This is an HVAC ductwork design and demolition plan prepared by the Commonwealth of Kentucky Finance and Administration Cabinet, Department for Facilities & Support Services, Division of Engineering, in conjunction with KLH Engineers, PSC for the Gateway Urban Campus located at 438-440 Scott Street, Covington, Kentucky. The project involves the installation of new HVAC ductwork in the basement of a classroom center facility, along with the demolition of existing HVAC ductwork and piping. The mechanical plan (Sheet HV1.0) depicts new air handling units (ACU-B-01, ACU-B-02, and ACU-B-03) with varying capacities ranging from 187 CFM to 770 CFM, connected via supply, return, and exhaust ductwork to ceiling diffusers and exhaust grilles throughout the basement level. The scope of work requires complete furnishing, installation, and placement into operation of all systems shown on the drawings in accordance with all state and local codes and ordinances. The plan was approved for program concept on December 18, 2015, and prepared under KLH Project Number 11369.04.
The contractor must provide all labor, material, and equipment necessary for installation and coordinate work with other trades regarding ceiling space requirements and roof-mounted equipment placement. Key requirements include installation of volume dampers at all ductwork branch takeoffs, turning vanes in 90-degree mitered elbows (except in acoustic-lined return ducts), flexible duct connections to ceiling diffusers with proper support, and compliance with manufacturer-recommended clearances for service and access. Existing HVAC units must be turned over to Gateway in workable condition prior to demolition of all existing ductwork and piping. No pricing information, set-asides, funding sources, or contract terms are specified in this design document.
View the file
Other files
Show 40 more
Latest 50 of 80 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T
T
T
B C D EA G
F
STUDENT LOUNGE
EXISTING STORAGE
EXISTING MECHANICAL
ROOM
EXISTING ELEVATOR
MACHINE ROOM
EXISTING STAIR
A
EXISTING ELEVATOR
E
ACU-B-03
ACU-B-02
ACU-B-02
12X10 SG
385 CFM
12X10 SG
330 CFM
12"ø 14"x12"
"x
ACU-B-01
16X12 RG
770 CFM
ACU-B-03
ACU-B-01
3/4"ø COND.
3/4"ø COND.
3/4"ø COND. 6x6 SR
12 CFM
6"ø
10"x12"
10"ø
8"ø8x8 SG
187 CFM
8"x14"
UP
CONDENSATE DN
TO FLOOR DRAIN
B C D EA G
F
SYMBOL DESCRIPTION
HVAC SYMBOLS LEGEND
SUCTION GAS, LIQUID, AND DISCHARGE GAS LINES
GAS AND LIQUID LINE
CEILING DIFFUSER
CD
EXHAUST GRILLE
EG
FLEXIBLE DUCTWORK CONNECTION
EXISTING WORK TO REMAIN
EXISTING WORK TO BE REMOVED
NEW WORK
FIRE DAMPER
FD
APPROVED FOR PROGRAM CONCEPT ONLY
APPROVED FOR PROGRAM CONCEPT ONLY
DATE
DATE
ENGINEERING
DIVISION OF
AGENCY
AUTHORIZED AGENT
FOR INTENT ONLY
DIV. OF ENGR.
REVIEWED
ENGR. ACCT NO.
DRAWING NO.
DATE
A&E FILE NO.
CHECKED BY
SHEET DRAWN BY
RECORD DATE
DATEREVISIONS
COMMONWEALTH OF KENTUCKY
FINANCE AND ADMINISTRATION CABINET
DEPARTMENT FOR FACILITIES & SUPPORT SERVICES
DIVISION OF ENGINEERING
FRANKFORT, KENTUCKY
WWW.KLHENGRS.COM
ENGINEERS, PSC
MECHANICAL/ELECTRICAL ENGINEERS
KOHRS LONNEMANN HEIL
LEXINGTON, KENTUCKY
COLUMBUS, OHIO
DAYTON, OHIO
NEW YORK, NEW YORK
1538 ALEXANDRIA PIKE, SUITE
11 FT. THOMAS, KENTUCKY
41075 800-354-9783 859-442-8050
859-442-8058 FAX
KLH PRO. NO.
11369.04
PROFESSIONAL SERVICES CLASSROOM CENTER
/1
/2
:1 :5
P
M
HV1.0
HVAC DUCTWORK - NEW AND
DEMOLITION - BASEMENT
C5N5-NC11-01
GATEWAY URBAN CAMPUS
438-440 Scott St., Covington, KY 41011
12/18/15
201114.02
KTW
KTW
GENERAL NOTES
A. PROVIDE ALL LABOR, MATERIAL, AND EQUIPMENT NECESSARY TO
COMPLETELY FURNISH, INSTALL, AND PLACE INTO OPERATION, ALL
SYSTEMS SHOWN ON THE DRAWINGS AND DELINEATED IN THE
SPECIFICATIONS IN ACCORDANCE WITH ALL STATE AND LOCAL CODES
AND ORDINANCES. REPORT ANY KNOWN DISCREPANCIES TO THE
ARCHITECT/ENGINEER PRIOR TO INSTALLATION.
B. COORDINATE WORK AND SPACE REQUIREMENTS IN CEILING SPACES
WITH OTHER TRADES PRIOR TO INSTALLATION.
C. COORDINATE LOCATIONS AND ORIENTATION OF ROOF MOUNTED
EQUIPMENT WITH ARCHITECTURAL AND STRUCTURAL DRAWINGS.
D. PROVIDE VOLUME DAMPERS AT ALL SUPPLY, RETURN, AND EXHAUST
DUCT BRANCH TAKE-OFFS.
E. PROVIDE TURNING VANES IN ALL 90 DEGREE MITERED ELBOWS. OMIT
TURNING VANES IN ACOUSTIC LINED RETURN DUCT ELBOWS.
F. PROVIDE FLEXIBLE DUCT ON INLET TO EACH CEILING DIFFUSER. CUT
FLEXIBLE DUCTS TO LENGTH NEEDED AND INSTALL WITHOUT KINKS OR
SHARP BENDS (BENDS WITH CENTERLINE RADIUS LESS THAN DUCT
DIAMETER).SUPPORT FLEXIBLE DUCTS WITH MINIMUM 1" WIDE METAL
STRAPS OR SADDLES.
G. SIZES OF ACOUSTIC LINED DUCTS ARE NET INSIDE DIMENSION.
INCREASE SHEET METAL SIZE ACCORDINGLY.
H. RUNOUTS TO CEILING DIFFUSERS ARE THE SAME SIZE AS THE DIFFUSER
NECK UNLESS NOTED OTHERWISE.
I. INSTALL ALL EQUIPMENT WITH CODE REQUIRED AND MANUFACTURER
RECOMMENDED MINIMUM CLEARANCES FOR SERVICE, ACCESS, AND
FIRE PROTECTION.
SCALE: 1/4" = 1'-0"HV1.0
HVAC DUCTWORK - NEW -
BASEMENT FLOOR
SCALE: 1/4" = 1'-0"HV1.0
HVAC - DEMOLITION -
BASEMENT FLOOR
KEYED NOTES
1 TURN EXISTING UNITS OVER TO GATEWAY IN WORKABLE CONDITION.
2 DEMOLISH ALL EXISTING HVAC DUCTWORK & PIPING WHETHER SHOWN OR NOT.
File details come from the government source that posted it. Updated .