMETER AND PENETRATIONS
EACH SIDE OF WALL (FOR WALL TYPE 906A)
(FOR WALL TYPES 906RA SEALANT SHALL
COMPLY WITH UL ASSEMBLY)
DEFLECTION TRACK
38 N/A0906.1
30 N/A0923
3 5/8" METAL STUDS AT 16" O.C.
1 LAYER 5/8" GYPSUM BOARD
EXISTING OR NEW DECKING (FLOOR OR ROOF)
EXTEND METAL STUDS TO DECK ABOVE
SEE REFLECTED CEILING PLAN FOR
MATERIAL AND HEIGHT
SEE FINISH SCHEDULE FOR BASE AND FLOOR
WALL TYPE
SCALE: 1 1/2"=1'-0"
WALL U.L. #HRSTC
3 5/8" SOUND ATTENUATION BATTS
(FOR WALL TYPE 923A)
40 N/A0923A
STAND GYPSUM BOARD OFF CONCRETE
MIN. 1/4" PROVIDE "J" TRIM
SEALANT AT PERIMETER AND PENETRATIONS
EACH SIDE OF WALL (FOR WALL TYPE 923A)
SEALANT AT PERIMETER AND PENETRATIONS
EACH SIDE OF WALL (FOR WALL TYPE 923A)
4 1/4"
DEFLECTION TRACK
30 N/A0924
6" METAL STUDS AT 16" O.C.
1 LAYER 5/8" GYPSUM BOARD
EXISTING OR NEW DECKING (FLOOR OR ROOF)
EXTEND METAL STUDS TO DECK ABOVE
SEE REFLECTED CEILING PLAN FOR
MATERIAL AND HEIGHT
SEE FINISH SCHEDULE FOR BASE AND FLOOR
WALL TYPE
SCALE: 1 1/2"=1'-0"
WALL U.L. #HRSTC
6" SOUND ATTENUATION BATTS (FOR
WALL TYPE 924A)
40 N/A0924A
STAND GYPSUM BOARD OFF CONCRETE MIN.
1/4" PROVIDE "J" TRIM
SEALANT AT PERIMETER AND PENETRATIONS
EACH SIDE OF WALL (FOR WALL TYPE 924A)
SEALANT AT PERIMETER AND PENETRATIONS
EACH SIDE OF WALL (FOR WALL TYPE 924A)
6 5/8"
DEFLECTION TRACK
39 U4151964R
FIRESAFING INSULATION
SEALANT AT PERIMETER
2 1/2" METAL C-H STUDS AT 24" O.C.
WITH J-RUNNER OR E-STUD AT JAMBS
DECKING (FLOOR OR ROOF)
1 LAYER 5/8" TYPE "X" GYSPUM BOARD
SEE FINISH SCHEDULE FOR BASE AND FLOOR
WALL TYPE
964R
SCALE: 1 1/2"=1'-0"
WALL U.L. #HRSTC
2 1/2" J-RUNNER
1" GYPSUM SHAFT LINER PANEL
SEE REFLECTED CEILING PLAN FOR
MATERIAL AND HEIGHT
SEALANT AT PERIMETER
2 1/2" J-RUNNER
SLAB
EDGE
OR EDGE
ANGLE
PLAN
VIEW
SHAFT OR
CHASE
SIDE
3 1/8"
GENERAL NOTES
A. WALL TYPE NUMBERS ARE NOT NECESSARILY CONSECUTIVE.
B. WALL TAGS ON PLAN SHEETS MAY CONTAIN A LETTER SUFFIX (A.
RA., ETC.) THE FIRST THREE NUMBERS IDENTIFY THE WALL TYPE.
THE SUFFIX DENOTES ADDITIONAL MATERIALS NECESSARY TO
ACHIEVE ENHANCED FIRE/AND OR ACOUSTICAL RATINGS. FOR THAT
PARTICULAR WALL TYPE. REFER TO CHART AND PARENTHETICAL
NOTES IN EACH WALL TYPE FOR THE ADDITIONAL INFORMATION.
A= ACOUSTICAL RATING
R= FIRE RATING
C. A WALL TYPE TAG SHALL APPLY TO AN ENTIRE LENGTH OF WALL
WHETHER INTERSECTED BY OTHER WALLS OR NOT. IF DIFFERING
TAGS OCCUR ALONG LENGTH OF A WALL. THE TAG SHALL ONLY
APPLY TO THAT SECTION OF WALL BETWEEN INTERSECTIONS.
REFER TO EGRESS PLANS FOR CLARIFICATION OR RATED AREAS.
D. FIRE STOPPING REQUIRED AT ALL FIRE RATED WALLS AT
FLOOR DECKS.
E. FOR TYPE AND EXTENTS OF FINISHES SEE A6- AND A8- SHEETS.
F. REPLACE TYPICAL GYPSUM WALL BOARD WITH 5/8" MOISTURE
RESISTANT GYPSUM WALL BOARD AT TILE LOCATIONS. ON ALL
WET WALLS REPLACE TYPICAL GYPSUM WALL BOARD WITH 5/8"
CEMENTITIOUS BACKER BOARD AT TILE LOCATIONS.
G. ALL DOORS WITH WOOD FRAMES ARE 6" MIN. FROM FACE OF
ADJACENT WALL, U.N.O. TO ACCOMMODATE 5 1/2" WOOD CASING.
1 5/8"
2 1/2"
3 5/8"
4"
6"
14'-0" 16'-0" 17'-0" 19'-0" 22'-0" 24'-0" 26'-0"
HEIGHTSTUD
SIZE
25 GA 20 GA 18 GA -- -- ----
25 GA 20 GA -- -- --20 GA 18 GA
25 GA 25 GA 25 GA 25 GA 25 GA 20 GA 18 GA
9'-0"
20 GA -- -- -- -- -- -- --
25 GA
25 GA
25 GA
20GA25 GA -- -- -- -- -- --
METAL STUD GAUGE GUIDE
GENERAL STUD GAUGE NOTES:
1. STUD GAUGE GUIDE FOR INTERIOR PARTITIONS ONLY.
2. PROVIDE 20 GAUGE STUDS AT WALL MOUNTED CABINET
LOCATIONS AND AT WALLS SCHEDULED TO RECEIVE
CERAMIC TILE UNLESS OTHERWISE NOTED.
6" STUDS @ 12" O.C.
24 GAUGE (MIN.)
L1 3/8 x 1 3/8 x 0-5 1/2
INSTALL INSIDE WALL
STUD
#12 SCREW EA. FLANGE
WOOD FLOOR SYSTEM
(EXISTING)
P 3/16 x 2 x 0-6L
E Q
E Q
1". 4". 1".
CONT. 6" TRACK W/
2" FLANGES,
24 GAUGE MIN.
(2) #12 SCREWS
(L TO STUD)
1/4" DIA. A307
THRU BOLT
C
COMMONWEALTH
T
R E
R
A
H C
I
N K E
UT
OF
B
3 87
I
R E G
No.
TS E
NT U
C E
YK T
N E R
D
ER
RB
APPROVED FOR PROGRAM CONCEPT ONLY
APPROVED FOR PROGRAM CONCEPT ONLY
DATE
DATE
ENGINEERING
DIVISION OF
AGENCY
AUTHORIZED AGENT
FOR INTENT ONLY
DIV. OF ENGR.
REVIEWED
ENGR. ACCT. NO.
DRAWING NO.
DATE
A&E FILE NO.
CHECKED BY
SHEET DRAWN BY
RECORD DATE
DATEREVISIONS
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES MANAGEMENT
DIVISION OF ENGINEERING
FRANKFORT, KENTUCKY
/5
/2
:5 :5
P
M C
U s e rs
\R H in s o n \D o c u m e n ts
\1
G
C T
C
A b o d e B u il d in g R e n o v a ti o n rh in s o n .r v t
A0.1
CODE INFO AND WALL TYPES
470-C5N5-NC11-01
GATEWAY URBAN CAMPUS
09/25/14
201114.02
BB
REH
PROFESSIONAL SERVICES CLASSROOM CENTER
438-440 Scott St., Covington, KY 41011
SCALE: 1/8" = 1'-0"A0.1
1 BASEMENT - EGRESS PLAN
SCALE: 1/8" = 1'-0"A0.1
2 FIRST FLOOR - EGRESS PLAN
SCALE: 1/8" = 1'-0"A0.1
3 SECOND FLOOR - EGRESS PLAN
SCALE: 1/8" = 1'-0"A0.1
4 THIRD FLOOR - EGRESS PLAN
NORTH
PLAN
NORTH
PLAN
NORTH
PLAN
NORTH
PLAN
SCALE: 3" = 1'-0"A0.1
5 FREE STANDING WALL - BASE DETAIL
AS-BUILT
12-18-15
RECORD DRAWINGS
THESE RECORD DRAWINGS HAVE BEEN PREPARED IN PART, ON THE BASIS OF INFORMATION COMPILED BY OTHERS. THE ARCHITECT/ENGINEER HAS NOT VERIFIED THE ACCURACY OR COMPLETENESS OF THE INFORMATION, AND SHALL NOT BE RESPONSIBLE FOR ANY ERRORS OR OMISSIONS THAT MAY BE
INCORPORATED AS A RESULT OF ERRONEOUS INFORMATION PROVIDED BY OTHERS.